You are on page 1of 74

Aircon heat load calculation sheet

Project Name: WINMART


Address: Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN

12/March/2021
Heat load sum up table

Cooling Heating Heat load per area


Floor
Qty.
Sys area
Room name Fl of Indoor SH Total Selected Time Total Selected Humid. Time Cooling Heating
-tem
rooms
[W] [Hr] [W] [kg/h] [Hr] [m2] [W/m2]

F5_KHO HCNS 5 1 1 1994 2555 2683 15 19.9 134.8


F5_PT NHAN LUC 5 1 1 45788 97364 102232 14 354.4 288.5
F5_P.HOP NHO 5 1 1 2059 2925 3071 15 5.2 590.6
F5_P. AN 5 1 1 6485 8907 9352 14 26.5 352.9
F5_FOCUS 5 1 1 409 874 918 13 4.0 229.4
F5_P. HOP NHO 1 5 1 1 486 2276 2390 13 6.9 346.3
F5_P. HOP VUA 01 5 1 1 2030 6517 6843 13 18.5 369.9
F5_TAI CHINH 5 1 1 11363 26473 27797 13 100.2 277.4
F5_KE TOAN 5 1 1 42241 98116 103022 13 330.0 312.2
F5_PTGD KE TOAN 5 1 1 969 2394 2514 13 15.7 160.1
F5_ME 5 1 1 508 1420 1491 13 5.6 266.3
F6_CALL CENTER 6 1 1 4260 7300 7665 15 19.8 387.1
F6_P. HOP VUA 01 6 1 1 5061 9376 9845 15 24.4 403.5
F6_P. HOP LON 02 6 1 1 9054 19812 20803 15 56.9 365.6
F6_P. HOP LON 01 6 1 1 7213 17983 18882 15 58.7 321.7
F6_KHU TIEP TAN 6 1 1 5202 7673 8057 16 78.6 102.5
F6_MOTHER ROOM 6 1 1 681 1562 1640 15 7.5 218.7
F6_P.HOP NHO 02 6 1 1 1112 3318 3484 14 9.3 374.6
F6_P. AN 6 1 1 9187 18017 18918 14 38.3 493.9
F6_P.CHUOI CUNG UNG 6 1 1 14352 25403 26673 15 98.5 270.8
F6_P. HOP NHO 01 6 1 1 1730 4396 4616 14 13.8 334.5
F6_P. ÐONG DAU 6 1 1 1593 3384 3553 14 11.0 323.0
F6_P. COMMERCIAL30 6 1 1 16078 29624 31105 14 98.4 316.1
F6_PTGD 6 1 1 2397 4642 4874 15 24.7 197.3
F6_P. HOP VUA 02 6 1 1 1696 3587 3766 13 20.6 182.8
F6_COMMERCIAL50 6 1 1 29167 65422 68693 13 260.3 263.9
F6_P. PTGD PT 6 1 1 1228 2644 2776 13 15.1 183.9
F6_P. HOP NHO 03 6 1 1 1065 3307 3472 13 9.5 365.5
F6_KHU IN AN 6 1 1 4297 4782 5021 13 6.9 727.7
F6_ME 6 1 1 316 790 830 13 5.3 156.5
F7_ME 7 1 1 627 1082 1136 15 5.6 202.9
F7_P. HOP NHO 7 1 1 1255 3457 3630 14 8.7 417.2
F7_CNTT 7 1 1 55066 105892 111187 14 343.9 323.3
F5_HL TM 5 1 1 916 2348 2465 13 17.3 142.5
F6_HL TM 6 1 1 1459 3240 3402 15 17.6 193.3

Peak load of building 35 285909 595257 625020 14 2137.6 292.4

SH : Sensible heat

-1-
Table of system heat load

Cooling Heating
Sys
Time F/A vol Indoor SH Indoor Outside Total Selected Time F/A vol Indoor Outside Total Selected Humid.
-tem
[Hr] [m3/h] [W] [Hr] [m3/h] [W] [kg/h]

1 14 13560 285909 356921 238336 595257 625020

F/A : Fresh air


SH : Sensible heat

-2-
System table

System Room name Floor Rooms System Room name Floor Rooms

1 F5_KHO HCNS 5 1
1 F5_PT NHAN LUC 5 1
1 F5_P.HOP NHO 5 1
1 F5_P. AN 5 1
1 F5_FOCUS 5 1
1 F5_P. HOP NHO 1 5 1
1 F5_P. HOP VUA 01 5 1
1 F5_TAI CHINH 5 1
1 F5_KE TOAN 5 1
1 F5_PTGD KE TOAN 5 1
1 F5_ME 5 1
1 F6_CALL CENTER 6 1
1 F6_P. HOP VUA 01 6 1
1 F6_P. HOP LON 02 6 1
1 F6_P. HOP LON 01 6 1
1 F6_KHU TIEP TAN 6 1
1 F6_MOTHER ROOM 6 1
1 F6_P.HOP NHO 02 6 1
1 F6_P. AN 6 1
1 F6_P.CHUOI CUNG UNG 6 1
1 F6_P. HOP NHO 01 6 1
1 F6_P. ÐONG DAU 6 1
1 F6_P. COMMERCIAL30 6 1
1 F6_PTGD 6 1
1 F6_P. HOP VUA 02 6 1
1 F6_COMMERCIAL50 6 1
1 F6_P. PTGD PT 6 1
1 F6_P. HOP NHO 03 6 1
1 F6_KHU IN AN 6 1
1 F6_ME 6 1
1 F7_ME 7 1
1 F7_P. HOP NHO 7 1
1 F7_CNTT 7 1
1 F5_HL TM 5 1
1 F6_HL TM 6 1

-3-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F5_KHO HCNS Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 5
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 1
Floor area(m2) 19.9
Depth of underground wall(m) 0.0
Ceiling height(m) 2.7 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.8 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 3.9 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 6.5 0.6 0.0 1.2 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 0 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-4-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F5_KHO HCNS 5 1 1 Office 19.9 2.7 1 Summer 20.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 11 0 115 0 277 17 91 56 76 462 0 0 938 167 201 1306


9 32.5 75.4 14 0 153 0 360 23 107 56 76 462 0 0 1068 183 242 1493
10 34.1 74.3 21 0 191 0 432 29 124 56 76 462 0 0 1191 200 284 1675
11 35.5 73.1 29 0 223 0 483 34 139 56 76 462 0 0 1287 215 321 1823
12 36.4 72.5 39 0 244 0 513 37 149 56 76 462 0 0 1351 225 347 1923
13 36.8 72.2 49 0 254 0 684 38 154 56 76 462 0 0 1543 230 358 2131
14 36.6 72.2 61 0 249 0 956 38 151 56 76 462 0 0 1822 227 352 2401
*15 36.1 72.7 74 0 237 0 1129 36 146 56 76 462 0 0 1994 222 339 2555
16 35.3 73.1 88 0 219 0 1168 33 136 56 76 462 0 0 2026 212 314 2552
17 34.3 74.0 101 0 195 0 1071 29 125 56 76 462 0 0 1914 201 289 2404
18 33.1 74.9 109 0 167 0 880 25 113 56 76 462 0 0 1699 189 257 2145

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-5-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F5_PT NHAN LUC Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 5
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 112
Floor area(m2) 354.4
Depth of underground wall(m) 0.0
Ceiling height(m) 2.7 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 8.8 7.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 18.9 15.1 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 1.6 8.4 6.6 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 22300 1000
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-6-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F5_PT NHAN LUC 5 1 1 Office 354.4 2.7 112 Summer2240.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 98 0 230 0 2408 309 1613 6272 8512 8222 22300 1000 39839 11125 22505 73469
9 32.5 75.4 127 0 304 0 3135 411 1902 6272 8512 8222 22300 1000 40771 11414 27065 79250
10 34.1 74.3 186 0 381 0 3763 512 2206 6272 8512 8222 22300 1000 41636 11718 31812 85166
11 35.5 73.1 254 0 446 0 4206 600 2473 6272 8512 8222 22300 1000 42300 11985 35962 90247
12 36.4 72.5 342 0 488 0 4458 657 2662 6272 8512 8222 22300 1000 42739 12174 38849 93762
13 36.8 72.2 435 0 508 0 5484 682 2747 6272 8512 8222 22300 1000 43903 12259 40133 96295
*14 36.6 72.2 533 0 498 0 7294 669 2694 6272 8512 8222 22300 1000 45788 12206 39370 97364
15 36.1 72.7 639 0 475 0 8284 638 2598 6272 8512 8222 22300 1000 46830 12110 37880 96820
16 35.3 73.1 750 0 437 0 8220 587 2423 6272 8512 8222 22300 1000 46788 11935 35237 93960
17 34.3 74.0 837 0 390 0 7185 524 2235 6272 8512 8222 22300 1000 45730 11747 32295 89772
18 33.1 74.9 890 0 334 0 5451 448 2009 6272 8512 8222 22300 1000 43917 11521 28759 84197

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-7-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F5_P.HOP NHO Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 5
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 2
Floor area(m2) 5.2
Depth of underground wall(m) 0.0
Ceiling height(m) 2.7 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 2.1 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 4.5 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 1.4 1.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-8-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F5_P.HOP NHO 5 1 1 Office 5.2 2.7 2 Summer 40.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 13 0 33 0 319 5 24 112 152 121 200 0 803 176 402 1381
9 32.5 75.4 17 0 44 0 414 6 28 112 152 121 200 0 914 180 484 1578
10 34.1 74.3 25 0 55 0 498 8 32 112 152 121 200 0 1019 184 568 1771
11 35.5 73.1 34 0 65 0 556 9 36 112 152 121 200 0 1097 188 642 1927
12 36.4 72.5 46 0 70 0 589 10 39 112 152 121 200 0 1148 191 693 2032
13 36.8 72.2 58 0 74 0 856 10 40 112 152 121 200 0 1431 192 717 2340
14 36.6 72.2 72 0 72 0 1270 10 40 112 152 121 200 0 1857 192 703 2752
*15 36.1 72.7 89 0 69 0 1459 9 38 112 152 121 200 0 2059 190 676 2925
16 35.3 73.1 108 0 63 0 1466 9 36 112 152 121 200 0 2079 188 629 2896
17 34.3 74.0 125 0 56 0 1308 8 33 112 152 121 200 0 1930 185 577 2692
18 33.1 74.9 136 0 48 0 1020 7 29 112 152 121 200 0 1644 181 514 2339

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-9-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F5_P. AN Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 5
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board No Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 5
Floor area(m2) 26.5
Depth of underground wall(m) 0.0
Ceiling height(m) 3.8 !Underground wall is valid only when outer wall is negative value.

Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass


ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 1.8 0.0 0.0
Roof(without ceiling board) 2.16 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 5.3 0.0 0.0 Ceiling(without ceiling board) 2.69
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 5.6 3.3 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 4100 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-10-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F5_P. AN 5 1 1 Office 26.5 3.8 5 Summer 100.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 7 0 173 0 376 33 170 280 380 615 4100 0 5584 550 1005 7139
9 32.5 75.4 9 0 230 0 488 43 200 280 380 615 4100 0 5765 580 1209 7554
10 34.1 74.3 13 0 287 0 587 54 232 280 380 615 4100 0 5936 612 1420 7968
11 35.5 73.1 18 0 337 0 656 63 260 280 380 615 4100 0 6069 640 1606 8315
12 36.4 72.5 25 0 369 0 694 69 280 280 380 615 4100 0 6152 660 1734 8546
13 36.8 72.2 31 0 383 0 795 72 289 280 380 615 4100 0 6276 669 1791 8736
*14 36.6 72.2 38 0 375 0 1007 70 284 280 380 615 4100 0 6485 664 1758 8907
15 36.1 72.7 45 0 358 0 1097 67 273 280 380 615 4100 0 6562 653 1691 8906
16 35.3 73.1 52 0 329 0 1038 62 255 280 380 615 4100 0 6476 635 1573 8684
17 34.3 74.0 57 0 294 0 851 55 235 280 380 615 4100 0 6252 615 1442 8309
18 33.1 74.9 60 0 251 0 574 47 211 280 380 615 4100 0 5927 591 1284 7802

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-11-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F5_FOCUS Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 5
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 1
Floor area(m2) 4.0
Depth of underground wall(m) 0.0
Ceiling height(m) 2.7 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 1.7 0.0 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-12-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F5_FOCUS 5 1 1 Office 4.0 2.7 1 Summer 20.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 0 0 24 0 0 3 18 56 76 93 200 0 376 94 201 671


9 32.5 75.4 0 0 31 0 0 5 21 56 76 93 200 0 385 97 242 724
10 34.1 74.3 0 0 39 0 0 6 25 56 76 93 200 0 394 101 284 779
11 35.5 73.1 0 0 46 0 0 7 28 56 76 93 200 0 402 104 321 827
12 36.4 72.5 0 0 50 0 0 7 30 56 76 93 200 0 406 106 347 859
*13 36.8 72.2 0 0 52 0 0 8 31 56 76 93 200 0 409 107 358 874
14 36.6 72.2 0 0 51 0 0 8 30 56 76 93 200 0 408 106 352 866
15 36.1 72.7 0 0 49 0 0 7 29 56 76 93 200 0 405 105 339 849
16 35.3 73.1 0 0 45 0 0 7 27 56 76 93 200 0 401 103 314 818
17 34.3 74.0 0 0 40 0 0 6 25 56 76 93 200 0 395 101 289 785
18 33.1 74.9 0 0 34 0 0 5 23 56 76 93 200 0 388 99 257 744

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-13-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F5_P. HOP NHO 1 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 5
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 4
Floor area(m2) 6.9
Depth of underground wall(m) 0.0
Ceiling height(m) 2.7 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 2.9 0.0 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 0 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-14-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F5_P. HOP NHO 1 5 1 1 Office 6.9 2.7 4 Summer 80.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 0 0 40 0 0 6 31 224 304 160 0 0 430 335 803 1568


9 32.5 75.4 0 0 53 0 0 8 37 224 304 160 0 0 445 341 967 1753
10 34.1 74.3 0 0 66 0 0 10 43 224 304 160 0 0 460 347 1136 1943
11 35.5 73.1 0 0 78 0 0 12 48 224 304 160 0 0 474 352 1285 2111
12 36.4 72.5 0 0 85 0 0 13 52 224 304 160 0 0 482 356 1388 2226
*13 36.8 72.2 0 0 89 0 0 13 53 224 304 160 0 0 486 357 1433 2276
14 36.6 72.2 0 0 87 0 0 13 52 224 304 160 0 0 484 356 1406 2246
15 36.1 72.7 0 0 83 0 0 12 51 224 304 160 0 0 479 355 1353 2187
16 35.3 73.1 0 0 76 0 0 11 47 224 304 160 0 0 471 351 1259 2081
17 34.3 74.0 0 0 68 0 0 10 44 224 304 160 0 0 462 348 1153 1963
18 33.1 74.9 0 0 58 0 0 9 39 224 304 160 0 0 451 343 1027 1821

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-15-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F5_P. HOP VUA 01 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 5
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 10
Floor area(m2) 18.5
Depth of underground wall(m) 0.0
Ceiling height(m) 2.7 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 3.2 3.5 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 800 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-16-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F5_P. HOP VUA 01 5 1 1 Office 18.5 2.7 10 Summer 200.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 0 0 93 0 0 16 84 560 760 429 800 0 1898 844 2009 4751
9 32.5 75.4 0 0 123 0 0 21 99 560 760 429 800 0 1933 859 2417 5209
10 34.1 74.3 0 0 153 0 0 27 115 560 760 429 800 0 1969 875 2841 5685
11 35.5 73.1 0 0 180 0 0 31 129 560 760 429 800 0 2000 889 3211 6100
12 36.4 72.5 0 0 197 0 0 34 139 560 760 429 800 0 2020 899 3468 6387
*13 36.8 72.2 0 0 205 0 0 36 143 560 760 429 800 0 2030 903 3584 6517
14 36.6 72.2 0 0 201 0 0 35 141 560 760 429 800 0 2025 901 3516 6442
15 36.1 72.7 0 0 191 0 0 33 136 560 760 429 800 0 2013 896 3383 6292
16 35.3 73.1 0 0 176 0 0 31 126 560 760 429 800 0 1996 886 3146 6028
17 34.3 74.0 0 0 157 0 0 27 117 560 760 429 800 0 1973 877 2884 5734
18 33.1 74.9 0 0 134 0 0 23 105 560 760 429 800 0 1946 865 2568 5379

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-17-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F5_TAI CHINH Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 5
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 33
Floor area(m2) 100.2
Depth of underground wall(m) 0.0
Ceiling height(m) 2.7 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 13.0 0.0 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 6600 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-18-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F5_TAI CHINH 5 1 1 Office 100.2 2.7 33 Summer 660.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 0 0 180 0 0 87 456 1848 2508 2325 6600 0 11040 2964 6631 20635
9 32.5 75.4 0 0 239 0 0 116 538 1848 2508 2325 6600 0 11128 3046 7975 22149
10 34.1 74.3 0 0 298 0 0 145 624 1848 2508 2325 6600 0 11216 3132 9373 23721
11 35.5 73.1 0 0 349 0 0 170 699 1848 2508 2325 6600 0 11292 3207 10596 25095
12 36.4 72.5 0 0 383 0 0 186 753 1848 2508 2325 6600 0 11342 3261 11446 26049
*13 36.8 72.2 0 0 397 0 0 193 777 1848 2508 2325 6600 0 11363 3285 11825 26473
14 36.6 72.2 0 0 390 0 0 189 762 1848 2508 2325 6600 0 11352 3270 11600 26222
15 36.1 72.7 0 0 372 0 0 180 735 1848 2508 2325 6600 0 11325 3243 11161 25729
16 35.3 73.1 0 0 342 0 0 166 685 1848 2508 2325 6600 0 11281 3193 10383 24857
17 34.3 74.0 0 0 305 0 0 148 632 1848 2508 2325 6600 0 11226 3140 9516 23882
18 33.1 74.9 0 0 261 0 0 127 568 1848 2508 2325 6600 0 11161 3076 8473 22710

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-19-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F5_KE TOAN Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 5
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 117
Floor area(m2) 330.0
Depth of underground wall(m) 0.0
Ceiling height(m) 2.7 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 5.0 0.0 2.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 10.8 0.0 4.3 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 16.1 15.2 7.2 15.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 23400 2500
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-20-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F5_KE TOAN 5 1 1 Office 330.0 2.7 117 Summer2340.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 85 0 742 0 3310 288 1502 6552 8892 7656 23400 2500 42033 12894 23510 78437
9 32.5 75.4 134 0 984 0 3325 382 1771 6552 8892 7656 23400 2500 42433 13163 28273 83869
10 34.1 74.3 192 0 1226 0 2878 476 2054 6552 8892 7656 23400 2500 42380 13446 33232 89058
11 35.5 73.1 245 0 1439 0 2255 559 2302 6552 8892 7656 23400 2500 42106 13694 37568 93368
12 36.4 72.5 289 0 1574 0 1976 612 2479 6552 8892 7656 23400 2500 42059 13871 40583 96513
*13 36.8 72.2 321 0 1635 0 2042 635 2558 6552 8892 7656 23400 2500 42241 13950 41925 98116
14 36.6 72.2 333 0 1605 0 2130 623 2509 6552 8892 7656 23400 2500 42299 13901 41127 97327
15 36.1 72.7 334 0 1529 0 2059 594 2420 6552 8892 7656 23400 2500 42124 13812 39571 95507
16 35.3 73.1 331 0 1408 0 1816 547 2256 6552 8892 7656 23400 2500 41710 13648 36809 92167
17 34.3 74.0 322 0 1256 0 1435 488 2081 6552 8892 7656 23400 2500 41109 13473 33737 88319
18 33.1 74.9 305 0 1074 0 951 418 1870 6552 8892 7656 23400 2500 40356 13262 30043 83661

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-21-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F5_PTGD KE TOAN Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 5
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 3
Floor area(m2) 15.7
Depth of underground wall(m) 0.0
Ceiling height(m) 2.7 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 3.5 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 300 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-22-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F5_PTGD KE TOAN 5 1 1 Office 15.7 2.7 3 Summer 60.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 0 0 49 0 0 14 71 168 228 364 300 0 895 299 603 1797
9 32.5 75.4 0 0 64 0 0 18 84 168 228 364 300 0 914 312 725 1951
10 34.1 74.3 0 0 80 0 0 23 98 168 228 364 300 0 935 326 852 2113
11 35.5 73.1 0 0 94 0 0 27 110 168 228 364 300 0 953 338 963 2254
12 36.4 72.5 0 0 103 0 0 29 118 168 228 364 300 0 964 346 1041 2351
*13 36.8 72.2 0 0 107 0 0 30 122 168 228 364 300 0 969 350 1075 2394
14 36.6 72.2 0 0 105 0 0 30 119 168 228 364 300 0 967 347 1055 2369
15 36.1 72.7 0 0 100 0 0 28 115 168 228 364 300 0 960 343 1015 2318
16 35.3 73.1 0 0 92 0 0 26 107 168 228 364 300 0 950 335 944 2229
17 34.3 74.0 0 0 82 0 0 23 99 168 228 364 300 0 937 327 865 2129
18 33.1 74.9 0 0 70 0 0 20 89 168 228 364 300 0 922 317 771 2010

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-23-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F5_ME Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 5
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 2
Floor area(m2) 5.6
Depth of underground wall(m) 0.0
Ceiling height(m) 2.7 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.8 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-24-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F5_ME 5 1 1 Office 5.6 2.7 2 Summer 40.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 0 0 25 0 0 5 25 112 152 130 200 0 472 177 402 1051
9 32.5 75.4 0 0 33 0 0 6 30 112 152 130 200 0 481 182 484 1147
10 34.1 74.3 0 0 41 0 0 8 35 112 152 130 200 0 491 187 568 1246
11 35.5 73.1 0 0 48 0 0 9 39 112 152 130 200 0 499 191 642 1332
12 36.4 72.5 0 0 53 0 0 10 42 112 152 130 200 0 505 194 693 1392
*13 36.8 72.2 0 0 55 0 0 11 43 112 152 130 200 0 508 195 717 1420
14 36.6 72.2 0 0 54 0 0 11 43 112 152 130 200 0 507 195 703 1405
15 36.1 72.7 0 0 51 0 0 10 41 112 152 130 200 0 503 193 676 1372
16 35.3 73.1 0 0 47 0 0 9 38 112 152 130 200 0 498 190 629 1317
17 34.3 74.0 0 0 42 0 0 8 35 112 152 130 200 0 492 187 577 1256
18 33.1 74.9 0 0 36 0 0 7 32 112 152 130 200 0 485 184 514 1183

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-25-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F6_CALL CENTER Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 6
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 7
Floor area(m2) 19.8
Depth of underground wall(m) 0.0
Ceiling height(m) 2.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 19.8 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.8 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 3.6 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 6.7 0.7 0.0 1.5 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 1400 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-26-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F6_CALL CENTER 6 1 1 Office 19.8 2.6 7 Summer 140.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 12 46 118 0 255 17 87 392 532 459 1400 0 2699 619 1406 4724
9 32.5 75.4 15 76 158 0 332 22 102 392 532 459 1400 0 2854 634 1691 5179
10 34.1 74.3 22 128 196 0 399 28 119 392 532 459 1400 0 3024 651 1988 5663
11 35.5 73.1 30 207 230 0 445 32 133 392 532 459 1400 0 3195 665 2248 6108
12 36.4 72.5 40 309 253 0 473 35 143 392 532 459 1400 0 3361 675 2428 6464
13 36.8 72.2 51 421 262 0 632 37 148 392 532 459 1400 0 3654 680 2508 6842
14 36.6 72.2 64 529 257 0 883 36 145 392 532 459 1400 0 4020 677 2461 7158
*15 36.1 72.7 77 611 244 0 1043 34 140 392 532 459 1400 0 4260 672 2368 7300
16 35.3 73.1 93 661 226 0 1078 32 130 392 532 459 1400 0 4341 662 2203 7206
17 34.3 74.0 106 667 202 0 988 28 120 392 532 459 1400 0 4242 652 2018 6912
18 33.1 74.9 114 631 173 0 812 24 108 392 532 459 1400 0 4005 640 1797 6442

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-27-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F6_P. HOP VUA 01 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 6
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 10
Floor area(m2) 24.4
Depth of underground wall(m) 0.0
Ceiling height(m) 2.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 24.4 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 3.5 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 7.3 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 3.1 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 800 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-28-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F6_P. HOP VUA 01 6 1 1 Office 24.4 2.6 10 Summer 200.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 21 57 41 0 517 21 107 560 760 566 800 0 2583 867 2009 5459
9 32.5 75.4 28 93 55 0 673 27 126 560 760 566 800 0 2802 886 2417 6105
10 34.1 74.3 40 158 68 0 808 34 146 560 760 566 800 0 3034 906 2841 6781
11 35.5 73.1 55 255 80 0 903 40 164 560 760 566 800 0 3259 924 3211 7394
12 36.4 72.5 74 381 88 0 959 44 177 560 760 566 800 0 3472 937 3468 7877
13 36.8 72.2 94 518 91 0 1281 45 182 560 760 566 800 0 3955 942 3584 8481
14 36.6 72.2 116 652 90 0 1790 44 179 560 760 566 800 0 4618 939 3516 9073
*15 36.1 72.7 141 753 85 0 2114 42 172 560 760 566 800 0 5061 932 3383 9376
16 35.3 73.1 169 814 79 0 2186 39 161 560 760 566 800 0 5213 921 3146 9280
17 34.3 74.0 193 822 70 0 2005 35 148 560 760 566 800 0 5051 908 2884 8843
18 33.1 74.9 209 778 60 0 1647 30 133 560 760 566 800 0 4650 893 2568 8111

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-29-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F6_P. HOP LON 02 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 6
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 25
Floor area(m2) 56.9
Depth of underground wall(m) 0.0
Ceiling height(m) 2.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 56.9 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 2.7 0.0 0.0 1.7 3.5 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 3.5 7.3 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 5.6 0.0 0.0 2.6 4.3 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 800 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-30-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F6_P. HOP LON 02 6 1 1 Office 56.9 2.6 25 Summer 500.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 74 132 167 0 765 48 249 1400 1900 1320 800 0 4706 2149 5023 11878
9 32.5 75.4 97 217 221 0 995 63 294 1400 1900 1320 800 0 5113 2194 6042 13349
10 34.1 74.3 140 368 276 0 1195 79 341 1400 1900 1320 800 0 5578 2241 7101 14920
11 35.5 73.1 192 595 323 0 1336 93 382 1400 1900 1320 800 0 6059 2282 8028 16369
12 36.4 72.5 258 888 355 0 1417 102 412 1400 1900 1320 800 0 6540 2312 8672 17524
13 36.8 72.2 328 1209 369 0 1805 105 425 1400 1900 1320 800 0 7336 2325 8958 18619
14 36.6 72.2 404 1521 361 0 2455 103 417 1400 1900 1320 800 0 8364 2317 8788 19469
*15 36.1 72.7 495 1757 344 0 2839 99 402 1400 1900 1320 800 0 9054 2302 8456 19812
16 35.3 73.1 594 1899 317 0 2871 91 375 1400 1900 1320 800 0 9292 2275 7865 19432
17 34.3 74.0 680 1917 283 0 2567 81 346 1400 1900 1320 800 0 9048 2246 7208 18502
18 33.1 74.9 737 1814 241 0 2025 69 311 1400 1900 1320 800 0 8406 2211 6420 17037

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-31-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F6_P. HOP LON 01 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 6
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 25
Floor area(m2) 58.7
Depth of underground wall(m) 0.0
Ceiling height(m) 2.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 58.7 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 3.5 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 7.3 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 3.3 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 800 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-32-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F6_P. HOP LON 01 6 1 1 Office 58.7 2.6 25 Summer 500.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 21 136 44 0 517 49 257 1400 1900 1362 800 0 4329 2157 5023 11509
9 32.5 75.4 28 224 58 0 673 65 303 1400 1900 1362 800 0 4610 2203 6042 12855
10 34.1 74.3 40 380 73 0 808 82 352 1400 1900 1362 800 0 4945 2252 7101 14298
11 35.5 73.1 55 614 85 0 903 96 394 1400 1900 1362 800 0 5315 2294 8028 15637
12 36.4 72.5 74 916 94 0 955 105 425 1400 1900 1362 800 0 5706 2325 8672 16703
13 36.8 72.2 94 1247 97 0 1094 109 438 1400 1900 1362 800 0 6203 2338 8958 17499
14 36.6 72.2 114 1569 95 0 1386 107 430 1400 1900 1362 800 0 6833 2330 8788 17951
*15 36.1 72.7 135 1812 91 0 1511 102 414 1400 1900 1362 800 0 7213 2314 8456 17983
16 35.3 73.1 156 1959 84 0 1429 94 386 1400 1900 1362 800 0 7284 2286 7865 17435
17 34.3 74.0 171 1978 75 0 1173 84 356 1400 1900 1362 800 0 7043 2256 7208 16507
18 33.1 74.9 179 1871 64 0 790 72 320 1400 1900 1362 800 0 6538 2220 6420 15178

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-33-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F6_KHU TIEP TAN Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 6
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 5
Floor area(m2) 78.6
Depth of underground wall(m) 0.0
Ceiling height(m) 2.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 78.6 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 350 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-34-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F6_KHU TIEP TAN 6 1 1 Office 78.6 2.6 5 Summer 100.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 0 183 0 0 0 66 345 280 380 1824 350 0 2703 725 1005 4433
9 32.5 75.4 0 300 0 0 0 88 406 280 380 1824 350 0 2842 786 1209 4837
10 34.1 74.3 0 509 0 0 0 109 471 280 380 1824 350 0 3072 851 1420 5343
11 35.5 73.1 0 822 0 0 0 128 528 280 380 1824 350 0 3404 908 1606 5918
12 36.4 72.5 0 1226 0 0 0 140 569 280 380 1824 350 0 3820 949 1734 6503
13 36.8 72.2 0 1670 0 0 0 146 587 280 380 1824 350 0 4270 967 1791 7028
14 36.6 72.2 0 2101 0 0 0 143 575 280 380 1824 350 0 4698 955 1758 7411
15 36.1 72.7 0 2427 0 0 0 136 555 280 380 1824 350 0 5017 935 1691 7643
*16 35.3 73.1 0 2623 0 0 0 125 518 280 380 1824 350 0 5202 898 1573 7673
17 34.3 74.0 0 2649 0 0 0 112 477 280 380 1824 350 0 5215 857 1442 7514
18 33.1 74.9 0 2505 0 0 0 96 429 280 380 1824 350 0 5055 809 1284 7148

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-35-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F6_MOTHER ROOM Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 6
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 2
Floor area(m2) 7.5
Depth of underground wall(m) 0.0
Ceiling height(m) 2.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 7.5 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 150 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-36-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F6_MOTHER ROOM 6 1 1 Office 7.5 2.6 2 Summer 40.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 0 17 0 0 0 6 33 112 152 174 150 0 459 185 402 1046
9 32.5 75.4 0 29 0 0 0 8 39 112 152 174 150 0 473 191 484 1148
10 34.1 74.3 0 49 0 0 0 10 45 112 152 174 150 0 495 197 568 1260
11 35.5 73.1 0 78 0 0 0 12 50 112 152 174 150 0 526 202 642 1370
12 36.4 72.5 0 117 0 0 0 13 54 112 152 174 150 0 566 206 693 1465
13 36.8 72.2 0 159 0 0 0 14 56 112 152 174 150 0 609 208 717 1534
14 36.6 72.2 0 200 0 0 0 14 55 112 152 174 150 0 650 207 703 1560
*15 36.1 72.7 0 232 0 0 0 13 53 112 152 174 150 0 681 205 676 1562
16 35.3 73.1 0 250 0 0 0 12 49 112 152 174 150 0 698 201 629 1528
17 34.3 74.0 0 253 0 0 0 11 46 112 152 174 150 0 700 198 577 1475
18 33.1 74.9 0 239 0 0 0 9 41 112 152 174 150 0 684 193 514 1391

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-37-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F6_P.HOP NHO 02 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 6
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 5
Floor area(m2) 9.3
Depth of underground wall(m) 0.0
Ceiling height(m) 2.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 9.3 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 350 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-38-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F6_P.HOP NHO 02 6 1 1 Office 9.3 2.6 5 Summer 100.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 0 22 0 0 0 8 41 280 380 216 350 0 876 421 1005 2302
9 32.5 75.4 0 36 0 0 0 10 48 280 380 216 350 0 892 428 1209 2529
10 34.1 74.3 0 60 0 0 0 13 56 280 380 216 350 0 919 436 1420 2775
11 35.5 73.1 0 97 0 0 0 15 62 280 380 216 350 0 958 442 1606 3006
12 36.4 72.5 0 145 0 0 0 17 67 280 380 216 350 0 1008 447 1734 3189
13 36.8 72.2 0 198 0 0 0 17 69 280 380 216 350 0 1061 449 1791 3301
*14 36.6 72.2 0 249 0 0 0 17 68 280 380 216 350 0 1112 448 1758 3318
15 36.1 72.7 0 287 0 0 0 16 66 280 380 216 350 0 1149 446 1691 3286
16 35.3 73.1 0 310 0 0 0 15 61 280 380 216 350 0 1171 441 1573 3185
17 34.3 74.0 0 313 0 0 0 13 56 280 380 216 350 0 1172 436 1442 3050
18 33.1 74.9 0 296 0 0 0 11 51 280 380 216 350 0 1153 431 1284 2868

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-39-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F6_P. AN Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 6
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 20
Floor area(m2) 38.3
Depth of underground wall(m) 0.0
Ceiling height(m) 2.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 38.3 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 1.6 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 3.3 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 3.6 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 5300 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-40-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F6_P. AN 6 1 1 Office 38.3 2.6 20 Summer 400.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 10 89 48 0 234 32 168 1120 1520 889 5300 0 7722 1688 4019 13429
9 32.5 75.4 13 146 64 0 304 43 198 1120 1520 889 5300 0 7879 1718 4833 14430
10 34.1 74.3 19 248 79 0 365 53 230 1120 1520 889 5300 0 8073 1750 5680 15503
11 35.5 73.1 26 401 93 0 408 62 257 1120 1520 889 5300 0 8299 1777 6422 16498
12 36.4 72.5 34 598 102 0 432 68 277 1120 1520 889 5300 0 8543 1797 6937 17277
13 36.8 72.2 44 814 106 0 495 71 286 1120 1520 889 5300 0 8839 1806 7167 17812
*14 36.6 72.2 53 1024 104 0 627 70 280 1120 1520 889 5300 0 9187 1800 7030 18017
15 36.1 72.7 63 1183 99 0 683 66 270 1120 1520 889 5300 0 9403 1790 6764 17957
16 35.3 73.1 73 1278 91 0 645 61 252 1120 1520 889 5300 0 9457 1772 6293 17522
17 34.3 74.0 80 1291 81 0 530 55 233 1120 1520 889 5300 0 9346 1753 5767 16866
18 33.1 74.9 83 1221 70 0 357 47 209 1120 1520 889 5300 0 9087 1729 5135 15951

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-41-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F6_P.CHUOI CUNG UNG Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 6
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 25
Floor area(m2) 98.5
Depth of underground wall(m) 0.0
Ceiling height(m) 2.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 98.5 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 3.5 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 7.3 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 12.8 3.9 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 5350 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-42-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F6_P.CHUOI CUNG UNG 6 1 1 Office 98.5 2.6 25 Summer 500.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 21 229 223 0 517 83 432 1400 1900 2285 5350 0 10108 2332 5023 17463
9 32.5 75.4 28 376 296 0 673 110 509 1400 1900 2285 5350 0 10518 2409 6042 18969
10 34.1 74.3 40 638 369 0 808 137 591 1400 1900 2285 5350 0 11027 2491 7101 20619
11 35.5 73.1 55 1030 432 0 903 161 662 1400 1900 2285 5350 0 11616 2562 8028 22206
12 36.4 72.5 74 1537 474 0 955 176 713 1400 1900 2285 5350 0 12251 2613 8672 23536
13 36.8 72.2 94 2093 492 0 1094 183 735 1400 1900 2285 5350 0 12991 2635 8958 24584
14 36.6 72.2 114 2633 483 0 1386 179 721 1400 1900 2285 5350 0 13830 2621 8788 25239
*15 36.1 72.7 135 3041 459 0 1511 171 695 1400 1900 2285 5350 0 14352 2595 8456 25403
16 35.3 73.1 156 3287 423 0 1429 157 649 1400 1900 2285 5350 0 14487 2549 7865 24901
17 34.3 74.0 171 3319 377 0 1173 140 598 1400 1900 2285 5350 0 14215 2498 7208 23921
18 33.1 74.9 179 3139 323 0 790 120 538 1400 1900 2285 5350 0 13586 2438 6420 22444

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-43-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F6_P. HOP NHO 01 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 6
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 6
Floor area(m2) 13.8
Depth of underground wall(m) 0.0
Ceiling height(m) 2.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 13.8 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 680 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-44-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F6_P. HOP NHO 01 6 1 1 Office 13.8 2.6 6 Summer 120.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 0 32 0 0 0 12 60 336 456 320 680 0 1380 516 1206 3102
9 32.5 75.4 0 53 0 0 0 15 71 336 456 320 680 0 1404 527 1450 3381
10 34.1 74.3 0 89 0 0 0 19 83 336 456 320 680 0 1444 539 1704 3687
11 35.5 73.1 0 144 0 0 0 22 93 336 456 320 680 0 1502 549 1926 3977
12 36.4 72.5 0 215 0 0 0 25 100 336 456 320 680 0 1576 556 2081 4213
13 36.8 72.2 0 293 0 0 0 26 103 336 456 320 680 0 1655 559 2150 4364
*14 36.6 72.2 0 369 0 0 0 25 101 336 456 320 680 0 1730 557 2109 4396
15 36.1 72.7 0 426 0 0 0 24 97 336 456 320 680 0 1786 553 2029 4368
16 35.3 73.1 0 460 0 0 0 22 91 336 456 320 680 0 1818 547 1887 4252
17 34.3 74.0 0 465 0 0 0 20 84 336 456 320 680 0 1821 540 1730 4091
18 33.1 74.9 0 440 0 0 0 17 75 336 456 320 680 0 1793 531 1540 3864

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-45-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F6_P. ÐONG DAU Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 6
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 4
Floor area(m2) 11.0
Depth of underground wall(m) 0.0
Ceiling height(m) 2.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 11.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 800 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-46-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F6_P. ÐONG DAU 6 1 1 Office 11.0 2.6 4 Summer 80.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 0 26 0 0 0 9 48 224 304 255 800 0 1314 352 803 2469
9 32.5 75.4 0 42 0 0 0 12 57 224 304 255 800 0 1333 361 967 2661
10 34.1 74.3 0 71 0 0 0 15 66 224 304 255 800 0 1365 370 1136 2871
11 35.5 73.1 0 115 0 0 0 18 74 224 304 255 800 0 1412 378 1285 3075
12 36.4 72.5 0 172 0 0 0 20 80 224 304 255 800 0 1471 384 1388 3243
13 36.8 72.2 0 234 0 0 0 20 82 224 304 255 800 0 1533 386 1433 3352
*14 36.6 72.2 0 294 0 0 0 20 81 224 304 255 800 0 1593 385 1406 3384
15 36.1 72.7 0 340 0 0 0 19 78 224 304 255 800 0 1638 382 1353 3373
16 35.3 73.1 0 367 0 0 0 18 72 224 304 255 800 0 1664 376 1259 3299
17 34.3 74.0 0 371 0 0 0 16 67 224 304 255 800 0 1666 371 1153 3190
18 33.1 74.9 0 351 0 0 0 13 60 224 304 255 800 0 1643 364 1027 3034

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-47-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F6_P. COMMERCIAL30 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 6
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 30
Floor area(m2) 98.4
Depth of underground wall(m) 0.0
Ceiling height(m) 2.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 98.4 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 5.4 12.0 0.0 10.5 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 8500 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-48-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F6_P. COMMERCIAL30 6 1 1 Office 98.4 2.6 30 Summer 600.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 0 229 372 0 0 83 431 1680 2280 2283 8500 0 13147 2711 6028 21886
9 32.5 75.4 0 376 495 0 0 110 508 1680 2280 2283 8500 0 13444 2788 7250 23482
10 34.1 74.3 0 637 616 0 0 137 590 1680 2280 2283 8500 0 13853 2870 8521 25244
11 35.5 73.1 0 1029 723 0 0 160 661 1680 2280 2283 8500 0 14375 2941 9633 26949
12 36.4 72.5 0 1535 791 0 0 176 712 1680 2280 2283 8500 0 14965 2992 10406 28363
13 36.8 72.2 0 2091 821 0 0 182 734 1680 2280 2283 8500 0 15557 3014 10750 29321
*14 36.6 72.2 0 2630 806 0 0 179 720 1680 2280 2283 8500 0 16078 3000 10546 29624
15 36.1 72.7 0 3038 768 0 0 171 695 1680 2280 2283 8500 0 16440 2975 10147 29562
16 35.3 73.1 0 3283 707 0 0 157 648 1680 2280 2283 8500 0 16610 2928 9438 28976
17 34.3 74.0 0 3316 630 0 0 140 598 1680 2280 2283 8500 0 16549 2878 8650 28077
18 33.1 74.9 0 3136 539 0 0 120 537 1680 2280 2283 8500 0 16258 2817 7703 26778

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-49-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F6_PTGD Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 6
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 5
Floor area(m2) 24.7
Depth of underground wall(m) 0.0
Ceiling height(m) 2.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 2.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 4.2 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 3.8 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 450 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-50-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F6_PTGD 6 1 1 Office 24.7 2.6 5 Summer 100.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 12 0 51 0 298 21 108 280 380 573 450 0 1685 488 1005 3178
9 32.5 75.4 16 0 67 0 387 28 128 280 380 573 450 0 1801 508 1209 3518
10 34.1 74.3 23 0 84 0 465 34 148 280 380 573 450 0 1909 528 1420 3857
11 35.5 73.1 31 0 98 0 520 40 166 280 380 573 450 0 1992 546 1606 4144
12 36.4 72.5 42 0 108 0 550 44 179 280 380 573 450 0 2047 559 1734 4340
13 36.8 72.2 53 0 112 0 630 46 184 280 380 573 450 0 2144 564 1791 4499
14 36.6 72.2 64 0 110 0 798 45 181 280 380 573 450 0 2320 561 1758 4639
*15 36.1 72.7 76 0 105 0 870 43 174 280 380 573 450 0 2397 554 1691 4642
16 35.3 73.1 88 0 96 0 821 39 163 280 380 573 450 0 2347 543 1573 4463
17 34.3 74.0 97 0 86 0 675 35 150 280 380 573 450 0 2196 530 1442 4168
18 33.1 74.9 101 0 74 0 454 30 135 280 380 573 450 0 1962 515 1284 3761

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-51-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F6_P. HOP VUA 02 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 6
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 4
Floor area(m2) 20.6
Depth of underground wall(m) 0.0
Ceiling height(m) 2.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 4.4 5.0 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 680 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-52-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F6_P. HOP VUA 02 6 1 1 Office 20.6 2.6 4 Summer 80.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 0 0 126 0 0 17 90 224 304 478 680 0 1525 394 803 2722
9 32.5 75.4 0 0 167 0 0 23 106 224 304 478 680 0 1572 410 967 2949
10 34.1 74.3 0 0 207 0 0 29 123 224 304 478 680 0 1618 427 1136 3181
11 35.5 73.1 0 0 243 0 0 34 138 224 304 478 680 0 1659 442 1285 3386
12 36.4 72.5 0 0 267 0 0 37 149 224 304 478 680 0 1686 453 1388 3527
*13 36.8 72.2 0 0 276 0 0 38 154 224 304 478 680 0 1696 458 1433 3587
14 36.6 72.2 0 0 271 0 0 37 151 224 304 478 680 0 1690 455 1406 3551
15 36.1 72.7 0 0 259 0 0 36 145 224 304 478 680 0 1677 449 1353 3479
16 35.3 73.1 0 0 238 0 0 33 136 224 304 478 680 0 1653 440 1259 3352
17 34.3 74.0 0 0 213 0 0 29 125 224 304 478 680 0 1624 429 1153 3206
18 33.1 74.9 0 0 182 0 0 25 112 224 304 478 680 0 1589 416 1027 3032

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-53-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F6_COMMERCIAL50 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 6
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 79
Floor area(m2) 260.3
Depth of underground wall(m) 0.0
Ceiling height(m) 2.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 5.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 10.4 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 15.3 12.4 0.0 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 15800 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-54-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F6_COMMERCIAL50 6 1 1 Office 260.3 2.6 79 Summer1580.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 72 0 370 0 2895 219 1141 4424 6004 6039 15800 0 29819 7145 15874 52838
9 32.5 75.4 117 0 491 0 2820 290 1345 4424 6004 6039 15800 0 29981 7349 19091 56421
10 34.1 74.3 165 0 612 0 2313 362 1560 4424 6004 6039 15800 0 29715 7564 22438 59717
11 35.5 73.1 210 0 717 0 1660 424 1749 4424 6004 6039 15800 0 29274 7753 25366 62393
12 36.4 72.5 242 0 785 0 1361 465 1883 4424 6004 6039 15800 0 29116 7887 27403 64406
*13 36.8 72.2 262 0 815 0 1345 482 1943 4424 6004 6039 15800 0 29167 7947 28308 65422
14 36.6 72.2 262 0 800 0 1264 473 1906 4424 6004 6039 15800 0 29062 7910 27770 64742
15 36.1 72.7 251 0 762 0 1126 451 1838 4424 6004 6039 15800 0 28853 7842 26719 63414
16 35.3 73.1 235 0 702 0 938 415 1714 4424 6004 6039 15800 0 28553 7718 24854 61125
17 34.3 74.0 217 0 626 0 716 371 1581 4424 6004 6039 15800 0 28193 7585 22780 58558
18 33.1 74.9 197 0 536 0 467 317 1421 4424 6004 6039 15800 0 27780 7425 20285 55490

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-55-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F6_P. PTGD PT Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 6
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 3
Floor area(m2) 15.1
Depth of underground wall(m) 0.0
Ceiling height(m) 2.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 2.9 0.0 0.0 5.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 450 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-56-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F6_P. PTGD PT 6 1 1 Office 15.1 2.6 3 Summer 60.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 0 0 106 0 0 13 66 168 228 350 450 0 1087 294 603 1984
9 32.5 75.4 0 0 140 0 0 17 78 168 228 350 450 0 1125 306 725 2156
10 34.1 74.3 0 0 174 0 0 21 91 168 228 350 450 0 1163 319 852 2334
11 35.5 73.1 0 0 204 0 0 25 101 168 228 350 450 0 1197 329 963 2489
12 36.4 72.5 0 0 224 0 0 27 109 168 228 350 450 0 1219 337 1041 2597
*13 36.8 72.2 0 0 232 0 0 28 113 168 228 350 450 0 1228 341 1075 2644
14 36.6 72.2 0 0 228 0 0 27 111 168 228 350 450 0 1223 339 1055 2617
15 36.1 72.7 0 0 218 0 0 26 107 168 228 350 450 0 1212 335 1015 2562
16 35.3 73.1 0 0 200 0 0 24 99 168 228 350 450 0 1192 327 944 2463
17 34.3 74.0 0 0 179 0 0 22 92 168 228 350 450 0 1169 320 865 2354
18 33.1 74.9 0 0 153 0 0 18 82 168 228 350 450 0 1139 310 771 2220

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-57-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F6_P. HOP NHO 03 Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 6
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 5
Floor area(m2) 9.5
Depth of underground wall(m) 0.0
Ceiling height(m) 2.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 3.3 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 450 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-58-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F6_P. HOP NHO 03 6 1 1 Office 9.5 2.6 5 Summer 100.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 0 0 44 0 0 8 42 280 380 220 450 0 1002 422 1005 2429
9 32.5 75.4 0 0 58 0 0 11 49 280 380 220 450 0 1019 429 1209 2657
10 34.1 74.3 0 0 73 0 0 13 57 280 380 220 450 0 1036 437 1420 2893
11 35.5 73.1 0 0 85 0 0 15 64 280 380 220 450 0 1050 444 1606 3100
12 36.4 72.5 0 0 94 0 0 17 69 280 380 220 450 0 1061 449 1734 3244
*13 36.8 72.2 0 0 97 0 0 18 71 280 380 220 450 0 1065 451 1791 3307
14 36.6 72.2 0 0 95 0 0 17 70 280 380 220 450 0 1062 450 1758 3270
15 36.1 72.7 0 0 91 0 0 16 67 280 380 220 450 0 1057 447 1691 3195
16 35.3 73.1 0 0 84 0 0 15 63 280 380 220 450 0 1049 443 1573 3065
17 34.3 74.0 0 0 75 0 0 14 58 280 380 220 450 0 1039 438 1442 2919
18 33.1 74.9 0 0 64 0 0 12 52 280 380 220 450 0 1026 432 1284 2742

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-59-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F6_KHU IN AN Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 6
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 1
Floor area(m2) 6.9
Depth of underground wall(m) 0.0
Ceiling height(m) 2.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 2.3 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 4000 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-60-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F6_KHU IN AN 6 1 1 Office 6.9 2.6 1 Summer 20.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 0 0 31 0 0 6 30 56 76 160 4000 0 4253 106 201 4560


9 32.5 75.4 0 0 41 0 0 8 36 56 76 160 4000 0 4265 112 242 4619
10 34.1 74.3 0 0 51 0 0 10 41 56 76 160 4000 0 4277 117 284 4678
11 35.5 73.1 0 0 60 0 0 11 46 56 76 160 4000 0 4287 122 321 4730
12 36.4 72.5 0 0 65 0 0 12 50 56 76 160 4000 0 4293 126 347 4766
*13 36.8 72.2 0 0 68 0 0 13 51 56 76 160 4000 0 4297 127 358 4782
14 36.6 72.2 0 0 66 0 0 13 51 56 76 160 4000 0 4295 127 352 4774
15 36.1 72.7 0 0 63 0 0 12 49 56 76 160 4000 0 4291 125 339 4755
16 35.3 73.1 0 0 58 0 0 11 45 56 76 160 4000 0 4285 121 314 4720
17 34.3 74.0 0 0 52 0 0 10 42 56 76 160 4000 0 4278 118 289 4685
18 33.1 74.9 0 0 44 0 0 8 38 56 76 160 4000 0 4268 114 257 4639

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-61-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F6_ME Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 6
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 1
Floor area(m2) 5.3
Depth of underground wall(m) 0.0
Ceiling height(m) 2.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 2.6 1.7 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 0 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-62-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F6_ME 6 1 1 Office 5.3 2.6 1 Summer 20.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 0 0 58 0 0 4 23 56 76 123 0 0 241 99 201 541


9 32.5 75.4 0 0 76 0 0 6 27 56 76 123 0 0 261 103 242 606
10 34.1 74.3 0 0 95 0 0 7 32 56 76 123 0 0 281 108 284 673
11 35.5 73.1 0 0 111 0 0 9 36 56 76 123 0 0 299 112 321 732
12 36.4 72.5 0 0 122 0 0 9 38 56 76 123 0 0 310 114 347 771
*13 36.8 72.2 0 0 127 0 0 10 40 56 76 123 0 0 316 116 358 790
14 36.6 72.2 0 0 124 0 0 10 39 56 76 123 0 0 313 115 352 780
15 36.1 72.7 0 0 119 0 0 9 37 56 76 123 0 0 307 113 339 759
16 35.3 73.1 0 0 109 0 0 8 35 56 76 123 0 0 296 111 314 721
17 34.3 74.0 0 0 97 0 0 8 32 56 76 123 0 0 284 108 289 681
18 33.1 74.9 0 0 83 0 0 6 29 56 76 123 0 0 268 105 257 630

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-63-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F7_ME Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 7
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 1
Floor area(m2) 5.6
Depth of underground wall(m) 0.0
Ceiling height(m) 2.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 5.6 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 0.0 2.1 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 200 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-64-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F7_ME 7 1 1 Office 5.6 2.6 1 Summer 20.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 0 13 28 0 0 5 25 56 76 130 200 0 432 101 201 734


9 32.5 75.4 0 21 37 0 0 6 29 56 76 130 200 0 450 105 242 797
10 34.1 74.3 0 36 46 0 0 8 34 56 76 130 200 0 476 110 284 870
11 35.5 73.1 0 59 54 0 0 9 38 56 76 130 200 0 508 114 321 943
12 36.4 72.5 0 87 60 0 0 10 41 56 76 130 200 0 543 117 347 1007
13 36.8 72.2 0 119 62 0 0 10 42 56 76 130 200 0 577 118 358 1053
14 36.6 72.2 0 150 61 0 0 10 41 56 76 130 200 0 607 117 352 1076
*15 36.1 72.7 0 173 58 0 0 10 40 56 76 130 200 0 627 116 339 1082
16 35.3 73.1 0 187 53 0 0 9 37 56 76 130 200 0 635 113 314 1062
17 34.3 74.0 0 189 47 0 0 8 34 56 76 130 200 0 630 110 289 1029
18 33.1 74.9 0 178 41 0 0 7 31 56 76 130 200 0 612 107 257 976

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-65-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F7_P. HOP NHO Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 7
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 5
Floor area(m2) 8.7
Depth of underground wall(m) 0.0
Ceiling height(m) 2.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 8.7 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 0.0 2.9 3.1 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 350 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-66-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F7_P. HOP NHO 7 1 1 Office 8.7 2.6 5 Summer 100.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 0 20 80 0 0 7 38 280 380 202 350 0 939 418 1005 2362
9 32.5 75.4 0 33 106 0 0 10 45 280 380 202 350 0 981 425 1209 2615
10 34.1 74.3 0 56 132 0 0 12 52 280 380 202 350 0 1032 432 1420 2884
11 35.5 73.1 0 91 155 0 0 14 58 280 380 202 350 0 1092 438 1606 3136
12 36.4 72.5 0 136 170 0 0 16 63 280 380 202 350 0 1154 443 1734 3331
13 36.8 72.2 0 185 176 0 0 16 65 280 380 202 350 0 1209 445 1791 3445
*14 36.6 72.2 0 233 174 0 0 16 64 280 380 202 350 0 1255 444 1758 3457
15 36.1 72.7 0 269 165 0 0 15 61 280 380 202 350 0 1281 441 1691 3413
16 35.3 73.1 0 290 152 0 0 14 57 280 380 202 350 0 1288 437 1573 3298
17 34.3 74.0 0 293 136 0 0 12 53 280 380 202 350 0 1273 433 1442 3148
18 33.1 74.9 0 277 116 0 0 11 47 280 380 202 350 0 1236 427 1284 2947

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-67-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F7_CNTT Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 7
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 113
Floor area(m2) 343.9
Depth of underground wall(m) 0.0
Ceiling height(m) 2.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 343.9 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 5.0 0.0 2.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 10.4 0.0 4.2 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 21.4 13.4 16.6 16.3 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 26600 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-68-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F7_CNTT 7 1 1 Office 343.9 2.6 113 Summer2260.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 84 799 905 0 3193 289 1508 6328 8588 7978 26600 0 46176 10096 22706 78978
9 32.5 75.4 133 1313 1199 0 3207 384 1777 6328 8588 7978 26600 0 47142 10365 27307 84814
10 34.1 74.3 188 2226 1494 0 2778 478 2062 6328 8588 7978 26600 0 48070 10650 32096 90816
11 35.5 73.1 241 3597 1753 0 2180 561 2310 6328 8588 7978 26600 0 49238 10898 36284 96420
12 36.4 72.5 284 5366 1918 0 1911 614 2488 6328 8588 7978 26600 0 50999 11076 39195 101270
13 36.8 72.2 315 7307 1993 0 1975 637 2567 6328 8588 7978 26600 0 53133 11155 40492 104780
*14 36.6 72.2 326 9191 1955 0 2062 626 2517 6328 8588 7978 26600 0 55066 11105 39721 105892
15 36.1 72.7 327 10618 1864 0 1996 596 2428 6328 8588 7978 26600 0 56307 11016 38219 105542
16 35.3 73.1 323 11475 1716 0 1759 549 2264 6328 8588 7978 26600 0 56728 10852 35551 103131
17 34.3 74.0 314 11589 1531 0 1391 490 2088 6328 8588 7978 26600 0 56221 10676 32584 99481
18 33.1 74.9 298 10961 1309 0 921 419 1877 6328 8588 7978 26600 0 54814 10465 29016 94295

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-69-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F5_HL TM Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 5
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 3
Floor area(m2) 17.3
Depth of underground wall(m) 0.0
Ceiling height(m) 2.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 0.0 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 8.8 0.0 0.0 1.9 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 0 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-70-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F5_HL TM 5 1 1 Office 17.3 2.6 3 Summer 60.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 0 0 142 0 0 15 76 168 228 401 0 0 726 304 603 1633
9 32.5 75.4 0 0 190 0 0 19 89 168 228 401 0 0 778 317 725 1820
10 34.1 74.3 0 0 236 0 0 24 104 168 228 401 0 0 829 332 852 2013
11 35.5 73.1 0 0 277 0 0 28 116 168 228 401 0 0 874 344 963 2181
12 36.4 72.5 0 0 303 0 0 31 125 168 228 401 0 0 903 353 1041 2297
*13 36.8 72.2 0 0 315 0 0 32 129 168 228 401 0 0 916 357 1075 2348
14 36.6 72.2 0 0 309 0 0 31 127 168 228 401 0 0 909 355 1055 2319
15 36.1 72.7 0 0 294 0 0 30 122 168 228 401 0 0 893 350 1015 2258
16 35.3 73.1 0 0 271 0 0 28 114 168 228 401 0 0 868 342 944 2154
17 34.3 74.0 0 0 242 0 0 25 105 168 228 401 0 0 836 333 865 2034
18 33.1 74.9 0 0 207 0 0 21 94 168 228 401 0 0 797 322 771 1890

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-71-
Room data(Input data)

Project name WINMART Design room temperature in summer(CDB) 26.0


Design room humidity in summer(%RH) 55.0
Address Internation Centre tower, 17 Ngo Quyen, Hoan Kiem, HN Design room temperature in winter(CDB) ----
Design room humidity in winter(%RH) ----
City Hanoi/Viet Nam
Fresh air intake Air volume(m3/h person)
Outer wall assembly Others Summer 20.0
Winter ----
Max. fresh air temp.
36.8
in summer(C)
infiltration ventilation(Times/h) Summer 0.20
Min. fresh air temp.
---- Winter ----
in winter(C)
Room name F6_HL TM Heating load internal heat gain[to ratio of cooling load internal heat gain](%)
Lighting:--- Persons:--- Equipments:---
Floor No 6
Window type <1> Clear 10mm
System No 1 Blind type Neutral tints
Shading factor/OHTC 0.60/4.80
No of rooms 1

Usage of Room Office

Ceiling board Available Lighting Fluorescent lamp(W/m2) 20.0


Incandescent lamp(W/m2) 0.0
Method of
Common ventilation fan
fresh air intake
No of persons 4
Floor area(m2) 17.6
Depth of underground wall(m) 0.0
Ceiling height(m) 2.6 !Underground wall is valid only when outer wall is negative value.
Height above attic(m) 0.8
Roof&Non-air-conditioned Overhead room, Flat roof , Inclined roof , Window glass
ceiling area(m2) 0.0 17.6 0.0 0.0 Humidifying method ----------

Non-air-conditioned Earth floor , with air layer, Without air layer, Pilotis Overall heat transfer coefficient (W/m2K) Wall type
floor area(m2) 0.0 0.0 0.0 0.0 Outer wall <1> 2.72 III

N E S W NE SE SW NW Shade Inner Wall <1> 2.62


Outer wall length(m) <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof(with ceiling board) 1.66 IV
Window area on <1> 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ceiling(with ceiling board) 1.95
outer wall(m2) Mezz floor(with air layer) 1.49
Non-conditioned inner<1> 0.0 0.0 0.0 0.0 9.2 0.0 0.0 0.0 Mezz floor(without air layer) 2.69
wall length(m) Pilotis 3.29
!Outer wall length with negative value is regarded as underground wall. Earth floor 0.90
Underground wall(depth<=2.4m) 1.56 (W/mK)
Cooling load heat gain Sensible heat, Latent heat Underground wall(depth>2.4m) 0.45
from equipments(W) 0 0
Safety factor Cooling 1.05
Heating ----
Operating time zone 8:00 to 18:00

Internal heatgaing schedule(%) Time 8 9 10 11 12 13 14 15 16 17 18


Lighting 100 100 100 100 100 100 100 100 100 100 100
Persons 100 100 100 100 100 100 100 100 100 100 100
Equipments 100 100 100 100 100 100 100 100 100 100 100

OHTC : Overall heat transfer coefficient

-72-
Table of room heat load
Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

F6_HL TM 6 1 1 Office 17.6 2.6 4 Summer 80.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 30.9 76.4 0 41 123 0 0 15 77 224 304 408 0 0 811 381 803 1995
9 32.5 75.4 0 67 163 0 0 20 91 224 304 408 0 0 882 395 967 2244
10 34.1 74.3 0 114 203 0 0 24 106 224 304 408 0 0 973 410 1136 2519
11 35.5 73.1 0 184 238 0 0 29 118 224 304 408 0 0 1083 422 1285 2790
12 36.4 72.5 0 275 261 0 0 31 127 224 304 408 0 0 1199 431 1388 3018
13 36.8 72.2 0 374 271 0 0 33 131 224 304 408 0 0 1310 435 1433 3178
14 36.6 72.2 0 470 266 0 0 32 129 224 304 408 0 0 1400 433 1406 3239
*15 36.1 72.7 0 543 253 0 0 31 124 224 304 408 0 0 1459 428 1353 3240
16 35.3 73.1 0 587 233 0 0 28 116 224 304 408 0 0 1480 420 1259 3159
17 34.3 74.0 0 593 208 0 0 25 107 224 304 408 0 0 1458 411 1153 3022
18 33.1 74.9 0 561 178 0 0 21 96 224 304 408 0 0 1392 400 1027 2819

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-73-