LOSSES OCCURED IN COOLING TOWER

1. BLOWDOWN LOSS (B)

2. EVAPORATION LOSS (E)

3. DRIFT LOSS (D)

Makeup water Required(M)

M= B+E+D

Range of Cooling Tower


=Hot water Temp- Cold water Temp

Approach of Cooling Tower


=Cold water Temp- Wet Bulb Temp

Efficiency of Cooling Tower


= Range / ( Range+ Approach) x 100 %

Where
Hot water Temp = Condensor water outlet Temp (34.6 Deg C )
[As per AHRI 550/590 std]
Cold water Temp = Condensor water inlet Temp ( 29.4 Deg C)
Wet Bulb Temp will as per location & season