Professional Documents
Culture Documents
Page 1 of 5
The Capacitor are connected to the supply at the load point and are connected in
parallel configuration.
Case study: Sizing a Capacitor for improvement of PF from 0.75 to 0.9.of a load of
100HP Motor.
∑ Since the load is in HP ,the same needs to be changed to KW;
1HP= 0.746 KW.
Page 2 of 5
∑ We have to find out the new angle ∅2, from the expression of Cos ∅2 =
0.90.
∑ New angle ∅2 = cos 0.90 = 25.841 degrees.
∑ New Kvar2 = KW x tan ∅2.
∑ Therefore the Capacitive Kvar to be added to nullify the Inductive Kvar is
as follows.
∑ Kvar (Capacitive) = Kvar1 − Kvar2
∑ Kvar (Capacitive)= Kw x (tan ∅ – tan∅ .)
∑ KVAR = 74.6 x (tan 41.409 degrees - tan 25.84 degrees).
∑ Kvar = 74.6(0.8819 - 0.4842)
∑ Kvar = 74.6 x 0.3977.
∑ Kvar = 29.6908. Ans.
∑ Say 30 Kvar.
As could be seen from above is 74.6 KW load is multiplied with 0.3977, which tallies
with the Table for correction of PF from 0.75 to o.9. (mf-0.398).
Page 3 of 5
Page 4 of 5
Automatic Power Factor Correction (APFC) Panel
Power Factor Improving:
∑ The compensation for motor should be calculated taking the details from the
rating plate of motor Or
∑ the capacitor should be rated for 1/3 of HP
Page 5 of 5