You are on page 1of 8

Boiler Cycling Considerations https://www.babcock.com/en/resources/learning-center/boiler-cycling-co...

Boiler Cycling Considerations

Boiler Cycling Considerations


Many fossil fuel-fired boilers are now experiencing load cycling or on/off cycling operation. These modes of
operation involve cycling a unit on and off line or reducing loads to absolute minimums in response to varying load
demand. This can be caused by daily or weekly load shifts experienced on nights and weekends, power generators
dispatching units to the grid which utilize a lower cost fuel, such as natural gas, or the availability of alternate and less
consistent generation sources such as solar or wind power.

Most of these units were originally designed for base loaded operation and not designed to accommodate frequent
on/off cycles. The stresses placed on the weld joints, headers, drums and attachments between expanding and
contracting parts, can cause failures after a finite number of cycles. Cycling operation can shorten the life span of such
equipment based on number and duration of cycles. A thorough condition assessment program can determine
potential equipment modifications that can make the unit more flexible and alleviate possible problem areas.
Technology developments for the newest units designed for cycling have made a wide variety of steam generator
modifications available to be retrofitted to baseload designs.

Cycling Effects and Solutions


In assessing a boiler’s ability to withstand cycling, those components most vulnerable to cycling are reviewed first.
These components are discussed from two standpoints: the operating methods which minimize cyclic damage, and
design modifications which permit the component to better withstand cycling conditions.

Cycle definition

Two types of cycling service are usually considered: load cycling and on/off cycling.

A load cycle is considered to start at full load, full temperature steady-state conditions. It goes through a load
reduction, then returns to the initial conditions. A typical load cycle is composed of three phases:

1. load reduction,
2. low load operation, and
3. reload.

A typical on/off cycle has four phases:

1. load reduction,
2. removal from operation
3. restart, and
4. reload.

The offline period can offer one area of potential for reducing cyclic damage. The following are issues related mainly to
on/off cycling.

Economizer thermal shock

On boilers that are on/off cycled, economizers often show more cyclic damage than other components. The economizer
receives water from the extraction feedwater heater system, and the inner metal surface temperature follows the
feedwater temperature with practically no time delay. As a result, high rates of metal temperature change can occur
with high local stresses.

Fig. 1 shows economizer inlet temperatures during an overnight shutdown cycle. The first two hours are for load
reduction, followed by eight hours of idle condition. Next, the boiler is fired in preparation for restart. The rates of
temperature change during the load decrease and increase are usually not excessive, but would represent load cycling
conditions for the economizer.

1 of 8 25-11/19, 07:05
Boiler Cycling Considerations https://www.babcock.com/en/resources/learning-center/boiler-cycling-co...

Fig. 1 Economizer temperatures during overnight shutdown cycles.

During the offline period, there is typically some air leakage through the boiler with a resulting decay in boiler
pressure. As this happens, the drum water level decreases. At the same time, the air passing through the boiler is
heated to near saturation temperature, and that air then heats the economizer. An economizer metal temperature can
increase at 30 to 50F/h (17 to 28C/h) during this period and can approach saturation temperatures. When the drum
level drops as the unit cools, the operator usually reestablishes drum level by adding feedwater so the unit is ready for
firing. Because there is no extraction steam available, the feedwater temperature is low. This slug of cold water quickly
cools the economizer, causing thermal shock as indicated by the solid lines in Fig. 1. Typically, the inlet header and
inlet tubes receive the greatest shock.

When the boiler is fired in preparation for turbine restart, rollup and synchronization, the economizer heats up rapidly,
often nearing saturation temperature. Feedwater flow is started when the initial load is applied to the turbine. Because
little extraction heating is available, feedwater temperature is initially low. A thermal shock can occur as extractions are
cut into feedwater heaters and the temperature can increase several hundred degrees F (C) in a few minutes.

Typically, early damage consists of cracks initiating in the tube bore holes of the inlet header which are closest to the
feedwater inlet connection.

Other damage has also been seen from this cyclic service. Outlet headers have shown damage similar to inlet headers.
Furthermore, some tube bank support systems cannot accommodate the high temperature differences between rows.

Solutions are available to reduce the frequency and magnitude of thermal shocks. These address the out-of-service and
restart conditions. One solution is called trickle feed cooling. Very small quantities of feedwater are frequently
introduced during the shutdown and restart periods. This prevents the inlet header from heating and reduces the
cooling rate during feedwater introduction. Because feedwater introduction is controlled to limit economizer
temperature rise, some drum blowdown may be necessary to prevent a high water level.

A second method of reducing thermal shock is to permit the economizer to reheat during the idle period and then to
provide higher temperature feedwater for restart. This can occur by pressurizing a high-pressure heater with steam
from an auxiliary source or from the drum of the unit. The quantity of steam required is low because it only heats the
initial low flow of feedwater.

Furnace subcooling

Drum boilers that have been subjected to on/off cycling have also been found to develop multiple cracks in lower
furnace wall tubes where the tubes are restrained from expansion or contraction. Typical cracking areas have been at

2 of 8 25-11/19, 07:05
Boiler Cycling Considerations https://www.babcock.com/en/resources/learning-center/boiler-cycling-co...

the lower windbox attachment where filler bars or plates are welded to the tubes. (See Fig. 2.)

Fig. 2 Lower windbox attachment cracking due to subcooling.

Investigation of these failures indicated that, during the shutdown or idle period, relatively cold (cooled below
saturation temperature) water settled in the lowest circuits of the furnace bottom. When circulation was started by
initial firing or the circulating pump, the cold-water interface is moved upward through the walls, rapidly cooling the
tubes. As the cooler water moves up the furnace its temperature gradient is decreased and as such the rate of cooling is
decreased, therefore reducing damage higher in the furnace. Experience indicates that if this subcooling can be limited
to 100F (56C), there is a low probability of damage.

An out-of-service circulating pump system may be used to limit the subcooling. (See Fig. 3.) This is a low capacity
pump that draws from the bottom of the downcomers and discharges water to the drum, therefore preventing the
stratification temperatures of water within the unit.

3 of 8 25-11/19, 07:05
Boiler Cycling Considerations https://www.babcock.com/en/resources/learning-center/boiler-cycling-co...

Fig. 3 Out-of-service circulating pump system.

Corrosion fatigue

The impact of on/off cycling continues to present itself to other areas of the boiler as the unit ages and the number of
cycles increases. Circuits such as supply tubes and risers are susceptible to damage given enough years in operation
and enough cycles. Owners must be particularly alert to damage in circuits that are outside the boiler enclosure and
pose greater safety hazards in the event of failure. B&W has prepared a plant service bulletin discussing this topic.

Tube leg flexibility

The enclosure walls of most boilers are water- or steam-cooled. The water-cooled circuits carry boiling water, and the
steam-cooled circuits carry steam from the drum. As a result, they operate near the saturation temperature
corresponding to the drum pressure. Whether the boiler is being fired or shut down, considerable heat absorption or
loss is necessary to change the temperature of the walls. As a result, they change temperature more slowly than the
other components.

The economizer, superheater and reheaters penetrate these walls; the penetrations are designed to be gas-tight. At the
point of penetration, the side-to-side expansion follows saturation temperature. However, the header that forms the
inlet or outlet of the component expands with the temperature of the steam or water that it contains. Fig. 4 shows the
typical motions of the header end and the outermost connecting leg for a superheater or reheater outlet. Note that the
greatest deflection is when the header temperature is at a maximum.

4 of 8 25-11/19, 07:05
Boiler Cycling Considerations https://www.babcock.com/en/resources/learning-center/boiler-cycling-co...

Fig. 4 Superheater tube leg flexibility.

In the case of economizers and the reheater inlet, the deflection is in the opposite direction because these headers
operate near or below saturation temperature. For these components the greatest temperature difference, and
therefore the greatest deflection, is at low loads.

Regardless of the direction, the greatest temperature difference produces the maximum differential expansion and the
maximum bending stresses in the connecting legs. The stress range and amplitude dictate component fatigue life.

The first indications of cyclic damage are external cracks on the tube-to-header welds or the stub-to-tube welds of the
outermost header legs. This damage is relatively easy to inspect and repair. Successive damage is also usually limited to
closely adjacent legs because they have experienced similar stress levels. Most sensitive are high-temperature headers
located at relatively short distances from the penetration seal on large units. On large boilers, the headers are long
which, when coupled with short outlet tube legs, will produce the greatest bending stresses at the header welds.

Steam drums

The cycling of utility drum boilers has the potential to produce significant variation in drum temperatures. The drum is
a large thick-walled vessel that inherently responds slowly to temperature changes. Top-to-bottom variations in drum
temperature can lead to drum humping, excessive stresses on connections, and fatigue in welds.

Any areas of significant temperature variations, including nozzle penetrations, have the potential to produce excessive
thermal stresses and drum damage over time, given enough cycles. Consequently, the drum must be addressed when
cycling operation is to be the norm.

The steam drum should be included in a condition assessment program to identify evidence of any damage that has
occurred. However, operating conditions that can lead to damage should be mitigated. Operating data should be
analyzed or instrumentation installed to assess drum upsets. Thermocouples can be installed on the drum to monitor
temperature differentials. A review of the boiler operating history can verify that the rate of pressure (saturation
temperature) changes are controlled. If cycling upsets cannot be controlled by changes to operating practices, system
upgrades may be necessary.

5 of 8 25-11/19, 07:05
Boiler Cycling Considerations https://www.babcock.com/en/resources/learning-center/boiler-cycling-co...

Cycling Boiler Circulation Upgrade

As previously mentioned, furnace subcooling, boiler-forced cooling during a shutdown, and intermittent cold feedwater
flow into the boiler during startup are three sources of thermal differentials and cyclic cracking. The thermal stresses
produced within the components may be sufficient to produce low cycle fatigue cracks. The solution in most cases is to
modify the boiler and/or feedwater system to prevent the sudden entry of cold water into hot boiler components.

When a boiler is experiencing cracking due to subcooling and cold feedwater flow upon startup, one solution is to
install an offline pump-assisted circulation system to reduce the thermal transients. The system, as shown in Fig. 5,
consists of an offline circulation pump, a thermal-sleeved tee connection between the offline pump and the feedwater
line, a connection line from the boiler downcomer to the pump, a warming bypass system, various valves, and a control
system.

Fig. 5 Offline recirculation system to reduce thermal shock.

The offline pump is operated only when the boiler is shut down. Its purpose is to provide a small amount of circulation
within the furnace circuit and through the economizer to prevent temperature stratification in the water circuits. The
tee connection permits the introduction of a small amount of hot water from the furnace into the feedwater stream
when feedwater is intermittently supplied to the boiler and before a steady feedwater flow is established. The warm
furnace water introduced at the tee connection raises the feedwater temperature enough to prevent thermal shock to
the economizer.

The connection contains an internal thermal sleeve that protects the tee from a thermal shock when cold feedwater is
first fed to the economizer. A control system monitors the feedwater temperature and flow and controls the
recirculation pump.

When the boiler startup sequence is initiated, the offline system is shut down and isolated. Warming lines permit
natural circulation through the pump when it is shut down and the boiler is off line.

Experience with offline recirculation systems has shown that thermal shock differentials can be reduced to less than
100F (56C) from previous levels of 200 to 400F (111 to 222C). Such a reduction may eliminate the fatigue cracking that
is associated with frequent unit cycling.

Load Cycling Effects and Solutions


The issues above are mainly related to on/off cycling. Load cycling to various ranges presents another set of unique
challenges. The main challenges relate to maintaining stable combustion, and the ability to maintain air quality
control system equipment (AQCS) in operation.

These challenges become more difficult to address as the desired minimum sustained load is reduced. Generally
desired operating ranges can be classified as:

1. turndown to higher values of approximately 40 to 50%,


2. middle range of 25 to 40%, and
3. the lowest range of house load (generating only enough electricity to power plant equipment) to 25%.

6 of 8 25-11/19, 07:05
Boiler Cycling Considerations https://www.babcock.com/en/resources/learning-center/boiler-cycling-co...

Flame stability

One of the major issues with load cycling is developing the necessary system(s) to maintain stable combustion during
low load operation. Modern wall-fired burners provide well controlled air-fuel mixing. The amount of mixing
varies with the firing rate of the burners. Acceptable air-fuel mixing is achieved at reduced boiler loads by operating
with fewer burners in service and by operating those burners at higher firing rates. Burner mixing can be induced by
using the primary air/pulverized coal stream, by using the secondary air, or by a combination of the two. Below a
certain load the burners will not have the ability to maintain a stable flame without the use of auxiliary fuel for support.

To minimize auxiliary fuel costs during periods where flame stabilization is needed, duel capacity igniters can be
utilized. The igniters operate at either of two capacities. One higher capacity will be at a class 1 input level at 10% of the
coal burner capacity per NFPA 85. The other lower capacity would be at 5% of the coal burner capacity, which NFPA 85
defines as a class 2 igniter, the smallest permitted for coal ignition. When a pulverizer is being started the, igniters will
operate at their full higher capacity, as required per NFPA 85. At all other times as permitted by NFPA 85, such as
when igniter support is desired for extended low pulverizer loading, the igniter input can be reduced to the lower class
2 capacity. While class 2 igniters cannot be used in all situations that a class 1 igniter may be used, class 2 igniters are
permitted to be used to stabilize the coal flame for low-load operation under specific prescribed conditions.

Pulverizer Turndown

Pulverizer turndown is a key in providing flexibility for boiler turndown. Generally, minimum turndown range is
limited to two pulverizers in operation. A single pulverizer in operation with auxiliary fuel risks tripping the unit if the
pulverizer trips. Primary air requirements are a function of the specific pulverizer design. Most pulverizers require 40
to 70% of their full-load primary air requirements at their minimum output level. In addition, the PA/PC mixture
traveling to the burners must be transported at a minimum of 3000 ft/min (15 m/s). This velocity serves to prevent the
coal particles from dropping out of suspension in horizontal runs of coal pipe. Minimum primary air flow is the greater
of the minimum PA flow required for the pulverizer or the minimum required to satisfy burner line velocity limits.

The primary air and coal mixture conveyed to the burners reaches a maximum velocity and solids loading at full
pulverizer load and follows the pulverizer output as mill loading is reduced. As the burner nozzle velocity increases, the
ignition point gradually moves farther from the burner. At some point, continued increases in nozzle velocity can lead
to blowoff of the flame, a potentially hazardous condition where coal ignition and flame stability are lost. The weight
ratio of coal to primary air typically reaches a peak of 0.4 to 0.65 at full load and a minimum of 0.15 to 0.3 for
minimum pulverizer load.

The combined use of the DSVS® classifier with spring load adjustor can improve pulverizer operating flexibility for
reduced turndown. The tendency toward a courser product can be controlled by the classifier. The classifier can also be
used to, in effect, increase the pulverizer working load at low outputs by increasing fineness to values higher than
would be achieved with a static classifier. An increase in pulverizer working load at low outputs may simultaneously
improve turndown and ignition stability.

If the economics of the low-load operation justify it, several options are available to provide uniform stable heat input.
Natural gas firing provides uniform stable heat input to the furnace for operation down to and including house load.
Dedicated smaller capacity pulverizers and burners are another option to provide the lower heat input from a lower
cost fuel. Half mill firing is utilized to provide even further turndown with the existing pulverizers. In this design half of
the burners are isolated while the other half operate in a more fuel rich environment providing stable minimum heat
input. Excess fuel-laden primary air is routed to a baghouse where the fuel is separated and returned to the mill while
the primary air is vented to the boiler. This excess primary air is metered to assure adequate combustion air is feeding
the active burners.

Air Quality Control

Maintaining air quality control systems in service at lower loads presents a special challenge. Nitrogen oxides (NOx)
can generally be controlled by combustion down to about 40% load with proper tuning and controls. NOx will increase
as load drops from about 40 to 25%; in this case, the selective catalytic reduction (SCR) system goes out of service.
Therefore, from a NOx control perspective, keeping the SCR in service to the lowest possible load requires one or more
design solutions. To prevent the formation of ammonium bisulfate from forming in the catalyst, SCR inlet flue gas
temperature should be maintained above a minimum injection temperature provided by the catalyst supplier. The
following options can be used to maintain gas temperatures entering the SCR:

1. Flue gas bypass – A portion of the flue gas is bypassed around the economizer and mixed with the flue gas that
passes through the economizer.
2. V-TempTM economizer – in this patented design the feedwater to the economizer is split into an overflow path
and an underflow path, each feeding from its own economizer inlet header. The economizer tube bank consists of
a mix of underflow and overflow tube sections fed from the underflow and overflow headers. Water through the
overflow and underflow section is biased as load decreases and recombined in the mix headers.
3. Split economizer – a portion of the economizer surface is relocated downstream of the SCR reactor.
4. Water recirculation – a portion of water from a source near saturation, like a downcomer, is mixed with the
feedwater to the economizer.
5. Water bypass – a portion of feedwater to the economizer is bypassed around the economizer and mixed with
the water that passes through the economizer.

7 of 8 25-11/19, 07:05
Boiler Cycling Considerations https://www.babcock.com/en/resources/learning-center/boiler-cycling-co...

6. Surface removal – a portion of the convective surface (superheater, reheater, or economizer) is removed.

AQCS equipment located downstream of the air heater requires that the exit gas temperature remain above limits for
proper operation as well. The equipment most susceptible to low gas temperatures at very low loads is a spray dryer
absorber (SDA) and pulse jet fabric filter (PJFF). The recommended minimum average gas temperature
entering this equipment is 220F (104C) for cold startup purposes. The minimum inlet gas temperature required to
meet the specified SO2 emissions rate is a function of the inlet SO2 concentration and the atomizer feed slurry solids
concentration. For a unit that is deep load cycled (house load to 25%), lower average gas temperatures may be possible
based on testing and experience.

Boilers are designed to maintain the exit gas temperature of the air heater to control corrosion of the cold-end surface.
The general assumption made is that the cold-end metal temperature is approximately equal to the average of the gas
outlet and the air inlet temperatures. Most air heaters are designed to operate with gas outlet temperature above the
acid dewpoint but minimum metal temperatures somewhat below the dewpoint, where the efficiency gain more than
offsets the additional maintenance costs. The measures used to control the air heater exit gas temperature can involve
heating of the entering air utilizing a heat exchanger, bypassing air around the air heater, hot air recirculation, or
bypassing flue gas around the air heater. These methods have certain disadvantages that must be evaluated prior to
implementation. The bypassing options, while more efficient at lower loads, suffer from undesirable leakage of air or
gas around closed dampers at high load leading to efficiency loss. The most utilized solution of heating entering air via
a heat exchanger may produce a higher heat rate penalty at the lowest load.

8 of 8 25-11/19, 07:05

You might also like