Tests to be conducted after Rewinding of Motor

Ref No
Date

Name plate details


Frame
Make Year kW Rpm Voltage Current PF Insulation
size

No load test & Winding resistance test


Ohms/ Ohms/ Insulation
Insulation
Voltage Current PF kW phase as phase resistance
level
per RTC measured value

2 Megohm
Bad
or less
2-5
Critical
Insulation resistance test- Phase to Ground Megohm
5-10
R Y B Megohm
Abnormal

10-50
Good
Megohm
50-100
Very good
Megohm
100
Megohm or Excellent
more
Remarks & Observations:
Terminal Board & Studs
Fan & Fan cover
Shaft and Key- Key way

Tested by Approved by
No-load power- IE2
(No-load input/ name plate output is for reference only)
kW 2 pole-Watts In % 4 pole- Watts In % 6 pole- Watts In %
0.37 45 12 65 18 90 24
0.55 60 11 105 19 120 22
0.75 90 12 120 16 135 18
1.1 121 11 106 10 140 13
1.5 255 17 117 8 145 10
2.2 256 12 186 8 242 11
3.7 279 8 208 6 248 7
5.5 337 6 286 5 272 5
7.5 349 5 285 4 396 5
11 396 4 376 3 540 5
15 433 3 444 3 556 4
18.5 470 3 577 3 682 4
22 655 3 623 3 692 3
30 891 3 810 3 885 3
37 1113 3 833 2 900 2
45 1136 3 909 2 945 2
55 1750 3 1037 2 1036 2
75 2517 3 1432 2 1600 2
90 2613 3 1727 2 1650 2
110 2700 2 2400 2 1753 2

The no-load power should be measured using a 3 phase power analyser which is
suitable for measurung Power Factor from 0.00 Lag to 0.00 Lead.

1 There are power analysers available which can measure from 0.20 lag to 0.20 lead
or 0.40 lag to 0.40 Lead which are unsuitable for measuring the no-load kW
accurately. Hence use accurate Power Analyser.

2 The above percentage of no-load power is indicative only. If the kW measured


after the reinding exceeds 2 times the indicated values above, decision can be
made to replace the motor.

3 Measuring no-load current is not indicative of the quality of the winding or the health
of the motor.

4 Measuring winding resistance using micro ohm meter is recommended for the copper
value restored while rewinding
IR Value for Electric motor
For electric motor, we used a insulation tester to measure the resistance of motor winding with earthing (E).
For rated voltage below 1KV, measured with a 500VDC Megger.
For rated voltage above 1KV, measured with a 1000VDC Megger.
In accordance with IEEE 43, clause 9.3, the following formula should be applied.
Min IR Value (For Rotating Machine) =(Rated voltage (v) /1000) + 1
Insulation resistance (IR) value for electric motor

As per IEEE 43
Standard 1974,
2000
IR Value
in MΩ
IR (Min)
For most windings made before about 1970, all field windings, and others not described below
= kV+1
IR (Min)
= 100 For most dc armature and ac windings built after about 1970 (form wound coils)

IR (Min)
For most machines with random -wound stator coils and form-wound coils rated below 1kV
= 5 MΩ
Example-1: For 11KV, Three Phase Motor.
IR Value =11+1=12 MΩ but as per IEEE43 It should be 100 MΩ
Example-2: For 415V,Three Phase Motor
IR Value =0.415+1=1.41 MΩ but as per IEEE43 It should be 5 MΩ.
As per IS 732 Min IR Value of Motor=(20XVoltage(p-p/(1000+2XKW)