System Basics
(1) Initiating device circuits and signaling line circuits that transmit an alarm or
supervisory signal, or notification appliance circuits that allow all connected
devices to operate during a single open or a nonsimultaneous single ground
fault on any circuit conductor, shall be designated as Class A
(2) Initiating device circuits and signaling line circuits that do not transmit an
alarm or supervisory signal, or notification appliance circuits that do not allow
all connected devices to operate beyond the location of a single open on any
circuit conductor, shall be designated as Class B
2007 NFPA 72, 6.4.2.2. An open or ground fault condition shall result in the
annunciation of a trouble signal at the protected premise within 200 seconds as
required in 4.4.7
Class B Circuits
4.7K
EOLR
•Conventional
•Addressable
•Analog Addressable
Conventional Systems
Conventional control panels range in size from 1 zone
to over 100 zones.
Zones typically consist of some or all of the initiating
devices in an area or floor of a building.
Some control panels zone capacity is expandable
while others are not, limiting its usefulness if a facility
adds additional buildings or rooms.
Conventional Systems
Zone 1
4.7K
EOLR
Zone 2
FIRE FIRE FIRE FIRE FIRE FIRE FIRE FIRE FIRE FIRE
FACP SILENT KNIGHT SILENT KNIGHT SILENT KNIGHT SILENT KNIGHT SILENT KNIGHT
NAC 1 4.7K
EOLR
SILENT KNIGHT
NAC 1 4.7K
EOLR
NAC #1
4.7K
EOLR
FIRE!
NAC #1
4.7K
EOLR
NAC #1
4.7K
4.7K
EOLR
EOLR
RJ RJ
NAC #1
4.7K
EOLR
FIRE FIRE
SILENT KNIGHT
Addressable
FACP Relay Module
(Fan Shutdown)
NAC #1
4.7K
EOLR
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
Addressable
FACP Relay Module
(Fan Shutdown) 003
NAC #1
4.7K
EOLR
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
Addressable
FACP Relay Module
(Fan Shutdown) 003
NAC #1
4.7K
EOLR
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
Addressable
FACP Relay Module
(Fan Shutdown) 003
NAC #1
4.7K
EOLR
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
Addressable
FACP Relay Module
(Fan Shutdown) 003
NAC #1
4.7K
EOLR
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
Addressable
FACP Relay Module
(Fan Shutdown) 003
NAC #1
4.7K
EOLR
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
Addressable
FACP Relay Module
(Fan Shutdown) 003
NAC #1
4.7K
EOLR
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
Addressable
FACP Relay Module
(Fan Shutdown) 003
NAC #1
4.7K
EOLR
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
Addressable
FACP Relay Module
(Fan Shutdown) 003
NAC #1
4.7K
EOLR
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
Addressable
FACP Relay Module
(Fan Shutdown) 003
NAC #1
4.7K
EOLR
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
Addressable
FACP Relay Module
(Fan Shutdown) 003
NAC #1
4.7K
EOLR
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
Addressable
FACP Relay Module
(Fan Shutdown) 003
NAC #1
4.7K
EOLR
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
Addressable
FACP Relay Module
(Fan Shutdown) 003
NAC #1
4.7K
EOLR
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
Addressable
FACP Relay Module
(Fan Shutdown) 003
NAC #1
4.7K
EOLR
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
Addressable
FACP Relay Module
(Fan Shutdown) 003
NAC #1
4.7K
EOLR
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
Addressable
FACP Relay Module
(Fan Shutdown) 003 FIRE!
NAC #1
4.7K
EOLR
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
Addressable
FACP Relay Module
(Fan Shutdown) 003
NAC #1
4.7K
EOLR
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
Addressable
FACP Relay Module
(Fan Shutdown) 003
RJ RJ
NAC #1
4.7K
EOLR
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
Addressable
FACP Relay Module
(Fan Shutdown) 003
NAC #1
4.7K
EOLR
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
Addressable
FACP Relay Module
(Fan Shutdown) 003 FIRE!
NAC #1
4.7K
EOLR
004
001 002 006
005
Addressable
Relay Module 003
(Fan Shutdown)
10K
EOLR
NAC #1
HEAT DETECTOR Supervision is still checked by
MECHANICAL ROOM polling. In addition an analog
POINT 001 A=062 value is transmitted to the
NORMAL F=190 panel for processing.
Analog Addressable Systems
Addressable
Addressable Addressable Input Module Addressable Addressable
Heat Sensor Smoke Sensor (Waterflow) Pull Station Smoke Detector
004
001 002 006
005
Addressable
Relay Module 003
(Fan Shutdown)
10K
EOLR
NAC #1
SMOKE DETECTOR Supervision is still checked by
LOBBY NORTH polling. In addition an analog
POINT 002 A=060 value is transmitted to the
NORMAL F=188 panel for processing.
Analog Addressable Systems
Addressable
Addressable Addressable Input Module Addressable Addressable
Heat Sensor Smoke Sensor (Waterflow) Pull Station Smoke Sensor
004
001 002 006
005
Addressable
Relay Module 003
(Fan Shutdown)
10K
EOLR
NAC #1
RELAY MODULE Supervision is still checked by
FAN SHUTDOWN polling. In addition an analog
POINT 003 A=N/A value is transmitted to the
NORMAL F=N/A panel for processing.
Analog Addressable Systems
Addressable
Addressable Addressable Input Module Addressable Addressable
Heat Sensor Smoke Sensor (Waterflow) Pull Station Smoke Sensor
004
001 002 006
005
Addressable
Relay Module 003
(Fan Shutdown)
10K
EOLR
NAC #1
INPUT MODULE Supervision is still checked by
WATERFLOW polling. In addition an analog
POINT 004 A=N/A value is transmitted to the
NORMAL F=N/A panel for processing.
Analog Addressable Systems
Addressable
Addressable Addressable Input Module Addressable Addressable
Heat Sensor Smoke Sensor (Waterflow) Pull Station Smoke Sensor
004
001 002 006
005
Addressable
Relay Module 003
(Fan Shutdown)
10K
EOLR
NAC #1
INPUT MODULE Supervision is still checked by
MANUAL PULL polling. In addition an analog
POINT 005 A=N/A value is transmitted to the
NORMAL F=N/A panel for processing.
Analog Addressable Systems
Addressable
Addressable Addressable Input Module Addressable Addressable
Heat Sensor Smoke Sensor (Waterflow) Pull Station Smoke Sensor
004
001 002 006
005
Addressable
Relay Module 003
(Fan Shutdown)
10K
EOLR
NAC #1
SMOKE DETECTOR Supervision is still checked by
FRONT DESK polling. In addition an analog
POINT 006 A=061 value is transmitted to the
NORMAL F=189 panel for processing.
Analog Addressable Systems
Addressable
Addressable Addressable Input Module Addressable Addressable
Heat Sensor Smoke Sensor (Waterflow) Pull Station Smoke Sensor
004
001 002 006
005
Addressable
Relay Module 003
(Fan Shutdown)
10K
EOLR
NAC #1
HEAT DETECTOR Supervision is still checked by
MECHANICAL ROOM polling. In addition an analog
POINT 001 A=062 value is transmitted to the
NORMAL F=190 panel for processing.
Analog Addressable Systems
Addressable
Addressable Addressable Input Module Addressable Addressable
Heat Sensor Smoke Sensor (Waterflow) Pull Station Smoke Sensor
004
001 002 006
005
Addressable
Relay Module 003
(Fan Shutdown)
10K
EOLR
NAC #1
SMOKE DETECTOR Supervision is still checked by
LOBBY NORTH polling. In addition an analog
POINT 002 A=060 value is transmitted to the
NORMAL F=188 panel for processing.
Analog Addressable Systems
Addressable
Addressable Addressable Input Module Addressable Addressable
Heat Sensor Smoke Sensor (Waterflow) Pull Station Smoke Sensor
004
001 002 006
005
Addressable
Relay Module 003
(Fan Shutdown)
10K
EOLR
NAC #1
RELAY MODULE Supervision is still checked by
FAN SHUTDOWN polling. In addition an analog
POINT 003 A=N/A value is transmitted to the
NORMAL F=N/A panel for processing.
Analog Addressable Systems
Addressable
Addressable Addressable Input Module Addressable Addressable
Heat Sensor Smoke Sensor (Waterflow) Pull Station Smoke Sensor
004
001 002 006
005
Addressable
Relay Module 003
(Fan Shutdown)
10K
EOLR
NAC #1
INPUT MODULE Supervision is still checked by
WATERFLOW polling. In addition an analog
POINT 004 A=N/A value is transmitted to the
NORMAL F=N/A panel for processing.
Analog Addressable Systems
Addressable
Addressable Addressable Input Module Addressable Addressable
Heat Sensor Smoke Sensor (Waterflow) Pull Station Smoke Sensor
004
001 002 006
005
Addressable
Relay Module 003
(Fan Shutdown)
10K
EOLR
NAC #1
INPUT MODULE Supervision is still checked by
MANUAL PULL polling. In addition an analog
POINT 005 A=N/A value is transmitted to the
NORMAL F=N/A panel for processing.
Analog Addressable Systems
Addressable
Addressable Addressable Input Module Addressable Addressable
Heat Sensor Smoke Sensor (Waterflow) Pull Station Smoke Sensor
004
001 002 006
005
Addressable
Relay Module 003
(Fan Shutdown)
10K
EOLR
NAC #1
SMOKE DETECTOR
FRONT DESK
POINT 006 A=061 < Replay
NORMAL F=189
Analog Addressable Systems
Addressable
Addressable Addressable Input Module Addressable Addressable
Heat Sensor Smoke Sensor (Waterflow) Pull Station Smoke Sensor
004
001 002 006
005
Addressable
Relay Module 003
(Fan Shutdown)
10K
EOLR
NAC #1
HEAT DETECTOR This analog value corresponds
MECHANICAL ROOM to the amount of heat or
POINT 001 A=062 smoke in that detectors area
NORMAL F=190 of coverage. Higher = more.
Analog Addressable Systems
Addressable
Addressable Addressable Input Module Addressable Addressable
Heat Sensor Smoke Sensor (Waterflow) Pull Station Smoke Sensor
004
001 002 006
005
Addressable
Relay Module 003
(Fan Shutdown)
10K
EOLR
NAC #1
HEAT DETECTOR If the analog value exceeds
MECHANICAL ROOM the alarm threshold, an alarm
POINT 001 A=062 occurs. This alarm threshold is
NORMAL F=190 calculated by the panel.
Analog Addressable Systems
Addressable
Addressable Addressable Input Module Addressable Addressable
Heat Sensor Smoke Sensor (Waterflow) Pull Station Smoke Sensor
004
001 002 006
005
Addressable
Relay Module 003
(Fan Shutdown)
10K
EOLR
NAC #1
INPUT MODULE Input/output modules do not
WATERFLOW relay analog values to the
POINT 004 A=N/A panel as they are monitoring
NORMAL F=N/A or controlling on/off devices.
Analog Addressable
Features
Digital
Comparing Protocols
Addressable
Addressable Addressable Input Module Addressable Addressable
Heat Detector Smoke Detector (Waterflow) Pull Station Smoke Detector
004
001 002 006
005
003
Addressable
Relay Module
(Fan Shutdown)
24v
looking for voltage rather
than the length of a pulse.
0 0 0
Digital Protocol
Even if a source of
interference causes
rounding off of the digital
pulses the voltage is still
1 1 1 1
24v
present for the panel to
determine the digital
0 0 0
value.
Digital Protocol
Digital protocol panels do
not typically require
special cabling since
interference does not
1 1 1 1
24v
pose any substantial
signal problems.
0 0 0
Retrofits can be done
using existing cable.
Non-digital Loop Response
When an alarm occurs on many non-digital protocol
systems, some panels must continue polling until it
reaches the alarming device, before an alarm is initiated.
Larger systems with hundreds of points can cause
delays initiating an alarm.
Non-Digital Loop Response
Addressable
Addressable Addressable Input Module Addressable Addressable
Heat Detector Smoke Detector (Waterflow) Pull Station Smoke Detector
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
003
Addressable
Relay Module
(Fan Shutdown)
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
FIRE! 003
Addressable
Relay Module
(Fan Shutdown)
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
FIRE! 003
Addressable
Relay Module
(Fan Shutdown)
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
FIRE! 003
Addressable
Relay Module
(Fan Shutdown)
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
FIRE! 003
Addressable
Relay Module
(Fan Shutdown)
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
FIRE! 003
Addressable
Relay Module
(Fan Shutdown)
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
FIRE! 003
Addressable
Relay Module
(Fan Shutdown)
ALARM
POINT 001 ALARM!
HEAT DETECTOR
15-Jan-00 3:10 PM
Non-Digital Loop Response
Addressable
Addressable Addressable Input Module Addressable Addressable
Heat Detector Smoke Detector (Waterflow) Pull Station Smoke Detector
FIRE FIRE
004
001 002 SILENT KNIGHT
006
005
FIRE! 003
Addressable
Relay Module
(Fan Shutdown)
004
001 002 006
005
003
Addressable
Relay Module
(Fan Shutdown)
004
001 002 006
005
FIRE! 003
Addressable
Relay Module
(Fan Shutdown)
004
001 002 006
005
FIRE! 003
Addressable
Relay Module
(Fan Shutdown)
004
001 002 006
005
FIRE! 003
Addressable
Relay Module
(Fan Shutdown)
ALARM
POINT 001 ALARM!
HEAT SENSOR
15-Jan-00 3:10 PM
THE END