You are on page 1of 2

S

N DESCRIPTION UNITS 3CX50+1CX35 SQ.MM


1 GENERAL  
Name of Manufacturer  
Voltage grade kV 6.35/11(12)kV ('E)
Standard Applicable   Generally as per IS:7098(part-2)
   
2 PHASE CONDUCTOR(INSULATED )  
i. No of phase Conductors   3
ii. Nominal cross-sectional area Sq. mm 50
Diameter of compacted conductor
iii. (Approx.) mm 8.4
iv. Max. D.C resistance at 20°C Ohm/km 0.641
v. Insulation thickness (Nominal) mm 3.6
vi. Insulation thickness (Minimum) mm 3.14
Stranded Compacted circular Aluminum of H4 Grade
vii. Material   as per Class 2 of IS:8130
viii. Max. D.C resistance at 20°C Ohm/km 0.641
x. Standard to which this material confirms   Class - 2 of IS:8130-1934
   
3 CONDUCTOR TEMPERATURE  
i. Rated Deg. C 90 Deg.C
ii. During short circuit Deg. C 250 Deg.C
4 CONDUCTOR SCREEN  
i. Material   Extruded Semi-Conducting compound
ii. Thickness(Min) mm 0.3
5 INSULATION  
i. Material   Extruded XLPE as per IS: 7098(Part-2)/85
ii. Thickness(Nom) mm 3.6
iii. Volume Resistivity (Min)   at 27 Deg. C:- 1x10 14 ohm-cm
    at 90 Deg. C:-1x10 12 ohm-cm
6 INSULATION SCREEN  
i. Material   Extruded Semi-Conducting compound
ii. Thickness (Min) mm 0.3
   
7 METALLIC SHIELD  
i. Material and Thickness   Copper Tape of 0.045 mm (Approx.) & 10% overlap
   

By colored strips of Red, Yellow and blue shall be provided


8 CORE COLOUR under copper tape and R,Y &B shall be printed on outer
sheath
 
   
9 OUTER SHEATH  
i. Material   Extruded PVC Type ST-2 as per IS :5831/84
ii. Thickness(Nom.)   2
iii. Colour   Black
   
10 MESSENGER CONDUCTOR(BARE)  
i. Nominal cross-sectional area Sq.mm 35
ii. Material   Stranded Aluminium alloy conductor as per IS:398P-4
iii. Approx. Breaking load kN 41
iv. Standard to which this material confirms   Generally as per IS:398 P-2/96
   
11 CABLE DATA  
i. Current carrying capacity  
a)In air Ampere 140
b)In Ground Ampere ???
ii. Embossing on any sheathed core   KEI cable Electric 6.35/11kV, Cable size ,Year of Manufacture
12 Drum Details   In non-Returnable wooden
i. Standard Drum Length   1000/500 meter with +/-5%
ii. Overall Quantity Tolerance   +/-5%