Air System Sizing Summary for MCC room

Project Name: A Reef Pump Station 04/05/2021


Prepared by: AEC 10:15AM

Air System Information


Air System Name MCC room Number of zones 1
Equipment Class SPLT AHU Floor Area 40.0 ft²
Air System Type SZCAV Location Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 1.0 Tons Load occurs at Jun 1700
Total coil load 12.1 MBH OA DB / WB 107.7 / 73.4 °F
Sensible coil load 11.7 MBH Entering DB / WB 76.6 / 64.5 °F
Coil CFM at Jun 1700 627 CFM Leaving DB / WB 59.2 / 58.1 °F
Max block CFM 627 CFM Coil ADP 57.3 °F
Sum of peak zone CFM 627 CFM Bypass Factor 0.100
Sensible heat ratio 0.968 Resulting RH 53 %
ft²/Ton 39.6 Design supply temp. 58.0 °F
BTU/(hr-ft²) 302.8 Zone T-stat Check 1 of 1 OK
Water flow @ 10.0 °F rise N/A Max zone temperature deviation 0.0 °F

Central Heating Coil Sizing Data


Max coil load 3.6 MBH Load occurs at Des Htg
Coil CFM at Des Htg 627 CFM BTU/(hr-ft²) 90.7
Max coil CFM 627 CFM Ent. DB / Lvg DB 69.6 / 75.0 °F
Water flow @ 20.0 °F drop N/A

Supply Fan Sizing Data


Actual max CFM 627 CFM Fan motor BHP 0.00 BHP
Standard CFM 625 CFM Fan motor kW 0.00 kW
Actual max CFM/ft² 15.68 CFM/ft² Fan static 0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM 12 CFM CFM/person 6.20 CFM/person
CFM/ft² 0.31 CFM/ft²

Hourly Analysis Program v4.90 Page 1 of 6


Zone Sizing Summary for MCC room
Project Name: A Reef Pump Station 04/05/2021
Prepared by: AEC 10:15AM

Air System Information


Air System Name MCC room Number of zones 1
Equipment Class SPLT AHU Floor Area 40.0 ft²
Air System Type SZCAV Location Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 11.5 627 627 Jun 1700 3.4 40.0 15.68

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
MCC room 1 11.5 Jun 1700 627 3.4 40.0 15.68

Hourly Analysis Program v4.90 Page 2 of 6


Air System Design Load Summary for MCC room
Project Name: A Reef Pump Station 04/05/2021
Prepared by: AEC 10:15AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 107.7 °F / 73.4 °F HEATING OA DB / WB 52.0 °F / 43.6 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 226 ft² 7728 - 226 ft² 2828 -
Roof Transmission 40 ft² 2286 - 40 ft² 546 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 50 W 171 - 0 0 -
Task Lighting 50 W 171 - 0 0 -
Electric Equipment 185 W 631 - 0 0 -
People 2 490 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 11476 410 - 3374 0
Zone Conditioning - 11300 410 - 3388 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 627 CFM 0 - 627 CFM 0 -
Ventilation Load 12 CFM 423 -23 12 CFM 240 1
Supply Fan Load 627 CFM 0 - 627 CFM 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 11724 387 - 3628 1
Central Cooling Coil - 11724 388 - 0 0
Central Heating Coil - 0 - - 3628 -
>> Total Conditioning - 11724 388 - 3628 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 6


System Psychrometrics for MCC room
Project Name: A Reef Pump Station 04/05/2021
Prepared by: AEC 10:15AM

June DESIGN COOLING DAY, 1700

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 107.7 0.00980 12 400 423 -23
Vent - Return Mixing Outlet 76.6 0.01019 627 1293 - -
Central Cooling Coil Outlet 59.2 0.01005 627 1293 11724 388
Central Heating Coil Outlet 59.2 0.01005 627 1293 0 -
Supply Fan Outlet 59.2 0.01005 627 1293 0 -
Cold Supply Duct Outlet 59.2 0.01005 627 1293 - -
Zone Air - 76.0 0.01019 627 1311 11300 410
Return Plenum Outlet 76.0 0.01019 627 1311 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.077 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4731.5 BTU/(hr-CFM)
Site Altitude = 88.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 11476 Cooling 11300 76.0 627 1311 0 0

Hourly Analysis Program v4.90 Page 4 of 6


System Psychrometrics for MCC room
Project Name: A Reef Pump Station 04/05/2021
Prepared by: AEC 10:15AM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 52.0 0.00409 12 400 -240 -1
Vent - Return Mixing Outlet 69.6 0.00410 627 792 - -
Central Cooling Coil Outlet 69.6 0.00410 627 792 0 0
Central Heating Coil Outlet 75.0 0.00410 627 792 3628 -
Supply Fan Outlet 75.0 0.00410 627 792 0 -
Cold Supply Duct Outlet 75.0 0.00410 627 792 - -
Zone Air - 70.0 0.00410 627 800 -3388 0
Return Plenum Outlet 70.0 0.00410 627 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.077 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4731.5 BTU/(hr-CFM)
Site Altitude = 88.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -3374 Heating -3388 70.0 627 800 0 0

Hourly Analysis Program v4.90 Page 5 of 6


Psychrometric Analysis for MCC room
Project Name: A Reef Pump Station 04/05/2021
Prepared by: AEC 10:15AM

Hourly Analysis Program v4.90 Page 6 of 6