Motor Fan Overtravel (Sec) :: Complete Lifts Lisa Controller
Motor Fan Overtravel (Sec) :: Complete Lifts Lisa Controller
LiSA CONTROLLER
- set the switch-off retardation to a very low value (e.g. 5 ms) direction signal will be switched off immediately after
v0-signal. After that the travel contactors are switched off as soon as the time has elapsed that is set by this
parameter "interval between direction off and travel contactor off" (approx. 1500 ms).
Start: End of braking retardation
As soon as retarded switching off has elapsed.
Speed control starts slowing down to speed 0 (electric stop).
End: time elapsed.
LiSA switches travel contactors K3 and K3Z off.
Interrogation in case of traction elevators: