Professional Documents
Culture Documents
ALSPA HMI V6
Reference Manual
SH/SH
REFERENCE LG REV ENTITY FORMAT NUM SH
END
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the
information contained therein. Reproduction, use or disclosure to third parties without express
authority is strictly forbidden.
TABLE OF CONTENTS
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
The Alarms and Events Viewer reference manual provides the complete description
of the alarms and events of ALSPA HMI, the plant supervision and monitoring
interface of the ALSPA® Control System.
The Alarms and Events Viewer helps the operator to view, analyse and manage the
real-time and Historian alarms and events of the plant. This enables the operator to
take corrective actions whenever required.
This document is intended for the operators and engineers of a power plant.
Hardware repair
Annual preventive maintenance
Telephone, e-mail, fax, remote maintenance, Web facilities
On site intervention
Software maintenance
Training session for commissioning engineers and customer users.
Contact: helpdesk.control-systems@power.alstom.com
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
DANGER
WARNING
CAUTION
ELECTRICAL WARNING
Refers to a document.
Refers to a Medium.
This document is based on information available at the time of its publication. While efforts have been
made to be accurate, the information contained herein does not purport to cover all details or variations
in hardware or software, nor to provide for every possible contingency in connection with installation,
operation, or maintenance.
Features may be described herein which are not present in all systems. Alstom assumes no obligation
of notice to holders of this document with respect to changes subsequently made.
In this publication, no mention is made of rights with respect to trademarks or trade names that may
attach to certain words or signs. The absence of such mention, however, in no way implies there is no
protection.
Partial reproduction of this document is authorized, but limited to internal use, for information only and
for no commercial purpose. However, such authorization is granted only on the express condition that
any partial copy of the document bears a mention of its property, including the copyright statement.
ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of
ALSTOM. The other names mentioned, registered or not, are the property of their respective
companies.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
ELECTRICAL WARNING
ELECTRICAL PROTECTION
CAUTION
CAUTION
The ALSPA control system equipment has been developed, manufactured and
tested to comply with the relevant standards.
All these standards are indicated in the following document
[STD&COD] - ALSPA Series 6 - Standards and Codes - refer to the
documents list of the project.
In order to achieve optimum operation of the equipment, the user must always keep
in mind that the standards should be complied with.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
1.6 Glossary
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
The Alarms and Events Viewer of the ALSPA HMI displays the alarms and events of
the plant. It enables the operator to analyse and manage the real-time and Historian
alarms and events of the plant.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
2.3 Workspace
The workspace is an area dedicated to the ALSPA HMI on ALSPA HMI operator
workstation* screen.
The workspace is composed of the following graphic objects:
Explorer
Work area which the ALSPA HMI viewers* occupy
Alarm bar
Status bar
Workspace configurator
For more information on the workspace, see [HMI_WORK] (cf. 1.7 List of
Referenced Documents).
2.4 Explorer
The Explorer allows navigating and accessing the data and functions of the plant
(Historic data of variables, Trend, Mimics, Sequence monitoring functions…).
The Explorer gives access to the following tabs:
Plant: explores the data and functions of the plant
Groups: explores the HMI functions groups
Favorites: explores all the shortcuts and the key shortcuts lists
The Explorer also includes a small window called Clipboard. The clipboard
temporarily holds the variables and /or the results of the function search.
For more information on the Explorer, see [HMI_EXPL] (cf. 1.7 List of
Referenced Documents).
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
The Alarms and Events viewer can be opened in different operational modes.
The table below explains the operational modes of the Alarms and Events Viewer:
Mode Description
Alarm Points Shows only the real-time alarms from ALSPA HMI real-time
database and not from Historian database.
This mode shows only the latest state of an alarm.
Only the Alarm Points mode allows acknowledging the alarms.
The alarm acknowledgement of the Alarms and Events Viewer indicates that an
operator is aware of the alarm raised.
The features of alarm acknowledgement are:
The alarm acknowledgement can be performed in any operator station by the
operators with the appropriate rights.
For more information on the operator rights, see [HMI_WORK] (cf. 1.7 List
of Referenced Documents).
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
2.7 Filters
The filters of the Alarms and Events Viewer help to display the sub-set of the alarms
and/or events, or variables.
The filters can be classified into the following categories:
Alarm state quick filter
Alarm category quick filter
Alarm level quick filter
Advance filter
Variables properties quick filter
The table below explains the types of filters of the Alarms and Events Viewer:
Filter Categories Description
Alarm state quick Allows filtering the alarms and/or events based on the
filter acknowledgement of their appearance and disappearance.
The different states are:
the alarms which are active and not acknowledged
the alarms, which are active and acknowledged
the alarms which are inactive and their appearance
unacknowledged
the alarms, which are inactive and their disappearance
unacknowledged
Alarm category Allows filtering the alarms and/or events based on the
quick filter following categories:
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Information on the filters in the Alarms and Events Viewer are available in
the later section of this document (cf. 4.2.3,Advanced Filter Screen).
The features of the filters are:
The filters are available in all the operational modes of the Alarms and Events
Viewer.
The filters applied on a list of alarms and/or events or variables are saved in the
user’s workspace.
The next time when the operator logs into the ALSPA HMI, the viewer
automatically displays the list of alarms and/or events or variables with the same
filters applied.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
In the ALSPA HMI, the Alarms and Events Viewer can be opened from the following
components:
Functional structure
System structure
Mimics
Single variable
Set alarm bar
Another viewer
Home icon
Shortcuts / Key Shortcuts
The opened Alarms and Events Viewer can be displayed (made active) from the
viewers’ tabs with the alarms and events viewer icon of the respective operational
mode (for example, Alarm Points mode ) at the top of the viewer.
More information on the active viewer’s tab is available in the later section
of this document (cf. 4.1,Active Viewer’s Tab).
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
This number excludes windows such as: Last alarm view, Last 2 alarms
view, Last 3 alarms view, real time and Historian views.
Alarms and Events Viewer can be opened from the contextual menu of the nodes in
the Functional Structure of the Plant tab of the Explorer.
The opening path is:
Explorer > Plant > Functional Structure > (contextual menu of any node) >
View Alarms / Events Viewer
The figure below shows how to open the Alarms and Events Viewer from the nodes
of the Functional Structure:
Alarms and Events Viewer can be opened from the contextual menu of the controller
node of the System Structure in the Plant tab of the Explorer.
The opening path is:
Explorer > Plant > System Structure > (contextual menu of any Cell) > View
Cell Alarms
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Alarms and Events Viewer can be opened from the contextual menu of a mimic in
the Groups tab of the Explorer.
The opening path is:
Explorer > Groups > Mimics > (contextual menu of any mimic) > Open ’Alarms
to Mimic’
The figure below shows how to open the Alarms and Events Viewer from a mimic:
The Alarms and Events Viewer can also be opened for a single variable .
The single variable is available in the Explorer (e.g., in the Functional Structure), in
the viewers in the work area (e.g., Y=f(t) Curves Viewer, Variables List Viewer etc.)
The contextual menu of a single variable provides an item to open the Alarms and
Events Viewer.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
The Alarms and Events Viewer can be opened from the sets/zones displayed in the
alarm bar.
A click on a zone in the alarm bar displays the Alarms and Events Viewer in the
work area for that zone.
More information on the alarm bar is available in the later section of this
document (cf. Section 8,Zones Management).
The Alarms and Events Viewer can be opened from another viewer as given below:
by an associated view (in the standard viewer toolbar)
For more information on the associated view, see [HMI_WORK] (cf. 1.7
List of Referenced Documents).
by a direct link available in Procedure/Alarm sheets
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
The Alarms and Events Viewer can be opened from the Home icon ( ) in the
top frame of the ALSPA HMI operator interface.
A click on the Home icon shows a menu with the items to access the ALSPA HMI
viewers and tools.
To open the Alarms and Events Viewer, the opening path is:
Note : Only the previous seven operational modes of the viewer can be opened from the home
icon.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
For an Alarms and Events Viewer once opened, a keyboard shortcut can be created
so that the viewer is added to the Key Shortcuts under the Favorites tab of the
Explorer.
The same viewer can be added to the Shortcuts under the Favorites tab of the
Explorer. This is done by using ”Add to favorites” icon ( ) of the functions toolbar.
Information on the functions toolbar is available in the later section of this
document (cf. 4.2,Functions Toolbar).
For more information on the Station and Private, see [HMI_WORK] (cf.
1.7 List of Referenced Documents).
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
The Alarms and Events Viewer can also be opened by just pressing the
corresponding function keys (”F10” in the above example).
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
When the Alarms and Events Viewer is opened, it occupies the work area of the
ALSPA HMI.
The Alarms and Events Viewer is composed of the following three graphic objects:
Active Viewer’s tab (cf. 4.1,Active Viewer’s Tab)
Functions toolbar (cf. 4.2,Functions Toolbar)
Data list (cf. 4.3,Data List)
The figure below shows the graphic objects of the Alarms and Events Viewer:
The viewers’ tabs allow the operator to navigate through the opened viewers.
The active viewer’s tab refers to the currently displayed viewer.
The tab of the Alarms and Events Viewer has the alarms and events viewer icon
(which depends on the operational mode of the viewer) along with the details of the
component from which the viewer is opened
Information on the alarms and events viewer icons of different operational
modes is available in the later section of this document (cf. 4.2,Functions
Toolbar).
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
For more information on the viewers’ tabs bar, see [HMI_WORK] (cf. 1.7
List of Referenced Documents).
The functions toolbar allows performing different functions such as changing mode,
applying filters, printing and saving the filters etc.
The table below shows the picture of the functions toolbar for each operational
mode of the Alarms and Events Viewer:
Mode Functions Toolbar
Alarm Points
Real-time
Alarms
Real-time
Events
Historian
Alarms and
Events
Variables List
Variables list.
Allows clearing the alarms currently
displayed in the viewer. Real-Time
Alarms
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Events;
Historian Alarms
and Events.
Alarm Acknowledgement
Image Description Available Modes
Allows taking the control to acknowledge
the alarms. Alarm Points
Allows acknowledging all the selected
alarms of the Alarm viewer in a single
click.
Allows acknowledging all the visible
alarms in the Alarm viewer in a single
click.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Click on “all alarms” icon ( ) to acknowledge all the visible alarms of the
data list or “selected and visible alarms” icon ( ) to acknowledge only the
selected and visible alarms of the data list.
It is also possible to acknowledge alarms through contextual menu of the
alarm variables in Alarm Points mode (cf. 3.4,Opening from the Single
Variable).
More information on the acknowledgement of an alarm is available in the
earlier section of this document (cf. 5.4,Acknowledgement and Selection).
Alarm Quantity
Image Description Available Modes
Shows the number of
unacknowledged alarms and the total Alarm Points
number of alarms and currently
displayed in the data list of the
viewer.
The quantity displayed takes into
consideration, the filters and the
accessible zones.
Shows the total number of alarms All modes except
and/or events displayed in the
viewer. Alarm Points
Displayed when the list saturated All modes except
Real Time
Events
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Advanced Filters
Image Description Available Modes
Shows the advanced filter screen to select the All modes
sophisticated filtering criteria* to be applied on
the alarms and/or events or the variables in
the viewer.
3. Click the “save” icon ( ) in the filter toolbar of the advanced filter screen.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
icon ( ).
If the operator does not want to save the filters, then the step 3 and 4 can
be skipped.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
For more information on the icons of the standard viewer toolbar, see
[HMI_WORK] (cf. 1.7 List of Referenced Documents).
A click on the tools icon ( ) of the functions toolbar shows the following menu:
A click on the “Select database” icon ( ) of the functions toolbar opens the
following Historian window:
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
The dates can also be selected from the calendar that is displayed by the
drop down arrow.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
A click on advanced filter icon ( ) in any mode of the Alarms and Events Viewer
opens the following Advanced Filter Form window:
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Allows deleting the selected filter from the Public Filters or Private Filters.
Note: Only the operator with appropriate rights can delete the public
filters.
Tabs
The tabs available in the advanced filter screen differs according to the operational
modes.
The table below gives the details of the tabs, their description and the modes in
which they are available:
Tab Description Available Modes
Signal Type Allows filtering the data list with All modes
different types of alarms and
variables.
Process Alarm Allows filtering the variables of
Condition different thresholds and state Alarm Points ;
change.
Real-time Alarms;
Historian Alarms
and Events.
Process Signal Allows filtering the events of
Event different thresholds and state Real-time Events;
change.
Process Signal Allows filtering the variables of
State different thresholds and state Variables List
change.
Sensor Alarm Allows filtering the variables
condition responsible for various faults and Alarm Points ;
limits attainment.
Real-time Alarms;
Historian Alarms
and Events.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Variables List
Event Type and Allows filtering the variables for
Date Time sequence monitoring, Real-time Events;
Acknowledgement, comment or
operator Historian Alarms
and Events.
Extended Filter Allows adding more filter All modes
conditions to the data list using
logical “AND” and ”OR” operators.
ID filter Allows filtering the variables with All modes
the various ids.
Priority Level Allows filtering the data list with the All modes, except
different types of Priorities
Variables List
Filter Windows
Signal Type
Variables
List.
System Allows filtering the variables
associated to the system alarms. Real-time
Alarms;
Historian
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Historian
Alarms and
Events.
Variables
List
Multistate Allows filtering the multi-state
variables, which represent the state,
value or process operations of the
variable by the numerical values.
Command Allows filtering the command
variables, which represent the logical
commands transmitted to controllers.
Masked Allows filtering the masked variables.
Historian
Alarms and
Events
UnMasked Allows filtering the unmasked
variables.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Extended Filter:
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Common buttons:
All
The All button, if present in the filter window, acts as a switch. It selects and
deselects all the filter options
OK
Confirms the selections and closes the window. Then it displays the Alarms and
Events Viewer listing all the alarms and/or events or variables matching the filter
criteria.
Cancel
The data list allows viewing the various properties of the variables in different
operational modes of the Alarms and Events Viewer.
The table below shows the picture of the data list for each operational mode of the
Alarms and Events Viewer:
Mode Data List
Alarm
Points
Real-
time
Alarms
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Historian
Alarms
and
Events
Variables
List
The selection of the display columns is done by right clicking on the column titles
band. Find her under the selection menu for each mode.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Real-time
Alarms
Variables List
Unit Shows the unit of the analog variables.
The field shows no value for Boolean variables.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Historian
Alarms and
Events
State Shows the state corresponding to the thresholds All modes,
and limits (LO LO, HI etc) for the analog except:
variables.
The field shows the state label corresponding to Variables
the value (0 or 1) for the Boolean variables. List
In case of sensor fault, the state label displays
the sensor fault icon.
Status Shows the status of the variable which can be:
Empty field – Indicates On monitoring (for Alarm
analog and Boolean) Points ;
Locked ( ) Real-time
Alarms mode ;
On Test ( )
When the intervention is Normal, the field is Variables
empty. List
Doubt Shows the letter ”D” only when the variable is
doubtful.
Otherwise, the field is empty.
Valid
Shows the icon when the variable is invalid.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Real-time
Alarms ;
Variables
List
Alarm Comment Rev Req column:
Indicates the availability of comment for the Alarm
alarm acknowledgement. Points;
Real-time
Alarms
Mimic Shows the mimic id, to which the alarms and/or All Modes
events is associated.
Cell Shows the number of the cell, to which the
alarms and/or events belongs. Real-time
Events mode;
Historian
Alarms and
Events
Station Indicates the operator station where comes from
the action.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
The contextual menu in the data list of the viewer provides various items to view the
alarms, events or variables in different viewers.
The figure below shows the contextual menu:
Description of items:
Item Description
Acknowledge Alarm Allows acknowledging the alarms.
with One Comment
It displays a window to enter a comment on the alarm and
after validation of operator rights, acknowledges the
alarm.
The item is available only in the Alarm Points mode.
Open Shows a sub-menu which gives a list of Viewers with
which the variable can be opened.
- Variables List view Opens the Variables List Viewer in the work area for the
selected variable.
-Y=f(t) Curve view Opens the Y=f(t) Curves Viewer in real-time mode for the
selected variable in the work area.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
The fact that the line represents a sensor fault is shown by the symbol .
Any other process alarm messages linked to this variable are flagged as invalid.
The occurrence of another sensor fault causes a new alarm row to appear.
On appearance of an alarm, the color block of alarm row corresponds to the urgency
degree. The color block of alarm line reverts to "normal state color" when the
variable quits the alarm state. This color can be configured for each degree.
The acknowledgement button at the start of the row is displayed:
In the color of the degree of urgency when acknowledgement of the appearance
of an alarm is required.
In the "normal state color" when acknowledgement of the disappearance of an
alarm is required.
The color of the urgency degree (for color block or acknowledgement button) can be
configured for each variable and can be a flashing color.
the button in the alarm toolbar. This action acknowledges only the selected
and visible alarms.
If more than 50 alarms are selected then only the visible alarms are kept
selected when an operator actions redisplays the list.
To acknowledge all the visible alarms, click the button in the alarm toolbar.
The "Standard" mode of the Alarm Point viewer is designed for a stable display of
the viewer in case of a new alarm appearance or reappearance of existing alarms
(cf. Section 5,Dynamic principles of the Alarm Point Viewer).
The "Automatic sorting" mode of the Alarm Point viewer is designed for a dynamic
display of the viewer as per selected chronology in case of new alarm appearance
or reappearance of the existing alarms.
With the "Automatic Sorting" mode:
A new alarm always appears at the top or bottom of the current alarm list based
on the chronology selected.
If the Alarm Point Viewer is sorted on KKS, the new alarm appears in the
start/middle/end of the list based on the KKS of the alarm variable.
The list automatically sorts after insertion of each new alarm as per the selected
chronology.
The acknowledgement of alarms is always preceded by the selection of the
alarms to acknowledge.
The rules of acknowledgement with automatic sorting are described in
§6.2.
By default, a freshly opened Alarm Point viewer is sorted in anti-chronological
order (the more recent at the top)
The sorting can be changed to chronological or anti-chronological order by
clicking the time column header.
Before acknowledging the alarm, the operator must select the alarm or the group of
alarms to be acknowledged (cf. 5.4,Acknowledgement and Selection).
In the "automatic sorting" mode, concerning the selection behaviour, the only
difference with the "Standard" mode is when clicking on the alarm symbol ( ) at
the beginning of the alarm row:
If the row is not selected the selection will be done.
If the row is already selected, the alarms will be acknowledged.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
In the case of the Advanced Alarm Management option, when the alarm list is
The "Automatic Sorting" option is configured in the HMI configuration file on operator
station.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
7.1 Principles
To catch the attention of the operator, an alarm can be associated to a sound called
a “horn”. The configuration of the horn is done in Controcad.
Depending on the configuration, the horn can be triggered:
when an alarm appears,
when an alarm disappears,
when an alarm appears and disappears.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
The horn can be acknowledged from the alarm bar with the audible alarm icon:
When a new alarm appears or disappears, the horn keeps playing till it is
acknowledged. The audible alarm icon flashes yellow.
Clicking the audible alarm icon acknowledges the horn that is to say stops the sound
on all the stations until a new alarm appears or disappears.
Clicking the audible alarm icon is the only way to stop the sound.
To disable the sound on the station, click the drop-down arrow of the audible alarm
icon and choose Mute Station Sound:
When the sound is disabled, the audible alarm icon becomes and no sound
is produced thereafter for any alarm.
The sound can be reactivated by clicking the drop-down arrow and choosing Enable
Station Sound:
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
When you acknowledge the horn using the audible alarm icon (cf. 7.2
Acknowledging the horn), the horn stops even if the alarms are not all
acknowledged. When a new alarm appears, the system reassesses the
acknowledgement state of all the alarms and the horn sounds for the
highest priority alarm that is not acknowledged.
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
A Zone is an operational entity of the plant that groups information of the same
scope of geographical or functional authority.
The projects can be classified into the following categories based on the number of
zones defined in Controcad (in Controcad, Zone is defined as Set).
Single zone project – Number of zones is one
Multi zone project – Number of zones is more than one
In the ALSPA HMI, the zones are displayed in the alarm bar of the top frame.
The alarm bar helps to view the zones defined in the project and to manage the
audible alarms.
The zones help to view the alarms present in it.
The figure below shows the alarm bar:
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
The global section provides an overview of all the zones defined in the plant.
The features of the zones in the Global section are:
The color of the zone is the color of an alarm with the highest urgency degree in
that zone.
When a zone has no color it indicates that there are no alarms associated to the
zone.
The tooltip of the zone shows the zone number, the number of unacknowledged
alarms and the total number of alarms in that zone.
The user section provides only the zones accessible to the operator and the station.
For a zone to be displayed, the station and operator must have the access rights on
the zone.
For more information on the operator right, see [HMI_WORK] (cf1.7 List of
Referenced Documents).
A zone is displayed as a frame containing:
the zone name
the total number of unacknowledged alarms for the zone / the total number of
alarms for this zone
the color of the alarm with the highest urgency degree
The tooltip of the zone which shows the zone number, the number of
unacknowledged alarms and the total number of alarms in that zone.
Example:
- Zone1
No of UnkAlarms: 5
No of Alarms: 12
- Zone17
No of UnkAlarms: 2
No of Alarms: 4
A click on a zone in the user section opens the Alarms and Events Viewer with a
filter on the requested zone.
Information on data displayed in the viewer is given earlier in this
document (cf. Section 4,Description of the Alarms and Events Viewer).
© ALSTOM 2014 - All rights reserved. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.