LOADS

Dead Load
1) Selfweight
Concrete unit weight = 24 kN/m3

2) Member Load
150mm CHB 3.11 kN/m per meter height
100mm CHB 2.98 kN/m per meter height

Floor Load Floors Roof


100m deck slab 2.40 - kN/m2
corrugated panel - 0.30 kN/m3
Floor finish 1.10 - kN/m2
Ceiling 0.10 0.10 kN/m2
MEP 0.10 0.10 kN/m2
Interior Partition - kN/m2
Water proofing - kN/m2
3.70 0.50

Live Load
2.4 kN/m2 0.60 kN/m2

Seismic Parameters
UBC 97 / NSCP 2015
Zone = 4
Seismic Source Type = A
Importance Factor ( I ) = 1.0 (Standard Occupancy)
Rx = 6 Eccentric Braced Frame
Rz = 8.5 Moment Frame
Structure is located 40km from seismic source
Ct = 0.0731
2.5 0.24 0.24 2.98
UBC 1997

0.75
PARAMETERS T = Ct (hn) sec UBC Eq. (30-8)
Z 0.4 = 0.232 sec
I 1 < 0.70 sec therefore Ft = 0;
Rwx 8.5
Rwz 8.5
Na 1
Nv 1 V= CvIW KN UBC Eq. (30-4)
S 4 RT
Ct 0.0488 = 496.20 KN
hn 8
W 1529.8
Cv 0.64
Ca 0.44

Total design base shear need not exceed:


V = 2.5Ca IW KN UBC Eq. (30-5)
R
= 197.97 KN DESIGN BASE SHEAR IS TOO LARGE!
USE THIS VALUE!

Design base shear shall not be less than:


V = 0.11CaIW KN UBC Eq. (30-6)
= 74.04 KN OK!

V = 0.8ZNvIW KN UBC Eq. (30-7)


R
= 57.59 KN OK!

If Ft≠ 0:
Ft = 0.07TV UBC Eq. (30-14)
= 8.06 KN
< 0.25V = 124.05

ENGR JOHN PAUL DELA ROSA (CE)


LICENSE # 98600_PRC MANILA
168

0.00420
0.005952
40km

Seismic Source Type A


Malolos City Bulacan
1.2 DL + 1.00 E + 0.5 LL

1 1.400 D
1 1.200 D + 1.600 Lp
1 1.420 D + 0.500 Lp + 1.250 E1
1 1.420 D + 0.500 Lp + 1.250 E2
1 1.420 D + 0.500 Lp - 1.250 E1
1 1.420 D + 0.500 Lp - 1.250 E2
1 1.420 D + 1.250 E1
1 1.420 D + 1.250 E2
1 1.420 D - 1.250 E1
1 1.420 D - 1.250 E2
1 0.680 D + 1.250 E1
1 0.680 D + 1.250 E2
1 0.680 D - 1.250 E1
1 0.680 D - 1.250 E2
E = ρ Eh + Ev
1.25

= 1.25 Eh

Ev = 0.5 Ca I DL
0.5 0.44 1 DL
= DL

= 0.22 DL