You are on page 1of 1

TYPICAL BOP CONTROL UNIT SCHEMATIC

1. RIG AIR SUPPLY: Normal air supply is at 125 psi (9 bar). Higher air pressure may 24. MANIFOLD RELIEF VALVE: Valve set to relieve at 5,500 psi.
require an air regulator for No. 88660 air pumps. 25. HYDRAULIC BLEEDER VALVE: Manually operated – normally closed.
2. AIR LUBRICATOR: Located on the air inlet line to the air operated pumps. The oil- NOTE. This valve should be kept OPEN when pre-charging the accumulator
mist in the air ensures internal lubrication and helps to protects against internal bottles.
corrosion. Use SAE 10 lubricating oil. 26. PANEL-UNIT SELECTOR: Manual 3-way valve. Used to apply pilot air pressure to
3. BYPASS VALVE: To automatic hydro-pneumatic pressure switch. When pressures the air operated Koomey pressure reducing and regulating valve, either from the air
higher than the normal 3,000 psi (207 bar) are required, open this valve. Keep closed regulator on the unit or from the air regulator on the remote control panel.
at all other times. 27. KOOMEY PRESSURE REDUCING AND REGULATING VALVE – AIR OPERATED
4. AUTOMATIC HYDRO-PNEUMATIC PRESSURE SWITCH: Pressure switch is set at (ANNULAR PRESSURE REGULATOR): Reduces the accumulator pressure to the
2,900 (200 bar) psi cut-out when air and electric pumps are used. Otherwise set at required annular BOP operating pressure. Pressure ran be varied for stripping
3,000 psi (207 bar) for air pumps alone. Adjustable spring tension control. operations. Maximum recommended operating pressure of the annular preventer
5. AIR SHUT-OFF VALVES: Manually operated – to open or close the air supply to the should not be exceeded.
air operated hydraulic pumps. 28. ACCUMULATQR PRESSURE GAUGE (normally 3000 psi/207 bar)
6. AIR OPERATED HYDRAULIC PUMPS: Normal operating air pressure is 125 psi. 29. MANIFOLD PRESSURE GAUGE (normally 1500 psi/103 bar)
7. SUCTION SHUT-OFF VALVE: Manually operated. Keep normally open. One for each 30. ANNULAR PREVENTER PRESSURE GAUGE (normally 600–1500psi / 41-103 bar)
air operated hydraulic pump suction line. 31. PNEUMATIC PRESSURE TRANSMITTER FOR ACCUMULATOR PRESSURE.
8. SUCTION STRAINER: One for each air operated hydraulic pump suction line. Has 32. PNEUMATIC PRESSURE TRANSMITTER FOR MANIFOLD PRESSURE.
removable screens. Clean every 30 days. 33. PNEUMATIC PRESSURE TRANSMITTER FOR ANNULAR PREVENTER
9. CHECK VALVE (Non-return valve) : One for each air operated hydraulic pump PRESSURE
delivery line. 34. AIR FILTER : Located on the supply line to the air regulators.
10. ELECTRIC MOTOR DRIVEN TRIPLEX OR DUPLEX PUMP ASSEMBLY. 35. AIR REGULATOR FOR KOOMEY PRESSURE REDUCING AND REGULATING
11. AUTOMATIC HYDRO-ELECTRIC PRESSURE SWITCH: Pressure switch is set at VALVE – AIR OPERATED (ANNULAR REGULATOR)
3,000 psi cut-out and 250 psi (18 bar) cut in differential. Adjustable. 36. AIR REGULATOR FOR PNEUMATIC TRANSMITTER (33) FOR ANNULAR
12. ELECTRIC MOTOR STARTER (AUTOMATIC): Automatically starts or stops the PRESSURE.
electric motor driving the triplex or duplex pump. Is controlled by the automatic hydro- 37. AIR REGULATOR FOR PNEUMATIC PRESSURE TRANSMlTTER (31) FOR
electric pressure switch and has a manual overriding on-off switch. ACCUMULATOR PRESSURE.
13. SUCTION SHUT-OFF VALVE: Manually operated, normally open. Located in the 38. AIR REGULATOR FOR PNEUMATIC PRESSURE TRANSMlTTER (32) FOR
suction line of the triplex or duplex pump. MANIFOLD PRESSURE.
14. SUCTION STRAINER: Located in the suction line of the triplex or duplex pump. NOTE. Air regulator controls for pneumatic transmitters normally set at 15 psi.
15. CHECK VALVE (Non-return valve): Located in the delivery line of the triplex or Increase or decrease air pressure to calibrate panel gauge to hydraulic pressure
duplex pump. gauge on unit.
16. ACCUMULATOR SHUT-OFF VALVE: Manually operated. Normally in open position 39. AIR JUNCTION BOX: To connect the air lines on the unit to the air lines coming from
when the unit is in operation. Close when testing or skidding rig or when applying the remote control panels through air cable.
pressure over 3,000 psi to open side of ram preventers. OPEN WHEN TEST IS 40. RIG TEST CHECK VALVE (non-return valve).
COMPLETED. 41. HYDRAUUC FLUID FILL PORT.
17. ACCUMULATORS: Check nitrogen pre-charge in accumulator system every 30 days. 42. INSPECTION PLUG PORT.
Nitrogen pre-charge should be 1000 psi ± 10 % (69 bar). CAUTION. Use NITROGEN 43. RIG TEST OUTLET ISOLATION VALVE: High pressure, manually operated. Close
when adding to pre-charge. Other gasses and air may cause fire and/or explosion. when rig testing – open when test is complete.
18. ACCUMULATOR RELIEF VALVE: Valve set to relieve at 3,500 psi. 44. RIG TEST RELIEF VALVE: Valve set to relieve at 6500 psi.
19. FLUID STRAINER: Located on the inlet side of the pressure reducing and regulating 45. RIG TEST PRESSURE GAUGE
valves. Clean strainer every 30 days. 46. [A] RIG SKID OUTLET and [46B]. VALVE HEADER ISOLATION VALVES:
20. KOOMEY PRESSURE REDUCING AND REGULATING VALVE (Manifold pressure Manually operated. Close valve header isolator valve and open rig skid isolator valve
regulator): Manually operated. Adjust to the required continuous operating pressure when rig skidding. Open value header isolator valve and close rig skid isolator valve
of ram type BOP's. during normal drilling operations.
21. MANIFOLD: 5000 psi W.P., 2" all welded. 47. RIG SKID RELIEF VALVE : Valve set to relieve at 2500 psi.
22. 3/4-WAY VALVES (3 positions, 4 connections): With air cylinder operators for 48. RIG SKID PRESSURE GAUGE.
remote operation from the control panels. Keep in standard operating mode (open or 49. ACCUMULATOR BANK ISOLATION VALVES: Manually operated, normally open.
close), NEVER IN CENTER (block) POSITION. 50. RIG SKID RETURN: Customer's connection.
23. BYPASS VALVE: With air cylinder operator for remote operation from the control 51. RIG SKID OUTLET: Customer's connection.
panels. In CLOSE position. it puts regulated pressure on main value header (21), and 52. ELECTRIC POWER: Customer's connection.
in OPEN position, it puts full pump pressure on that header. Keep in CLOSE position 53. RIG TEST OUTLET: Customer’s connection.
unless 3,000 psi (or more) is required on ram type BOP's.

You might also like