You are on page 1of 2

Commissioning Service Department

Commissioning Standard Test Formats

Description: DC SUPERVISION RELAY XR152 Record No. :


Bay no.: Drawing ref.: Sheet : 1 of 2
Contractor : Contract no.: Substation No :

1. GENERAL DATA AND INFORMATION:

Bay no. Serial No.


Bay name Model No. EPXR152S511306
Make REYROLLE Voltage 125 VDC
Flag Type SELF RESET No. of Contacts 3 NC + 1 NO

2. MECHANICAL CHECKS AND VISUAL INSPECTION:

ITEM DESCRIPTION CHECKED


1 Inspect for any physical damage or defects.

2 Check reset operation

3 Check serial no. of relay matching with serial no. of case

3. ELECTRICAL TESTS:
3.1. FUNCTION TEST:

ITEM DESCRIPTION CHECKED

1 All contact checked

2 All output contacts resistance checked

3 Flag Operation Checked

3.2. PICK UP/DROP OFF TEST:

PICK UP DROP OFF


Coil
Reference
VOLTS (V) CURRENT (mA) VOLTS (V) CURRENT (mA)

13 - 14

Limits: Pick up voltage: 70% Drop off not less than 26%0f Vn ( According to relay catalogue )

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats

Description: DC SUPERVISION RELAY XR152 Record No. :


Bay no.: Drawing ref.: Sheet : 2 of 2
Contractor : Contract no.: Substation No :

3.3. TIMING TEST:

Coil Contact Contact


Pick up (mS) Drop Off (mS)
Reference Terminals Terminals

13 - 14 1-3 1-3

Limits: Resetting Time: >100 mS ( According to relay catalogue )

3.4. BURDEN:

Coil Relay Burden


Voltage (V) Current (mA)
Reference Watts (W)

13 - 14 125

Limits: Burden : 1.25 W ( According to relay catalogue )

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date: