You are on page 1of 2

Samsun Positioner

For Max Calibration:


Rotate the selector switch to code 3,
Code 3 Press the selector switch, code 3 will
start blinking

Rotate the selector switch again to


Enable the configuration;
toggle the configuration from No to
that is press Yes
yes. Press the selector switch to Exit
the code

Rotate the selector switch to code 6,


code 6 Press the selector switch, code 6 will
start blinking

Rotate the selector switch again to


Press Max and Press the pin to toggle it max. Press the selector switch
initialize the calibration
to Exit the code

For Manual Calibration:

Toggle the selector switch to code 36, Reset the Positioner

Go to code 3, select Yes

Go to Menu 0, Select manual

Go to Menu 1, Rotate the selector up to your desired stroke

Go to Menu 6, select Manual and Press the Pin.