Sleeve Sleeve 53% 40% 31% 20%

Location of Sleeve/Conduit Size Area Capacity Capacity Capacity Capacity


Qty of Area Total Lbs Total 3/4 0.533 0 124 0 248
Type of Installed Cable per Cable per Cable 1 0.864 0 77 0 153
Cable Cables Diameter Cable Area foot weight 1 1/4 1.496 0 45 0 89
Cat 3 0.161 0.0204 0.0000 0.0200 0.0000 1 1/2 2.036 0 33 0 65
Cat 5e 0.190 0.0284 0.0000 0.0230 0.0000 2 3.356 0 20 0 40
Cat 6 0.250 0.0491 0.0000 0.0270 0.0000 2 1/2 5.858 0 12 0 23
Cat 6A 0.354 0.0984 0.0000 0.0415 0.0000 3 8.846 0 8 0 15
Cat 6 STP 0.300 0.0707 0.0000 0.0410 0.0000 3 1/2 11.545 0 6 0 12
RG6 Quad 0.300 0.0707 0.0000 0.0320 0.0000 4 14.753 0 5 0 9
RG6 0.272 0.0581 0.0000 0.0320 0.0000 24X6 Cable Tray 144.000 0 1 1
RG11 2 0.405 0.1288 0.2576 0.2100 0.4200 24X4 Cable Tray 96.000 0 1 2
50% Fill
Hardline jacketed 0.750 0.4418 0.0000 0.3300 0.0000 12X6 Cable Tray 72.000 0 1 2
Ratio
24 Strand 42 0.320 0.0804 3.3778 0.0190 0.7980 12X4 Cable Tray 48.000 0 2 3
48 Strand 42 0.580 0.2642 11.0967 0.0280 1.1760 12X2 Cable Tray 24.000 0 3 5
24 Strand Interlock 0.610 0.2922 0.0000 0.1300 0.0000 2X3 Duct 6.000 0 11 0 22
24 Strand Tray 0.620 0.3019 0.0000 0.1710 0.0000 3X4 Duct 12.000 0 6 0 11
144 Strand Interlock 1.360 1.4527 0.0000 0.5580 0.0000 W/M 4000 7.500 0 9 0 18
25 Pairs 0.530 0.2206 0.0000 0.1490 0.0000 W/M 6000 15.330 0 5 0 9
50 Pairs 34 0.660 0.3421 11.6321 0.2450 8.3300 T-70 Panduit 5.150 0 13 0 26
100 Pairs 0.850 0.5674 0.0000 0.4240 0.0000 T-45 Panduit 1.720 0 39 0 77
200 Pairs 1.200 1.1310 0.0000 0.7960 0.0000 Twin-70 Panduit 9.180 0 8 0 15
300 Pairs 1.400 1.5394 0.0000 1.1370 0.0000 TG70 10.850 0 7 0 13
600 Pairs 1.900 2.8353 0.0000 2.1210 0.0000 Total Area Req at fill % 49.7439 65.9107 85.0460 131.8213
1200 Pairs 2.600 5.3093 0.0000 4.0360 0.0000
Sleeves and conduits should be designed to 20% fill.
1800 Pairs 3.100 7.5477 0.0000 5.9950 0.0000
Unlisted Cable 0.0000 0.0000 0.0000 If there is only one cable in a conduit/sleeve, max fill is 53%
Innerduct 1.500 1.7671 0.0000 0.0000 If there are only 2 cables in a conduit/sleeve, max fill is 31%
Total Cables Total Area Cable If there are 3 or more cables in a conduit/sleeve, max fill is 40%
120 26.3643 10.7240
Installed Of Cables Wgt

Areas for Designer input

156 strand fiber 0.87


216 strand fiber 0.784
288 strand fiber 0.99
Sleeve Sleeve 53% 40% 31% 20%
Location of Sleeve/Conduit/Tray Size Area Capacity Capacity Capacity Capacity
Qty of Area Total Lbs Total 3/4 0.533 0 0 0 0
Type of Installed Cable per Cable per Cable Wt 1 0.864 0 0 0 0
Cable Cables Diameter Cable Area foot per foot 1 1/4 1.496 0 0 0 0
Cat 3 0.161 0.0204 0.0000 0.0200 0.0000 1 1/2 2.036 0 0 0 0
Cat 5e 0.2 0.0314 0.0000 0.0230 0.0000 2 3.356 0 0 0 0
Cat 6 0.236 0.0437 0.0000 0.0280 0.0000 2 1/2 5.858 0 0 0 0
Cat 6 OSP 0.25 0.0491 0.0000 0.0250 0.0000 3 8.846 0 0 0 0
Cat 6A 0.3 0.0707 0.0000 0.0415 0.0000 3 1/2 11.545 0 0 0 0
Cat 6 STP 0.236 0.0437 0.0000 0.0410 0.0000 4 14.753 0 0 0 0
RG6 Quad 0.3 0.0707 0.0000 0.0320 0.0000 5 19.63494 0 0 0 0
RG6 0.272 0.0581 0.0000 0.0320 0.0000 6 28.27431 0 0 0 0
RG11 0.405 0.1288 0.0000 0.2100 0.0000 18X4 Cable Tray 72 0 0
500 Hardline jacket 0.75 0.4418 0.0000 0.3300 0.0000 24X4 Cable Tray 96 0 0
50% Fill 25% Fill
Half inch DAS Coax 0.625 0.3068 0.0000 0.1500 0.0000 12X6 Cable Tray 72 0 Ratio 0 Ratio
7/8 inch DAS Coax 1.1 0.9503 0.0000 0.3000 0.0000 12X4 Cable Tray 48 0 0
12 Strand 0.23 0.0415 0.0000 0.0230 0.0000 12X2 Cable Tray 24 0 0
24 Strand 0.32 0.0804 0.0000 0.0450 0.0000 EZ Path 22 0.66 0 0 0 0
48 Strand 0.58 0.2642 0.0000 0.1350 0.0000 EZ Path 33 3.85 0 0 0 0
24 Strand Interlock 0.66 0.3421 0.0000 0.1300 0.0000 EZ Path 44 9.19 0 0 0 0
24 Strand Tray 0.62 0.3019 0.0000 0.1710 0.0000 Hilti 2" Sleeve 3.356 0 0 0 0
144 Strand Interlock 1.36 1.4527 0.0000 0.5580 0.0000 Hilti 4" Sleeve 14.753 0 0 0 0
25 Pairs 0.53 0.2206 0.0000 0.1490 0.0000 2X3 Duct 6 0 0 0 0
50 Pairs 0.66 0.3421 0.0000 0.2450 0.0000 3X4 Duct 12 0 0 0 0
100 Pairs 0.85 0.5674 0.0000 0.4240 0.0000 W/M 4000 7.5 0 0 0 0
200 Pairs 1.2 1.1310 0.0000 0.7960 0.0000 W/M 6000 15.33 0 0 0 0
300 Pairs 1.4 1.5394 0.0000 1.1370 0.0000 T-70 Panduit 5.15 0 0 0 0
600 Pairs 1.9 2.8353 0.0000 2.1210 0.0000 T-45 Panduit 1.72 0 0 0 0
1200 Pairs 2.6 5.3093 0.0000 4.0360 0.0000 Twin-70 Panduit 9.18 0 0 0 0
1800 Pairs 3.1 7.5477 0.0000 5.9950 0.0000 TG70 10.85 0 0 0 0
Unlisted Cable 0.0000 0.0000 0.0000 Total Area Req at fill % 0.0000 0.0000 0.0000 0.0000
Innerduct 1.31 1.3478 0.0000 0.0000
Sleeves and conduits should be designed to 20% fill.
Total Cables Total Area Cable
0 0.0000 0.0000 Cable trays should be designed to 25% fill.
Installed Of Cables Wgt
If there is only one cable in a conduit/sleeve, max fill is 53%
Distance
between tray 6 If there are only two cables in a conduit/sleeve, max fill is 31%
Areas for Designer input supports (ft) If there are 3 or more cables in conduit/sleeve, max fill is 40%
Cable weight De-rating is 15% for 1 bend; 30% for 2 from the 40% capacity
0
per support

156 strand fiber 0.87


216 strand fiber 0.784
288 strand fiber 0.99