Contents Contents

Introduction 2 General 29
Data Sheets
Applications 3
Technical Data Open-Close Duty 30-31
Type Designation 4 Electrical Data Open-Close Duty 32-33
Multi-turn Actuators 5 Technical Data Regulating Duty 34
Electrical Data Regulating Duty 35
Design Principle 6-7
Dimension Sheet, Norm 36
Functions 8 Dimension Sheet, Compact 37
Open-Close Duty 8 Dimension Sheet, E-pac 38
Regulating Duty 8 Output Drives 39
Limit Switching 9 Linear Thrust Unit 40
Torque Switching 10 Terminal Plan (Norm) 41
Wiring Diagram (Integral Starter) 42
Control Equipment 11
Legend - Integral Starter 43
Micro Switches 11
Reduction Gear Unit 12
Position Indicators 12
Intermediate Switch 13
Manual Operation 13
Top Bevel Gear Set 13
Space Heater 13 Introduction
Motors 14-15
In the course of ever increasing demand for
Actuators for Regulating Duty 16-20 automation in all sectors of industries, electric
Actuator Types 21 actuators for process control and regulation
have become more and more important. For
Auma Norm Actuators 21 more than 30 years, Auma concentrates on
Auma Integral Starter Actuators 21 design, development and manufacturing of
Control Versions 22 electric actuators. During this period, Auma
has acquired a know-how in this field that can
Auma Compact 22
hardly be surpassed. Auma today is one of the
Auma e-pac 23 leading manufacturers of electric actuators in
the world.
Interface 24
Valve Attachment 24 Auma India (Ltd.,) is now a subsidiary of
Auma Werner Riester Gmbh & Co. KG,
Output Drives 24 Germany manufacturing electric actuators
Electrical Connection 25 under brand name . Auma (India) Ltd.,
Actuator Gearbox Combination 26 started its operations in the year 1985 with HQ
and sophisticated manufacturing base at
Service Conditions 27 Bangalore.
Enclosure Protection 27 Sales support and after sales service are
Ambient Temperature 27 provided by network consisting of regional
Explosion Proof 28 offices & service centers.

2
Applications

Auma multi-turn actuators of the type range SA


can be used wherever the automation of the
valve is required. The adoption to the
requirements of nearly every valve automation
task is possible. This is on account of :
An extermely wide torque range
Various combination possibilities with
Auma Valve Gear boxes. Thereby the torque
range can be further extended and / or the
multiturn actuator can be converted into
part turn, lever or linear actuator.
A large variety of versions, whether for open
or closed loop control, explosion proof
applications, a suitable version is available.

Energy
Power Plants
Air Pollution Control
District Heating
Pipelines

Water / Waste Water


Water Works
Water Pipelines
Sewage Treatment
Pump Stations
Locks / Dams

Chemical Industry
Petro-chemical
Chemical
Pharmaceutical

Others
Air Conditioning
Steel Mills
Ship Building
Cement Plants
Food Industry

3
Type Designation

Auma OPEN-CLOSE Duty Model : SA


Norm Regulating Duty Model : SAR

Auma OPEN-CLOSE Duty Model :SA Compact


Compact Regulating Duty Model : SAR Compact
Actuator Auma
Types Integral Starter
Auma OPEN-CLOSE Duty Model :SA e-pac
e-pac Regulating Duty Model : SAR e-pac

Expl. Proof OPEN-CLOSE Duty Model :SAEx


Norm Regulating Duty Model : SAREx
Auma
Flame Proof /
Explosion Proof
Expl. Proof OPEN-CLOSE Duty Model :SACEx
Compact Regulating Duty Model : SARCEx
Torque Ratings 3 m kg Output Drives A Stem nut
6 m kg B Plug Sleeve
12 m kg C Dog Coupling
15 m kg D Stub Shaft
25 m kg E Bore with Keyway
30 m kg
50 m kg
60 m kg
100 m kg

Output Speed 4 rpm


5.6 rpm
8 rpm
11 rpm
16 rpm
22 rpm
32 rpm
45 rpm
63 rpm
90 rpm
125 rpm
180 rpm

Type Designation : Example

SA 12 A 22

Model Output Speed in RPM


Torque Rating Output Drive

4
Multi-turn Actuators

Multi-turn Actuator SA3 - SA100


Torque range 3 m kg to 100 m kg
Output speed 4 rpm to 180 rpm

Multi-turn Actuator Multi-turn Actuator


Integral Starter - Compact Integral Starter - e pac

Multi-turn Actuator
Flame Proof / Explosion Proof

5
Design Principle

Manual Operation

Motor

Change Gears Terminal


Compartment

Reduction Gearing

Valve Attachment

Switch Compartment

6
Design Principle
Motor Terminal Compartment

Especially high starting torque is frequently All electrical connections are terminated inside
required to unseat valves from end positions. the terminal compartment. Screw type terminals
The motors developed by Auma fulfil this are provided for easy connections. Multi-pin
basic requirement. plug-socket connector can be provided for ease
of connections & maintenance.

Change Gears Valve Attachment

Auma actuators are driven by special The mounting flange is according to ISO 5210 /
combination of gears which are outside the DIN 3210. Various output drives are available for
grease filled housing & require no lubrication. for adaption to various types of valves.
If required, output speed can be easily altered
by changing the gear pair and / or motor at
site.

Reduction Gearing Manual Operation

A well proved principle of worm gearing is For commissioning or in an emergency, actuator


used to reduce the motor speed to required can be operated with hand wheel. When starting
output speed of actuator. Self-locking feature the motor, the manual drive is automatically
is achieved by worm gearing upto 90 output disengaged.
rpm. Worm shaft and output shaft with worm
wheel run in ample sized bearings. The sliding
worm is positioned between two sets of
springs on worm shaft. The worm moves
axially in relation to thrust which is the
measure for torque. Via lever & gears the
torque is transmitted to control unit.

Switch Compartment

Depending upon type of valve, the actuator


must be switched off at end positions by limit
switch or torque switch. For this purpose,
independent limit switching or torque
switching devices are provided in the switch
compartment. The switching devices are easily
accessible for any setting at site.

7
Functions
Open Close Duty

The characteristic feature of this actuator is


open loop. The normal valve positions in
OPEN-CLOSE Duty are end positions OPEN
and CLOSED. After receiving command, the
actuator operates the valve to one of the end
positions or if necessary to a preset
intermediate position. The valves are operated
relatively seldom, the time intervals can span
between a few minutes to several months.

Auma multi-turn actuators type SA for open


close service are rated for short time duty
S2-15min.
Typical Characteristics of
OPEN-CLOSE DUTY

Regulating / Modulating Duty

The characteristic feature of this actuator is


closed loop in which input command signal to
actuator is directly influenced by the flow
through the valve. Regulating / Modulating
duty actuator SAR operates between two set
bands between open-close positions depending
upon actual valve position and feedback signal.
The motors of these actuators are rated for
intermittent duty S4-25%. The mechanical
components and motor are designed to withstand
a large number of operations required for
Typical Characteristics of
modulating applications.
Regulating / Modulating Duty

Pemissible number of starts-stops depends upon


actuator size & speed. The details are available
in Data Sheets.

Short Time and Intermittent Duty IS 12824

Short time Duty S2 Intermittent Duty S4


Operation at constant load during a given A sequence of identical duty cycles, each cycle
time, less than that required to reach thermal including a significant period of starting, a period
equilibrium, followed by a rest and de- of operation at constant load and a rest and de-
energized period of sufficient duration to re- energized period. These periods being too short
establish machine temperatures within 2oC. to attain thermal equilibrium during one duty
cycle.
The duration of short time is limited to 15, 30
or 60 min. The relative on time at S4-25% is limited to
25% of the cycle time.

8
Functions
Limit Switching

The limit switching enables to switch off the switching points operate the electrical limit
actuator when reaching defined valve switches by cams. The setting accuracy is 1/10 of
position, usually end positions. The valve a turn of actuator output shaft.
travel is measured by mechanical counter gear
mechanism which when reaching the set In limit switching, two train counter gear and
four train counter gear versions are available :

Two Train Counter Gear

For Two train counter gear, two limit switches,


one for each direction of travel having 1 NO
+ 1 NC or 2 NO + 2 NC contacts are provided.
The number of spindle turns can be set
between 1 and 480 or 1 and 4800.

Two Train Counter Gear

Four Train Counter Gear

If limit switching is required at two end The accuracy of setting is 1/10 of a turn of
positions only, two train counter gear is used. actuator output shaft. For four train counter
However, if two additional intermediate gear, 4 limit switches of 1 NO + 1 NC or 2 NO
switching positions are desired, Four Train + 2 NC contacts are provided.
Counter Gear is required. This limit switching
has 4 counter gears and 4 micro switches. Two
counter gears are used to switch off at end
positions as in Two Train Counter Gear. The
other two are available for setting any desired
intermediate positions between end positions.
After cam actuation, the switches remain
actuated till reaching end of valve travel.
Examples of such application are :

To stop at intermediate position


Sequence control, that is to start
another equipment like pump or bypass
valve actuator after certain travel
of valve.
Four Train Counter Gear

9
Functions
Torque Switching

The torque switching enables to switch off the


actuator when pre-determined torque is
reached instead of a defined position. The
torque switching works on principle of sliding
worm.

Axial displacement of worm proportional to


thrust is transmitted to torque switches.
Torque switches operate in closing & opening
directions. The required tripping torque can be
easily set on the graduated dial. If limit switch
cut off is selected prior to torque switch, then
torque switch serves as overload protection.

For tight seating of certain valves, the actuator Torque Switching


must be operated to end position CLOSED
with defined force. Such operation can be When torque seating is used at end position,
carried out by torque seating. Limit seating is limit switches can be used for signalization.
commonly used in the end position OPEN. Therefore actuator controls can differentiate
whether actuator was switched off by torque
switch or by limit switch. Micro switches of
torque switching are provided with 1 NO + 1 NC
or 2 NO + 2 NC contacts for both open & close
directions.

Running Indication

Blinker switch is provided in the actuator and


can be used as running indicator.

10
Control Equipment
Micro Switches

With the help of micro switches, mechanical Limit switches are tripped when an end position
parameters such as travel & torque are is reached and torque switches are tripped when
converted into electrical signals for actuator the set tripping torque is exceeded.
control. There are four switches in the basic
version : The micro switches are sealed to enclosure
One limit switch each for the end protection class IP66, as per IS 13947. The micro
positions OPEN and CLOSE switches have double break change over
One torque switch each for the potential free contacts. The circuit is interrupted
directions OPEN and CLOSE. simultaneously at two points. The basic versions
of the switch contacts are of silver. For low
current ratings, micro switches with gold plated
contacts are available.

Single and Tandem Micro Switches

Limit and Torque Switches are available in Switching another circuit also with
single or tandem versions. different voltage & current
Safety function, to operate with single
switch
Multiplying the available contacts,
example for signalization.

For such applications, a relay is recommended


Single Micro Switch since there may be small differences in tripping
points of tandem switches.

Limit or Torque Switches in tandem version


have additional switching contacts. These
contacts can be wired for following applications :

Tandem Micro Switch

Micro Switch Ratings


Type of Rating in Amp at Approx. Electrical
Type of Switch
Current 30 V 75 V 125 V 250 V contact rating
AC, cos O = 0.8 500,000 cycles at
8 7 6 5 250 V AC, 5A
Inductive
Limit and 50,000 cycles at
Torque DC inductive 5 1 0.2 0.1 250 V DC, 0.1A
50,000 cycles at
DC resistive 7 1 0.5 0.25
250 V DC, 0.25A
AC, cos O = 0.8
Blinker 4
Inductive

11
Control Equipment
Reduction Gear Unit

A reduction gear unit (RGU) in the actuator is at site, variable ratio RGU is available which
used for mechanical position indication, allows simple modification at site depending
remote position indication & for operation of upon number of turns of output shaft for full
intermediate switches. The output shaft of the stroke of valve.
actuator drives final output shaft of RGU
through a series of reduction gears and final
o
shaft turns by approximately 270 while
actuator output shaft performs full number of
turns as set on two train or four train counter
gear unit. The reduction gear ratio needed for
each particular case is fitted at works if the
ratio is known. For this purpose fixed RGU
is supplied. If the ratio needs to be altered
Reduction Gear Unit (RGU)
Position Indicators

Mechanical Position Indicator

The position of the valve is indicated


continuously by adjustable discs having
symbols for OPEN and CLOSE. The discs can
be seen through an indicator glass on switch
compartment cover. The open-close discs can
be set to coincide with limit switching. The
mechanical position indicator requires
reduction gear unit for operation.

Remote Position Indicator Mechanical Position Indicator

The position of the valve can be transmitted as read off continuously on position meter
a continuous signal for remote indication. A calibrated & mounted on control panel.
potentiometer mounted on RGU is used for
this purpose. A power supply unit provides Technical Data
necessary voltage to the potentiometer. The Std: 220 ohms, 3W, Linearity + 3%
o
potentiometer rotates through 270 for one full Optional : 100, 560, 1000 ohms,
stroke of valve & output signal from Potentiometer 3W, Linearity + 3%
potentiometer is proportional to valve travel. Precision : 200, 500, 1000 ohms,
Thus the actual position of the valve can be 1W, Linearity + 0.5%
Power PS01, input 220V, 50Hz, output
Supply Unit 24V DC
Position 0 - 100% in various sizes
Meter

Digital Remote Position Indicator

Actual position display can be provided by


digital remote position indicator, which
displays open position in percentage.
Remote Position Indicator

12
Control Equipment
Intermediate Switches

With this limit switching, additional switching


points can be set for each direction of rotation.
The switching can be set between 25 and 75%
of valve travel in each direction. The switch
sub assembly consisting of 2 or 4 cam switches
is mounted on output shaft of RGU. Each
micro switch has 1 NO + 1 NC contact.

Intermediate Switches
Manual Operation

For commissioning or in an emergency when


there is no power supply, actuator can be
operated by hand wheel. The manual drive is
engaged by means of a lever. When motor
starts running, the manual drive gets
disengaged immediately & hand wheel does
not rotate during power operation.

In manual operation, hammer blow can be


effected with hand wheel. The hammer blow
makes it possible to open a jammed or rarely
operated valve.

Top Bevel Gear Set

Manual effort on hand wheel can be further


reduced by using a side mounted hand wheel
instead of standard hand wheel. Reduction
ratios available are
SA3 / 6 / 12 / 15 2:1
SA25 / 30 / 50 / 60 3:1
SA 100 4:1
Instead of hand wheel, a chain pulley can be
provided for actuators mounted in inaccessible
zones.
Top Bevel Gear Set

Space Heater

Condensation in the actuator is possible due to Technical Data


wide fluctuation of the ambient temperature.
Volts, AC 230 230 110 110
The heater integrated in the control unit
prevents the water condensation. The heater is Resistance
5K 2.7K 1.2K 0.6K
rated for continuous duty. This may be ohms
continuously energized or when the actuator Rating
is not operating. 10 20 10 20
Watts

13
Control Equipment
Motors

As a standard, Auma multi turn actuators are Single Phase AC Motors


equipped with 3 phase induction motors.
Auma motors are class F insulated and Auma actuators can be supplied with single
withstand winding temperature upto 140o C. phase AC motor. The required capacitor is fitted
in the terminal compartment cover.
The motors are used for short time duty (S2-15
min or S4-25% as per IS 12824) and provide DC Motors
approximately three times rated torque for
short duration. The size of the motor is smaller Auma actuators are also available with DC
compared to continuous duty motor S1 of motors. These motors operate on 24 V, 110 V or
same output power. This results in reduced 220 V DC supply.
inertia of the rotor and therefore less
overshoot after switching off of motor. Auma AC Motors with Other Voltages and
motors are designed for enclosure protection Frequency
class IP 68 when mounted on the actuator. All
motor cables are brought to terminal Three phase induction motors are available in
compartment cover from inside of the actuator wide range of operating voltages from 220 V to
thus avoiding terminal box. 560 V and operating frequency of 50 or 60 Hz.

Technical Data

3 ph AC Motor 1 ph AC Motor DC Motor


50/60 Hz : 220 V, 380 V 50/60 Hz :
400 V, 415 V 220 V
220 V - 240 V
Voltages 440 V, 460 V 110 V
110 V - 220 V
480 V, 500 V 48 V
550 V 24 V
Permissible Variation + 10% + 10%
+ 10%
in Voltage
Mounting C Type Flange, B14, IS 2223

Enclosure Protection IP 67 or IP 68 after mounting

Type of Cooling Surface Cooled


o
Insulation Class F Class, IS 325 (max. temp. rise 140 C)

Starting Direct on line

Type of Duty S2-15 min. or S4-25 % IS 12824

Direction of Rotation Clockwise and anticlockwise

Motor Protection 3 thermo switches 2 thermo switches 4 thermo switches

14
Control Equipment
Motor Protection

Motor winding may get overheated if the


Technical Data
actuator is run beyond rated duty or if the
rotor is stalled for considerably longer time or
AC Voltage Switch Rating
if too high ambient temperature is
encountered. In order to protect the motor 250 V AC
against over heating, thermo switches are 2.5 A
Cos O = 1
embedded in the windings of three phase, 250 V AC
single phase AC motors and DC motors. When 1.6 A
Cos O = 0.6
integrated into the control circuits, they will
protect the motor against damage due to Tripping Temp 140o C
excessive winding temperature.
Reset Temp 90 - 110o C
The thermo switches interrupt the control
circuit as soon as winding temperature of
o Note : The motor protection device must be
140 C is exceeded. After cooling down to a integrated into the controls, otherwise warranty
o
temperature of approx. 110 C, the actuator can for motor is not valid.
be switched on once again. PTC thermistors
can also be provided for motor protection.

Output Speeds

With large range of available output speeds, exchanging the change wheels and or motor at
almost every required operating time can be site. The grease filled housing need not be
achieved with Auma actuators. opened for this purpose. The torque switch
setting & limit switch setting remains the same.
The actuator output speed is determined by For actuators with output drive A (Stem nut),
the motor speed, change gears and reduction max. permissible stem velocity must be
gear ratio of worm / worm wheel. observed:
- for gate valves max. 500 mm/min
The output speeds are available from 4 - 180 - for globe valves max. 250 mm/min
rpm in geometric progression of 1: 1.4.
For higher velocities it is recommended to use
During trial run, if found necessary, the
spring loaded stem nut type AF (special design).
output speed can be easily changed by

Self Locking

Auma multi turn actuators SA/SAR3 to Note on Self Locking :


SA/SAR100 are self locking (see note below)
with exception of output speeds 125 & 180 Self-locking gearing does not ensure safe
rpm. Actuators with 125 & 180 rpm are having stopping after an operation. If this is required,
double start worm drive. After torque switch is separate locking arrangement must be provided.
tripped, the sliding worm may move back to
initial position by the action of torque
measuring springs. This allows torque switch
to be released. If control system provides
continuous signal, this results in hunting of
motor. This can be avoided by the use of
auxiliary relay.

15
Actuators for Regulating Duty
Description of Regulating Duty

Auma actuators of type SAR are suitable for - Max. No. of starts
Regulating duty / Modulating duty. SAR 1200 cycles / hour with motor power upto
actuator operates between two set bands in 0.55 kW & 600 cycles / hour with motor
closed loop and the motor is started, stopped power above 0.55 kW.
& reversed at short intervals to correct the - Output speed of actuator max. 45 rpm.
deviation from the set value. SAR actuators - Torque for regulating duty should not exceed
differ from SA actuators in several respects : 50% of max. torque of actuator.
- Max. torque of actuator can be used for
- 4 pole motors are used to reduce overshoot seating & unseating of the valve.
- Worm with high quality finish on flanks for - For reversing service, duration of impulse
better efficiency should be minimum of 50 ms.
- Disc springs on worm shaft are pre - Electronic position transducer or precision
compressed to reduce dead band when potentiometer should be used for remote
reversing. position indication.
- The motor should be short time duty
While selecting Auma actuators for regulating class S4 - 25%.
duty applications, following points should be
The SAR actuator basically consists of
noted :
control units as explained in following
diagram.

Principle of Operation

SAR : Regulating duty actuator CU01 : Electronic positioner

MSAR : Sensor for actuator, i.e. V : Regulating valve


position transmitter at actuator
M : Sensor for regulating valve
(potentiometer or inductive
LVDT) MU : Signal converter for sensor

MUSAR : Signal converter for SAR i.e. SE : Setting nominal value


Electronic position transducer
(RWG 1001/RWG 2002) or W : Reference input
inductive position transmitter
XR : Input value at controller
(IWG 1002/ IWG 1003).
YR : Output value at electronic
positioner

16
Actuators for Regulating Duty
Description of Electronic Units

Sensor for Actuator Technical Data


A potentiometer is used as sensor for actuator. Resistance 4.7 k ohms + 0.5 %
Single turn wire wound potentiometer with Power rating
o
3 Watt at 40 C
4.7 k ohms with linearity of + 0.5 % is available
for this purpose. It is available in single or Angle of rotation 275o + 5o
tandem version.
Linearity + 0.5%
Electronic position transducer RWG 1001

This device is a signal converter for the


transformation of resistance value into
proportionate current signal. It can also be
placed in the actuator where the position
determined by the potentiometer is converted
into 4-20 mA current signal.

As position transmitter, preferably a


potentiometer of 4.7 k ohm should be used so RWG 1001
that the reference voltage source is not over
loaded. This device requires 24V DC power Technical Data - RWG 1001
supply regulated within + 15%. Auma power Configuration 3 Wire
supply unit PS01 is recommended for this 24V DC
Supply Voltage
purpose. RWG 1001 is a 3 wire system and is min. 18, max. 33V
having linearity of 0.05 %. 0-20 mA
Output Current
(4-20 mA)
Electronic position transducer RWG 2002 Input resistance 150 k ohms
Displacement of zero
+ 25%
This is basically same as RWG 1001, however position, max.
with 2 wire system. The linearity is less than 1%. Displacement of end
position, max. from 50 to 100%
Influence of supply Max. 0.2%
voltage variation
Temp. drift 0.2% 10o C
Linearity not considering
0.05%
potentiometer

Technical Data - RWG 2002


Configuration 2 Wire
24V DC
Supply Voltage
min. 18, max. 33V
Output Current 4-20 mA
Input resistance 150 k ohms
Displacement of zero + 25%
RWG 2002 position, max.
Displacement of end
position, max. from 60 to 100%
Influence of supply Max. 0.15%
voltage variation
Linearity not considering
< 1%
potentiometer
17
Actuators for Regulating Duty
Description of Electronic Units

Dual Output Position Transmitter RWG 2002 DG :

It is a signal converter device for the Technical Data - RWG 2002 DG


transformation of resistance value into
proportionate galvanically isolated two current 24V DC
Supply Voltage
outputs. This device requires 24 V DC power + 10% regulated
supply regulated within + 10%. Auma power Output 1 (Isolated) 0/4-20 mA
supply unit PS01 is recommended for Output 2 (Isolated) 0/4-20 mA
this purpose. Current Drawn 100 mA
Adjustability of Span + 50%
Adjustability of Zero + 25%
Change in Output due to
Input Supply Variation < 0.2%
Operating Temperature o o
Range - 20 C to + 80 C
Linearity Error for both
Outputs < 1%

Inductive Position Transmitter IWG 1002

When using Auma actuators for regulating duty


with demand of high accuracy, an inductive
position transmitter can be fitted to give precise
read out of position.

The output signal is used as feed back to


electronic positioner or for position indicator.
The system consists of two parts, a linear
variable differential transformer (LVDT) and
an electronic unit. The smallest change of
magnetic core in the measuring coil is
transformed into proportional signal. The IWG 1002
transmitter has no moving contacts. This device
requires 24 V DC power supply regulated
Technical Data - IWG 1002
within + 15%. Auma power supply
unit PS01 is recommended for this purpose. Configuration 2 Wire
The linearity of the unit is less than 0.3%. 24V DC
Supply Voltage
+ 15% regulated
Output Current 4-20 mA
Resistance max. 600 ohms
Displacement of zero + 25%
position, max.
Displacement of end
position, max. 60 to 100%

Temp. drift 0.4% / 10o C


Linearity (not
< 0.3%
considering LVDT)
18
Actuators for Regulating Duty
Description of Electronic Units

Inductive position transmitter IWG 1003

IWG 1003 is similar to IWG 1002 however with Technical Data - IWG 1003
3 wire system.
Configuration 3 Wire
24V DC
Supply Voltage
+ 15% regulated
Output Current 0 / 4-20 mA
Resistance max. 600 ohms
Displacement of zero
+ 25%
position, max.
Displacement of end
position, max. 60 to 100%
o
Temp. drift 0.4% / 10 C
Linearity (not
considering LVDT) < 0.3%
IWG 1003

Electronic Positioner CU01

The electronic positioner CU01 is designed as a closing) depends upon the plus or minus sign of
three level positioner for regulating of actuator. the deviation. Thus the regulating signal
By comparing two input signals (reference generated by potentiometer or LVDT changes &
signal W & regulating signal X), the positioner when the regulating signal & reference signal
determines the difference. In case this exceeds a become equal, the actuator stops as long as no
certain value, the actuator is switched on by new correction is required.
relays. The direction of rotation (opening or

Technical Data
Input WE1 0-20 mA (4-20 mA)
XE2 0-20 mA (4-20 mA)
or 0-Uref
Time delay 0.5-15 secs.
Adjustment of zero 0 - 20%
point
Adjustment of end
position 60 to 100%
Sensitivity (dead 1% - 2.5%
band)
Relay output (max. 230V, 10A
resistive load

CU 01

19
Actuators for Regulating Duty
Description of Electronic Units

Signal Isolator

Auma signal isolators are available in various Various output signals :


versions : 4-20 mA single or dual or 4-20 mA & 1-5V
Power supply conditions :
230V AC, 110V AC or 24V DC Isolation is provided between input and output
Various input signals : and between two outputs.
4-20 mA or 1-5 V
Technical Data
230V AC + 15%
Power Supply 110V AC + 15%
24V DC + 1V
Input 4-20 mA
1-5V
4-20 mA single
Output 4-20 mA dual
4-20 mA & 1-5 V
Accuracy + 0.1% of output span
Zero & span + 2% min. at zero
adjustment + 10% min. at span
Signal Isolator

Power supply unit PS01

This unit gives 24V DC power supply for Version II : For remote position indication with
regulating system (example : for CU01) & for potentiometer 220 ohms as position transmitter :
remote position indication (example : by a In this two additional potentiometers P1 and P2
voltmeter suitably calibrated). There are two are provided for positions zero and maximum.
versions available:
Version I : For regulating application with
CU01 :
The output voltage Uo & Uc require no trimming
potentiometer. The voltage Uc is diverted from
voltage Uo, thus Uc can serve as common
reference potential for whole regulating system.
This version is suitable for IWG 1003 or
RWG 1001.
Supply voltage to PS01 is 220V or 110V + Version II
15%, 50 Hz
The maximum output voltage is Technical Data - PS01
Uo = 24V + 1 V DC
Supply voltage and 220V or 115V (+ 15%)
Uc = 5.5V + 0.5V DC
frequency 50 Hz or 60 Hz
Power drawn 9 VA
Output voltage 24V +1V DC
max.
Mounting Snap on type for DIN
rail 46277
Version I
20
Actuator Types
Auma Norm Actuators

This actuator offers a complete actuator type SA


with electric motor, torque switch for open -
close direction, limit switches for both end
positions & blinker switch for running
indication. The required reversing contactor
should be installed separately & wired to the
motor. For signalization of the switching and to
trip the contactors over micro switches, control
wires are required from actuator terminal
compartment cover to reversing contactor
installed separately.
Auma Norm

Auma Integral Starter Actuators

The purpose of offering Integral motor controls - Several actuators can be connected to common
for the actuator is to enable the customer to save supply cable using isolating switch for each
high installation costs for external controls. actuator.
Actuators with integral controls include control - Actuator signals are processed in the controls,
& switching elements and are supplied only feed back to process control system is
ready for use. necessary.
- Integral starter housing can be easily
All electrical components such as limit, torque, exchanged due to multi pin plug connector
thermo switches, all monitoring elements & between actuator & integral starter unit.
position transmitter are integrated into modern - Actuator can be operated from Local or
controls.This results in following simplification.
Remote position by means of selector switch
- No extensive wiring in the external control on the integral starter unit.
cabinet

Auma Integral Starter

21
Actuator Types
Control Versions of Integral Starter Units

Auma Compact Auma compact is available as Norm or


Regulating duty actuator. Depending upon Norm
This is a simpler version of Integral Starter Unit or Regulating duty, following features /
with selector switch & push buttons. The optionals are available :
selector switch has 3 positions :
Reversing contactors
LOCAL : Selector switch
Push buttons & indicating lamps
The actuator can be operated locally i.e. at the
Thermal overload relay
actuator by push buttons OPEN-OFF-CLOSE.
Power supply unit PS01 for 24 V DC output
The running direction is indicated by LEDs.
Electronic positioner CU01
REMOTE : Electronic position transducer RWG / IWG
Phase discriminator
The actuator can be operated from remote Signal isolator
control station. The running direction is DC relay for remote operation
indicated by LEDs on the actuator. Remote annunciation relay for supply
indication
OFF :
Multi pin connector can be provided between
The actuator cannot be operated with local actuator and compact and between compact &
controls or from remote. terminals for customer connections.
The selector switch can be locked in any position
with pad lock. The compact unit is completely
wired with reversing contactors and no
additional control box is required.

Auma Compact

22
Actuator Types
Control Versions of Integral Starter Units
Auma e-pac

The electronic version of Auma India Integral Programmable Control Logic Module consists
Starter e-pac incorporates sophisticated of
electronic controls with field programming
feature. E-pac is modular in construction and Inching & Non-inching in local mode by dip
consists of Power Supply Module, Relay switches
Module & Programmable Control Module. Inching & Non-inching in remote mode by dip
switches
Power Supply Module consists of Limit switch seating or Torque seating by dip
switches
24 V DC, 150 mA source
Wide varieties of versions of e-pac & optional
Reversing contactors electrically and
mechanically interlocked features make the actuator controls adaptable to
any field situation. Versions & optionals
Selector switch LOCAL-OFF-REMOTE,
available are :
lockable & potential free contacts for local-
off & remote Emergency shut down (ESD)
Push buttons OPEN-STOP-CLOSE for 2 wire make-break
local controls Timer board to run the actuator in ON-OFF
Single phase supply for space heater 10W steps
Open-Close inhibit
Relay Module consists of Negative switching
Remote control & local stop
Monitor relay for collective fault Electronic positioner for regulating duty, with
signals (Thermo switch trip, torque switch or without isolator
trip in mid travel) with potential free contacts Single phase protection
Local status annunciation (Green) & fault Automatic phase correction
annunciation (Red) by LEDs Remote annunciation relays
Thermal overload relay
Positioner with PID features
Wall mountable e-pac
For detailed literature, refer separate catalogue.

Auma e-pac

23
Interface
Valve Attachment

Valve attachment is according to ISO 5210 or DIN 3210

Flange Sizes
Actuator size
3 6 12 15 25 30 50 60 100
SA/SAR
Max. Torque
30 60 120 150 250 300 500 600 1000
Nm
ISO 5210 F10 F10 F10 F10 F14 F14 F14 F14 F16

DIN 3210 G0 G0 G0 G0 G 12 G 12 G 12 G 12 G3

Output Drives

Various output drive types according to ISO Output Drive Type D


5210 / DIN 3210 are available in order to
adapt the actuators to different types of valves. Stub Shaft :
Special sizes can be supplied on request.
The shaft with key engages with bore and
Output Drive Type A keyway of mating part.

Stem nut : Output Drive Type E

The output drive has stem nut for rising or non Bore with Keyway :
rotating valve stem. The mounting flange
together with stem nut and thrust bearings form This type is mainly used for connecting to a gear
one assembly which is suitable for accepting box, example Auma Gear Box type GS
thrust loads. (worm / worm wheel) or GK (Bevel gear box).

Output Drive Type B Linear Thrust Unit (LTU)

Plug Sleeve : With the linear thrust unit, the rotary movement
of the actuator output shaft is converted into an
Plug sleeve has bore and keyway and is designed axial movement. Thus the multiturn actuator
for transmission of torque. becomes linear actuator. Different stroke lengths
can be provided.
Output Drive Type C

Dog Coupling : Technical Data


Linear Thrust Tr. Max. Stroke
This is similar to type B, however with dog thrust length
Unit Thread kN mm
coupling for torque transmission.
LTU 6 24 x 5 20 50 & 100
LTU 12 32 x 6 35 60 & 120
LTU 25 40 x 7 63 80 & 160
LTU 50 50 x 8 100 80 & 160

24
Interface
Electrical Connection
Terminals
Screw type terminals are used for electrical Version I :
connection as standard. Stud type terminals can
be provided for power connections. Terminals 32 x 2 = 64 pins for control
are DIN rail mountable and are available as 3 + 1 = 4 pins for power
single or double decker versions also.
Version II :
Plug socket connector
50 pin circular connector for control
The actuators can also be equipped with plug
socket connectors in two versions. 6 + 1 = 7 pins for power

Electrical Connection for Integral Starter Versions


Between actuator and compact or e-pac :
64 pin connector with 3+1 pins for power
connection or 50 pin circular connector with
6+1 pins for power connection. This simplifies
trouble shooting at site.
From compact or e-pac to customer connections:
Screw type terminals or 64 pin connector with
3+1 pins for power connection or 50 pin circular
connector with 6+1 pins for power connection.

Technical Data Screw type terminals


Power Earth Controls
Screw type terminals
Terminals max. 3 1 64
Voltage max. 750 V - 500 V
Current max. 34 A - 25 A
Type of Connection Scr or
Scr or stud Scr
stud
Cross section max. 4 sq mm 4 sq mm 2.5 sq mm
Plug socket connector 32 x 2 & 3 + 1
No. of contacts 3 1 64
Multi-pin Connector
Voltage max. 750 V - 500 V
Current max. 25 A - 16 A
Type of connections Screws Screws Screws
for customer use
Cross sec. max. 6 sq mm 6 sq mm 2.5 sq mm
Plug socket connector, circular
6
No. of contacts (3 used) 1 50
Voltage max. 750 V - 250 V
Current max. 25 A - 16 A
Circular Connector
Type of connections Screws Screws Screws
for customer use
Cross sec. max. 6 sq mm 6 sq mm 2.5 sq mm
25
Interface
Threads for Cable Glands

As standard, Auma actuators are supplied with 3 '' , 1'' can be


Additional cable glands of sizes 3/4''
4
2 cable glands with British Conduit threads provided. For additional protection under
111/
''
4 BSC. The cable glands are directly tightened extreme conditions for weather proof & water
on the threads provided in cable entry cover. At proof applications, double compression cable
the time of despatch, the cable entry opening in glands in various sizes can be supplied. NTP &
the cable gland is sealed with aluminium shim PG threads can also be provided.
& neoprene rubber sheet to prevent ingress of
dust & water.

Stem Protection Tube

To protect rising valve stem, a protection tube as a standard. If protection tube is not required,
can be fitted to the hand wheel hub. Internal the bore of the hand wheel hub is closed with lid.
threads are provided in the hand wheel hub

Actuator - Gear box Combinations


Combination with Worm Gear boxes

In combination with worm gear box of type


GS40.2 to GS500, a multiturn actuator is
converted into part turn actuator usually for 90o
movement. This is an ideal solution for large part
turn valves with high torque requirements. The
torque range goes upto 250000 Nm.

Combination with Bevel Gear boxes

By combining multiturn actuators with Bevel


gear boxes GK10.1 to GK35.1, the torque speed
ranges are considerably extended. Output
torques upto 8000 Nm and thrust load upto
820 KN are possible.

Combination with Lever Gear boxes

Louvers, dampers or valves which are operated GEAR OPERATORS

via lever arrangement require lever gear boxes.


For such application multiturn actuator is
combined with lever operated Gear box type
GF40 to GF315. The torque range goes
upto 63000 Nm.

26
Service Conditions
Enclosure Protection

Auma actuators conform to enclosure protection The lowest point of equipment is atleast 1 m
IP67 as per IS 13947 (Part I) : 1993, Appendix C. below the surface of water
Auma actuators are also available with improved Duration of test is 30 min.
enclosure protection IP68. The definition of
IP67 & IP68 as per standard is as follows : Under above conditions, ingress of water in
IP : Ingress Protection harmful quantity shall not be possible.
First numeral 6 : Dust tight, prevents ingress Second numeral 8 : Test conditions as above,
of dust. however no ingress of water is permitted.
Second numeral 7 : Protected against the effects
of immersion. Test is made by completely
immersing the equipment in water so that :
Surface of water is atleast 150 mm above
highest point of equipment.

Ambient Temperature Life Time

Temp. Auma multi-turn actuators meet the following


Type Actuator Type
Range requirements of operating cycles at 30 turns per
Standard o
stroke of close - open - close.
SA -20 to +80 C
Multi-turn actuator
SA3 to SA100 15000 Cycles
Multi-turn
o SAR6 to SAR100 15000 Cycles
SAR Actuator for -20 to +60 C
Regulating Duty
SAEx Explosion Proof
SAREx actuators, standard o
SACEx compact & -20 to +40 C
SARCEx regulating duty

Painting

Type of paint Epoxy Any other type & colour of paint can be provided
Standard colour DA grey IS 5 on request.
Primer thickness 40 microns min.
Paint thickness 75 microns min.

27
Service Conditions
Explosion Proof / Flame Proof Actuators

For installation of actuators in potentially Necessary approvals from statutory authorities


hazardous or explosive areas, special protective have been obtained.
measures are required. These are specified in
Indian Standard IS 2148-1981 ''Specifications Actuator Models
for Flame Proof Enclosures of Electrical
Actual Type Model
Apparatus''. Auma India actuators developed for
this purpose are suitable for group II gases and in Explosion Proof SAEx3/6/12/15
application other than coal mines. The Norm SAEx25/30/50/60
enclosures of explosion proof / flame proof Open-Close Duty SAEx100
actuators are designed in consideration of
clauses specified in IS 2148-1981 & the Explosion Proof SAREx6/12/15
actuators have been tested and certified by Norm SAREx25/30/50/60
CMRI, Dhanbad. Regulating Duty SAREx100

Explosion Proof SACEx3/6/12/15


Compact SACEx25/30/50/60
Open-Close Duty SACEx100

Explosion Proof SARCEx6/12/15


Compact SARCEx25/30/50/60
Regulating Duty SARCEx100

For details please refer separate catalogue.

SAEx3 - SAEx100
SAREx6 - SAREx100

SACEx3 - SACEx100
SARCEx6 - SARCEx100

EN ISO 9001
Certificate : 041005262

28
General
Mounting Position Functional Tests

Auma actuators also with integral controls can After assembly, all actuators are thoroughly
be operated without restriction in any mounting tested and torque switches are calibrated. Final
position. inspection record is provided to the customer.

Test Certificates

Auma actuators and critical components of


actuators have been tested & guaranteed for
performance. Some of the Type test certificates
available are listed.
Endurance Test as per GDCD Standard
Damp Heat Cycle Test as per IS 9000
Vibration Test as per IS 12075
Noise Test as per IS 12065
Enclosure Protection Test as per IS 13947
Tests on Micro Switches
Motor Performance Tests

29
Technical Data SA3-SA100
Open-Close duty
1)
Tripping Torque Auma India Valve Stem dia. Permissible Revolutions Hand Hand wheel Weight
both directions Actuator Type Mounting Output drive Thrust for for wheel Ratio Auma India Norm
Flange Type-A Type-A Full stroke Dia.
Type Output Speed Standard Std. Std. With bevel Std. With bevel
DIN:3210 gear set
(Special gear set
2)
Min.Nm Max.Nm 1/min ISO:5210) Max. mm Max. kN Min. / Max. Kgs. Kgs.
SA 3 ..... 11
SA 3 ..... 16
SA 3 ..... 22
SA 3 ..... 32 1-480
SA 3 ..... 45
20 30 G0 26 25 or 250 1:1 2:1 39 45
SA 3 ..... 63
(F10) 1-4800
SA 3 ..... 90
SA 3 ..... 1253)
SA 3 ..... 1803)
SA 6 ..... 4
SA 6 ..... 5.6
SA 6 ..... 8
SA 6 ..... 11
SA 6 ..... 16
..... 1-480
SA 6 22
20 60 ..... G0 26 40 or 250 1:1 2:1 39 45
SA 6 32
SA 6 ..... 45 (F10) 1-4800
SA 6 ..... 63
SA 6 ..... 90
SA 6 ..... 125
SA 6 ..... 1803)
55 SA 12 ..... 4 3)
SA 12 ..... 5.6
SA 12 ..... 8
SA 12 ..... 11
SA 12 ..... 16
SA 12 ..... 22 1-480
SA 12 ..... 32
30 120 G0 38 60 or 250 1:1 2:1 39 45
SA 12 ..... 45
(F10) 1-4800
SA 12 ..... 63
SA 12 ..... 90
SA 12 ..... 125
SA 12 ..... 180
SA 15 ..... 4 3)
110 SA 15 ..... 5.6 3)
SA 15 ..... 8
SA 15 ..... 11
SA 15 ..... 16
SA 15 ..... 22 1-480
SA 15 ..... 32
50 150 G0 38 60 or 250 1:1 2:1 39 45
SA 15 ..... 45
(F10) 1-4800
SA 15 ..... 63
SA 25 ..... 4
SA 25 ..... 5.6
SA 25 ..... 8
SA 25 ..... 11
SA 25 ..... 16
SA 25 ..... 22
SA 25 ..... 32
SA 25 ..... 45
SA 25 ..... 63 1-480
60 250 SA 25 ..... 90 G 12 52 120 or 360 1:1 3:1 72 88
SA 25 ..... 125 (F14) 1-4800
SA 25 ..... 180

3)
220 3)

1) Infinitely adjustable 3) Non self locking


2) At 50 Hz

We reserve the right to alter data according to improvements made. Previous data sheets become invalid with the issue of this data sheet.

30
Technical Data SA3-SA100
Open-Close duty
1)
Tripping Torque Auma India Valve Stem dia. Permissible Revolutions Hand Hand wheel Weight
Actuator Type Mounting Output drive Thrust for for wheel Ratio Auma India Norm
both directions Flange Type-A Type-A Full stroke Dia.
Type Output Speed Standard Std. Std. With bevel Std. With bevel
DIN:3210 gear set
Min. Max. (Special Max. gear set
2)
Nm. Nm. 1/min ISO:5210) kN Min. / Max. Kgs. Kgs.
SA 30 ..... 4
SA 30 ..... 5.6
SA 30 ..... 8
SA 30 ..... 11
SA 30 ..... 16
SA 30 ..... 22 1-480
100 300 SA 30 ..... 32 G 12 52 120 or 360 1:1 3:1 72 88
SA 30 ..... 45 (F14) 1-4800
SA 30 ..... 63
SA 30 ..... 90
SA 30 ..... 125 3)
SA 30 ..... 180
264 3)
SA 50 ..... 4
SA 50 ..... 5.6
SA 50 ..... 8
SA 50 ..... 11
SA 50 ..... 16
SA 50 ..... 22 1-480
SA 50 ..... 32
100 500 G 12 52 160 or 640 1:1 3:1 75 92
SA 50 ..... 45
(F14) 1-4800
SA 50 ..... 63
SA 50 ..... 90
SA 50 ..... 125
SA 50 ..... 1803)
SA 60 ..... 4 3)
450 .....
SA 60 5.6
SA 60 ..... 8
SA 60 ..... 11
SA 60 ..... 16
SA 60 ..... 22
SA 60 ..... 32 1-480
SA 60 ..... 45
100 600 ..... G 12 52 160 or 640 1:1 3:1 75 92
SA 60 63
..... (F14) 1-4800
SA 60 90
SA 60 ..... 125
SA 60 ..... 180
SA 100 ..... 4 3)
540 SA 100 ..... 5.6 3)
SA 100 ..... 8
SA 100 ..... 11
SA 100 ..... 16
SA 100 ..... 22
SA 100 ..... 32
SA 100 ..... 45 1-480
SA 100 ..... 63
200 1000 G3 65 190 or 800 1:1 4:1 107 128
SA 100 ..... 90
(F16) 1-4800
SA 100 ..... 125
SA 100 ..... 180

3)

900 3)

Enclosure : IP67 - IS:13947


Actuators are rated for short time duty S2-15min, based on 40o C ambient temperature. The nominal current
is based on an average load of approximately 35% of max. torque. The max. torque can be utilised for a short
time (e.g. to seat or unseat a valve) and the current can rise to max. value. Refer corresponding column for
current at max. torque in Electrical Data.

1) Infinitely adjustable 2) At 50 Hz 3) Non self locking


We reserve the right to alter data according to improvements made. Previous data sheets become invalid with the issue of this data sheet.

31
Electrical Data SA3-SA100
Open-Close duty
Auma India
Three phase Squirrel cage AC Motor 415V, 50 Hz
Actuator Type
Torque
Max. Type Output Speed Nominal Speed Size Nominal Current at Starting Power Full load
at 50 Hz Output 1/min Current Max. Torque Current Factor Efficiency
KW A 1) A A Cos o (%)
Nm 1/min
SA 3 ..... 11 0.06 1400 71 0.3 0.30 1.2 0.6 46
SA 3 ..... 16 0.06 1400 71 0.3 0.38 1.2 0.6 46
SA 3 ..... 22 0.06 1400 71 0.3 0.50 1.2 0.6 46
SA 3 ..... 32 0.12 1400 71 0.5 0.62 2.3 0.6 55
SA 3 ..... 45 0.18 2800 71 0.6 0.84 3.3 0.7 60
30 ..... 0.6 1.16 3.3 0.7 60
SA 3 63 0.18 2800 71
SA 3 ..... 90 0.37 2800 71 1.0 1.62 5.5 0.76 68
SA 3 ..... 125 0.37 2800 71 1.0 1.40 5.5 0.76 68
SA 3 ..... 180 0.37 2800 71 1.0 2.05 5.5 0.76 68
SA 6 ..... 4 0.06 1400 71 0.3 0.25 1.2 0.6 46
SA 6 ..... 5.6 0.06 1400 71 0.3 0.30 1.2 0.6 46
SA 6 ..... 8 0.06 1400 71 0.3 0.38 1.2 0.6 46
SA 6 ..... 11 0.12 1400 71 0.5 0.45 2.3 0.6 55
SA 6 ..... 16 0.12 1400 71 0.5 0.62 2.3 0.6 55
SA 6 ..... 22 0.12 1400 71 0.5 0.90 2.3 0.6 55
60 SA 6 ..... 32 0.18 2800 71 0.6 1.18 3.3 0.7 60
SA 6 ..... 45 0.37 2800 71 1.0 1.62 5.5 0.76 68
SA 6 ..... 63 0.37 2800 71 1.0 2.34 5.5 0.76 68
SA 6 ..... 90 0.55 2800 71 1.8 3.08 9.0 0.62 70
SA 6 ..... 125 0.55 2800 71 1.8 2.45 9.0 0.62 70
SA 6 ..... 180 0.55 2800 71 1.8 3.52 9.0 0.62 70
55 SA 12 ..... 4 0.06 1400 71 0.3 0.38 1.2 0.6 46
SA 12 ..... 5.6 0.12 1400 71 0.5 0.46 2.3 0.6 55
SA 12 ..... 8 0.12 1400 71 0.5 0.62 2.3 0.6 55
SA 12 ..... 11 0.12 1400 71 0.5 0.90 2.3 0.6 55
SA 12 ..... 16 0.25 1400 71 1.4 1.45 4.6 0.5 50
SA 12 ..... 22 0.25 1400 71 1.4 1.80 4.6 0.5 50
120 SA 12 ..... 32 0.37 2800 71 1.0 2.42 5.5 0.76 68
SA 12 ..... 45 0.55 2800 71 1.8 3.08 9.0 0.62 70
SA 12 ..... 63 1.1 2800 71 2.9 4.58 16.0 0.72 72
SA 12 ..... 90 1.1 2800 71 2.9 6.50 16.0 0.72 72
SA 12 ..... 125 1.1 2800 71 2.9 5.10 16.0 0.72 72
SA 12 ..... 180 1.1 2800 71 2.9 7.50 16.0 0.72 72
SA 15 ..... 4 0.06 1400 71 0.3 0.45 1.2 0.6 46
110 SA 15 ..... 5.6 0.12 1400 71 0.5 0.55 2.3 0.6 55
SA 15 ..... 8 0.12 1400 71 0.5 0.83 2.3 0.6 55
SA 15 ..... 11 0.25 1400 71 1.4 1.36 4.6 0.5 50
SA 15 ..... 16 0.25 1400 71 1.4 1.66 4.6 0.5 50
SA 15 ..... 22 0.37 2800 71 1.0 2.00 5.5 0.76 68
SA 15 ..... 32 0.55 2800 71 1.8 2.75 9.0 0.62 70
150 .....
SA 15 45 1.1 2800 71 2.9 4.26 16.0 0.72 72
SA 15 ..... 63 1.1 2800 71 2.9 5.67 16.0 0.72 72
SA 25 ..... 4 0.12 1400 71 0.5 0.65 2.3 0.6 55
SA 25 ..... 5.6 0.25 1400 71 1.4 1.29 4.6 0.5 50
SA 25 ..... 8 0.55 1400 71 2.8 1.64 12.0 0.51 60
SA 25 ..... 11 0.55 1400 71 2.8 1.92 12.0 0.51 60
SA 25 ..... 16 0.55 1400 71 2.8 2.60 12.0 0.51 60
SA 25 ..... 22 0.55 1400 71 2.8 3.58 12.0 0.51 60
250 ..... 2.9 4.75 16.0 0.72 72
SA 25 32 1.1 2800 71
SA 25 ..... 45 1.1 2800 71 2.9 6.58 16.0 0.72 72
SA 25 ..... 63 2.2 2800 90 4.6 8.44 40.0 0.83 80
SA 25 ..... 90 2.2 2800 90 4.6 12.5 40.0 0.83 80
SA 25 ..... 125 2.2 2800 90 4.6 8.95 40.0 0.83 80
SA 25 ..... 180 2.2 2800 90 4.6 13.6 40.0 0.83 80

220

1) Current at max. torque. We recommend to select switch gear and cables suitable for those values.

We reserve the right to alter data according to improvements made. Previous data sheets become invalid with the issue of this data sheet.

32
Electrical Data SA3-SA100
Open-Close duty
Auma India
Three phase Squirrel cage AC Motor 415V, 50 Hz
Actuator Type
Torque
Max. Type Output Speed Nominal Speed Size Nominal Current at Starting Power Full load
at 50 Hz Output 1/min Current Max. Torque Current Factor Efficiency
KW A 1) A A Cos o (%)
Nm 1/min
SA 30 ..... 4 0.12 1400 71 0.5 0.82 2.3 0.6 55
SA 30 ..... 5.6 0.25 1400 71 1.4 1.39 4.6 0.5 50
SA 30 ..... 8 0.55 1400 71 2.8 1.77 12.0 0.51 60
SA 30 ..... 11 0.55 1400 71 2.8 2.20 12.0 0.51 60
SA 30 ..... 16 0.55 1400 71 2.8 3.08 12.0 0.51 60
300 ..... 3.7 3.95 25.0 0.58 72
SA 30 22 1.1 1400 90
SA 30 ..... 32 1.1 2800 71 2.9 5.72 16.0 0.72 72
SA 30 ..... 45 1.25 2800 90 2.7 8.65 22.0 0.81 79
SA 30 ..... 63 2.2 2800 90 4.6 10.0 40.0 0.83 80
SA 30 ..... 90 2.5 2800 90 5.3 15.5 40.0 0.83 79
SA 30 ..... 125 2.5 2800 90 5.3 11.5 40.0 0.83 79
264 SA 30 ..... 180 4.0 2800 90 10.2 16.5 65.0 0.7 78
SA 50 ..... 4 0.25 1400 71 1.4 1.48 4.6 0.5 50
SA 50 ..... 5.6 0.55 1400 71 2.8 1.95 12.0 0.51 60
SA 50 ..... 8 0.55 1400 71 2.8 2.60 12.0 0.51 60
SA 50 ..... 11 0.55 1400 71 2.8 3.58 12.0 0.51 60
SA 50 ..... 16 1.1 1400 90 3.7 4.80 25.0 0.58 72
SA 50 ..... 22 1.1 1400 90 3.7 6.65 25.0 0.58 72
500 SA 50 ..... 32 2.2 2800 90 4.6 8.52 40.0 0.83 80
SA 50 ..... 45 2.2 2800 90 4.6 12.5 40.0 0.83 80
SA 50 ..... 63 4.0 2800 90 10.2 17.1 65.0 0.7 78
SA 50 ..... 90 4.0 2800 90 10.2 26.0 65.0 0.7 78
SA 50 ..... 125 5.0 2800 112 9.9 18.2 80.0 0.86 88
SA 50 ..... 180 5.0 2800 112 9.9 28.5 80.0 0.86 50
450 SA 60 ..... 4 0.25 1400 71 1.4 1.67 4.6 0.55 50
SA 60 ..... 5.6 0.55 1400 71 2.8 2.2 12.0 0.51 60
SA 60 ..... 8 0.55 1400 71 2.8 3.08 12.0 0.51 60
SA 60 ..... 11 0.55 1400 71 2.8 5.15 12.0 0.51 60
SA 60 ..... 16 1.1 1400 90 3.7 5.75 25.0 0.58 72
SA 60 ..... 22 2.2 1400 90 6.9 7.92 40.0 0.63 72
SA 60 ..... 32 2.2 2800 90 4.6 10.04 40.0 0.83 80
600 .....
SA 60 45 4.0 2800 90 10.2 15.05 65.0 0.7 78
SA 60 ..... 63 4.0 2800 90 10.2 21.08 65.0 0.7 78
SA 60 ..... 90 5.0 2800 112 9.9 31.08 80.0 0.86 88
SA 60 ..... 125 5.0 2800 112 9.9 22.5 80.0 0.86 88
SA 60 ..... 180 5.0 2800 112 9.9 35.5 80.0 0.86 88
SA 100 ..... 4 0.55 1400 71 2.8 2.55 12.0 0.51 60
540 SA 100 ..... 5.6 0.55 1400 71 2.8 3.85 12.0 0.51 60
SA 100 ..... 8 0.75 1400 90 2.0 4.65 12.0 0.72 75
SA 100 ..... 11 1.1 1400 90 3.7 6.65 25.0 0.58 72
SA 100 ..... 16 2.2 1400 90 6.9 9.06 40.0 0.63 72
SA 100 ..... 22 2.2 1400 90 6.9 12.5 40.0 0.63 72
SA 100 ..... 32 4.0 2800 90 10.2 17.5 65.0 0.7 78
1000 SA 100 ..... 45 4.0 2800 90 10.2 26.0 65.0 0.7 78
SA 100 ..... 63 7.5 2800 112 15.6 40.0 116.0 0.78 86
SA 100 ..... 90 7.5 2800 112 15.6 60.0 116.0 0.78 86
SA 100 ..... 125 7.5 2800 112 15.6 44.6 116.0 0.78 86
SA 100 ..... 180 7.5 2800 112 15.6 68.0 116.0 0.78 86

900

Permissible voltage variation : + 10%, Permissible frequency variation : + 5%, Permissible combined variation : 10%
if voltage drops below there will be reduction of nominal output.
Auma motors are provided with 3 thermoswitches one in each winding connected in series to protect windings. Our
warranty is void if those thermoswitches are not connected in control circuit.
Motor data are approximate. Due to usual manufacturing tolerances there may be deviations from the values given.

1) Current at max. torque. We recommend to select switch gear and cables suitable for those values.
We reserve the right to alter data according to improvements made. Previous data sheets become invalid with the issue of this data sheet.

33
Technical Data SAR6-SAR100
Regulating duty
1)
Tripping Regu- Auma India No. of Valve Stem dia. Permissible Hand Hand wheel Weight
Torque lating Actuator Type starts Mounting Output drive Thrust for wheel Ratio Auma India Norm
in both Torque Flange Type-A Type-A Dia.
Standard
directions Type Output Speed
DIN:3210
Std. Std. With bevel Std. With bevel
2) Max. gear set gear set
Min. Max. Max. (Special
Nm Nm Nm 1/min c/h ISO:5210) Max. mm Max. kN Kgs. Kgs.
SAR 6 ..... 4
SAR 6 ..... 5.6
SAR 6 ..... 8
SAR 6 ..... 11
SAR 6 ..... 16
G0
30 60 30 1200
(F10) 26 40 250 1:1 2:1 39 45
SAR 6 ..... 22
SAR 6 ..... 32
SAR 6 ..... 45
SAR 12 ..... 4
SAR 12 ..... 5.6
SAR 12 ..... 8
SAR 12 ..... 11
SAR 12 ..... 16 G0 38 60 250 1:1 2:1 39 45
60 120 60 SAR 12 ..... 22 1200 (F10)
SAR 12 ..... 32
SAR 12 ..... 45
SAR 15 ..... 4 900
SAR 15 ..... 5.6
SAR 15 ..... 8
SAR 15 ..... 11
SAR 15 ..... 16 G0
60 150 75 .....
1200
(F10) 38 60 250 1:1 2:1 39 45
SAR 15 22
SAR 15 ..... 32
SAR 25 ..... 4
SAR 25 ..... 5.6
SAR 25 ..... 8
SAR 25 ..... 11
SAR 25 ..... 16
..... 1200 G 12
SAR 25 22
120 250 120 SAR 25 ..... 32
52 120 360 1:1 3:1 72 88
.....
(F14)
SAR 25 45 900
SAR 30 ..... 4
30 ..... 5.6
600
SAR
SAR 30 ..... 8
SAR 30 ..... 11
SAR 30 ..... 16 1200
SAR 30 ..... 22
..... G 12
150 300 150 SAR 30 32 52 120 360 1:1 3:1 72 88
SAR 30 ..... 45 (F14)
SAR 50 ..... 4
..... 600
SAR 50 5.6
SAR 50 ..... 8
SAR 50 ..... 11
.....
1200
SAR 50 16
SAR 50 ..... 22
SAR 50 ..... 32 900 G 12
250 500 250 SAR 50 ..... 45 52 160 640 1:1 3:1 75 92
SAR 60 ..... 4 (F14)
SAR 60 ..... 5.6 600
SAR 60 ..... 8
SAR 60 ..... 16
SAR 60 ..... 22 1200
SAR 60 ..... 32 G 12
300 600 300 SAR 100 ..... 4 52 160 640 1:1 3:1 75 92
SAR 100 ..... 5.6 (F14)
..... 600
SAR 100 8
SAR 100 ..... 11
100 ..... 16
1200
SAR
SAR 100 ..... 22 900
G3
500 1000 500 (F16) 65 190 800 1:1 4:1 107 128
600

Enclosure : IP67 - IS:13947


Actuators are rated for Intermittent duty S - 25% ED, based on 40o C ambient temperature. The nominal current is based on an
average load of approximately 35% of max. torque. The max. torque can be utilised for a short time (e.g. to seat or unseat
a valve) and the current can rise to max. value. Refer corresponding column for current at max. torque in Electrical Data.

1) Infinitely adjustable 2) At 50 Hz
We reserve the right to alter data according to improvements made. Previous data sheets become invalid with the issue of this data sheet.

34
Electrical Data SAR6-SAR100
Regulating duty
Auma India
Regulating Torque Three phase Squirrel cage AC Motor 415V, 50 Hz
Actuator Type
Type Output Speed Nominal Speed Size Nominal Current at Starting Power Full load
Max. at 50 Hz Output 1/min Current Max. Torque Current Factor Efficiency
Nm KW A 1) A A Cos o (%)
1/min
SAR 6 ..... 4 0.06 1400 71 0.3 0.25 1.2 0.6 46
SAR 6 ..... 5.6 0.06 1400 71 0.3 0.30 1.2 0.6 46
SAR 6 ..... 8 0.06 1400 71 0.3 0.38 1.2 0.6 46
SAR 6 ..... 11 0.12 1400 71 0.5 0.45 2.3 0.6 55
SAR 6 ..... 16 0.12 1400 71 0.5 0.62 2.3 0.6 55
30 SAR 6 ..... 22 0.12 1400 71 0.5 0.90 2.3 0.6 55
SAR 6 ..... 32 0.25 1400 71 1.4 1.45 4.6 0.5 50
SAR 6 ..... 45 0.25 1400 71 1.4 1.86 4.6 0.5 50
SAR 12 ..... 4 0.06 1400 71 0.3 0.38 1.2 0.6 46
SAR 12 ..... 5.6 0.12 1400 71 0.5 0.46 2.3 0.6 55
SAR 12 ..... 8 0.12 1400 71 0.5 0.62 2.3 0.6 55
SAR 12 ..... 11 0.12 1400 71 0.5 0.90 2.3 0.6 55
60 SAR 12 ..... 16 0.25 1400 71 1.4 1.45 4.6 0.5 50
SAR 12 ..... 22 0.25 1400 71 1.4 1.80 4.6 0.5 50
SAR 12 ..... 32 0.55 1400 71 2.8 2.52 12.0 0.51 60
SAR 12 ..... 45 0.55 1400 71 2.8 3.52 12.0 0.51 60
SAR 15 ..... 4 0.06 1400 71 0.3 0.45 1.2 0.6 46
SAR 15 ..... 5.6 0.12 1400 71 0.5 0.55 2.3 0.6 55
SAR 15 ..... 8 0.12 1400 71 0.5 0.83 2.3 0.6 55
SAR 15 ..... 11 0.25 1400 71 1.4 1.36 4.6 0.5 50
75 SAR 15 ..... 16 0.25 1400 71 1.4 1.66 4.6 0.5 50
SAR 15 ..... 22 0.55 1400 71 2.8 2.20 12.0 0.51 60
SAR 15 ..... 32 0.55 1400 71 2.8 3.08 12.0 0.51 60
SAR 25 ..... 4 0.12 1400 71 0.5 0.65 2.3 0.6 55
SAR 25 ..... 5.6 0.25 1400 71 1.4 1.29 4.6 0.5 50
SAR 25 ..... 8 0.25 1400 71 1.4 1.64 4.6 0.5 50
SAR 25 ..... 11 0.55 1400 71 2.8 1.92 12.0 0.51 60
SAR 25 ..... 16 0.55 1400 71 2.8 2.60 12.0 0.51 60
SAR 25 ..... 22 0.55 1400 71 2.8 3.58 12.0 0.51 60
125 .....
SAR 25 32 1.1 1400 90 3.7 4.80 25.0 0.58 72
SAR 25 ..... 45 1.1 1400 90 3.7 6.67 25.0 0.58 72
SAR 30 ..... 4 0.12 1400 71 0.5 0.82 2.3 0.6 55
SAR 30 ..... 5.6 0.25 1400 71 1.4 1.39 4.6 0.5 50
SAR 30 ..... 8 0.25 1400 71 1.4 1.77 4.6 0.5 50
SAR 30 ..... 11 0.55 1400 71 2.8 2.20 12.0 0.51 60
SAR 30 ..... 16 0.55 1400 71 2.8 3.08 12.0 0.51 60
SAR 30 ..... 22 1.1 1400 90 3.7 3.95 25.0 0.58 72
150 SAR 30 ..... 32 1.1 1400 90 3.7 5.75 25.0 0.58 72
SAR 30 ..... 45 2.2 1400 90 6.9 8.0 40.0 0.63 72
SAR 50 ..... 4 0.25 1400 71 1.4 1.48 4.6 0.5 50
SAR 50 ..... 5.6 0.55 1400 71 2.8 1.95 12.0 0.51 60
SAR 50 ..... 8 0.55 1400 71 2.8 2.60 12.0 0.51 60
SAR 50 ..... 11 0.55 1400 71 2.8 3.58 12.0 0.51 60
SAR 50 ..... 16 1.1 1400 90 3.7 4.80 25.0 0.58 72
SAR 50 ..... 22 1.1 1400 90 3.7 6.65 25.0 0.58 72
250 SAR 50 ..... 32 2.2 1400 90 6.9 9.06 40.0 0.63 72
SAR 50 ..... 45 2.2 1400 90 6.9 13.4 40.0 0.63 72
SAR 60 ..... 4 0.25 1400 71 1.4 1.67 4.6 0.5 50
SAR 60 ..... 5.6 0.55 1400 71 2.8 2.2 12.0 0.51 60
SAR 60 ..... 8 0.55 1400 71 2.8 3.08 12.0 0.51 60
SAR 60 ..... 16 1.1 1400 90 3.7 5.75 25.0 0.58 72
SAR 60 ..... 22 2.2 1400 90 6.9 7.92 40.0 0.63 72
SAR 60 ..... 32 2.2 1400 90 6.9 11.1 40.0 0.63 72
300 SAR 100 ..... 4 0.55 1400 71 2.8 2.55 12.0 0.51 60
SAR 100 ..... 5.6 0.55 1400 71 2.8 3.85 12.0 0.51 60
SAR 100 ..... 8 0.75 1400 90 2.0 4.65 12.0 0.72 75
SAR 100 ..... 11 1.1 1400 90 3.7 6.65 25.0 0.58 72
SAR 100 ..... 16 2.2 1400 90 6.9 9.06 40.0 0.63 72
SAR 100 ..... 22 2.2 1400 90 6.9 12.5 40.0 0.63 72
500

Permissible voltage variation : + 10%, Permissible frequency variation : + 5%, Permissible combined variation : 10%
if voltage drops below there will be reduction of nominal output.
Auma motors are provided with 3 thermoswitches one in each winding connected in series to protect windings. Our
warranty is void if those thermoswitches are not connected in control circuit.
Motor data are approximate. Due to usual manufacturing tolerances there may be deviations from the values given.
1) Current at Max. torque. We recommend to select switch gear and cables suitable for those values.
We reserve the right to alter data according to improvements made. Previous data sheets become invalid with the issue of this data sheet.

35
SA3-SA100
Norm actuator SAR6-SAR100

SA3 & SA6 SA12 & SA15 SA25 & SA30 SA50 & SA60 SA100
Dimensions SAR6 SAR12 & SAR15 SAR25 & SAR30 SAR50 & SAR60 SAR100
A 215 215 245 245 275
B 257 257 282 282 307
C 210 235 275 275 380
D 250 250 360 640 800
D1 110 - 125 110 - 125 110 - 160 125 - 160 125 - 200
D2 42 x 3.3 60 x 3.7 76 x 3.7 76 x 3.7 89 x 4.1
E 195 195 255 255 255
J 185 185 210 210 230
L max. 175-230 175-230 175-280 210-280 210-305
LL min. 35 35 45 45 60
M min. 80 80 80 80 80
N 110 110 170 170 210
O 96 96 96 96 96
P 142 142 167 167 192
Q min 65 65 65 65 65
R (Conduit th) 2x1 BSC 2x1 BSC 2x1 BSC 2x1 BSC 2x1 BSC
1 1 1 1 1
S 255 4 '' 255 4 '' 255 4 '' 255 4 '' 255 4 ''
Y 182 185 250 250 306
d 125 125 175 175 210
g (TYPE - A) 35 37 51 51 69
g1 (TYPE - B & C) 50 50 65 65 80
g2 ( TYPE - D & E) 15 15 22 22 30
DIN 3210 Designation G0 G0 G G G3
1 1
2 2

We reserve the right to alter data, dimensions and weights according to improvement made. (all dimensions are in mm)
Figures and diagrams are not binding.

36
SA3-SA100
Integral starter compact actuator SAR6-SAR100

SA3 & SA6 SA12 & SA15 SA25 & SA30 SA50 & SA60 SA100
Dimensions SAR6 SAR12 & SAR15 SAR25 & SAR30 SAR50 & SAR60 SAR100
A 215 215 245 245 275
B 430 430 451 451 467
C 210 235 275 275 380
D 250 250 360 640 800
D1 110 - 125 110 - 125 110 - 160 125 - 160 125 - 200
D2 42 x 3.3 60 x 3.7 76 x 3.7 76 x 3.7 89 x 4.1
E 195 195 255 255 255
J 185 185 210 210 230
K 342 342 342 342 342
L max. 340 340 450 450 515
LL min. 35 35 45 45 60
M min. 80 80 80 80 80
N 227 227 227 227 227
O 96 96 96 96 96
P 315 315 340 340 365
Q min 65 65 65 65 65
R (Conduit th) 2x1 BSC 2x1 BSC 2x1 BSC 2x1 BSC 2x1 BSC
S 25514 '' 25514 '' 25514 '' 25514 '' 25514 ''
V 160 160 160 160 160
W 185 185 185 185 185
d 125 125 175 175 210
g (TYPE - A) 35 37 51 51 69
g1 (TYPE - B & C) 50 50 65 65 80
g2 ( TYPE - D & E) 15 15 22 22 30
DIN 3210 Designation G0 G0 G G G3
1 1
2 2

We reserve the right to alter data, dimensions and weights according to improvement made. (all dimensions are in mm)
Figures and diagrams are not binding.

37
SA3-SA100
Integral starter epac actuator SAR6-SAR100

e-pac

e-pac

e-pac

SA3 & SA6 SA12 & SA15 SA25 & SA30 SA50 & SA60 SA100
Dimensions SAR6 SAR12 & SAR15 SAR25 & SAR30 SAR50 & SAR60 SAR100
A 215 215 245 245 275
B 278.5 278.5 303.5 303.5 329.5
C 210 235 275 325 380
D 250 250 360 640 800
D1 110 - 125 110 - 125 110 - 160 125 - 160 125 - 200
D2 42 x 3.3 60 x 3.7 76 x 3.7 76 x 3.7 89 x 4.1
E 195 195 255 255 255
J 185 185 210 210 230
K 256 256 256 256 256
L max 340 340 450 450 515
LL min. 35 35 45 45 60
M min. 80 80 80 80 80
N 240.5 240.5 240.5 240.5 240.5
O 96 96 96 96 96
P 400.5 400.5 425.5 425.5 451.5
Q min 65 65 65 65 65
R (Conduit th) 2x1 BSC 2x1 BSC 2x1 BSC 2x1 BSC 2x1 BSC
S 25514 '' 25514 '' 25514 '' 25514 '' 25514 ''
V 185 185 185 185 185
W 175 175 175 175 175
Z (For ON-OFF Duty) 121 121 121 121 121
Z1 (For Regulating Duty) 202 202 202 202 202
d 125 125 175 175 210
g (TYPE - A) 35 37 51 51 69
g1 (TYPE - B & C) 50 50 65 65 80
g2 ( TYPE - D & E) 15 15 22 22 30
DIN 3210 Designation G0 G0 G G G3
1 1
2 2
We reserve the right to alter data, dimensions and weights according to improvement made. (all dimensions are in mm)
Figures and diagrams are not binding.

38
SA3-SA100
Output drives according to DIN 3210 SAR6-SAR100
SA3/ SA12/ SAR12/ SA25/ SAR25/ SA50/ SAR50/ SA100/
SAR 6
SA6 SA15 SAR15 SA30 SAR30 SA60 SAR60 SAR100

39
SA6-SA100
Linear Thrust Unit for control valves with
LTU6-LTU100

For all other dimensions of actuator, please refer separate data sheet (all dimensions are in mm)

Dimensions LTU6 LTU12 LTU25 LTU50 LTU100


SA / SAR6 SA / SAR12 SA / SAR25 SA / SAR50 SA / SAR100
Stroke (L) mm 50 100 60 120 80 160 80 160
Thrust max. kN 20 35 63 100
Thrust max. kN
10 18 31.5 50
for Regulating
Stem thread, LH Tr. 24x5 Tr. 32x6 Tr. 40x7 Tr. 50x8
A 150 200 155 215 219 299 219 299
B 60 70 101 101
C 25 30 55 55
D 70 70 100 100
E 125 125 175 175
F
15 15 16 16
G
M10 M10 M16 M16
H
3 3 4 4
J
102 102 140 140
K
M16x1.5 M20x1.5 M36x3 M36x3

40
Terminal plan - Norm actuator

DSR Torque switch, closing, clockwise rotation


DOL Torque switch, opening, anti-clockwise rotation
WSR Limit switch, closing, clockwise rotation
WOL Limit switch, opening, anti-clockwise rotation
DSR1
DOL1 } Torque switch in tandem operation
with DSR/DOL
WSR1
WOL1 } Limit switch in tandem operation
with WSR/WOL
Th Thermo switch
b1 Push button for stop
b2 Push button for close
b3 Push button for open
C1 Contactor-close
C2 Contactor-open
e4 Thermal overload relay
e5 Control fuse
h1 Indicator lamp-close
h2 Indicator lamp-open
h3 Indicator lamp-trouble
M Motor (3Phase AC) 415V, 3 , 50Hz
a1 Main switch
SH Space heater
b4 Selector switch
N Neutral
E Earth
R,S,T(L1,L2,L3) Phases
e1-e3 Main fuse
A Auto
m Manual

41
Wiring diagram - Integral starter, epac

42
Info-A
Collective fault indication for Display board legend:-
- Thermoswitch trip Symbol Type Description Symbol Type Description
- Torque switch trip
Status Actuator in open direction Fault Torque switch open
Info-B
Potential free contact Local-Off-Remote
Status Actuator in Close direction Fault Torque switch close

Status Limit switch open Fault Thermoswitch trip

Status Limit switch close Fault Thermal overload relay trip


K1 - Open Contactor
K2 - Close Contactor Status Actuator in local mode Fault Fault indication
Th - Thermoswitch
RL1 - 24V DC Relay for OPEN Contactor Status Actuator in remote mode Fault Single phasing
RL2 - 24V DC Relay for CLOSE Contactor
RL3 - 24V DC Relay for FAULT Annunciation Status 11V Internal power supply
C8M-C8F - 64 Pin Male-Female connector
8 8
C15M-C15F - 24 Pin Rack & panel Male-Female connector Status 23V Internal power supply
Legend - Integral starter, epac

M - Motor 3Ph, 415V, 50Hz.


DSR - Close torque switch Status 24V DC For Customer's use
DOL - Open torque switch
WSR - Close limit switch Dip switch particulars:-
WOL - Open limit switch
Switch Switch position Switch position
DSR1/DOL1 - Torque switch in tandem operation with DSR/DOL Remarks
No OFF ON
WSR1/WOL1 - Limit switch in tandem operation with WSR/WOL
1 Inching operation in Local mode Non-inching operation in Local mode Applicable
F,G - Plug in type terminals between basic actuator(Norm) (non self retaining) (self retaining)
2 Emergency shut down to Open Not-Applicable
and Integral starter(epac) 3 Emergency shut down to Close Not-Applicable
R,Y,B - Main supply 415V, 3o, 50Hz, AC Supply 4 Timer board operation enabled Timer board operation disenabled Not-Applicable
A,B,C - Motor terminals 5 Inhibit Open direction Not-Applicable
L 1-27 - Terminals for customer's connections 6 Inhibit Close direction Not-Applicable
SH - Space heater Inching operation in Remote Non-Inching operation in Remote mode
7 mode (non self retaining) Applicable
(self retaining)

43
8 Limit switch close bypass
(Closing by torque switch Close) Limit Seating Applicable
(Torque Seating)
automates valves

auma india norm auma india e-pac


SA3 - SA100 SA3 - SA100
SAR6 - SAR100 SAR6 - SAR100
Output torque from 30 to 1000 Nm Output torque from 30 to 1000 Nm

Worm Gear Boxes Bevel Gear Boxes Worm Gear Boxes


GS 40.2-GS 125.2 GK 10.2-GK 35.1 GF 40.2-GF 250
Output torque from 300 to 5600 Nm Output torque from 120 to 8000 Nm Output torque from 300 to 45000 Nm

Worm Gear Boxes Spur Gear Boxes


GS 160-GS 500 GST 12-GST 1600
Output torque from 8000 to 360000 Nm Output torque from 120 to 16000 Nm

Head Office and Works Branch Office Branch Office


AUMA (INDIA) LIMITED AUMA (INDIA) LIMITED AUMA (INDIA) LIMITED
Plot No. 39-B, II Phase 8-C, Block B-H,Munirka "Kalpadrum", 12, Pandurang Colony
Peenya Industrial Area NEW DELHI - 110 067. Behind New Karnataka High School
Bangalore - 560 058. Erandwana, Pune - 411 038.
Ph : 080-8394365 Ph : 011-6187063 Ph : 020-5410465
080-8394366
080-8392808
Fax : 080-8392809 Fax : 011-6109637 Fax : 020-5443186
E-mail : info@auma.co.in E-mail : aumandl@vsnl.net E-mail : aumapn@pn3.vsnl.net.in
DD / CT 001 issue 10/02