Professional Documents
Culture Documents
Catalogue
March
Sepam 1000+ Merlin Gerin
Series 20
2002 Series 40
Presentation 2
More solutions 2
Flexible architecture 5
User-machine interface 6
Selection table 8
Sepam series 20 8
Sepam series 40 9
Metering 10
Description 10
General settings and characteristics 11
Protection 12
Description 12
Setting ranges 14
Connection diagrams 16
Sepam series 20 16
Sepam series 40 17
Phase current inputs 18
Residual current inputs 19
Sepam series 20 voltage inputs 20
Sepam series 40 voltage inputs 21
Control and monitoring 22
Description 22
Logic inputs and outputs 23
Logic input / output assignment
for Sepam series 20 applications 24
Logic input / output assignment
for Sepam series 40 applications 25
Annunciation 26
Customization 27
Communication 28
Description and characteristics 28
Optional remote modules 30
Description 30
Connections 31
Sensors 32
LPCT type current sensors 32
Core balance CTs 33
Characteristics 34
Size and weight 34
Electrical characteristics 36
Environmental characteristics 37
Order form
Schneider Electric 1
Presentation More solutions
The Sepam series 20 B21 and B22 voltage units are suitable for the following
situations:
b monitoring of network voltage and frequency
b loss of mains detection by rate of change of frequency protection for installations
with local power generation.
Sepam series 40
Sepam series 40, with its current and voltage metering capabilities, offers high-
performing solutions for more demanding applications.
MT11017
Sepam series 40 units perform the following funcitons in addition to those performed
by Sepam series 20:
b protection of closed ring networks or networks with parallel incomers, by
directional protection
b directional earth fault protection suitable for all earthing systems: impedant,
isolated or compensated neutral
b protection of networks with variable configurations requiring the switching of
groups of settings and logic discrimination
M T11018
b all the necessary electrical measurements: phase and residual currents, phase-to-
neutral, phase-to-phase and residual voltage, frequency, power and energy, ...
b comprehensive network diagnosis assistance: 20 seconds of disturbance
recording, detailed history of the last 200 alarms, storage of the last 5 tripping
contexts
b adaptation of control functions by a logical equation editor
b customization of alarm messages to fit each application, and/or in the user’s
language.
2 Schneider Electric
Presentation More solutions
More simplicity
M T11026
Simple to install
b no constraints for integration in cubicles due to the compact size of the base units
and remote installation of optional modules
b universal auxiliary power supply.
Simple to commission
b all the functions are ready to use
b user-friendly, powerful PC setting software to utilize all the possibilities offered by
Sepam.
Simple to operate
With the advanced UMI, all local operations are made easier by a clear, complete
presentation of all the required information in your language.
Simple to maintain
b digital unit self-diagnosis and watchdog
Example: Advanced UMI customized for Chinese users.
b switchgear diagnosis assistance functions to assess equipment condition and
schedule preventive maintenance operations:
v cumulative breaking current
MT11027
More communication
MT 11019
Modbus communication
All the data needed for centralized management of your electrical network are
available with the communication option based on the open, international Modbus
protocol:
b measurement and diagnosis values
b remote indication and time-tagging of events
b remote control of the installation
b remote setting of protection functions
b reading of disturbance recording files.
PowerLogic System
Sepam is a component of PowerLogic System and may naturally be associated with
SMS centralized industrial and commercial electrical network management software.
Schneider Electric 3
Presentation More solutions
More modularity
Sepam 1000+ is available with 2 User-Machine Interface (UMI) levels:
b advanced UMI , with keypad and graphic LCD display
v to provide all the data required for local operation of the installation:
measurements, diagnosis information, alarms, etc.
v to set Sepam parameters and protection functions
v to be understood by all, the screens can be displayed in the user’s language.
The advanced UMI may be part of the base unit or installed as a remote unit in the
most convenient location for the user.
b basic UMI, with signal lamps
v for remotely operated installations, via the communication link, with no continuous
need for local operation; a PC equipped with the SFT2841 software tool may be used
for occasional operation.
In order to adapt to as many situations as possible and allow for subsequent
upgrading of the installation, Sepam may be functionally enhanced at any time
by the addition of optional modules.
b logic input/output module with parameterizable program logic
b communication module
b temperature sensor module
b analog output module.
M T10995
M T10997
Sepam 1000+ with basic UMI. Sepam 1000+ with advanced UMI.
M T10996
4 Schneider Electric
Presentation Flexible architecture
M T10111
Schneider Electric 5
Presentation User-machine interface
Advanced UMI
M T10123
This UMI is an optimal solution for local operation, which is made easier by its
legibility, content and access to the different data.
In addition to the basic UMI functions, this version provides:
b a "graphic" LCD display with automatic contrast adjustment and user-triggered
backlighting. It is used to display measurements, parameter/protection settings and
alarm and operating messages.
Number of lines, size of characters and symbols according to screens and language
versions.
b a 9-key keypad with two operating modes:
White keys for current operation:
➀ display of measurements.
➁ display of switchgear and network diagnosis data.
➂ display of alarm messages.
➃ resetting.
Advanced UMI with standard signal lamp assignment.
➄ acknowledgment and clearing of alarms.
Blue keys for parameter and protection setting:
➆ access to protection settings.
➇ access to Sepam 1000+ parameter settings (2).
➈ used to enter the 2 passwords required to change protection and parameter
settings.
The “ ↵, ▲ , ▼ ” keys ( ➃, ➄, ➅ ) are used to navigate in the menus, and to scroll and
accept the values displayed.
“Lamp test” key ➅:
switching-on sequence of all the signal lamps.
(1) This removable label may be replaced by a customized label produced using the SFT 2841
software tool.
(2) For parameter setting of the program logic, the expert UMI must be used.
6 Schneider Electric
Presentation User-machine interface
Expert UMI
M T11102
This UMI is available as a complement to the basic or advanced UMI on the screen
of a PC equipped with the SFT2841 software tool and connected to the RS 232 link
on the front panel of the Sepam (operating in a Windows u V95 or NT environment).
All the data used for the same task are grouped together in the same screen to
facilitate operation. Menus and icons are used for fast, direct access to the required
information.
Current operating mode
This UMI is the solution suited to occasional local operation for demanding personnel
who require fast access to all the information.
b display of all metering and operating data
b display of alarm messages with the time of appearance
b display of diagnosis data such as:
v tripping current
SFT2841: measurement screen. v number of switchgear operations and cumulative breaking current
b display of all protection and parameter settings made
b display of the logic status of inputs, outputs and signal lamps.
MT 11103
Schneider Electric 7
Selection table Sepam series 20
8 Schneider Electric
Selection table Sepam series 40
Schneider Electric 9
Metering Description
10 Schneider Electric
Metering General settings and
characteristics
Metering
Phase current 0.1 to 1.5 In typically ± 1% typically ± 0.5% b
Residual current 0.1 to 1.5 Ino typically ± 1% typically ± 1% b
Average current and peak demand phase 0.1 to 1.5 In typically ± 1% typically ± 0.5%
current
Phase-to-phase voltage 0.05 to 1.2 Unp typically ± 1% typically ± 0.5% b
Phase-to-neutral voltage 0.05 to 1.2 Vnp typically ± 1% typically ± 0.5% b
Residual voltage 0.015 to 3 Vnp typically ± 1% typically ± 1%
Positive sequence voltage 0.05 to 1.2 Vnp typically ± 5% typically ± 2%
Negative sequence voltage 0.05 to 1.2 Vnp - typically ± 2%
Frequency series 20 50 ± 5 Hz or 60 ± 5 Hz ± 0.05 Hz - b
Frequency series 40 25 to 65 Hz - ± 0.02 Hz b
Temperature -30°C to +200°C or -22°F to 392°F ± 1°C from +20 to +140°C ± 1°C from +20 to +140°C b
Active power 0.015 Sn (3) at 999 MW - typically ± 1% b
Reactive power 0.015 Sn (3) at 999 Mvar - typically ± 1% b
Apparent power 0.015 Sn (3) at 999 MVA - typically ± 1% b
Power factor -1 (CAP) to 1 (IND) - typically ± 1%
Peak demand active power 0.015 Sn (3) at 999 MW - typically ± 1%
Peak demand Maximètre de puissance 0.015 Sn (3) at 999 Mvar - typically ± 1%
réactive
Active energy 0 to 2.1.108 MW.h - ± 1%, ± 1 digit
Reactive energy 0 to 2.1.108 Mvar.h - ± 1%, ± 1 digit
Network diagnosis assistance
Phase tripping current 0.1 to 40 In ± 5% ± 5%
Earth fault tripping current 0.1 to 20 Ino ± 5% ± 5%
Unbalance / neg. seq. current li 10% to 500% Ib ± 2% ± 2%
Phase displacement ϕ 0 0 to 359° - typically ± 2°
Phase displacement ϕ 1, ϕ 2, ϕ 3 0 to 359° - typically ± 2°
Machine operation assistance
Running hours counter / operating time 0 to 65535 hours ± 1% or ± 0.5 h ± 1% or ± 0.5 h
Thermal capacity used 0 to 800% (100% for I phase = Ib) ± 1% ± 1% b
Remaining operating time before overload 0 to 999 mn ± 1 mn ± 1 mn
tripping
Waiting time after overload tripping 0 to 999 mn ± 1 mn ± 1 mn
Starting current 1.2 Ib à 24 In ± 5% ± 5%
Starting time 0 to 300 s ± 300 ms ± 300 ms
Start inhibit time delay 0 to 360 mn ± 1 mn ± 1 mn
Number of starts before inhibition 0 to 60 1 1
Cooling time constant 5 mn to 600 mn - ± 5%
Switchgear diagnosis assistance
Cumulative breaking current 0 to 65535 kA² ± 10% ± 10%
Number of operations 0 to 65535 1 1
Operating time 20 to 100 ms ± 1 ms ± 1 ms
Charging time 1 to 20 s ± 0.5 s ± 0.5 s
(1) In reference conditions (IEC 60255-6), typical for In or Unp.
(2) Measurements available in analog format according to parameter setting of MSA141 module.
(3) Sn: apparent power, = 3 .Unp.In.
Schneider Electric 11
Protection Description
12 Schneider Electric
Protection Description
Schneider Electric 13
Protection Setting ranges
14 Schneider Electric
Protection Setting ranges
Schneider Electric 15
Connection diagrams Sepam series 20
M T11050
Connection to 1 A / 5 A current sensors
16 Schneider Electric
Connection diagrams Sepam series 40
M T11052
T40 / T42 / M41 / G40 types
Connection to 1 A / 5 A current sensors
Connector Type Ref. Cable
A Screw- CCA620 1 wire 0.2 to 2.5mm 2
type ( u AWG24-12)
2 wires 0.2 to 1mm 2
( u AWG24-16)
Ring lug CCA622
6.35mm
B Ring lug CCA630 1.5 to 6mm 2
4mm (AWG16 to AWG10)
C RJ45 CCA612
D RJ45 CCA770: L=0.6m
CCA772: L= 2m
CCA774: L=4m
E Screw- CCA626 1 wire 0.2 to 2.5mm 2
type ( u AWG24-12)
2 wires 0.2 to 1mm 2
( u AWG24-16)
Ring lug CCA627
6.35mm
Schneider Electric 17
Connection diagrams Phase current inputs
The measurement of the 3 phase currents allows the calculation of residual current.
The measurement of phase currents 1 and 3 is sufficient to ensure all the current-
based protection functions.
The measurement of the 3 phase currents allows the calculation of residual current.
18 Schneider Electric
Connection diagrams Residual current inputs
Setting range from 0.1 Ino to 15 Ino, with Ino = 2 A or 20 A (or 5 A for series 40)
according to parameter setting.
b connection of CSH30 interposing ring CT to 1 A CT: make 2 turns through the CSH
primary winding
b connection of CSH30 interposing ring CT to 5 A CT: make 4 turns through the CSH
primary winding
b with series 40, the sensitivity can be multiplied by 10 by parameter setting of Ino =
In/10.
Setting range from 0.1 In to 15 In, or 0.01 In to 1.5 In (series 40) with In = CT primary
current.
MT11046
Variant 4: residual current measurement by core balance CT with ratio 1/n (n between 50 and 1500)
The ACE990 is used as an interface between a MV core balance CT with ratio 1/n
(50 < n < 1500) and the Sepam 1000+ residual current input.
MT11047
This arrangement makes it possible to keep the existing core balance CTs in the
installation.
Schneider Electric 19
Connection diagrams Sepam series 20 voltage inputs
The phase and residual voltage transformer secondary circuits are connected to the
CCT640 connector (item B ) on Sepam series 20, B type. The CCT640 connector
contains 4 transformers which perform isolation and impedance matching of the VTs
and Sepam input circuits.
Variant 1: measurement of 3 phase-to-neutral voltages (standard connection)
Phase voltage sensor parameter setting 3V
Residual voltage sensor parameter setting 3V sum
MT 10984
20 Schneider Electric
Connection diagrams Sepam series 40 voltage inputs
The phase and residual voltage transformer secondary circuits are connected
directly to the connector marked E .
The 3 impedance matching and isolation transformers are integrated in the
Sepam series 40 base unit.
Variant 1: measurement of 3 phase-to-neutral voltages (standard connection)
Phase voltage sensor parameter setting 3V
Residual voltage sensor parameter setting 3V sum
MT 10992
Schneider Electric 21
Control and monitoring Description
Sepam 1000+ performs the basic control and monitoring functions necessary for the
operation of the electrical network, thereby reducing the need for auxiliary relays.
The control and monitoring functions may be parameterized using the SFT2841
software tool, however each type of Sepam has parameter setting by default which
allows easier commissioning in the most frequent applications.
ANSI 94/69 - Circuit breaker/contactor control
Sepam 1000+ is used to control breaking devices equipped with different types of
closing and tripping coils:
b circuit breakers with shunt trip or undervoltage trip units
b latching contactors with shunt trip units.
The breaking device control function processes all the circuit breaker closing and
tripping conditions based on:
b breaking device status information
b remote control orders
b protection functions
b program logic specific to each application (e.g. recloser).
This function also inhibits breaking device closing according to the operating
conditions.
With Sepam series 20, it is necessary to use an MES108 or MES114 module in order
to have all the required logic inputs.
Switching of groups of settings
Used to switch from one group of phase overcurrent and earth fault protection
settings to another group of settings. Switching may be performed by a logic input or
via the communication link.
Inhibition of thermal protection
Thermal protection tripping may be inhibited via a logic input.
Re-acceleration
Allows a logic input to take into account the restarting of an unstopped motor.
ANSI 68 - Logic discrimination (SSL)
This function allows quick, selective tripping of the definite time or IDMT phase
overcurrent and earth fault protection relays, without requiring the use of time
intervals between upstream and downstream protection devices. The downstream
relay transmits a blocking input signal if the protection device set points are
exceeded.
The upstream relay receives the blocking input signal on the logic input used for the
inhibition function. A saving mechanism ensures the operation of the protection in the
event of an inhibition link failure.
ANSI 86 - Latching / acknowledgment
Output relay latching may be parameterized. Latched tripping orders are stored and
must be acknowledged in order for the device to be put back into service. The user
acknowledges via the keypad or remotely via a logic input or the communication link.
Latching is stored in the event of a power outage.
Trip circuit supervision
Detects trip circuit faults (shunt trip units). Detects open/closed position discrepancy
faults (undervoltage trip units).
Watchdog
Indicates Sepam unavailability via output O4.
Output relay test
This function is used to activate each output relay.
22 Schneider Electric
Control and monitoring Logic inputs and outputs
M T10143
The 4 relay outputs O1, O2, O3 and O4 on the base unit are connected to
connector A .
Connector A of the base unit may be either of the following:
b CCA620 screw-type connector
b CCA622 ring lug connector.
O1 and O2 are 2 control outputs used by the breaking device control function for:
b O1: breaking device tripping
b O2: inhibition of breaking device closing.
O3 and O4 are indication outputs, only O4 can be activated by the watchdog function.
MT 10145
By the addition of an input/output extension module, the 4 outputs on the base unit
may be completed by either of the following:
b 4 inputs and 4 outputs with the MES108 module
b 10 inputs and 4 outputs with the MES114 module.
An MES module is mounted on the back of the base unit.
Output characteristics
b 4 relay outputs O11, O12, O13, O14
v O11: control output, used for breaking device closing
v O12, O13, O14: indication outputs.
Input characteristics:
b 4 or 10 potential-free inputs
b DC input voltage of 24V DC to 250V DC, external DC power source.
M T10147
Schneider Electric 23
Control and monitoring Logic input / output assignment
for Sepam series 20 applications
24 Schneider Electric
Control and monitoring Logic input / output assignment
for Sepam series 40 applications
Schneider Electric 25
Control and monitoring Annunciation
26 Schneider Electric
Control and monitoring Customization
Each Sepam 1000+ has a logic scheme by default according to the type chosen
(S20, T20,...).
The default program logic links the data derived from the protection functions to the
signal lamps and output relays to fit the unit’s most frequently used application.
It may be adapted for specific operations using the SFT2841 software tool, which
offers the following customization functions:
b customization of the control matrix
b logical equation editor (for Sepam series 40 only)
b modification of message wording (for Sepam series 40 only).
Control matrix
MT11104
The control matrix as a simple way to assign the input data derived from:
b protection functions
b control and monitoring functions
b logic inputs
to the following output data:
b 9 signal lamps on the front panel of Sepam
b output relays
b triggering of disturbance recording.
Schneider Electric 27
Communication Description and characteristics
Characteristics
Type of transmission asynchronous serial
Protocol Modbus slave (Jbus profile)
Rate (1) 4800, 9600, 19200, 38400 bauds
Data format (1) no parity
1 start, 8 bits, 1 stop even parity
odd parity
Response time Less than 15 ms
Sepam 1000+ addresses on a Modbus 1 to 25
network (1)
RS 485 electrical interface ACE949-2, compliant with EIA standard
2-wire, differential RS 485
ACE959, compliant with EIA standard
4-wire, differential RS 485
Electrical interface power supply External by 12 V DC or 24 V DC power supply
Type of connection Screw-type terminals and tightening yokes for
shielding protection
Maximum length of RS 485 network With 12 V DC distributed power supply to
with standard cord interfaces
(lengths multiplied by 3 with FILECA cord, 320 m with 5 Sepam 1000+
with a maximum of 1300m) 180 m with 10 Sepam 1000+
160 m with 20 Sepam 1000+
125m with 25 Sepam 1000+
With 24 V DC distributed power supply to
interfaces
1000 m with 5 Sepam 1000+
750 m with 10 Sepam 1000+
450 m with 20 Sepam 1000+
375 m with 25 Sepam 1000+
(1) parameter to be set.
28 Schneider Electric
Communication Description and characteristics
compatibility) viewpoints.
M T10139
For more information, refer to the "Sepam - RS 485 network connection guide"
PCRED399074EN.
Rx+, Rx-: Sepam receiving (eq IN+, IN-)
Tx+, Tx-: Sepam transmitting (eq OUT+, OUT-)
(1) distributed power supply with separate wiring or included in
the shielded cable (3 pairs).
(2) terminal block for connection of the distributed power supply
module.
Schneider Electric 29
Optional remote modules Description
The DSM303 module provides the same functional features as the fixed advanced
UMI.
Associated with a Sepam 1000+ with a basic UMI, it may be installed on the front
panel of the cubicle in the most suitable operating location.
b reduced depth of 30 mm
b a single module for each Sepam 1000+ with a basic UMI, to be connected by one
of the CCA772 or CCA774 prefabricated cords (2 or 4 meters). This module may not
be connected to Sepam 1000+ units with integrated advanced UMIs.
The MSA141 module converts Sepam 1000+ measurements into analog signals.
b selection of the measurement to be converted by parameter setting
b 0-10 mA, 4-20 mA or 0-20 mA analog signal according to parameter setting
b connection of the analog output to a screw-type connector:
v 1 wire with cross-section 0.2 to 2.5 mm² (u AWG24-12)
v or 2 wires with cross-section 0.2 to 1 mm² (u AWG24-16)
b a single module for each Sepam 1000+ base unit, to be connected to one of the
CCA770, CCA772 or CCA774 prefabricated cords (0.6, 2 or 4 meters).
30 Schneider Electric
Optional remote modules Connections
Connection of DSM303
remote advanced UMI
Wiring of inter-module links
Different module connection combinations are possible and the modules are
connected by prefabricated cords which come in 3 different lengths:
MT 10151
b CCA770 (L = 0.6 m)
b CCA772 (L = 2 m)
b CCA774 (L = 4 m).
The modules are linked by cords which provide the power supply and act as
functional links with the Sepam unit (D connector to Da connector Da, Dd to Da, ...).
The DSM303 module may only be connected at the end of the link.
Connection of MSA141
remote analog output
MT10152
MT11054
Maximum configuration
Three modules at the most may be connected to the base unit in accordance with the
order and maximum lengths of connections specified in the chart below:
Schneider Electric 31
Sensors LPCT type current sensors
CLP1 sensors are voltage-output current sensors of the Low Power Current
Transducer (LPCT) type, compliant with the IEC 60044-8 standard.
CLP1 sensors are designed to measure rated currents of between 100 and 1250 A,
with a ratio of 100 A / 22.5 mV, and may be used on networks with a maximum of
17.5 kV.
The secondary winding of the CLP1 sensor is pre-equipped with a 5-m long shielded
cable fitted with an RJ45 connector, which is connected to the 9-pin sub-D connector
B on Sepam via a CCA670 interface connector, mounted on the rear panel of the
Sepam 1000+ base unit.
Characteristics
Rated primary current 100 A
Rated secondary voltage 22.5 mV
Rated primary extended current 1250 A
Measurement accuracy class 0.5
Protection accuracy class 5P
Rated accuracy limit primary current 40 kA
Accuracy burden u 2 kΩ
Rated thermal short-circuit current 31.5 kA x 4 s - 40 kA x 3 s
CLP1 sensor. Rated voltage (Um) 17.5 kV
Rated power frequency withstand voltage 38 kV - 42 kV
Rated lightning impulse withstand voltage 95 kV
Weight 8 kg
The ACE917 adapter is used to test the protection chain with a standard injection
box, when Sepam 1000+ is connected to LPCT sensors.
The ACE917 adapter is inserted between:
b the standard injection box, which delivers a 1 A secondary current
b the LPCT test plug:
v integrated in the Sepam 1000+ CCA670 connector
v or transferred by means of the CCA613 accessory.
MT 11056
MT 11028
32 Schneider Electric
Sensors Core balance CTs
The specifically designed CSH120 and CSH200 core balance CTs are used for direct
residual current measurement. The only difference between them is the diameter.
Characteristics:
b accurancy: ± 5% at 20°C
b transformation ratio: 1/470
b maximum permissible current: 20kA - 1 s
b operating temperature: - 25°C to +70°C
b storage temperature: - 40°C to +85°C
b drift in accuracy related to temperature: ±1%
b the wiring resistance should be < 10 Ω.
The CSH30 interposing ring CT is used as an interface when the residual current is
measured using 1 A or 5 A current transformers.
It should be installed near the Sepam input (L<2m).
b weight: 0.12 kg
b mounted on symmetrical DIN rail.
Schneider Electric 33
Characteristics Size and weight
MT 11060
MT 11061
Mounting shown with advanced UMI and optional MES114
module.
Weight series 20 =1.2 kg without option.
Mounting plate thickness < 3 mm.
1. kg with option.
Weight series 40 =1.4 kg without option.
1.9 kg with option.
34 Schneider Electric
Characteristics Size and weight
DSM303 module Cutout for panel-mounting (mounting plate thickness < 3 mm)
MT 11063
MT 11064
ACE949-2 module ACE959 module
b weight: 0.1 kg b weight: 0.25 kg
b mounted on symmetrical DIN rail b mounted on symmetrical DIN rail
MT10119
MT10130
M T10124
Schneider Electric 35
Characteristics Electrical characteristics
Analog inputs
Current transformer input impedance < 0.001 Ω
1 A or 5 A CT (with CCA630) consumption < 0.001 VA at 1 A
1 A to 6250 A ratings < 0.025 VA at 5 A
rated thermal withstand 3 In
1-second overload 100 In
Voltage transformer input impedance > 100 kΩ
220 V to 250 kV ratings input voltage 100 to 230/√3 V
rated thermal withstand 230 V (1.7 Unp)
1-second overload 480 V (3.6 Unp)
Temperature sensor input (MET148-2 module)
Type of sensor Pt 100 Ni 100 / 120
Isolation from earth none none
Current injected in sensor 4 mA 4 mA
Logic inputs (MES108 - MES114 module)
Voltage 24 to 250 Vcc -20/+10% (19.2 to 275 V DC)
Consumption typically 3 mA - -
Switching set point (2) typically 14 V - -
Control output relays (O1, O2, O11 contacts)
Voltage DC 24 / 48 V DC 127 V DC 220 V DC
AC (47.5 to 63 Hz) - - - 100 to 240 V AC
Rated current 8A 8A 8A 8A
Breaking resistive load 8/4A 0.7 A 0.3 A
capacity L/R load < 20 ms 6/2A 0.5 A 0.2 A
L/R load < 40 ms 4/1A 0.2 A 0.1 A
resistive load - - - 8A
p.f. load > 0.3 - - - 5A
Making < 15 A for 200 ms
capacity
Indication output relays (O3, O4, O12, O13, O14 contacts)
Voltage DC 24 / 48 V DC 127 V DC 220 V DC
AC (47.5 to 63 Hz) - - - 100 to 240 V AC
Rated current 2A 2A 2A 2A
Breaking L/R load < 20ms 2/1A 0.5 A 0.15 A
capacity p.f. load > 0.3 - - - 1A
Power supply (series 20)
range deactivated consumption (1) max. consumption (1) inrush current
24 V DC -20% +50% (19.2 to 36 V DC) 3 to 6 W 7 to 11 W < 10 A for 10 ms
48 / 250 V DC -20% +10% 2 to 4.5 W 6 to 8 W < 10 A for 10 ms
110 / 240 V AC -20% +10% 3 to 9 VA 9 to 15 VA < 15 A for
47.5 to 63 Hz 1st half-period
brownout withstand 10 ms
Power supply (series 40)
range deactivated consumption (1) max. consumption (1) inrush current
24 / 250 V DC -20% +10% 3 to 6 W 7 to 11 W < 28 A 100 µs
110 / 240 V AC -20% +10% 3 to 6 W 9 to 25 W < 28 A 100 µs
47.5 to 63 Hz
brownout withstand 20 ms
Analog output (MSA141 module)
Current 4 - 20 mA, 0 - 20 mA, 0 - 10 mA
Load impedance < 600 Ω (wiring included)
Accuracy 0.50%
(1) according to configuration.
(2) for higher values, please consult us.
36 Schneider Electric
Characteristics Environmental characteristics
Schneider Electric 37
Notes
38 Schneider Electric
Notes
Schneider Electric 39
Notes
40 Schneider Electric
Order form
Sepam 1000+
To make it easier for you to choose your equipment and fill in your order form, it is
advisable to use the Sepam 1000+ Schneider Electric electronic catalogue (please
consult us) or to attach this page to your order, indicating the requested quantities in
the spaces and checking off the boxes that correspond to your choices.
Base units Additional modules and accessories
Sepam series 20 Input / output modules
Type User-Machine Quantity Designation Reference Quantity
of application Interface 4 inputs + 4 outputs module MES108
S20 basic 10 inputs + 4 outputs module MES114
advanced Remote modules and connection cords
T20 basic Designation Reference Quantity
advanced 8 temperature sensor module MET148-2
M20 basic Analog output module MSA141
advanced Remote advanced UMI module DSM303
B21 basic Remote module connection cord L = 0.6 m CCA770
advanced Remote module connection cord L = 2 m CCA772
B22 basic Remote module connection cord L = 4 m CCA774
advanced Mounting plate AMT840
Working language Communication accessories
English / French Designation Reference Quantity
English / Spanish 2 wire, RS 485 network interface, without CCA612 cord ACE949-2
English / Local (1) 4-wire, RS 485 network interface, without CCA612 cord ACE959
Auxiliary power supply Network interface connection cord L = 3 m CCA612
24 V DC RS 485/RS 232 converter ACE909-2
48-250 V DC and 100-240 V AC RS 485/RS 485 interface (AC) ACE919CA
Type of phase current sensor RS 485/RS 485 interface (DC) ACE919CC
(for S20, T20 and M20) Core balance CTs
1 A / 5 A CT Designation Reference Quantity
LPCT Residual current sensor (diameter 120) CSH120
Type of main connector A Residual current sensor (diameter 200) CSH200
Screw-type connector Interposing ring CT for residual current input CSH30
Ring lug connector Core balance CT interface ACE990
Sepam series 40 LPCT phase current sensors
Type User-Machine Quantity Designation Reference Quantity
of application Interface LPCT phase current sensor CLP1
S40 basic LPCT injection adapter ACE917
advanced Remote LPCT test plug CCA613
S41 basic Software tools and documentation
advanced Designation Reference Quantity
S42 basic PC parameter setting and operation software kit SFT2841 kit
advanced with CCA783 cord
T40 basic Notice d’utilisation Sepam 1000+ série 20 PCRED301005FR
advanced Sepam 1000+ series 20 user’s manual PCRED301005EN
T42 basic Notice d’utilisation Sepam 1000+ série 40 PCRED301006FR
Schneider Electric Postal address: As standards, specifications and designs change from time to
Industries SA F - 38050 Grenoble cedex 9 time, please ask for confirmation of the information given in this
France document.
This document has been
printed on ecological paper.
Tel : +33 (0)4 76 57 60 60
Publishing: AMEG
http://www.schneider-electric.com Production: Schneider Electric
Printing:
PCRED301004EN/1
ART.08533
02-2002