Plant Sizing Summary for Chilled Water System

KIA Metro_BIAL 05/19/2021


Egis India Consulting Engineers Pvt Ltd. 07:29PM

1. Plant Information:
Plant Name ........................................................... Chilled Water System
Plant Type ........................................................... Generic Chilled Water
Design Weather ............................................................ Bangalore, India

2. Cooling Plant Sizing Data:


Maximum Plant Load ..................................................................... 2180.0 kW
Load occurs at ......................................................................... Jul 1600
m²/kW ................................................................................................ 4.2 m²/kW
Floor area served by plant .............................................................. 9065.6 m²

3. Coincident Cooling Loads for Jul 1600

System
Cooling
Coil Load
Air System Name Mult. [kW]
1. AHU-Platform(LHS)-PL 1 668.8
10. FCU-BMRCL-TR(RHS-2)-PL 1 3.3
11. FCU-Office-TR-PL 1 3.4
12. FCU-E&M UPS Batery Room-2-PL 1 4.6
13. FCU-SER&TER Room-CL-0 1 14.8
14. FCU-TER Room-CL-0 1 11.8
15. FCU-S&T UPS-CL-0 1 15.2
17a. FCU-Retail-1-CL-0 1 87.3
17b. FCU-Retail-2-CL-0 1 18.6
17c. FCU-Retail-3-CL-0 1 19.8
17d. FCU-Retail-4-CL-0 1 12.4
17e. FCU-Retail-5-CL-0 1 9.2
17f. FCU-Retail-6-CL-0 1 9.6
17g. FCU-Retail-7-CL-0 1 7.0
17h. FCU-Retail-8-CL-0 1 19.8
17i. FCU-Retail-9-CL-0 1 19.4
17j. FCU-Retail-10-CL-0 1 17.2
17k. FCU-Retail-11-CL-0 1 32.0
17l. FCU-Retail-12-CL-0 1 86.9
17m. FCU-Retail-13-CL-0 1 34.9
17n. FCU-Retail-14-CL-0 1 17.6
17o. FCU-Retail-15-CL-0 1 34.4
17p. FCU-Retail-16-CL-0 1 17.1
17q. FCU-Retail-17-CL-0 1 17.5
17r. FCU-Retail-18-CL-0 1 13.2
17s. FCU-Retail-19-CL-0 1 11.9
17t. FCU-Retail-20-CL-0 1 9.6
17u. FCU-Retail-21-CL-0 1 16.5
17v. FCU-Retail-22-CL-0 1 17.8
18a. FCU-Retail-1-CL-1 1 34.9
18b. FCU-Retail-2-CL-1 1 16.0
18c. FCU-Retail-3-CL-1 1 24.2
18d. FCU-Retail-4-CL-1 1 10.0
18e. FCU-Retail-5-CL-1 1 87.4
19. FCU-SMR-CL-1 1 4.5
2. AHU-Platform(RHS)-PL 1 668.8
20. FCU-Data Center-1-CL-1 1 7.4
21. FCU-Video Wall Rm-CL-1 1 7.8
22. FCU-First Aid Room-CL-1 1 2.0
23. FCU-Ticket Office-1-CL-1 1 4.0
24. FCU-SCR-CL-1 1 15.1
25. FCU-Data Center-2-CL-1 1 8.5
26. FCU-Ticket Office-2-CL-1 1 3.9

Hourly Analysis Program v5.01 Page 1 of 2


Plant Sizing Summary for Chilled Water System
KIA Metro_BIAL 05/19/2021
Egis India Consulting Engineers Pvt Ltd. 07:29PM

System
Cooling
Coil Load
Air System Name Mult. [kW]
27. FCU-Secuirity Room-CL-1 1 3.6
28. FCU-EFO-CL-1 1 1.2
3. FCU-PSD Room-PL 1 7.6
4. FCU-E&M UPS Battery Room-1-PL 1 5.4
5. FCU-BMRCL-TR(LHS)-PL 1 2.8
6. FCU-Supervisor Booth Room-PL 1 1.3
7. FCU-BMRCL-TR(RHS-1)-PL 1 5.1
8. FCU-Mess Room-PL 1 4.2
9. FCU-BIAL-TR-PL 1 2.7

Air system loads are for coils whose cooling source is ' Chilled Water ' or ' Any ' .

Hourly Analysis Program v5.01 Page 2 of 2