Type Deep seated fires as it's an electrical shelter (electrical cables

Steps (same for both surface and DS) Basic requirement: 34% if surface, 50% if deep seated (in gen
Material conversion factor if different than 34%
Loss through unclosable openings
Loss through ventilation
High/low temperature allowance

Dimensions of the shelter L*l*h (in m) 10 4 5


Volume of the battery room inside the shelter (m3) 45
Volume of the shelter (m3) 155
Design concentration (table 5.4.2.1) 50%
Volume factor (Kg CO2/m3) 1.33
Basic quantity of CO2 Required (Kg) 206.15

Rq: No openings --> no volume to compensate

Number of cylinders (Units ; With ref to Fike manual) 5


Quantity of CO2 (in Kg) 227
Number of cylinders (main + reserve) 10
Total quantity of CO2 (in Kg) 454
NFPA 12
electrical shelter (electrical cables …)