You are on page 1of 4

Clean Agent Calculation

Novec™ 1230 (FK-5-1-12)

With Equipment volume


Design Surface Flooding factor
Room H (m) volume (m3)
Concentration (m2) kg/m3

Ctrl 4.70% 30 2.7 81 0.6861


Electric 4.70% 9 2.7 24.3 0.6861
Prayer 4.50% 30 2.7 81 0.6555

Without Equipment volume


Design Surface equipement
Room H (m) volume (m3)
Concentration (m2) volume (m3)
Ctrl 4.70% 30 2.7 81 5.184
Electric 4.70% 9 2.7 24.3 4.86
Prayer 4.50% 30 2.7 81 -
Calculation
(FK-5-1-12)

Temperature 20°C

Novec 1230
quantity (kg)

55.5741
16.67223
53.0955
125.34183

olume
Reduced volume Flooding factor Novec 1230
(m3) kg/m3 quantity (kg)
75.816 0.6861 52.0173576
19.44 0.6861 13.337784
81 0.6555 53.0955
118.4506416
NFPA 2001: Standard on Clean Agent Fire Extinguishing