You are on page 1of 3

Design concentaration 7%

Temperature 20°C

With Equipment volume

Flooding FM-200
Surface Equipment
Room H (m) volume (m3) factor quantity
(m2) volume
kg/m3 (KG)
SWG 1157.75 5.7 800 5799.175 0.5498 3188.38642
FAR 254.88 5.7 0 1452.816 0.5498 798.758237
Battery room 85.6 5.7 40 447.92 0.5498 246.266416

Without Equipment volume


Flooding FM-200
Surface
Room H (m) volume (m3) factor quantity
(m2)
kg/m3 (KG)
SWG 1157.75 5.7 6599.175 0.5498 3628.22642
FAR 254.88 5.7 1452.816 0.5498 798.758237
Battery room 85.6 5.7 487.92 0.5498 268.258416
Clean Agent Calculation
Novec™ 1230 (FK-5-1-12)

Room Design concentaration Surface (m2) H (m) volume (m3)

Control room 4.70%


Electrical room 4.70%
Prayer room 4.50%
Flooding Novec 1230
factor quantity
kg/m3 (KG)