GENERATOR
SPECIFICATION
GENERATOR SIZING

Atotal 951,818.35 kWh


AVERAGE LOAD = = = 39,659.10 kW
24 HOURS 24 HOURS

MAXIMUM DEMANDOF THE SYSTEM 53,892.55 kW


DEMAND FACTOR = = = 0.9377
TOTALCONNECTED LOAD 57,471.76 kW

DIVERSITY FACTOR =
∑ OF THE INDIVIDUAL MAXIMUM DEMAND =
57,471.76 kW
=
MAXIMUM DEMAND 53,892.55 kW
1.0664

AVERAGE DEMAND 39,659.10 kW


LAOD FACTOR = = = 0.7359
MAXIMUM DEMANDOF THE SYSTEM 53,892.55 kW

MAXIMUM DEMANDOF THE SYSTEM


MAXIMUM GENERATED DEMAND =
POWER FACTOR

53,892.55 kW
MAXIMUM GENERATED DEMAND = = 62,231.582 kVA
0.866

MAXIMUM GENERATED DEMAND 53,892.55 kW


CAPACITY PER UNIT= = = 26,946.275
2 2
kVA

USE 2 – 30,000 kW GENERATOR AND 1-STANDBY UNIT

1.15 (DEMANDOF THE SYSTEM )


GENERATING CAPCITY =
POWER FACTOR OF THE SYSTEM

1.15(53,892.55 kW )
GENERATING CAPACITY = = 71,566.319 kVA
0.866

MAXIMUM GENERATED DEMAND 53,892.55 kVA


UTILIZATION FACATOR= =¿ = 0.753
GENERATING CAPACITY 71,566.319kVA

AVERAGE LOAD 39,659.10 KW


PLANT FACTOR = = = 0.661
TOTALGENERATING RATED CAPACITY 2 x 30 MVA