Professional Documents
Culture Documents
2. The ICCP continuous anode will be buried in the pipe trench at a distance of 0.5 m from the pipe at the 3 or 9 o'clock
position (i.e. halfway between bottom and top of pipe depth). Anode splicing shall be done using splice kits and shall
be done as per approved procedure and drawings. Anode tail cables shall be terminated at designated AJB. Sufficient
watering shall be carried out after anode laid in the trench and before backfilling. In any case anodes shall not be in
touch/in electrical contact with the pipe.
3. Where there are branching pipes, the sock anode will run all around the branching pipe if the branch length is lower
than five meters, while the sock anode will be spliced to a branching sock anode if the pipe branch length is above five
metres.
N = 2510.250 DRAWING LIMIT
4. Bonding cables shall be installed to maintain electrical continuity at locations such as nonwelded joints, mechanical
E = 1789.500
BD-EY-W400 BD-EY-W400 joints, flanges, couplings, concrete pits and locations where there is no electrical continuity within the piping system
W400 ELECTRICAL BURIED EXISTING W400 ELECTRICAL BURIED EXISTING
TRENCH
to be cathodically protected. Bonding/Jumper among the pipes shall be provided outside the pits.
TRENCH
5. The piping shall be isolated with neoprene rubber from any reinforced concrete support / wall to minimize current
2003.350FGL
N= 2505.350
E= 1827.763 BD-EY-W600 drains from rebars in reinforced concrete structures.
EXISTING FENCE 4- 6. Soil access shall be installed next to the test posts and junction boxes at paved areas.
BD-EY-W400 7. The number of Permanent Magnesium Anodes at TP Type 3 locations shall be as per "DETAILED DESIGN CALCULATION
REPORT " document no. 4058-VW-CX-00OO000013 (Ref. No. 19).
8. CP cable shall not be laid in instrument / ELECT Trench. A separate cable tray shall be used for CP at least 300mm away
from ELECT cable in order to avoid the interference. All cables shall be laid without coils or kinks, buried in sand at a
CJ
CJ
CJ
CJ
CJ
CJ
2003.350FGL IJ
depth of at least 0.75 m, provided with cable protection tiles and warning tape installed 250 mm above the cable. The
N= 2501.850
820-FX-43-01 E= 1886.850
BD-EY-W600
A430-DO-10"-A01BU-002 IJ guidelines/precautions, please refer to the Intallation Specification document (Ref. No. 23) and to the Installation
746-XA-71-01
HOLD-2
A FUN-077-6"x4"
N= 2494.032
2003.350FGL Drawings (Ref. No. 24).
820-PG-43-05A E= 1897.658
CJ 12. For the Schematic Drawing, please refer to the relevant Document (Ref. No. 25).
TP13
HOLD-1 (FV-011-02)
13. All installation works associated with the Cathodic Protection system shall be conducted in accordance with this
A430-DO-4"-A01BU-001
WF-VP-004 drawing and the complete CP design package (see documents Ref No. 16 to 29 for full list). Any conflict between this
14" EXISTING WF LINE EXISTING
A430-DO-10"-A01BU-003 drawing and other CP drawings and / or other project specifications and drawings shall be brought to the attention of
EXISTING NATURAL A IJ the CP Engineer in writing for clarification as soon as it is discovered.
CJ
CJ
CJ
CJ
CJ
CJ
SOIL 14" EXISTING WF LINE
(R-011-3) 14. The final location of the TR Units, Junction Boxes and Test Posts shall be checked by the CP Engineer in consultation
(EXISTING) N= 2486.318
E= 1836.900
24" EXISTING DO
6"-WF-71-4821-A01BU-N BD-IY-W300 24" EXISTING DO with the installation Sub-contractor and client. The TR Units, Junction Boxes and Test Posts shall, where practicable, be
LINE
DRAWING LIMIT
LINE
(R-011-1)
installed in such a fashion that safe and convenient access to them is maintained.
(RCF-011-4)
TIE-IN N= 2486.318
E= 1885.298 A430-DO-SM-030
(EXISTING)
N= 2486.661
E= 1929.295
Under no circumstances shall the TR Units, Junction Boxes and Test Posts be installed in a location where they could
TP-328
be damaged and / or cause an obstruction or interference to the regular activities of the operator.
15. Wherever there is a pit, Electrical continuity among the pipes like DO, DOV shall be provided at all the locations using
(R-011-2)
bonding Jumper cable (1c 25 mm2) and thermite welding.
EXTRA WIDTH
INSTALL PE / PVC SHEET TO 16. Packaged Sacrificial anodes shall be installed 1.5 m away from the pipes and shall be installed at the bottom level of
EXTRA WIDTH
MITIGATE INTERFERENCE
C OF 6.0M. WIDE
TRENCH
PLEASE SEE SHEET 7 FOR ADDITIONAL NOTES
24" EXISTING DO
ROAD
W400 INSTRUMENTAL BURIED EXISTING
MAP VIEW
L
TRENCH
LINE
LP1
LP1
1789.500
1832.150
E= 2040.000
E= 2044.000
E=
E=
N=
2510.250
N= 2507.000
E= 2063.775
DRAWING LIMIT DRAWING LIMIT N= 2497.801
E = 1789.500
DRAWING LIMIT
EXISTING LIGHT EXISTING LIGHT EXISTING LIGHT N=
2459.000
E= 1936.700
POLE POLE POLE
N= 2446.300
N= 2445.000
A340-DO-6"-A01BU-044
WIDTH
DRAWING LIMIT
E= 1937.010
DRAWING
N= 2383.100
LIMIT
N= 2378.700
DRAWING LIMIT
THIS PAGE
DRAWING
LIMIT
MATCH
LINE-A
LEGEND
TRANSFORMER RECTIFIER UNIT (TRU)
DRAWING LIMIT
DRAWING LIMIT
NEGATIVE DISTRIBUTION BOX (NDB) - OR
NEGATIVE JUNCTION BOX (NJB) - OR
DRAWING LIMIT
BOND BOX (BB)
N= 2168.300
N= 2149.446
DRAWING LIMIT
TEST BOX (TB) - TYPE 2 (PSP AND TCP) A B.LENKA PROCS 30-03-3021
TEST BOX (TB) - TYPE 3 (PCP) Comment status code:
A - Accepted CR - Commented. Resubmit for Acceptance
TEST BOX (TB) - TYPE 4 (INTERFERENCE MITIGATION)
AC - Accepted with Comment, NA
Resubmit
- Not accepted, Resubmit
TEST BOX (TB) - TYPE 5 (PVC CASING)
IMPORTANT: CONTRACTOR acceptance of this Document does not relieve the
STRUCTURE CONNECTION VENDOR from full compliance with contractual obligation
NEGATIVE WELD PAD/CLEAT CONNECTION
SPLICE KIT 5 25MAR21 25MAR21 REVISED PER CLIENT COMMENTS N.SIPPEL A.BONETTI S.FILMORE
PERMANENT CSE REFERENCE ELECTRODE
4 10FEB21 23FEB21 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
C COUPON
3 10FEB21 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
AND THERMOWELD CONNECTIONS)
7.7kg MAGNESIUM ANODE 2 15DEC20 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
A
(TEMPORARY CP)
1 23SEP20 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
14.5kg MAGNESIUM ANODE
A
(PERMANENT CP) 0 15JUL20 ISSUED FOR APPROVAL L.HULL N.SIPPEL A.BONETTI
PIPE LEGEND
A 2x ZINC RIBBON ANODES
WS: WATER SOURCE (PERMANENT CP)
DOV: VENT PIPE Realisation du 4eme Train GPL a ZCINA, Hassi Messaoud
DO: OPEN DRAIN (NON-HAZ) CT-EPC/001/SH/EPM-G/EP/18
DC: CLOSED DRAIN
E = 1789.500
E = 2063.775
(FV-0120-04) position (i.e. halfway between bottom and top of pipe depth). Anode splicing shall be done using splice kits and shall
24" EXISTING DO
TIE-IN TIE-IN TIE-IN
WF-VP-EXISTING
EXISTING TP-325 EXISTING ROAD TP-324 TP-323
(FV-0120-03) be done as per approved procedure and drawings. Anode tail cables shall be terminated at designated AJB. Sufficient
POLE (TYP)
LIGHT WF-VP-EXISTING watering shall be carried out after anode laid in the trench and before backfilling. In any case anodes shall not be in
TIE-IN INSTALL PE / PVC SHEET touch/in electrical contact with the pipe.
LINE
TP-323 TO MITIGATE 3. Where there are branching pipes, the sock anode will run all around the branching pipe if the branch length is lower
W400 ELECTRICAL BURIED EXISTING TRENCH
(FV-011-02) INTERFERENCE than five meters, while the sock anode will be spliced to a branching sock anode if the pipe branch length is above five
WF-VP-004 (R-012-13) W400 INSTRUMENTAL BURIED EXISTING TRENCH metres.
EXISTING A310-DO-MH-020
8"-WF-71-0815-A01BU-N 6"-WF-71-0832-A01BU-N 14" EXISTING WF LINE 4. Bonding cables shall be installed to maintain electrical continuity at locations such as nonwelded joints, mechanical
14" EXISTING WF LINE
joints, flanges, couplings, concrete pits and locations where there is no electrical continuity within the piping system
DO-TIE-IN-001 BD-IY-W300 A A to be cathodically protected. Bonding/Jumper among the pipes shall be provided outside the pits.
BD-IY-W300
24" EXISTING DO 6"-WF-71-0831-A01BU-N TIE-IN TP-301 5. The piping shall be isolated with neoprene rubber from any reinforced concrete support / wall to minimize current
LINE
N= 2486.619
TP14 TP15 BB2-1 drains from rebars in reinforced concrete structures.
BD-IY-W300 E= 1965.000 741-XW-71-10
741-XM-71-03 14" EXISTING WF LINE 6. Soil access shall be installed next to the test posts and junction boxes at paved areas.
N= 2486.619
E= 1958.624
A310-DO-16"-A01BU-007
(FV-012-4)
A310-WF-VP-001
(FV-012-5)
A310-WF-VP-002
TP16 7. The number of Permanent Magnesium Anodes at TP Type 3 locations shall be as per "DETAILED DESIGN CALCULATION
4"-WF-71-4809-A01BU-N
741-XM-71-02
R-012-1
4"-WF-71-4810-A01BU-N
(FV-012-7) REPORT " document no. 4058-VW-CX-00OO000013 (Ref. No. 19).
(EXISTING) A A320-WF-VP-001
8. CP cable shall not be laid in instrument / ELECT Trench. A separate cable tray shall be used for CP at least 300mm away
from ELECT cable in order to avoid the interference. All cables shall be laid without coils or kinks, buried in sand at a
BD-EY-W600
depth of at least 0.75 m, provided with cable protection tiles and warning tape installed 250 mm above the cable. The
A310-DO-16"-A01BU-001
A320-DO-16"-A01BU-002
N= 2482.275 N= 2482.275 TIE-IN
E= 2000.400 E= 2002.300
TP-302 trench shall be 300 mm wide.
BD-EY-W600
150THK.CURB 484-KF-41-01
9. Distance from piping to junction boxes and test posts shall be approx 1.5 m.
2-
Drawings (Ref. No. 24).
12. For the Schematic Drawing, please refer to the relevant Document (Ref. No. 25).
A320-DO-DT-006-W400
14" EXISTING WF LINE
13. All installation works associated with the Cathodic Protection system shall be conducted in accordance with this
N= 2469.500
E= 1989.000 drawing and the complete CP design package (see documents Ref No. 16 to 29 for full list). Any conflict between this
C
L OF G14-UF-24-01 C
L OF 484-UF-41-01 drawing and other CP drawings and / or other project specifications and drawings shall be brought to the attention of
DRAWING LIMIT
N= 2469.500
(RCF-012-3) E= 2025.000
TP29 the CP Engineer in writing for clarification as soon as it is discovered.
A310-DO-SM-007 6 THK. CHQUERED
N= 2464.900 PLATE
A320-DO-SM-015 14. The final location of the TR Units, Junction Boxes and Test Posts shall be checked by the CP Engineer in consultation
E= 1965.000
6 THK. CHQUERED A320-DO-MH-019 N= 2465.350
E= 2059.300
with the installation Sub-contractor and client. The TR Units, Junction Boxes and Test Posts shall, where practicable, be
PLATE A320-DO-TD-001-W400 installed in such a fashion that safe and convenient access to them is maintained.
W400 ELECTRICAL BURIED EXISTING TRENCH
A320-DOV-4"-A01BU-001
EXISTING ROAD
EXTRA WIDTH
A310-DO-16"-A01BU-002
C Under no circumstances shall the TR Units, Junction Boxes and Test Posts be installed in a location where they could
TR-EY-W600 A320-DO-16"-A01BU-001 N= 2464.550
E= 2049.000
be damaged and / or cause an obstruction or interference to the regular activities of the operator.
14" EXISTING WF LINE N= 2464.550
E= 2042.501
A320-DO-16"-A01BU-004 15. Wherever there is a pit, Electrical continuity among the pipes like DO, DOV shall be provided at all the locations using
A310-DOV-4"-A01BU-001
200W X 250H
INSTALL PE / PVC bonding Jumper cable (1c 25 mm2) and thermite welding.
BD-EY-W600
BD-EY-W800
SHEET TO MITIGATE
EXISTING ROAD
CUTOUT 200W X 250H 16. Packaged Sacrificial anodes shall be installed 1.5 m away from the pipes and shall be installed at the bottom level of
EXISTING EXTRA
MAINTENANCE AREA
300mm COMPACTED
N= 2456.120
E= 1959.575
TP21 20. Polarisation coupon and permanent reference cells shall be installed 100 mm away from the pipe and shall be 1/3rd of
884-FX-43-01
14" EXISTING WF LINE
EXISTING EXTRA
TUFF 2000.000
TIE-IN pipe depth from pipe bottom level.
TP-303
TP17 6"-WF-71-4801-A01BU-N
A
PLEASE SEE SHEET 7 FOR ADDITIONAL NOTES
WIDTH
A320-DO-16"-A01BU-003
A A 6" EXISTING WF LINE
741-XA-71-04
MAP VIEW
A310-DO-16"-A01BU-003
BD-IY-W300
A310-DO-SM-026
DRAWING LIMIT
N= 2441.504
A370-DO-4"-A01BU-001 E= 2004.946
AJB2-2
NJB2-3
DRAWING LIMIT
N= 2439.000 N= 2439.857
E= 1990.000 E= 2003.300
DRAWING
LIMIT
N= 2439.000
E= 2004.800 BD-IY-W300
A310-DO-MH-018
C A
DRAWING LIMIT
N= 2439.000 A310-DO-12"-A01BU-005 A310-DO-6"-A01BU-006 THIS PAGE
E= 1965.000
3"-HM-57-4403-A03-N
A310-DO-16"-A01BU-004
TP11
DRAWING
LIMIT
MATCH
LINE-A
A310-DOV-4"-A01BU-002
DRAWING LIMIT
TRANSFORMER RECTIFIER UNIT (TRU)
DRAWING LIMIT
NEGATIVE DISTRIBUTION BOX (NDB) - OR
DRAWING LIMIT
NEGATIVE JUNCTION BOX (NJB) - OR
BOND BOX (BB) DRAWING LIMIT
DRAWING LIMIT
PIPE LEGEND
A 2x ZINC RIBBON ANODES
WS: WATER SOURCE (PERMANENT CP)
DOV: VENT PIPE Realisation du 4eme Train GPL a ZCINA, Hassi Messaoud
DO: OPEN DRAIN (NON-HAZ) CT-EPC/001/SH/EPM-G/EP/18
DC: CLOSED DRAIN
A320-DO-16"-A01BU-003
N = 2439.000 2. The ICCP continuous anode will be buried in the pipe trench at a distance of 0.5 m from the pipe at the 3 or 9 o'clock
E = 1789.500
A310-DOV-4"-A01BU-002
2000.000
PIPE LEGEND
E = 2063.775
BD-IY-W300
position (i.e. halfway between bottom and top of pipe depth). Anode splicing shall be done using splice kits and shall
mm COMPACTED
3"-HM-41-4403-A03-N
WS: WATER SOURCE be done as per approved procedure and drawings. Anode tail cables shall be terminated at designated AJB. Sufficient
MAINTENANCE
watering shall be carried out after anode laid in the trench and before backfilling. In any case anodes shall not be in
A340-DO-6"-A01BU-044
N= 2432.145
OC1-VL-57-09
AJB2-1
E= 1959.650
AREA
W400 INSTRUMENTAL BURIED EXISTING TRENCH
N= 2428.140
TUFF
N= 2428.100 E= 2034.940
E= 1982.510 E= 2027.050
WF: FIRE WATER
300
A360-DO-MH-001
N= 2428.500
E= 1965.000 than five meters, while the sock anode will be spliced to a branching sock anode if the pipe branch length is above five
8"-DP-57-4349-M01-N N= 2428.141
metres.
N= 2428.100
A350-DO-6"-A01BU-006 A350-DOV-4"-A01BU-001 OWS: OILY WATER SYSTEM 4. Bonding cables shall be installed to maintain electrical continuity at locations such as nonwelded joints, mechanical
(TYP.)
E= 2034.940
OC1-VL-57-12 E= 1985.510 N= 2426.300
E= 2059.300
8"-DC-57-4343-A01BUCD-N 8"-DC-57-4343-A01BUCD-N C
8"-DP-57-4301-M01-N N= 2426.000
E= 2034.940 N= 2425.500
E= 2036.625
DOV: VENT PIPE joints, flanges, couplings, concrete pits and locations where there is no electrical continuity within the piping system
A350-DO-4"-A01BU-005
(RCF-012-18)
N= 2425.383
E= 1985.510
(RD-012-3)
A350-DO-SM-027
to be cathodically protected. Bonding/Jumper among the pipes shall be provided outside the pits.
A350-DO-CO-009
DO: OPEN DRAIN (NON-HAZ) 5. The piping shall be isolated with neoprene rubber from any reinforced concrete support / wall to minimize current
INSTALL PE /
6" EXISTING WF LINE
3"-HM-41-4301-A03-N
E= 2035.800
N= 2418.501
PVC SHEET TO DC: CLOSED DRAIN 6. Soil access shall be installed next to the test posts and junction boxes at paved areas.
3"-DC-57-4368-A01BUCD-N E= 2035.800 2000.000 FGL
N= 2418.353
E= 2035.800
MITIGATE 7. The number of Permanent Magnesium Anodes at TP Type 3 locations shall be as per "DETAILED DESIGN CALCULATION
INTERFERENCE DP: PROCESS DRAIN REPORT " document no. 4058-VW-CX-00OO000013 (Ref. No. 19).
A360-DO-16"-A01BU-001
MAINTENANCE AREA
8. CP cable shall not be laid in instrument / ELECT Trench. A separate cable tray shall be used for CP at least 300mm away
300mm COMPACTED
FUN-070-6"x4" HM: HEATING MEDIUM from ELECT cable in order to avoid the interference. All cables shall be laid without coils or kinks, buried in sand at a
8"-DC-57-4300-A01BUCD-N
E= 2039.358
C
L OF 884-VD-43-01 N= 2413.500
W400 ELECTRICAL BURIED EXISTING TRENCH
9. Distance from piping to junction boxes and test posts shall be approx 1.5 m.
TUFF
E= 2026.970
150 THK. CURB WALL
2"-HM-41-4405-A03-N
N= 2412.084 N= 2413.540
A370-DO-6"-A01BU-003
(TYP) E= 2016.600
10. For the Cable Schedule, please refer to the relevant Document (Ref. No. 27).
(TYP) 11. For the basic requirement/guidelines to be followed by construction personnel during installation, and for brief
8"-DP-57-4301-M01-N
2"-HM-41-4397-A03-N
E= 2018.791
N= 2409.569
E= 2013.453
guidelines/precautions, please refer to the Intallation Specification document (Ref. No. 23) and to the Installation
A330-DOV-4"-A01BU-003
N= 2408.505
N= 2408.505
E= 1995.700
MAINTENANCE
Drawings (Ref. No. 24).
N= 2409.650
50 THK. N= 2407.633
E= 1990.595
E= 1994.982
300
AREAmm COMPACTED TP 305 12. For the Schematic Drawing, please refer to the relevant Document (Ref. No. 25).
E= 1968.375
COVER
GRATING TUFF
13. All installation works associated with the Cathodic Protection system shall be conducted in accordance with this
EXISTING ROAD
EXISTING EXTRA
2000.000
A330-DO-4"-A01BU-007
N= 2405.000
2"-HM-41-4408-A03-N drawing and the complete CP design package (see documents Ref No. 16 to 29 for full list). Any conflict between this
A350-DO-6"-A01BU-003
E= 1997.000
drawing and other CP drawings and / or other project specifications and drawings shall be brought to the attention of
A330-DO-DT-002-W400
N= 2405.000
A340-DO-6"-A01BU-012
WIDTH
E= 1979.150
N= 2402.800
E= 1994.982
N= 2402.800
E= 1999.200 741-XA-71-05 14. The final location of the TR Units, Junction Boxes and Test Posts shall be checked by the CP Engineer in consultation
with the installation Sub-contractor and client. The TR Units, Junction Boxes and Test Posts shall, where practicable, be
3"-DP-57-4424-M01-N
A330-DO-4"-A01BU-009 2"-HM-41-4396-A03-N N= 2400.700
TP18 N= 2402.436
E= 2013.900
E= 2027.700
A installed in such a fashion that safe and convenient access to them is maintained.
A350-DO-16"-A01BU-001
HOLD-1
N= 2399.640
E= 2012.000 A340-DO-CO-008 TP22 Under no circumstances shall the TR Units, Junction Boxes and Test Posts be installed in a location where they could
A 6"-WF-71-4805-A01BU-N 741-XA-71-02
N= 2398.755
E= 2033.603 be damaged and / or cause an obstruction or interference to the regular activities of the operator.
A330-DO-6"-A01BU-001 3"-DC-57-4370-A01BUCD-N
(FV-012-8)
A340-WF-VP-001
15. Wherever there is a pit, Electrical continuity among the pipes like DO, DOV shall be provided at all the locations using
A330-DO-16"-A01BU-003 (RD-012-012) 2"-HM-41-4400-A03-N CURB WALL bonding Jumper cable (1c 25 mm2) and thermite welding.
A340-DO-CO-019 N= 2396.150
N= 2396.739
E= 2025.131
150 THK., 100 HT. 16. Packaged Sacrificial anodes shall be installed 1.5 m away from the pipes and shall be installed at the bottom level of
EXISTING LIGHT
C
L OF G14-CE-32-01
E= 2024.574
pipe.
484-PA-41-01A TP 308
NDB2 A330-DO-SM-005 17. Sacrificial anodes shall be laid horizontally. Anodes shall be soaked in water 24 hours prior to installation.
N= 2391.300
E= 1979.150 N= 2390.650
E= 1984.150
N= 2394.033
E= 2021.856
N= 2392.325
18. Test station shall be installed 1.5 m away from the pipe.
N= 2391.800
E= 1965.000 3"-DP-57-4429-M01-N N= 2390.739
E= 2030.725
19. AJB/PDB/BB/NDB/NJB shall be installed 1.5 m away from the pipe. Cables inside the TP/JB shall be terminated with
TR-2
N= 2390.600
PDB2
E= 2025.131
A330-DO-4"-A01BU-010
N= 2388.026
E= 2021.864
A N= 2386.900
E= 2043.600
4"-DP-57-4301-M01-N
3"-DP-57-4803-M01-N A340-DO-16"-A01BU-005
MAP VIEW
N= 2387.500 N= 2383.700 N= 2383.700
E= 1992.094 E= 2027.870 E= 2053.750
A340-DO-16"-A01BU-004
A330-DO-16"-A01BU-004
N= 2381.996
TP09 E= 2022.493
A340-DO-16"-A01BU-006
CL OF G14-VL-32-06 CL OF G14-VL-32-02
A340-DO-MH-003
N= 2383.700
(RCF-012-12)
N= 2383.700
E= 2033.250 E= 2049.000 A340-DO-MH-002 DRAWING LIMIT DRAWING LIMIT
DRAWING LIMIT
DRAWING LIMIT
A A340-DO-SM-013
A340-DO-SM-014
8"-DP-57-4301-M01-N
N= 2380.580
A340-DO-6"-A01BU-028
E= 2028.370
A340-DO-VP-001
6"-WF-71-0818-A01BU-N
TP31
(FDF-012-1)
DRAWING LIMIT
A340-DO-16"-A01BU-003
A
3"-DP-57-4383-M01-N N= 2379.004
TP19 TP35 A
E= 2022.493
A340-DOV-4"-A01BU-003
DRAWING LIMIT
3"-DP-57-4386-M01-N N= 2377.952
A 4"-WF-71-4815-A01BU-N E= 2030.203
N= 2375.650
E= 2059.300
A340-DO-16"-A01BU-007
DRAWING
N= 2374.000
LIMIT
E= 1958.250
DRAWING LIMIT
705-XM-71-10
INSTALL PE / PVC SHEET TO G14-PA-32-03A
N= 2374.600
E= 2032.444 N= 2374.850
14" EXISTING WF LINE
EXISTING
E= 2053.750
A340-DO-TD-001-W400 A340-DO-SM-012
MITIGATE INTERFERENCE N= 2373.335 THIS PAGE
DRAWING
E= 2024.944
LIMIT
MATCH
LINE-A
C
L OF
G14-VL-32-03
A340-DO-10"-A01BU-008
A380-DO-16"-A01BU-001
A340-DO-4"-A01BU-027
A380-DO-SM-002
3"-DP-57-4804-M01-N G14-PA-32-03B
2000.000 N= 2369.280
6" EXISTING WF LINE LEGEND
DRAWING LIMIT
E= 2024.944
A340-DO-CO-007
MAINTENANCE AREA TRANSFORMER RECTIFIER UNIT (TRU)
DRAWING LIMIT
DRAWING LIMIT
E= 2033.251
6"-DP-57-4301-M01-N
TUFF N= 2367.600
3"-DP-57-4387-M01-N E= 2037.810
NEGATIVE DISTRIBUTION BOX (NDB) - OR
TP 309
DRAWING LIMIT
N= 2364.675
E= 1998.000
6"-DP-57-4301-M01-N 4"-DC-57-4371-A01BUCD-N
N= 2365.595
E= 2040.692
(FV-012-9) NEGATIVE JUNCTION BOX (NJB) - OR
A340-WF-VP-002
N= 2362.250
E= 1971.800 A TP45 N= 2362.910
E= 2025.050
N= 2364.541
E= 2038.050 BOND BOX (BB) DRAWING LIMIT
3-
A380-DO-SM-003
TP38 TP23 NJB2-2 POSITIVE DISTRIBUTION BOX (PDB) DRAWING LIMIT
DRAWING LIMIT DRAWING LIMIT
G14-PA-32-01B G14-CB-32-01
AJB2-3 N= 2362.250
G14-PA-32-01A
A N= 2360.100
A ANODE JUNCTION BOX (AJB)
14" EXISTING WF LINE
A380-DO-16"-A01BU-002
E= 1965.000 E= 2047.250
10"-WF-71-0824-A01BU-N
A380-DO-DT-001-W400
N= 2359.025 N= 2360.400
E= 1957.475
E= 1957.475
2"-DP-57-4389-M01-N E= 2024.294
TEST BOX (TB) - TYPE 1 (PSP AND TCP) code
TP 310
A
N= 2359.079 E= 2037.419
N= 2357.050
A E= 2029.859
N= 2356.350
WITH ENCASING AC - Accepted with Comment, NA
Resubmit
(RCF-012-9)
E= 2030.870
N= 2356.350 - Not accepted, Resubmit
A
A340-DO-6"-A01BU-033
TP20 3"-DP-57-4395-M01-N N= 2353.000
E= 2029.400
N= 2353.650
E= 2036.285
STRUCTURE CONNECTION VENDOR from full compliance with contractual obligation
A380-DO-6"-A01BU-007
N= 2351.080 A380-DO-4"-A01BU-011 NEGATIVE WELD PAD/CLEAT CONNECTION
E= 1989.269
N= 2352.260
E= 1991.250
CURB WALL
TIE-IN MAINTENANCE 5 25MAR21 25MAR21 REVISED PER CLIENT COMMENTS N.SIPPEL A.BONETTI S.FILMORE
TP-335
A N= 2351.400 3"-DP-57-4392-M01-N
150 THK., 100 HT.
300 mm COMPACTED
AREA (RCF-012-14) SPLICE KIT
E= 1971.300 4"-DP-57-4391-M01-N 8"-DP-57-4301-M01-N TUFF
(RCF-012-16) A340-DO-SM-009
6"-WF-71-4806-A01BU-N
A340-DO-SM-010
2000.000 PERMANENT CSE REFERENCE ELECTRODE
N= 2346.080
E= 2024.750
N= 2345.655
E= 2031.100
N= 2346.080
E= 2033.263 N= 2346.080
E= 2053.750
4 10FEB21 23FEB21 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
C COUPON
mm COMPACTED
G14-KA-32-01
A340-DO-8"-A01BU-010 A
W400 ELECTRICAL BURIED EXISTING TRENCH
G14-KH-32-01 BD-EY-W600
(RCF-012-15) TP24 3 10FEB21 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
MAINTENANCE
741-XA-71-01
A380-DO-16"-A01BU-004
A340-DO-SM-011
6"-DP-57-4301-M01-N 741-XA-71-06 AND THERMOWELD CONNECTIONS)
2000.000
E= 2022.000
A
TUFF
AREA
(TEMPORARY CP)
300
N= 2340.500
N= 2340.500
E= 2031.100 A
A
BD-IY-W300 E= 2030.900
2000.000 FGL (PERMANENT CP)
N= 2338.316
E= 2021.350
N= 2337.000
0 15JUL20 ISSUED FOR APPROVAL L.HULL N.SIPPEL A.BONETTI
N= 2340.413 E= 2047.450
A340-DO-6"-A01BU-037
TP40 E= 2022.585 N= 2337.000
E= 2028.997
N= 2337.000
E= 2034.997
N= 2337.000
E= 2040.997 G14-MB-24-01A
A
A340-DO-8"-A01BU-011
BD-IY-W300
4"-DP-57-4400-M01-N
(RD-012-7) N= 2335.800
A 2x ZINC RIBBON ANODES
E= 2050.384
1- A340-DO-CO-004 G14-MB-24-02 (PERMANENT CP)
2000.000
N= 2335.800
E= 2022.000
N= 2334.450
E= 2046.200
(RD-012-10)
A340-DO-4"-A01BU-042
N= 2329.200
E= 2053.250
1-
INSTRUMENT BURIED TRENCH MAINTENANCE A340-DOV-4"-A01BU-007
CT-EPC/001/SH/EPM-G/EP/18
TUFF
N= 2323.499
(RCF-012-17)
BD-IY-W300
E= 2097.750
be done as per approved procedure and drawings. Anode tail cables shall be terminated at designated AJB. Sufficient
watering shall be carried out after anode laid in the trench and before backfilling. In any case anodes shall not be in
A380-DO-12"-A01BU-006
14" EXISTING WF LINE
2000.000FGL 2000.000FGL 3. Where there are branching pipes, the sock anode will run all around the branching pipe if the branch length is lower
than five meters, while the sock anode will be spliced to a branching sock anode if the pipe branch length is above five
metres.
4. Bonding cables shall be installed to maintain electrical continuity at locations such as nonwelded joints, mechanical
L OF EXISTING
(R-012-10) 8"-WF-71-0827-A01BU-N
A800-DO-MH-010 joints, flanges, couplings, concrete pits and locations where there is no electrical continuity within the piping system
EXISTING FIRE WATER
EY-DB-EXISTING EXISTING FIRE WATER TO BE
PIT to be cathodically protected. Bonding/Jumper among the pipes shall be provided outside the pits.
ROAD
WITH SPACER RING
PIT
1 2 200-PVC TO BE
DEMOLISHED 5. The piping shall be isolated with neoprene rubber from any reinforced concrete support / wall to minimize current
BD-IY-W400
C
TRENCH
1999.500 DEMOLISHED drains from rebars in reinforced concrete structures.
TOC TP 341
1999.100 BOC 6. Soil access shall be installed next to the test posts and junction boxes at paved areas.
(FV-011-01) N= 2301.150
7. The number of Permanent Magnesium Anodes at TP Type 3 locations shall be as per "DETAILED DESIGN CALCULATION
WF-VP-EXISTING 14"-WF-71-0847-A01BU-N
E= 1986.300
A800-DO-12"-A01BU-002
14"-WF-71-0858-A01BU-N TRENCH
6"-WF-71-0812-A01BU-N
14"-WF-71-0051-1A01BU-N
(EXISTING)
11. For the basic requirement/guidelines to be followed by construction personnel during installation, and for brief
EXISTING LIGHT guidelines/precautions, please refer to the Intallation Specification document (Ref. No. 23) and to the Installation
(TYP.)
POLE
TP 346 Drawings (Ref. No. 24).
EXISTING LIGHT 741-XM-71-05 W400 ELECTRICAL BURIED EXISTING 14" EXISTING WF LINE 12. For the Schematic Drawing, please refer to the relevant Document (Ref. No. 25).
(TYP.)
POLE TRENCH
13. All installation works associated with the Cathodic Protection system shall be conducted in accordance with this
drawing and the complete CP design package (see documents Ref No. 16 to 29 for full list). Any conflict between this
EXISTING ROAD
BOC TP 347 14. The final location of the TR Units, Junction Boxes and Test Posts shall be checked by the CP Engineer in consultation
(TYP) with the installation Sub-contractor and client. The TR Units, Junction Boxes and Test Posts shall, where practicable, be
installed in such a fashion that safe and convenient access to them is maintained.
BD-EYL-W400
Under no circumstances shall the TR Units, Junction Boxes and Test Posts be installed in a location where they could
BD-EYL-W400 be damaged and / or cause an obstruction or interference to the regular activities of the operator.
DRAWING LIMIT
DRAWING LIMIT
(RCF-006-1) BD-EYL-W400 15. Wherever there is a pit, Electrical continuity among the pipes like DO, DOV shall be provided at all the locations using
A210-DO-SM-021
14"-WF-71-0872-A01BU-N bonding Jumper cable (1c 25 mm2) and thermite welding.
LP1 W400 ELECTRICAL BURIED EXISTING TRENCH BD-IY-W300
16. Packaged Sacrificial anodes shall be installed 1.5 m away from the pipes and shall be installed at the bottom level of
BD-IY-W300
pipe.
BD-EYL-W400
TP 355
3"-DC-57-5825-A01BUCD-N
14"-WF-71-0872-A01BU-N
17. Sacrificial anodes shall be laid horizontally. Anodes shall be soaked in water 24 hours prior to installation.
BD-IY-W300
A210-DO-12"-A01BU-001
18. Test station shall be installed 1.5 m away from the pipe.
A210-DOV-4"-A01BU-002
(FDF-006-3) INSTALL PE / PVC SHEET TO 19. AJB/PDB/BB/NDB/NJB shall be installed 1.5 m away from the pipe. Cables inside the TP/JB shall be terminated with
A210-DC-VP-003
N= 2274.599
E= 1999.430
BB1-1 proper tagging for easy identifications.
EXISTING LIGHT POLE MITIGATE INTERFERENCE
BD-IY-W300
BD-EY-W600 20. Polarisation coupon and permanent reference cells shall be installed 100 mm away from the pipe and shall be 1/3rd of
N= 2269.550
pipe depth from pipe bottom level.
E= 1977.700 6"-DC-57-0811-A01BUCD-N
BD-IY-W300
N= 2268.400
PLEASE SEE SHEET 7 FOR ADDITIONAL NOTES
N= 2269.275
E= 1968.850 6"-DC-57-0811-A01BUCD-N C TP43 E= 2089.000
14"-WF-71-0874-A01BU-N
3"-DC-57-5819-A01BUCD-N
N= 2268.300
EXISTING FENCE TYPE 2 E= 2041.376 BD-EY-W800
A A210-DC-VP-004
3"-DC-57-5818-A01BUCD-N
NOTE-7
MAP VIEW
E= 1979.900
3"-DC-57-5817-A01BUCD-N
TP42 300X300 A N= 2266.000
4"-DC-57-0812-A01BUCD-N
EXTRA WIDTH
EXISTING FENCE TYPE 1
CL OF ROAD 4.0M. WIDE
E= 2052.040
3"-DC-57-0814-A01BUCD-N G01-UO-42-02 X400DEEP SUMP A
NOTE-7
TP01
EXTRA WIDTH
3"-DC-57-1001-A01BUCD-N PVC PIPE SLEEVE
EXTRA WIDTH
EXTRA WIDTH
BD-EYL-W400
CL OF OC1-VL-57-11
BD-EYL-W400
WITH ENCASING
BD-EY-W600 3"-DC-57-5823-A01BUCD-N
50 THK. GALVANIZED
DRAWING LIMIT
EXISTING LIGHT POLE (FDF-006-2)
14"-WF-71-0872-A01BU-N
GRATING COVER
3"-DC-57-1001-A01BUCD-N A210-DC-VP-002 TP 356
EXISTING WATER SUPPLY LINE (FDF-006-1)
3"-DC-57-5737-A01BUCD-N
N= 2261.300
3"-DC-57-5819-A01BUCD-N
(TO BE DISMANTLE AND RELOCATE) A210-DC-VP-001
E= 2086.518
DRAWING LIMIT
BD-EY-W1500
PVC PIPE SLEEVE
PIPE DIA + 100mm
WITH ENCASING
DRAWING
LIMIT
N= 2255600
E= 2061500
DRAWING LIMIT
N= 2253.296
E= 2068.071
TP44
N= 2254.304
E= 2062.326
LP1
3"-DC-57-5816-A01BUCD-N
AJB1-2
N= 2253.388
E= 2070.045
3"-DC-57-5832-A01BUCD-N
BD-IY-W300 N= 2254.186 N= 2253.476
E= 2072.197 E= 2079.560 A
DRAWING
N= 2252.956
LIMIT
MATCH
LINE-A
CL OF 430-VL-64-04 3"-DC-57-5816-A01BUCD-N
E= 2082.703
FUN-036-6"x4"
G09-VD-45-03
150 THK.x300H. CURB 2000.000 FGL N= 2252.020
(RD-006-1)
E= 2019.500
3"-DC-57-5812-A01BUCD-N
WALL (TYP)
EXISTING FENCE TYPE 1
A710-DO-CO-013
N= 2251.300 CL OF G09 CL OF G09 CL OF G09 CL OF G09 CL OF G09
THIS PAGE
DRAWING LIMIT
N= 2250.119
E= 2053.700
EXISTING WATER SUPPLY LINE
3"-DC-57-5836-A01BUCD-N
2000.000 FGL
DRAWING LIMIT
A710-DO-4"-A01BU-003
NJB1-3 N= 2251.100
LP1 (RCF-006-3) E= 2076.070
3"-DC-57-5820-A01BUCD-N
6" EXISTING WF
DRAWING LIMIT
NOTE-7
A710-DO-6"-A01BU-004
NOTE-7
CL OF 410
TP08 -MB-45-02A & B A210-DO-SM-017 N= 2251.800
BD-IY-W300
E= 2083.860
3"-DC-57-5834-A01BUCD-N
(TYP) DRAWING LIMIT
BD-EYL-W400 (TYP)
200W X 600H TR-EY-W500
BD-EYL-W200 DRAWING LIMIT DRAWING LIMIT
DROP AREA
C
LINE
(R-006-2)
N= 2243.620
A210-DO-MH-015
E= 2047.600
A210-DO-6"-A01BU-004 Acceptance status Eng. Dept. Date
A210-DO-6"-A01BU-003
430-UN-64-06 code
EXISTING NATURAL N= 2240.700
A710-DO-CB-001E= 2014.000
A710-DO-10"-A01BU-002 A710-DO-SM-028 N= 2243.620
N= 2240.050 N= 2240.050 N= 2237326 E= 2061.500
E= 2010.300 E= 2012.714 E= 2058425 N= 2239.550
E= 2060.200 (RD-006-5)
AC B.LENKA PROCS 14-08-2020
LIMIT
FOR CONTINUATION REFER SHEET 4
N= 2241.000 NEGATIVE DISTRIBUTION BOX (NDB) - OR be done as per approved procedure and drawings. Anode tail cables shall be terminated at designated AJB. Sufficient
A210-DO-6"-A01BU-003
NEGATIVE JUNCTION BOX (NJB) - OR watering shall be carried out after anode laid in the trench and before backfilling. In any case anodes shall not be in
touch/in electrical contact with the pipe.
DRAWING
BOND BOX (BB)
E= 2097.750
E= 2060.200 (RD-006-5)
N= 2240.375 N= 2238.595 A210-DO-CO-014
POSITIVE DISTRIBUTION BOX (PDB) 3. Where there are branching pipes, the sock anode will run all around the branching pipe if the branch length is lower
EXISTING ROAD
TP07 A710-DO-4"-A01BU-005 E= 2019.500 E= 2062.540
N= 2237856 than five meters, while the sock anode will be spliced to a branching sock anode if the pipe branch length is above five
430-UN-64-05A ANODE JUNCTION BOX (AJB)
E = 1789.500
A220-DOV-4"-A01BU-001
A N= 2236.275
E= 2091220
metres.
E= 2019.500
A710-DO-10"-A01BU-006
TEST BOX (TB) - TYPE 1 (PSP AND TCP) 4. Bonding cables shall be installed to maintain electrical continuity at locations such as nonwelded joints, mechanical
3"-DC-57-5803-A01BUCD-N
A710-DO-10"-A01BU-001
N= 2236.530 A710-DO-4"-A01BU-007 A220-DO-6"-A01BU-013 joints, flanges, couplings, concrete pits and locations where there is no electrical continuity within the piping system
3"-DC-57-5808-A01BUCD-N
E= 2010.300
TEST BOX (TB) - TYPE 2 (PSP AND TCP)
A220-DO-4"-A01BU-001
(RCF-006-2) to be cathodically protected. Bonding/Jumper among the pipes shall be provided outside the pits.
A710-DO-10"-A01BU-001
E= 2090.658
2000.000 FGL (RCF-006-4) A220-DO-2"-A01BU-002
A710-DO-SM-016 CRD-6"x4"
5. The piping shall be isolated with neoprene rubber from any reinforced concrete support / wall to minimize current
A220-DO-10"-A01BU-004
430-UN-64-05B A220-DO-SM-018N= 2236.275
TEST BOX (TB) - TYPE 3 (PCP) BOND CABLE
G09-PG-23-07
E= 2047.600
A710-DOV-4"-A01BU-002
A710-DOV-4"-A01BU-001 drains from rebars in reinforced concrete structures.
TEST BOX (TB) - TYPE 4 (INTERFERENCE MITIGATION)
FUN-053-6"x4"
A220-DO-4"-A01BU-012 ANODE SOCK 6. Soil access shall be installed next to the test posts and junction boxes at paved areas.
TEST BOX (TB) - TYPE 5 (PVC CASING) 7. The number of Permanent Magnesium Anodes at TP Type 3 locations shall be as per "DETAILED DESIGN CALCULATION
2000.000 FGL N= 2231.256
E= 2075.980 REPORT " document no. 4058-VW-CX-00OO000013 (Ref. No. 19).
(RD-006-3) STRUCTURE CONNECTION
N= 2228.110
E= 2019.778
A720-DO-CO-011
8. CP cable shall not be laid in instrument / ELECT Trench. A separate cable tray shall be used for CP at least 300mm away
BD-EY-W1000
SPLICE KIT from ELECT cable in order to avoid the interference. All cables shall be laid without coils or kinks, buried in sand at a
A220-DO-10"-A01BU-005
N= 2226.459
FUN-038-6"x4"E= 2013.000 depth of at least 0.75 m, provided with cable protection tiles and warning tape installed 250 mm above the cable. The
A720-DO-4"-A01BU-006 PERMANENT CSE REFERENCE ELECTRODE
A720-DO-6"-A01BU-007
CL OF ACCESS WAY 6.0M. WIDE trench shall be 300 mm wide.
TR-EY-W600
N= 2224.451
E= 2067.725
N= 2224.736
C COUPON 9. Distance from piping to junction boxes and test posts shall be approx 1.5 m.
E= 2067.725
A220-DO-10"-A01BU-008
CL OF 420-VL-63-04
10. For the Cable Schedule, please refer to the relevant Document (Ref. No. 27).
A220-DOV-4"-A01BU-002
EXISTING WELL
11. For the basic requirement/guidelines to be followed by construction personnel during installation, and for brief
BD-IY-W300
A220-DO-SM-019
TR-EY-W600
guidelines/precautions, please refer to the Intallation Specification document (Ref. No. 23) and to the Installation
NOTE-2
CHROMATOGRAPH
A220-DO-DT-001-W400
CO2-FIRE
(RCF-006-5)
EXTINGUISHING 7.7kg MAGNESIUM ANODE
BOTTLE
A Drawings (Ref. No. 24).
GAS
BD-EY-W600 (TEMPORARY CP)
12. For the Schematic Drawing, please refer to the relevant Document (Ref. No. 25).
50 THK. A220-DO-6"-A01BU-015 14.5kg MAGNESIUM ANODE 13. All installation works associated with the Cathodic Protection system shall be conducted in accordance with this
GALVANIZED
HYDRAULIC
A220-DO-4"-A01BU-014 A
GRATING COVER
STARTING SKID
N= 2217.250
(PERMANENT CP) drawing and the complete CP design package (see documents Ref No. 16 to 29 for full list). Any conflict between this
FUN-039-6"x4" E= 2076.700
drawing and other CP drawings and / or other project specifications and drawings shall be brought to the attention of
EXTRA WIDTH
EXTRA WIDTH
N= 2217.000
A720-DO-4"-A01BU-008
the CP Engineer in writing for clarification as soon as it is discovered.
DRAWING LIMIT
E= 2091.220
CL OF ROAD 4.0M. WIDE
N= 2216.252
E= 2010.648
N= 2213.297
420-UO-63-05A A 2x ZINC RIBBON ANODES 14. The final location of the TR Units, Junction Boxes and Test Posts shall be checked by the CP Engineer in consultation
200Wx600H CUTOUT
(RCF-006-6)
A720-DO-SM-020 BD-EY-W600 installed in such a fashion that safe and convenient access to them is maintained.
RAMP
FUN-040-6"x4" A720-DO-10"-A01BU-003 (R-006-8)
N= 2212.024
A720-DO-CB-001
N= 2212.575
N= 2212.200
E= 2019.778
A220-DO-MH-009 NEGATIVE WELD PAD/CLEAT Under no circumstances shall the TR Units, Junction Boxes and Test Posts be installed in a location where they could
E= 2010.648
E= 2015.000
CONNECTION be damaged and / or cause an obstruction or interference to the regular activities of the operator.
420-UO-63-05B
TP02 15. Wherever there is a pit, Electrical continuity among the pipes like DO, DOV shall be provided at all the locations using
BD-IY-W800
(TYP)
N= 2207.720 N= 2207.720
A720-DOV-4"-A01BU-002
E= 2009.949 E= 2016.000 BD-EY-W400 bonding Jumper cable (1c 25 mm2) and thermite welding.
A720-DO-10"-A01BU-004 150 THK. CURB WALL (TYP)
A720-DOV-4"-A01BU-001 N= 2205.600
E= 2009.524 N= 2205.600 16. Packaged Sacrificial anodes shall be installed 1.5 m away from the pipes and shall be installed at the bottom level of
A A720-DO-10"-A01BU-001
E= 2047.600
pipe.
BD-IY-W300
17. Sacrificial anodes shall be laid horizontally. Anodes shall be soaked in water 24 hours prior to installation.
A220-DO-10"-A01BU-009
A720-DO-8"-A01BU-002 A720-DO-10"-A01BU-001
BD-EY-W1500
742-XM-71-01 18. Test station shall be installed 1.5 m away from the pipe.
A220-DO-MH-007
6"-WF-71-0834-A01BU-N
BD-IY-W800
TP32 A720-DO-MH-005 N= 2205.600 INSTALL PE / PVC SHEET TO 6" EXISTING WF 19. AJB/PDB/BB/NDB/NJB shall be installed 1.5 m away from the pipe. Cables inside the TP/JB shall be terminated with
E= 2019.778
BB1-2 proper tagging for easy identifications.
INSTALL PE / PVC SHEET TO MITIGATE INTERFERENCE LINE
EXISTING ROAD
DIESEL STORAGE
20. Polarisation coupon and permanent reference cells shall be installed 100 mm away from the pipe and shall be 1/3rd of
TANK MITIGATE INTERFERENCE BD-IY-W300
pipe depth from pipe bottom level.
A220-DO-10"-A01BU-010
A720-DO-6"-A01BU-017
N= 2200.137
E= 2014.220
A720-DO-4"-A01BU-016
AJB1-3 A220-DO-MH-016
A220-DO-10"-A01BU-006 A220-DO-10"-A01BU-006 (R-006-7) A220-DO-10"-A01BU-007 N= 2199.300
E= 2091.220
PLEASE SEE SHEET 7 FOR ADDITIONAL NOTES
A220-DO-MH-014
A220-DO-10"-A01BU-011
N= 2199.300 N= 2199.300
E= 2047.600 E= 2071.511
N= 2195.284
A220-DO-10"-A01BU-003
A720-DO-4"-A01BU-015
E= 2019.031
NJB1-1
A220-DO-SM-024
TP03 N= 2194.419 DRAWING LIMIT
MAP VIEW
NJB1-2 LP1
E = 2154.756
DRAWING LIMIT
A220-DOV-4"-A01BU-003
A720-DO-4"-A01BU-014
N= 2190.807
E= 2011.776
A720-DO-10"-A01BU-005 C A 2"-FD-62-0804-A01BU-N (EXISTING)
2"-FD-62-0804-A01BU-N 2"-FD-62-0804-A01BU-N
DRAWING LIMIT
A720-DO-CB-002 N= 2191.700
E= 2047.600
A720-DO-4"-A01BU-013 (R-007-2)
A720-DO-4"-A01BU-012 C N= 2188.500
420-UO-63-06A E= 2117.500
N= 2189.125
DRAWING LIMIT
E= 2011.756
TP06
DRAWING
N= 2185.895
LIMIT
E= 2011.756
2000.000 FGL
DRAWING LIMIT
CL OF EXISTING ROAD 4.0M. WIDE
2"-FD-62-0808-A01BU-N
A720-DO-4"-A01BU-011 C OF ROAD 4.0M. WIDE
L
A720-DO-4"-A01BU-010
EXTRA WIDTH
430-UO-63-06B
DRAWING
N= 2184.215
LIMIT
MATCH
LINE-A
E= 2011.756
2000.000 FGL
TP33 INSTALL PE / PVC SHEET TO
DRAWING LIMIT
N= 2183.000
MITIGATE INTERFERENCE
E= 2009.199
DRAWING LIMIT
PDB1 TRU1 N= 2176.300
E= 2052.600
N= 2177.075
E= 2076.600
DRAWING LIMIT
NDB1
A720-DO-CO-012
A630-DO-10"-A01BU-009 A630-DO-10"-A01BU-007
A630-DO-6"-A01BU-005
DRAWING LIMIT
(RD-006-4)
E= 2119.300
EXTRA WIDTH
A630-DO-MH-021 DRAWING LIMIT
(R-006-5)
A630-DO-6"-A01BU-006
A630-DO-MH-022
EXISTING LIGHT POLE
BD-EY-W600
WATER DISTILLED ROOM
N= 2175.098
4MO-MA-50-02A A630-DOV-4"-A01BU-001
E= 2055.625 A630-DO-MH-005
(R-006-11)
14"-WF-71-0872-A01BU-N 4MO-MA-50-02B Acceptance status Eng. Dept. Date
code
FOR SUBSTATION BUILDING REFER DETAIL DRAWING NO.
6PO-EG-84-02
A630-DO-10"-A01BU-008
OBC2019-07-HMD-682ARC-LAY-0001 & 0010 BD-IY-W1000
2"-FD-62-0806-A01BU-N
SWITCHGEAR ROOM
INSTRUMENT ROOM BATTERY ROOM NOTE 8 Comment status code:
CONCRETE HOLLOW
BLOCK (EXISTING) A - Accepted CR - Commented. Resubmit for Acceptance
ECS ROOM (R-007-9)
(EXISTING)
EXTRA WIDTH
BD-IY-W400 N= 2164.540
(R-007-14)
AC - Accepted with Comment, NA
Resubmit
- Not accepted, Resubmit
E= 2046.600
DO-TIE-IN-003
EXISTING
TIE-IN TP-317 702-XM-71-01
N= 2162.409
E= 2130.115 IMPORTANT: CONTRACTOR acceptance of this Document does not relieve the
TRANSFERFOR
(R-006-9) N= 2162.409
VENDOR from full compliance with contractual obligation
E= 2119.300
TRANSFERFOR
CLEAN AGENT 6" EXISTING WF LINE A630-DO-MH-008 A630-DO-10"-A01BU-001 10" EXISTING DO LINE 12" EXISTING DO LINE
BAY
BD-IY-W400
BD-EY-W2000
N= 2152.600
2"-WS-62-0807-A01BU-N
E= 2046.600 EXTRA WIDTH 1 23SEP20 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
A630-OWS-MH-001 EXISTING
TIE-IN TP-349 EXISTING A630-OWS-MH-002
INSTALL PE / PVC SHEET TO N= 2152.600
E= 2035.583 LIGHT POLE LIGHT POLE
0 15JUL20 ISSUED FOR APPROVAL L.HULL N.SIPPEL A.BONETTI
(TYP.) (TYP.) 12" EXISTING DO LINE
MITIGATE INTERFERENCE A
NOTE 7 CL OF EXISTING ROAD 6.0M. WIDE
6"-WF-71-0833-A01BU-N
14" EXISTING WF LINE
DO: OPEN DRAIN (NON-HAZ)
14" EXISTING WF LINE
EXTRA WIDTH
NEW FENCE
DRAWING LIMIT HM: HEATING MEDIUM
DRAWING LIMIT
DRAWING LIMIT N= 2131.000
E = 2423.970
E = 2465.000
3. Where there are branching pipes, the sock anode will run all around the branching pipe if the branch length is lower
than five meters, while the sock anode will be spliced to a branching sock anode if the pipe branch length is above five
metres.
4. Bonding cables shall be installed to maintain electrical continuity at locations such as nonwelded joints, mechanical
W400 ELECTRICAL BURIED EXISTING joints, flanges, couplings, concrete pits and locations where there is no electrical continuity within the piping system
2000.000FGL
TRENCH to be cathodically protected. Bonding/Jumper among the pipes shall be provided outside the pits.
5. The piping shall be isolated with neoprene rubber from any reinforced concrete support / wall to minimize current
drains from rebars in reinforced concrete structures.
PIPE LEGEND 6. Soil access shall be installed next to the test posts and junction boxes at paved areas.
7. The number of Permanent Magnesium Anodes at TP Type 3 locations shall be as per "DETAILED DESIGN CALCULATION
WS: WATER SOURCE REPORT " document no. 4058-VW-CX-00OO000013 (Ref. No. 19).
8. CP cable shall not be laid in instrument / ELECT Trench. A separate cable tray shall be used for CP at least 300mm away
FD: FUEL DIESEL from ELECT cable in order to avoid the interference. All cables shall be laid without coils or kinks, buried in sand at a
depth of at least 0.75 m, provided with cable protection tiles and warning tape installed 250 mm above the cable. The
WF: FIRE WATER trench shall be 300 mm wide.
9. Distance from piping to junction boxes and test posts shall be approx 1.5 m.
OWS: OILY WATER SYSTEM
W400 ELECTRICAL BURIED EXISTING 10. For the Cable Schedule, please refer to the relevant Document (Ref. No. 27).
TRENCH
DOV: VENT PIPE 11. For the basic requirement/guidelines to be followed by construction personnel during installation, and for brief
guidelines/precautions, please refer to the Intallation Specification document (Ref. No. 23) and to the Installation
DO: OPEN DRAIN (NON-HAZ) Drawings (Ref. No. 24).
TRENCH
Under no circumstances shall the TR Units, Junction Boxes and Test Posts be installed in a location where they could
be damaged and / or cause an obstruction or interference to the regular activities of the operator.
15. Wherever there is a pit, Electrical continuity among the pipes like DO, DOV shall be provided at all the locations using
24" EXISTING DO
W400 ELECTRICAL BURIED EXISTING 17. Sacrificial anodes shall be laid horizontally. Anodes shall be soaked in water 24 hours prior to installation.
(EXISTING)
(R-016-2)
A100-DO-SM-022
TRENCH 18. Test station shall be installed 1.5 m away from the pipe.
TP27 19. AJB/PDB/BB/NDB/NJB shall be installed 1.5 m away from the pipe. Cables inside the TP/JB shall be terminated with
proper tagging for easy identifications.
SHOLUDER
A100-DOV-4"-A01BU-001
2000.000FGL
20. Polarisation coupon and permanent reference cells shall be installed 100 mm away from the pipe and shall be 1/3rd of
ROAD
TRENCH
35C-PA-35-04C
1789.500
1832.150
E= 2040.000
E= 2044.000
E=
E=
N=
2510.250
N= 2507.000
E= 2063.775
DRAWING LIMIT DRAWING LIMIT N= 2497.801
A100-DO-4"-A01BU-004
DRAWING LIMIT
35C-PA-35-04D
N=
2459.000
DRAWING LIMIT
FUN-049-6"x4"
E= 1936.700
N= 2446.300
N= 2445.000
24" EXISTING DO
BD-EY-W600 A100-DO-4"-A01BU-005
DRAWING LIMIT
E= 1937.010
DRAWING
N= 2383.100
LIMIT
N= 2378.700
DRAWING LIMIT
150 THK., 100 HT.
LINE
CURB WALL
THIS PAGE
DRAWING
LIMIT
MATCH
LINE-A
BD-IY-W300
BD-EY-W600
A100-DO-4"-A01BU-006 LEGEND
DRAWING LIMIT
TRANSFORMER RECTIFIER UNIT (TRU)
DRAWING LIMIT
W400 ELECTRICAL BURIED EXISTING NEGATIVE DISTRIBUTION BOX (NDB) - OR
DRAWING LIMIT
TRENCH
NEGATIVE JUNCTION BOX (NJB) - OR N= 2168.300
35C-SHL-01
POSITIVE DISTRIBUTION BOX (PDB) DRAWING LIMIT
DRAWING LIMIT DRAWING LIMIT
35C-PA-35-04A/B
35C-PA-35-04A/B
SPLICE KIT 5 25MAR21 25MAR21 REVISED PER CLIENT COMMENTS N.SIPPEL A.BONETTI S.FILMORE
PERMANENT CSE REFERENCE ELECTRODE
E = 2513.445
EMULSEUR MOUSSE 4 10FEB21 23FEB21 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
LINE
C COUPON
(FV-016-02)
BD-IY-W300 BD-IY-W300 WF-VP-EXISTING 3 10FEB21 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
AND THERMOWELD CONNECTIONS)
7.7kg MAGNESIUM ANODE 2 15DEC20 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
A
(TEMPORARY CP)
1 23SEP20 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
14.5kg MAGNESIUM ANODE
A
TP28 (PERMANENT CP)
706-RA-71-20
450-PD-42-01A/B
4" EXISTING WF LINE 0 15JUL20 ISSUED FOR APPROVAL L.HULL N.SIPPEL A.BONETTI
A
24" EXISTING DO
L OF EXISTING
SHOLUDER
TIE-IN TP-343
LINE
24" EXISTING DO
LINE
(EXISTING) (FV-016-01)
CT-EPC/001/SH/EPM-G/EP/18
(R-016-6) WF-VP-EXISTING
BOND CABLE
N = 2316.000
DRAWING LIMIT ANODE SOCK
MAP VIEW
DRAWING LIMIT DRAWING LIMIT
DRAWING LIMIT
DRAWING LIMIT
A
DRAWING
LIMIT
DRAWING LIMIT
DRAWING
LIMIT
MATCH
LINE-A
DRAWING LIMIT
ADDITIONAL NOTES
DRAWING LIMIT
21. Temporary Magnesium anodes at test station (Type 1 and 2) shall be disconnected prior to energisation of permanent cathodic
DRAWING LIMIT
protection.
22. All pipe to cable connections at TP/BB/Jumper locations shall be carried out using thermite welding connection. Pipe to cable DRAWING LIMIT
connections at all negative drain points shall be carried out using weld pad and cleat connections. All cable connections location coating DRAWING LIMIT DRAWING LIMIT
repair shall be carried out and holiday testing shall be carried out. DRAWING LIMIT
23. Carrier pipe inside the PVC casing shall be protected by Zinc ribbon anode. 2 no. Zn ribbon shall be tied to pipe at 5 & 7 O'clock position.
Acceptance status Eng. Dept. Date
Cables from Zn ribbon shall be terminated inside the Test post. Refer installation drawing no. 4058-VW-DW-00OO000018. Pipe shall be code
inserted inside the PVC sleeves along with Zn ribbon fitted to the pipe, care shall be taken while inserting the carrier inside the casing
that there shall not be any damage to Zn ribbon and cable. All 4 no. cables from Zn ribbon shall be terminated inside the test posts.
Cables shall be taken out from the casing and shall be routed to the test post and shall be terminated inside the test post. Both sides of Comment status code:
casing end shall be sealed using non metallic HDPE or other suitable sheets in order to prevent any water ingress inside the casing. A - Accepted CR - Commented. Resubmit for Acceptance
24. Cable routes shall be clearly marked using cable markers. These shall be installed every 50 m and at every change of direction of the AC - Accepted with Comment, NA
Resubmit
- Not accepted, Resubmit
cable route.
25. Linear anode routes shall be clearly marked using markers. These shall be installed every 50 m and at every change of direction of the IMPORTANT: CONTRACTOR acceptance of this Document does not relieve the
linear anode route. VENDOR from full compliance with contractual obligation
26. Prior to carry out thermite welding on existing piping,pipe thickness measurement shall be taken and necessary permission shall be
taken from the OWNER. 5 25MAR21 25MAR21 REVISED PER CLIENT COMMENTS N.SIPPEL A.BONETTI S.FILMORE