You are on page 1of 7

1. Please refer to the Coordinates Table for the Tag numbers and Coordinates of each component of CP Equipment.

2. The ICCP continuous anode will be buried in the pipe trench at a distance of 0.5 m from the pipe at the 3 or 9 o'clock
position (i.e. halfway between bottom and top of pipe depth). Anode splicing shall be done using splice kits and shall
be done as per approved procedure and drawings. Anode tail cables shall be terminated at designated AJB. Sufficient
watering shall be carried out after anode laid in the trench and before backfilling. In any case anodes shall not be in
touch/in electrical contact with the pipe.
3. Where there are branching pipes, the sock anode will run all around the branching pipe if the branch length is lower
than five meters, while the sock anode will be spliced to a branching sock anode if the pipe branch length is above five
metres.
N = 2510.250 DRAWING LIMIT
4. Bonding cables shall be installed to maintain electrical continuity at locations such as nonwelded joints, mechanical

E = 1789.500
BD-EY-W400 BD-EY-W400 joints, flanges, couplings, concrete pits and locations where there is no electrical continuity within the piping system
W400 ELECTRICAL BURIED EXISTING W400 ELECTRICAL BURIED EXISTING
TRENCH
to be cathodically protected. Bonding/Jumper among the pipes shall be provided outside the pits.
TRENCH
5. The piping shall be isolated with neoprene rubber from any reinforced concrete support / wall to minimize current
2003.350FGL
N= 2505.350
E= 1827.763 BD-EY-W600 drains from rebars in reinforced concrete structures.
EXISTING FENCE 4- 6. Soil access shall be installed next to the test posts and junction boxes at paved areas.
BD-EY-W400 7. The number of Permanent Magnesium Anodes at TP Type 3 locations shall be as per "DETAILED DESIGN CALCULATION
REPORT " document no. 4058-VW-CX-00OO000013 (Ref. No. 19).
8. CP cable shall not be laid in instrument / ELECT Trench. A separate cable tray shall be used for CP at least 300mm away
from ELECT cable in order to avoid the interference. All cables shall be laid without coils or kinks, buried in sand at a

CJ

CJ

CJ

CJ

CJ

CJ
2003.350FGL IJ
depth of at least 0.75 m, provided with cable protection tiles and warning tape installed 250 mm above the cable. The
N= 2501.850
820-FX-43-01 E= 1886.850

trench shall be 300 mm wide.


VALLEY LINE
A430-DOV-4"-A01BU-001 A430-DO-CB-001 9. Distance from piping to junction boxes and test posts shall be approx 1.5 m.
(TYP.) 820-VD-43-05
N= 2496.332
E= 1897.658
CJ 2003.350FGL 10. For the Cable Schedule, please refer to the relevant Document (Ref. No. 27).
FUN-072-6"x4"
N= 2495.286
E= 1887.695 11. For the basic requirement/guidelines to be followed by construction personnel during installation, and for brief

BD-EY-W600
A430-DO-10"-A01BU-002 IJ guidelines/precautions, please refer to the Intallation Specification document (Ref. No. 23) and to the Installation
746-XA-71-01
HOLD-2
A FUN-077-6"x4"
N= 2494.032
2003.350FGL Drawings (Ref. No. 24).
820-PG-43-05A E= 1897.658
CJ 12. For the Schematic Drawing, please refer to the relevant Document (Ref. No. 25).
TP13

FOR CONTINUATION REFER SHEET 2


N= 2492.861
820-PG-43-05B
TP12
E= 1887.695

HOLD-1 (FV-011-02)
13. All installation works associated with the Cathodic Protection system shall be conducted in accordance with this
A430-DO-4"-A01BU-001
WF-VP-004 drawing and the complete CP design package (see documents Ref No. 16 to 29 for full list). Any conflict between this
14" EXISTING WF LINE EXISTING
A430-DO-10"-A01BU-003 drawing and other CP drawings and / or other project specifications and drawings shall be brought to the attention of
EXISTING NATURAL A IJ the CP Engineer in writing for clarification as soon as it is discovered.

CJ

CJ

CJ

CJ

CJ

CJ
SOIL 14" EXISTING WF LINE
(R-011-3) 14. The final location of the TR Units, Junction Boxes and Test Posts shall be checked by the CP Engineer in consultation
(EXISTING) N= 2486.318
E= 1836.900

24" EXISTING DO
6"-WF-71-4821-A01BU-N BD-IY-W300 24" EXISTING DO with the installation Sub-contractor and client. The TR Units, Junction Boxes and Test Posts shall, where practicable, be
LINE
DRAWING LIMIT

LINE
(R-011-1)
installed in such a fashion that safe and convenient access to them is maintained.
(RCF-011-4)
TIE-IN N= 2486.318
E= 1885.298 A430-DO-SM-030
(EXISTING)
N= 2486.661
E= 1929.295
Under no circumstances shall the TR Units, Junction Boxes and Test Posts be installed in a location where they could
TP-328
be damaged and / or cause an obstruction or interference to the regular activities of the operator.
15. Wherever there is a pit, Electrical continuity among the pipes like DO, DOV shall be provided at all the locations using

(R-011-2)
bonding Jumper cable (1c 25 mm2) and thermite welding.

EXTRA WIDTH
INSTALL PE / PVC SHEET TO 16. Packaged Sacrificial anodes shall be installed 1.5 m away from the pipes and shall be installed at the bottom level of

EXTRA WIDTH
MITIGATE INTERFERENCE

W400 ELECTRICAL BURIED EXISTING


14" EXISTING WF LINE
BD-EY-W600 pipe.
17. Sacrificial anodes shall be laid horizontally. Anodes shall be soaked in water 24 hours prior to installation.
2003.350FGL
18. Test station shall be installed 1.5 m away from the pipe.
19. AJB/PDB/BB/NDB/NJB shall be installed 1.5 m away from the pipe. Cables inside the TP/JB shall be terminated with
proper tagging for easy identifications.
20. Polarisation coupon and permanent reference cells shall be installed 100 mm away from the pipe and shall be 1/3rd of
pipe depth from pipe bottom level.

C OF 6.0M. WIDE
TRENCH
PLEASE SEE SHEET 7 FOR ADDITIONAL NOTES

24" EXISTING DO

ROAD
W400 INSTRUMENTAL BURIED EXISTING
MAP VIEW

L
TRENCH
LINE

LP1
LP1

1789.500

1832.150

E= 2040.000

E= 2044.000
E=

E=
N=
2510.250
N= 2507.000

E= 2063.775
DRAWING LIMIT DRAWING LIMIT N= 2497.801
E = 1789.500

W400 ELECTRICAL BURIED EXISTING


TRENCH

DRAWING LIMIT
EXISTING LIGHT EXISTING LIGHT EXISTING LIGHT N=
2459.000

E= 1936.700
POLE POLE POLE
N= 2446.300
N= 2445.000

14" EXISTING WF LINE


EXISTING EXTRA

A340-DO-6"-A01BU-044
WIDTH

DRAWING LIMIT
E= 1937.010

DRAWING
N= 2383.100

LIMIT
N= 2378.700

N = 2459.000 DRAWING LIMIT

DRAWING LIMIT
THIS PAGE

DRAWING
LIMIT

MATCH
LINE-A
LEGEND
TRANSFORMER RECTIFIER UNIT (TRU)

DRAWING LIMIT
DRAWING LIMIT
NEGATIVE DISTRIBUTION BOX (NDB) - OR
NEGATIVE JUNCTION BOX (NJB) - OR

DRAWING LIMIT
BOND BOX (BB)
N= 2168.300

N= 2149.446
DRAWING LIMIT

POSITIVE DISTRIBUTION BOX (PDB) DRAWING LIMIT DRAWING LIMIT

ANODE JUNCTION BOX (AJB) DRAWING LIMIT

Acceptance status Eng. Dept. Date


TEST BOX (TB) - TYPE 1 (PSP AND TCP) code

TEST BOX (TB) - TYPE 2 (PSP AND TCP) A B.LENKA PROCS 30-03-3021
TEST BOX (TB) - TYPE 3 (PCP) Comment status code:
A - Accepted CR - Commented. Resubmit for Acceptance
TEST BOX (TB) - TYPE 4 (INTERFERENCE MITIGATION)
AC - Accepted with Comment, NA
Resubmit
- Not accepted, Resubmit
TEST BOX (TB) - TYPE 5 (PVC CASING)
IMPORTANT: CONTRACTOR acceptance of this Document does not relieve the
STRUCTURE CONNECTION VENDOR from full compliance with contractual obligation
NEGATIVE WELD PAD/CLEAT CONNECTION
SPLICE KIT 5 25MAR21 25MAR21 REVISED PER CLIENT COMMENTS N.SIPPEL A.BONETTI S.FILMORE
PERMANENT CSE REFERENCE ELECTRODE
4 10FEB21 23FEB21 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
C COUPON
3 10FEB21 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
AND THERMOWELD CONNECTIONS)
7.7kg MAGNESIUM ANODE 2 15DEC20 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
A
(TEMPORARY CP)
1 23SEP20 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
14.5kg MAGNESIUM ANODE
A
(PERMANENT CP) 0 15JUL20 ISSUED FOR APPROVAL L.HULL N.SIPPEL A.BONETTI

PIPE LEGEND
A 2x ZINC RIBBON ANODES
WS: WATER SOURCE (PERMANENT CP)

FD: FUEL DIESEL

WF: FIRE WATER

OWS: OILY WATER SYSTEM

DOV: VENT PIPE Realisation du 4eme Train GPL a ZCINA, Hassi Messaoud
DO: OPEN DRAIN (NON-HAZ) CT-EPC/001/SH/EPM-G/EP/18
DC: CLOSED DRAIN

DP: PROCESS DRAIN BOND CABLE

HM: HEATING MEDIUM ANODE SOCK

GENERAL LAYOUT DRAWINGS


29 PRE-COMMISSIONING AND COMMISSIONING CHECK SHEETS 4058-VW-RC-00OO000026
14 LAYOUT OF HAZARDOUS AREA CLASSIFICATION PROCESS TRAIN 4 4058-SN-DH-00OO000003-IS0 28 PRE-COMMISSIONING AND COMMISSIONING PROCEDURE 4058-VW-PC-00OO000025
13 LAYOUT OF HAZARDOUS AREA CLASSIFICATION OVERALL LPG TRAIN 4 4058-SN-DH-00OO000001-IS0 27 CABLE SCHEDULE 4058-VW-LK-00OO000023
12 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A800 4058-AQ-DA-A800000009 26 FOUNDATION AND BASE FRAME DETAIL DRAWINGS 4058-VW-DW-00OO000022
4058-VW-DG-00OO000020 1/7
11 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A630, A710 & A720 4058-AQ-DA-A630000008 25 SCHEMATIC WIRING DRAWINGS 4058-VW-DN-00OO000021
10 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A430 4058-AQ-DA-A430000011 24 INSTALLATION DRAWINGS 4058-VW-DW-00OO000018 EPC001-00-DD-EU-CPC-00020-M 1:250 5
9 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A340 & A350 4058-AQ-DA-A340000003 23 INSTALLATION SPECIFICATION 4058-VW-SG-00OO000017
8 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A330, A360 & A380 4058-AQ-DA-A330000005 22 BILL OF MATERIAL LIST 4058-VW-LM-00OO000016
7 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A310, A320 & A370 4058-AQ-DA-A310000004 21 MATERIALS SPECIFICATION 4058-VW-SG-00OO000015 Grantham, Lincs, UK, NG31 7XS Tel. +44(0)1476 590666
6 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A210 & A220 4058-AQ-DA-A220000002 20 POWER SUPPLY REQUIREMENTS 4058-VW-LN-00OO000014 E-mail cpc@cathodic.co.uk Web www.cathodic.co.uk
5 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A100, A101 & A102 4058-AQ-DA-A100000001 19 DETAILED DESIGN CALCULATION REPORT 4058-VW-CX-00OO000013
4 UNDERGROUND GENERAL DRAWINGS - KEY PLAN 4058-AQ-DX-A100000001 18 DESIGN PHILOSOPHY & SPECIFICATION 4058-VW-SG-00OO000012
3 COATING SPECIFICATION FOR BURIED SURFACES 4058-VW-SG-0000000005 17 PRE-DESIGN SITE SURVEY REPORT 4058-VW-RT-00OO000011
2 MATERIAL SPECIFICATION AND DATASHEET 4058-VW-SG-00OO000007-IS0 16 PRE-DESIGN SITE SURVEY SPECIFICATION 4058-VW-SG-00OO000010 VENDOR DOCUMENT NO.
1 CATHODIC PROTECTION SPECIFICATION 4058-VW-SG-00OO000006-ISA 15 LAYOUT OF HAZARDOUS AREA CLASSIFICATION COMPRESSOR 4058-SN-DH-00OO000004-IS0
42119-CLO-029
REF NO. DOCUMENT TITLE DOCUMENT NUMBER REF NO. DOCUMENT TITLE DOCUMENT NUMBER
DRAWING LIMIT N = 2497.801
1. Please refer to the Coordinates Table for the Tag numbers and Coordinates of each component of CP Equipment.
2. The ICCP continuous anode will be buried in the pipe trench at a distance of 0.5 m from the pipe at the 3 or 9 o'clock

E = 1789.500

E = 2063.775
(FV-0120-04) position (i.e. halfway between bottom and top of pipe depth). Anode splicing shall be done using splice kits and shall

24" EXISTING DO
TIE-IN TIE-IN TIE-IN
WF-VP-EXISTING
EXISTING TP-325 EXISTING ROAD TP-324 TP-323
(FV-0120-03) be done as per approved procedure and drawings. Anode tail cables shall be terminated at designated AJB. Sufficient
POLE (TYP)
LIGHT WF-VP-EXISTING watering shall be carried out after anode laid in the trench and before backfilling. In any case anodes shall not be in
TIE-IN INSTALL PE / PVC SHEET touch/in electrical contact with the pipe.

LINE
TP-323 TO MITIGATE 3. Where there are branching pipes, the sock anode will run all around the branching pipe if the branch length is lower
W400 ELECTRICAL BURIED EXISTING TRENCH
(FV-011-02) INTERFERENCE than five meters, while the sock anode will be spliced to a branching sock anode if the pipe branch length is above five
WF-VP-004 (R-012-13) W400 INSTRUMENTAL BURIED EXISTING TRENCH metres.
EXISTING A310-DO-MH-020
8"-WF-71-0815-A01BU-N 6"-WF-71-0832-A01BU-N 14" EXISTING WF LINE 4. Bonding cables shall be installed to maintain electrical continuity at locations such as nonwelded joints, mechanical
14" EXISTING WF LINE
joints, flanges, couplings, concrete pits and locations where there is no electrical continuity within the piping system
DO-TIE-IN-001 BD-IY-W300 A A to be cathodically protected. Bonding/Jumper among the pipes shall be provided outside the pits.
BD-IY-W300
24" EXISTING DO 6"-WF-71-0831-A01BU-N TIE-IN TP-301 5. The piping shall be isolated with neoprene rubber from any reinforced concrete support / wall to minimize current
LINE
N= 2486.619
TP14 TP15 BB2-1 drains from rebars in reinforced concrete structures.
BD-IY-W300 E= 1965.000 741-XW-71-10
741-XM-71-03 14" EXISTING WF LINE 6. Soil access shall be installed next to the test posts and junction boxes at paved areas.
N= 2486.619
E= 1958.624
A310-DO-16"-A01BU-007
(FV-012-4)
A310-WF-VP-001
(FV-012-5)
A310-WF-VP-002
TP16 7. The number of Permanent Magnesium Anodes at TP Type 3 locations shall be as per "DETAILED DESIGN CALCULATION
4"-WF-71-4809-A01BU-N
741-XM-71-02
R-012-1
4"-WF-71-4810-A01BU-N
(FV-012-7) REPORT " document no. 4058-VW-CX-00OO000013 (Ref. No. 19).
(EXISTING) A A320-WF-VP-001
8. CP cable shall not be laid in instrument / ELECT Trench. A separate cable tray shall be used for CP at least 300mm away
from ELECT cable in order to avoid the interference. All cables shall be laid without coils or kinks, buried in sand at a
BD-EY-W600
depth of at least 0.75 m, provided with cable protection tiles and warning tape installed 250 mm above the cable. The

A310-DO-16"-A01BU-001

A320-DO-16"-A01BU-002
N= 2482.275 N= 2482.275 TIE-IN
E= 2000.400 E= 2002.300
TP-302 trench shall be 300 mm wide.

BD-EY-W600
150THK.CURB 484-KF-41-01
9. Distance from piping to junction boxes and test posts shall be approx 1.5 m.

W400 ELECTRICAL BURIED EXISTING TRENCH


FUEL GAS SKID

FUEL GAS SKID


WALL (TYP)
G14-KF-24-01 10. For the Cable Schedule, please refer to the relevant Document (Ref. No. 27).
11. For the basic requirement/guidelines to be followed by construction personnel during installation, and for brief
FOR CONTINUATION REFER SHEET 1

W400 INSTRUMENTAL BURIED EXISTING TRENCH


(TYP)
guidelines/precautions, please refer to the Intallation Specification document (Ref. No. 23) and to the Installation

2-
Drawings (Ref. No. 24).
12. For the Schematic Drawing, please refer to the relevant Document (Ref. No. 25).

A320-DO-DT-006-W400
14" EXISTING WF LINE
13. All installation works associated with the Cathodic Protection system shall be conducted in accordance with this
N= 2469.500
E= 1989.000 drawing and the complete CP design package (see documents Ref No. 16 to 29 for full list). Any conflict between this
C
L OF G14-UF-24-01 C
L OF 484-UF-41-01 drawing and other CP drawings and / or other project specifications and drawings shall be brought to the attention of

DRAWING LIMIT
N= 2469.500
(RCF-012-3) E= 2025.000
TP29 the CP Engineer in writing for clarification as soon as it is discovered.
A310-DO-SM-007 6 THK. CHQUERED
N= 2464.900 PLATE
A320-DO-SM-015 14. The final location of the TR Units, Junction Boxes and Test Posts shall be checked by the CP Engineer in consultation
E= 1965.000
6 THK. CHQUERED A320-DO-MH-019 N= 2465.350
E= 2059.300
with the installation Sub-contractor and client. The TR Units, Junction Boxes and Test Posts shall, where practicable, be
PLATE A320-DO-TD-001-W400 installed in such a fashion that safe and convenient access to them is maintained.
W400 ELECTRICAL BURIED EXISTING TRENCH

A320-DOV-4"-A01BU-001

EXISTING ROAD
EXTRA WIDTH
A310-DO-16"-A01BU-002
C Under no circumstances shall the TR Units, Junction Boxes and Test Posts be installed in a location where they could
TR-EY-W600 A320-DO-16"-A01BU-001 N= 2464.550
E= 2049.000
be damaged and / or cause an obstruction or interference to the regular activities of the operator.
14" EXISTING WF LINE N= 2464.550
E= 2042.501
A320-DO-16"-A01BU-004 15. Wherever there is a pit, Electrical continuity among the pipes like DO, DOV shall be provided at all the locations using
A310-DOV-4"-A01BU-001
200W X 250H
INSTALL PE / PVC bonding Jumper cable (1c 25 mm2) and thermite welding.
BD-EY-W600

BD-EY-W800
SHEET TO MITIGATE
EXISTING ROAD

CUTOUT 200W X 250H 16. Packaged Sacrificial anodes shall be installed 1.5 m away from the pipes and shall be installed at the bottom level of
EXISTING EXTRA

150 CURB WALL CUTOUT INTERFERENCE pipe.


(TYP) 705-XM-71-11
N = 2459.000 (TYP) EXISTING 17. Sacrificial anodes shall be laid horizontally. Anodes shall be soaked in water 24 hours prior to installation.
2000.000HPP
18. Test station shall be installed 1.5 m away from the pipe.
WIDTH

6" EXISTING WF LINE


19. AJB/PDB/BB/NDB/NJB shall be installed 1.5 m away from the pipe. Cables inside the TP/JB shall be terminated with
proper tagging for easy identifications.

MAINTENANCE AREA
300mm COMPACTED
N= 2456.120
E= 1959.575

TP21 20. Polarisation coupon and permanent reference cells shall be installed 100 mm away from the pipe and shall be 1/3rd of

884-FX-43-01
14" EXISTING WF LINE

EXISTING EXTRA

TUFF 2000.000
TIE-IN pipe depth from pipe bottom level.
TP-303
TP17 6"-WF-71-4801-A01BU-N
A
PLEASE SEE SHEET 7 FOR ADDITIONAL NOTES
WIDTH

A320-DO-16"-A01BU-003
A A 6" EXISTING WF LINE
741-XA-71-04

MAP VIEW
A310-DO-16"-A01BU-003

6"-WF-71-4804-A01BU-N 741-XA-71-03 INSTALL PE / PVC


INSTALL PE / PVC SHEET TO SHEET TO MITIGATE
MITIGATE INTERFERENCE INTERFERENCE DRAWING LIMIT DRAWING LIMIT

BD-IY-W300
A310-DO-SM-026

DRAWING LIMIT
N= 2441.504
A370-DO-4"-A01BU-001 E= 2004.946
AJB2-2
NJB2-3

DRAWING LIMIT
N= 2439.000 N= 2439.857
E= 1990.000 E= 2003.300

DRAWING
LIMIT
N= 2439.000
E= 2004.800 BD-IY-W300
A310-DO-MH-018
C A

DRAWING LIMIT
N= 2439.000 A310-DO-12"-A01BU-005 A310-DO-6"-A01BU-006 THIS PAGE
E= 1965.000

3"-HM-57-4403-A03-N
A310-DO-16"-A01BU-004

TP11

DRAWING
LIMIT

MATCH
LINE-A
A310-DOV-4"-A01BU-002

N= 2435.500 FOR CONTINUATION REFER SHEET 3


LEGEND

DRAWING LIMIT
TRANSFORMER RECTIFIER UNIT (TRU)

DRAWING LIMIT
NEGATIVE DISTRIBUTION BOX (NDB) - OR

DRAWING LIMIT
NEGATIVE JUNCTION BOX (NJB) - OR
BOND BOX (BB) DRAWING LIMIT

POSITIVE DISTRIBUTION BOX (PDB)


DRAWING LIMIT DRAWING LIMIT

DRAWING LIMIT

ANODE JUNCTION BOX (AJB)


Acceptance status Eng. Dept. Date
TEST BOX (TB) - TYPE 1 (PSP AND TCP) code

TEST BOX (TB) - TYPE 2 (PSP AND TCP)


TEST BOX (TB) - TYPE 3 (PCP) Comment status code:
A - Accepted CR - Commented. Resubmit for Acceptance
TEST BOX (TB) - TYPE 4 (INTERFERENCE MITIGATION)
AC - Accepted with Comment, NA
Resubmit
- Not accepted, Resubmit
TEST BOX (TB) - TYPE 5 (PVC CASING)
IMPORTANT: CONTRACTOR acceptance of this Document does not relieve the
STRUCTURE CONNECTION VENDOR from full compliance with contractual obligation
NEGATIVE WELD PAD/CLEAT CONNECTION
SPLICE KIT 5 25MAR21 25MAR21 REVISED PER CLIENT COMMENTS N.SIPPEL A.BONETTI S.FILMORE
PERMANENT CSE REFERENCE ELECTRODE
4 10FEB21 23FEB21 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
C COUPON
3 10FEB21 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
AND THERMOWELD CONNECTIONS)
7.7kg MAGNESIUM ANODE 2 15DEC20 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
A
(TEMPORARY CP)
1 23SEP20 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
14.5kg MAGNESIUM ANODE
A
(PERMANENT CP) 0 15JUL20 ISSUED FOR APPROVAL L.HULL N.SIPPEL A.BONETTI

PIPE LEGEND
A 2x ZINC RIBBON ANODES
WS: WATER SOURCE (PERMANENT CP)

FD: FUEL DIESEL

WF: FIRE WATER

OWS: OILY WATER SYSTEM

DOV: VENT PIPE Realisation du 4eme Train GPL a ZCINA, Hassi Messaoud
DO: OPEN DRAIN (NON-HAZ) CT-EPC/001/SH/EPM-G/EP/18
DC: CLOSED DRAIN

DP: PROCESS DRAIN BOND CABLE

HM: HEATING MEDIUM ANODE SOCK

GENERAL LAYOUT DRAWINGS


29 PRE-COMMISSIONING AND COMMISSIONING CHECK SHEETS 4058-VW-RC-00OO000026
14 LAYOUT OF HAZARDOUS AREA CLASSIFICATION PROCESS TRAIN 4 4058-SN-DH-00OO000003-IS0 28 PRE-COMMISSIONING AND COMMISSIONING PROCEDURE 4058-VW-PC-00OO000025
13 LAYOUT OF HAZARDOUS AREA CLASSIFICATION OVERALL LPG TRAIN 4 4058-SN-DH-00OO000001-IS0 27 CABLE SCHEDULE 4058-VW-LK-00OO000023
12 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A800 4058-AQ-DA-A800000009 26 FOUNDATION AND BASE FRAME DETAIL DRAWINGS 4058-VW-DW-00OO000022
4058-VW-DG-00OO000020 2/7
11 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A630, A710 & A720 4058-AQ-DA-A630000008 25 SCHEMATIC WIRING DRAWINGS 4058-VW-DN-00OO000021
10 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A430 4058-AQ-DA-A430000011 24 INSTALLATION DRAWINGS 4058-VW-DW-00OO000018 EPC001-00-DD-EU-CPC-00020-M 1:250 5
9 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A340 & A350 4058-AQ-DA-A340000003 23 INSTALLATION SPECIFICATION 4058-VW-SG-00OO000017
8 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A330, A360 & A380 4058-AQ-DA-A330000005 22 BILL OF MATERIAL LIST 4058-VW-LM-00OO000016
7 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A310, A320 & A370 4058-AQ-DA-A310000004 21 MATERIALS SPECIFICATION 4058-VW-SG-00OO000015 Grantham, Lincs, UK, NG31 7XS Tel. +44(0)1476 590666
6 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A210 & A220 4058-AQ-DA-A220000002 20 POWER SUPPLY REQUIREMENTS 4058-VW-LN-00OO000014 E-mail cpc@cathodic.co.uk Web www.cathodic.co.uk
5 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A100, A101 & A102 4058-AQ-DA-A100000001 19 DETAILED DESIGN CALCULATION REPORT 4058-VW-CX-00OO000013
4 UNDERGROUND GENERAL DRAWINGS - KEY PLAN 4058-AQ-DX-A100000001 18 DESIGN PHILOSOPHY & SPECIFICATION 4058-VW-SG-00OO000012
3 COATING SPECIFICATION FOR BURIED SURFACES 4058-VW-SG-0000000005 17 PRE-DESIGN SITE SURVEY REPORT 4058-VW-RT-00OO000011
2 MATERIAL SPECIFICATION AND DATASHEET 4058-VW-SG-00OO000007-IS0 16 PRE-DESIGN SITE SURVEY SPECIFICATION 4058-VW-SG-00OO000010 VENDOR DOCUMENT NO.
1 CATHODIC PROTECTION SPECIFICATION 4058-VW-SG-00OO000006-ISA 15 LAYOUT OF HAZARDOUS AREA CLASSIFICATION COMPRESSOR 4058-SN-DH-00OO000004-IS0
42119-CLO-029
REF NO. DOCUMENT TITLE DOCUMENT NUMBER REF NO. DOCUMENT TITLE DOCUMENT NUMBER
A310-DO-16"-A01BU-00
FOR CONTINUATION REFER SHEET 2 1. Please refer to the Coordinates Table for the Tag numbers and Coordinates of each component of CP Equipment.

A320-DO-16"-A01BU-003
N = 2439.000 2. The ICCP continuous anode will be buried in the pipe trench at a distance of 0.5 m from the pipe at the 3 or 9 o'clock

E = 1789.500
A310-DOV-4"-A01BU-002

2000.000
PIPE LEGEND

E = 2063.775
BD-IY-W300
position (i.e. halfway between bottom and top of pipe depth). Anode splicing shall be done using splice kits and shall

mm COMPACTED

3"-HM-41-4403-A03-N
WS: WATER SOURCE be done as per approved procedure and drawings. Anode tail cables shall be terminated at designated AJB. Sufficient

MAINTENANCE
watering shall be carried out after anode laid in the trench and before backfilling. In any case anodes shall not be in

A340-DO-6"-A01BU-044
N= 2432.145
OC1-VL-57-09
AJB2-1
E= 1959.650

EXISTING LIGHT POLE


FD: FUEL DIESEL touch/in electrical contact with the pipe.
N= 2428.290 TP30 3. Where there are branching pipes, the sock anode will run all around the branching pipe if the branch length is lower

AREA
W400 INSTRUMENTAL BURIED EXISTING TRENCH
N= 2428.140

TUFF
N= 2428.100 E= 2034.940
E= 1982.510 E= 2027.050
WF: FIRE WATER

300
A360-DO-MH-001
N= 2428.500
E= 1965.000 than five meters, while the sock anode will be spliced to a branching sock anode if the pipe branch length is above five
8"-DP-57-4349-M01-N N= 2428.141
metres.
N= 2428.100
A350-DO-6"-A01BU-006 A350-DOV-4"-A01BU-001 OWS: OILY WATER SYSTEM 4. Bonding cables shall be installed to maintain electrical continuity at locations such as nonwelded joints, mechanical
(TYP.)

E= 2034.940
OC1-VL-57-12 E= 1985.510 N= 2426.300
E= 2059.300

8"-DC-57-4343-A01BUCD-N 8"-DC-57-4343-A01BUCD-N C
8"-DP-57-4301-M01-N N= 2426.000
E= 2034.940 N= 2425.500
E= 2036.625
DOV: VENT PIPE joints, flanges, couplings, concrete pits and locations where there is no electrical continuity within the piping system

A350-DO-4"-A01BU-005
(RCF-012-18)
N= 2425.383
E= 1985.510
(RD-012-3)
A350-DO-SM-027
to be cathodically protected. Bonding/Jumper among the pipes shall be provided outside the pits.
A350-DO-CO-009
DO: OPEN DRAIN (NON-HAZ) 5. The piping shall be isolated with neoprene rubber from any reinforced concrete support / wall to minimize current
INSTALL PE /
6" EXISTING WF LINE

drains from rebars in reinforced concrete structures.

6" EXISTING WF LINE


N= 2420.900

3"-HM-41-4301-A03-N
E= 2035.800

N= 2418.501
PVC SHEET TO DC: CLOSED DRAIN 6. Soil access shall be installed next to the test posts and junction boxes at paved areas.
3"-DC-57-4368-A01BUCD-N E= 2035.800 2000.000 FGL
N= 2418.353
E= 2035.800
MITIGATE 7. The number of Permanent Magnesium Anodes at TP Type 3 locations shall be as per "DETAILED DESIGN CALCULATION
INTERFERENCE DP: PROCESS DRAIN REPORT " document no. 4058-VW-CX-00OO000013 (Ref. No. 19).

A360-DO-16"-A01BU-001

MAINTENANCE AREA
8. CP cable shall not be laid in instrument / ELECT Trench. A separate cable tray shall be used for CP at least 300mm away

300mm COMPACTED
FUN-070-6"x4" HM: HEATING MEDIUM from ELECT cable in order to avoid the interference. All cables shall be laid without coils or kinks, buried in sand at a

14" EXISTING WF LINE


E= 2018.366
E= 2018.693
484-VL-41-02
N= 2415.177
E= 2014.477
N= 2415.179
E= 2019.375
FUN-006-6"x4" depth of at least 0.75 m, provided with cable protection tiles and warning tape installed 250 mm above the cable. The
N= 2416.000
trench shall be 300 mm wide.

8"-DC-57-4300-A01BUCD-N
E= 2039.358
C
L OF 884-VD-43-01 N= 2413.500
W400 ELECTRICAL BURIED EXISTING TRENCH

9. Distance from piping to junction boxes and test posts shall be approx 1.5 m.

TUFF
E= 2026.970
150 THK. CURB WALL

2"-HM-41-4405-A03-N
N= 2412.084 N= 2413.540

A370-DO-6"-A01BU-003
(TYP) E= 2016.600
10. For the Cable Schedule, please refer to the relevant Document (Ref. No. 27).
(TYP) 11. For the basic requirement/guidelines to be followed by construction personnel during installation, and for brief

8"-DP-57-4301-M01-N
2"-HM-41-4397-A03-N

E= 2018.791
N= 2409.569
E= 2013.453
guidelines/precautions, please refer to the Intallation Specification document (Ref. No. 23) and to the Installation
A330-DOV-4"-A01BU-003
N= 2408.505
N= 2408.505
E= 1995.700
MAINTENANCE
Drawings (Ref. No. 24).
N= 2409.650
50 THK. N= 2407.633
E= 1990.595
E= 1994.982
300
AREAmm COMPACTED TP 305 12. For the Schematic Drawing, please refer to the relevant Document (Ref. No. 25).
E= 1968.375
COVER
GRATING TUFF
13. All installation works associated with the Cathodic Protection system shall be conducted in accordance with this
EXISTING ROAD

EXISTING EXTRA

2000.000
A330-DO-4"-A01BU-007
N= 2405.000
2"-HM-41-4408-A03-N drawing and the complete CP design package (see documents Ref No. 16 to 29 for full list). Any conflict between this
A350-DO-6"-A01BU-003
E= 1997.000
drawing and other CP drawings and / or other project specifications and drawings shall be brought to the attention of

6" EXISTING WF LINE


6"-WF-71-4802-A01BU-N
A330-DO-SM-006
A330-DO-6"-A01BU-005 BB2-2 N= 2405.639
CRD-6"x4" E= 2013.455
the CP Engineer in writing for clarification as soon as it is discovered.

A330-DO-DT-002-W400
N= 2405.000
A340-DO-6"-A01BU-012
WIDTH

E= 1979.150

N= 2402.800
E= 1994.982
N= 2402.800
E= 1999.200 741-XA-71-05 14. The final location of the TR Units, Junction Boxes and Test Posts shall be checked by the CP Engineer in consultation
with the installation Sub-contractor and client. The TR Units, Junction Boxes and Test Posts shall, where practicable, be

3"-DP-57-4424-M01-N
A330-DO-4"-A01BU-009 2"-HM-41-4396-A03-N N= 2400.700

TP18 N= 2402.436
E= 2013.900
E= 2027.700
A installed in such a fashion that safe and convenient access to them is maintained.

A350-DO-16"-A01BU-001
HOLD-1
N= 2399.640
E= 2012.000 A340-DO-CO-008 TP22 Under no circumstances shall the TR Units, Junction Boxes and Test Posts be installed in a location where they could
A 6"-WF-71-4805-A01BU-N 741-XA-71-02
N= 2398.755
E= 2033.603 be damaged and / or cause an obstruction or interference to the regular activities of the operator.
A330-DO-6"-A01BU-001 3"-DC-57-4370-A01BUCD-N
(FV-012-8)
A340-WF-VP-001
15. Wherever there is a pit, Electrical continuity among the pipes like DO, DOV shall be provided at all the locations using
A330-DO-16"-A01BU-003 (RD-012-012) 2"-HM-41-4400-A03-N CURB WALL bonding Jumper cable (1c 25 mm2) and thermite welding.
A340-DO-CO-019 N= 2396.150
N= 2396.739
E= 2025.131
150 THK., 100 HT. 16. Packaged Sacrificial anodes shall be installed 1.5 m away from the pipes and shall be installed at the bottom level of

EXISTING LIGHT
C
L OF G14-CE-32-01
E= 2024.574
pipe.
484-PA-41-01A TP 308
NDB2 A330-DO-SM-005 17. Sacrificial anodes shall be laid horizontally. Anodes shall be soaked in water 24 hours prior to installation.
N= 2391.300
E= 1979.150 N= 2390.650
E= 1984.150
N= 2394.033
E= 2021.856
N= 2392.325
18. Test station shall be installed 1.5 m away from the pipe.
N= 2391.800
E= 1965.000 3"-DP-57-4429-M01-N N= 2390.739
E= 2030.725
19. AJB/PDB/BB/NDB/NJB shall be installed 1.5 m away from the pipe. Cables inside the TP/JB shall be terminated with
TR-2
N= 2390.600

PDB2
E= 2025.131

proper tagging for easy identifications.


E= 1992.094
A330-DO-16"-A01BU-002 2"-DP-57-4382-M01-N
N= 2390.150
G14-PA-32-02B E= 2024.574
484-PA-41-01B
484-VL-41-01
N= 2391.033
E= 2036.765 20. Polarisation coupon and permanent reference cells shall be installed 100 mm away from the pipe and shall be 1/3rd of
N= 2389.000
A330-DOV-4"-A01BU-001 A330-DOV-4"-A01BU-002 E= 1992.642
2000.000 FGL pipe depth from pipe bottom level.
N= 2389.000 A330-DO-6"-A01BU-011 3"-DP-57-4301-M01-N 3"-DP-57-4385-M01-N N= 2387.100
N= 2389.050 E= 2043.600
E= 1985.800
E= 1965.800

G14-PA-32-02A TP34 PLEASE SEE SHEET 7 FOR ADDITIONAL NOTES

A330-DO-4"-A01BU-010
N= 2388.026
E= 2021.864
A N= 2386.900
E= 2043.600

4"-DP-57-4301-M01-N
3"-DP-57-4803-M01-N A340-DO-16"-A01BU-005

MAP VIEW
N= 2387.500 N= 2383.700 N= 2383.700
E= 1992.094 E= 2027.870 E= 2053.750

A340-DO-16"-A01BU-004
A330-DO-16"-A01BU-004

N= 2381.996

TP09 E= 2022.493

A340-DO-16"-A01BU-006
CL OF G14-VL-32-06 CL OF G14-VL-32-02
A340-DO-MH-003
N= 2383.700
(RCF-012-12)
N= 2383.700
E= 2033.250 E= 2049.000 A340-DO-MH-002 DRAWING LIMIT DRAWING LIMIT
DRAWING LIMIT

DRAWING LIMIT
A A340-DO-SM-013
A340-DO-SM-014

8"-DP-57-4301-M01-N
N= 2380.580

A340-DO-6"-A01BU-028
E= 2028.370

A340-DO-VP-001
6"-WF-71-0818-A01BU-N
TP31

(FDF-012-1)

DRAWING LIMIT
A340-DO-16"-A01BU-003
A
3"-DP-57-4383-M01-N N= 2379.004

TP19 TP35 A
E= 2022.493
A340-DOV-4"-A01BU-003

DRAWING LIMIT
3"-DP-57-4386-M01-N N= 2377.952

A 4"-WF-71-4815-A01BU-N E= 2030.203
N= 2375.650
E= 2059.300
A340-DO-16"-A01BU-007

DRAWING
N= 2374.000

LIMIT
E= 1958.250

DRAWING LIMIT
705-XM-71-10
INSTALL PE / PVC SHEET TO G14-PA-32-03A
N= 2374.600
E= 2032.444 N= 2374.850
14" EXISTING WF LINE

EXISTING
E= 2053.750
A340-DO-TD-001-W400 A340-DO-SM-012
MITIGATE INTERFERENCE N= 2373.335 THIS PAGE

DRAWING
E= 2024.944

LIMIT

MATCH
LINE-A
C
L OF
G14-VL-32-03

A340-DO-10"-A01BU-008
A380-DO-16"-A01BU-001

A340-DO-4"-A01BU-027
A380-DO-SM-002

3"-DP-57-4804-M01-N G14-PA-32-03B
2000.000 N= 2369.280
6" EXISTING WF LINE LEGEND

DRAWING LIMIT
E= 2024.944
A340-DO-CO-007
MAINTENANCE AREA TRANSFORMER RECTIFIER UNIT (TRU)
DRAWING LIMIT

300mm COMPACTED 3"-DP-57-4387-M01-N N= 2368.376

DRAWING LIMIT
E= 2033.251
6"-DP-57-4301-M01-N
TUFF N= 2367.600
3"-DP-57-4387-M01-N E= 2037.810
NEGATIVE DISTRIBUTION BOX (NDB) - OR

TP 309

DRAWING LIMIT
N= 2364.675
E= 1998.000

6"-DP-57-4301-M01-N 4"-DC-57-4371-A01BUCD-N
N= 2365.595
E= 2040.692
(FV-012-9) NEGATIVE JUNCTION BOX (NJB) - OR
A340-WF-VP-002
N= 2362.250
E= 1971.800 A TP45 N= 2362.910
E= 2025.050
N= 2364.541
E= 2038.050 BOND BOX (BB) DRAWING LIMIT

3-
A380-DO-SM-003
TP38 TP23 NJB2-2 POSITIVE DISTRIBUTION BOX (PDB) DRAWING LIMIT
DRAWING LIMIT DRAWING LIMIT

G14-PA-32-01B G14-CB-32-01
AJB2-3 N= 2362.250
G14-PA-32-01A
A N= 2360.100
A ANODE JUNCTION BOX (AJB)
14" EXISTING WF LINE

A380-DO-16"-A01BU-002

E= 1965.000 E= 2047.250

10"-WF-71-0824-A01BU-N
A380-DO-DT-001-W400

Acceptance status Eng. Dept. Date


N= 2359.200
A
TP36
A380-DO-16"-A01BU-003

N= 2359.025 N= 2360.400
E= 1957.475
E= 1957.475
2"-DP-57-4389-M01-N E= 2024.294
TEST BOX (TB) - TYPE 1 (PSP AND TCP) code

6" EXISTING WF LINE


N= 2359.079
E= 1989.025 G14-PA-32-04A 8"-WF-71-4818-A01BU-N
A380-DOV-4"-A01BU-003 A380-DOV-4"-A01BU-002 N= 2358.734

TP 310
A

N= 2359.079 E= 2037.419
N= 2357.050

TEST BOX (TB) - TYPE 2 (PSP AND TCP)


8"-DC-57-4300-A01BUCD-N

E= 1994.345 E= 2032.865 N= 2357.050


A380-DOV-4"-A01BU-001 N= 2357.050
E= 2033.262
8"-DP-57-4301-M01-N

A E= 2029.859

A380-DO-6"-A01BU-008 TEST BOX (TB) - TYPE 3 (PCP) Comment status code:


PVC PIPE SLEEVE
N= 2358.850
E= 1957.475
PIPE DIA + 100mm TP39 A380-DO-4"-A01BU-009 N= 2356.300
E= 2024.294
G14-PA-32-04B TEST BOX (TB) - TYPE 4 (INTERFERENCE MITIGATION)
A - Accepted CR - Commented. Resubmit for Acceptance
2"-DP-57-4301-M01-N

N= 2356.350
WITH ENCASING AC - Accepted with Comment, NA
Resubmit
(RCF-012-9)
E= 2030.870
N= 2356.350 - Not accepted, Resubmit
A

A380-DO-SM-001 TP37 E= 2031.763


TEST BOX (TB) - TYPE 5 (PVC CASING)
A
IMPORTANT: CONTRACTOR acceptance of this Document does not relieve the

A340-DO-6"-A01BU-033
TP20 3"-DP-57-4395-M01-N N= 2353.000
E= 2029.400
N= 2353.650
E= 2036.285
STRUCTURE CONNECTION VENDOR from full compliance with contractual obligation
A380-DO-6"-A01BU-007
N= 2351.080 A380-DO-4"-A01BU-011 NEGATIVE WELD PAD/CLEAT CONNECTION
E= 1989.269
N= 2352.260
E= 1991.250
CURB WALL
TIE-IN MAINTENANCE 5 25MAR21 25MAR21 REVISED PER CLIENT COMMENTS N.SIPPEL A.BONETTI S.FILMORE
TP-335
A N= 2351.400 3"-DP-57-4392-M01-N
150 THK., 100 HT.
300 mm COMPACTED
AREA (RCF-012-14) SPLICE KIT
E= 1971.300 4"-DP-57-4391-M01-N 8"-DP-57-4301-M01-N TUFF
(RCF-012-16) A340-DO-SM-009
6"-WF-71-4806-A01BU-N

A340-DO-SM-010
2000.000 PERMANENT CSE REFERENCE ELECTRODE
N= 2346.080
E= 2024.750
N= 2345.655
E= 2031.100
N= 2346.080
E= 2033.263 N= 2346.080
E= 2053.750
4 10FEB21 23FEB21 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
C COUPON
mm COMPACTED

G14-KA-32-01
A340-DO-8"-A01BU-010 A
W400 ELECTRICAL BURIED EXISTING TRENCH

G14-KH-32-01 BD-EY-W600
(RCF-012-15) TP24 3 10FEB21 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
MAINTENANCE

741-XA-71-01
A380-DO-16"-A01BU-004

A340-DO-SM-011
6"-DP-57-4301-M01-N 741-XA-71-06 AND THERMOWELD CONNECTIONS)
2000.000

A340-DO-6"-A01BU-009 2 15DEC20 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI


DROP
A TP41
N= 2342.351
7.7kg MAGNESIUM ANODE
AREA

E= 2022.000
A
TUFF

AREA
(TEMPORARY CP)
300

4"-DP-57-4391-M01-N A340-DOV-4"-A01BU-006 6"-WF-71-4803-A01BU-N


G14-VD-24-01 N= 2339.850
1 23SEP20 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
3"-DP-57-4398-M01-N E= 2051.450
14.5kg MAGNESIUM ANODE
3"-DC-57-4376-A01BUCD-N

N= 2340.500
N= 2340.500
E= 2031.100 A
A

BD-IY-W300 E= 2030.900
2000.000 FGL (PERMANENT CP)
N= 2338.316
E= 2021.350
N= 2337.000
0 15JUL20 ISSUED FOR APPROVAL L.HULL N.SIPPEL A.BONETTI
N= 2340.413 E= 2047.450
A340-DO-6"-A01BU-037
TP40 E= 2022.585 N= 2337.000
E= 2028.997
N= 2337.000
E= 2034.997
N= 2337.000
E= 2040.997 G14-MB-24-01A
A

A340-DO-8"-A01BU-011
BD-IY-W300
4"-DP-57-4400-M01-N
(RD-012-7) N= 2335.800
A 2x ZINC RIBBON ANODES
E= 2050.384
1- A340-DO-CO-004 G14-MB-24-02 (PERMANENT CP)
2000.000

N= 2335.800
E= 2022.000

N= 2334.450
E= 2046.200
(RD-012-10)

6" EXISTING WF LINE


N= 2333.900
A340-DO-CO-017 E= 2050.382
FUN-021-6"x4"
C
L OF
BD-IY-W300

G14-GA-32-02A N= 2330.950 G14-VK-24-01B G14-VK-24-01C G14-MB-24-01B


E= 2023.000 G14-VK-24-01A
MAINTENANCE AREA
300mm COMPACTED

A340-DO-4"-A01BU-042
N= 2329.200
E= 2053.250

Realisation du 4eme Train GPL a ZCINA, Hassi Messaoud


N= 2327.590 N= 2329.200
E= 2046.850
C
L OF
E= 2016.554
2000.000
N= 2327.600
W400 NEW ROUTING OF G14-GA-32-02B E= 2023.450

1-
INSTRUMENT BURIED TRENCH MAINTENANCE A340-DOV-4"-A01BU-007
CT-EPC/001/SH/EPM-G/EP/18
TUFF

(WITHOUT EXTRA 300


AREAmm COMPACTED
LENGTH) C TUFF
N= 2323.500 A340-DO-6"-A01BU-041 N= 2323.500
E= 1971.300 E= 2053.675
A340-DO-6"-A01BU-043
A NJB2-1 (RD-012-9)
N = 2318.280 TP10 AJB2-4 A340-DO-CO-003 BOND CABLE
A380-DO-12"-A01BU-006

N= 2323.499
(RCF-012-17)
BD-IY-W300

E= 2021.000 2000.000 FGL A340-DO-SM-008


FOR CONTINUATION REFER SHEET 4 ANODE SOCK

GENERAL LAYOUT DRAWINGS


29 PRE-COMMISSIONING AND COMMISSIONING CHECK SHEETS 4058-VW-RC-00OO000026
14 LAYOUT OF HAZARDOUS AREA CLASSIFICATION PROCESS TRAIN 4 4058-SN-DH-00OO000003-IS0 28 PRE-COMMISSIONING AND COMMISSIONING PROCEDURE 4058-VW-PC-00OO000025
13 LAYOUT OF HAZARDOUS AREA CLASSIFICATION OVERALL LPG TRAIN 4 4058-SN-DH-00OO000001-IS0 27 CABLE SCHEDULE 4058-VW-LK-00OO000023
12 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A800 4058-AQ-DA-A800000009 26 FOUNDATION AND BASE FRAME DETAIL DRAWINGS 4058-VW-DW-00OO000022
4058-VW-DG-00OO000020 3/7
11 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A630, A710 & A720 4058-AQ-DA-A630000008 25 SCHEMATIC WIRING DRAWINGS 4058-VW-DN-00OO000021
10 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A430 4058-AQ-DA-A430000011 24 INSTALLATION DRAWINGS 4058-VW-DW-00OO000018 EPC001-00-DD-EU-CPC-00020-M 1:250 5
9 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A340 & A350 4058-AQ-DA-A340000003 23 INSTALLATION SPECIFICATION 4058-VW-SG-00OO000017
8 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A330, A360 & A380 4058-AQ-DA-A330000005 22 BILL OF MATERIAL LIST 4058-VW-LM-00OO000016
7 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A310, A320 & A370 4058-AQ-DA-A310000004 21 MATERIALS SPECIFICATION 4058-VW-SG-00OO000015 Grantham, Lincs, UK, NG31 7XS Tel. +44(0)1476 590666
6 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A210 & A220 4058-AQ-DA-A220000002 20 POWER SUPPLY REQUIREMENTS 4058-VW-LN-00OO000014 E-mail cpc@cathodic.co.uk Web www.cathodic.co.uk
5 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A100, A101 & A102 4058-AQ-DA-A100000001 19 DETAILED DESIGN CALCULATION REPORT 4058-VW-CX-00OO000013
4 UNDERGROUND GENERAL DRAWINGS - KEY PLAN 4058-AQ-DX-A100000001 18 DESIGN PHILOSOPHY & SPECIFICATION 4058-VW-SG-00OO000012
3 COATING SPECIFICATION FOR BURIED SURFACES 4058-VW-SG-0000000005 17 PRE-DESIGN SITE SURVEY REPORT 4058-VW-RT-00OO000011
2 MATERIAL SPECIFICATION AND DATASHEET 4058-VW-SG-00OO000007-IS0 16 PRE-DESIGN SITE SURVEY SPECIFICATION 4058-VW-SG-00OO000010 VENDOR DOCUMENT NO.
1 CATHODIC PROTECTION SPECIFICATION 4058-VW-SG-00OO000006-ISA 15 LAYOUT OF HAZARDOUS AREA CLASSIFICATION COMPRESSOR 4058-SN-DH-00OO000004-IS0
42119-CLO-029
REF NO. DOCUMENT TITLE DOCUMENT NUMBER REF NO. DOCUMENT TITLE DOCUMENT NUMBER
A380-DO-12"-
1. Please refer to the Coordinates Table for the Tag numbers and Coordinates of each component of CP Equipment.
N = 2318.280 FOR CONTINUATION REFER SHEET 3 2. The ICCP continuous anode will be buried in the pipe trench at a distance of 0.5 m from the pipe at the 3 or 9 o'clock
position (i.e. halfway between bottom and top of pipe depth). Anode splicing shall be done using splice kits and shall
E = 1789.500

E= 2097.750
be done as per approved procedure and drawings. Anode tail cables shall be terminated at designated AJB. Sufficient
watering shall be carried out after anode laid in the trench and before backfilling. In any case anodes shall not be in

W400 INSTRUMENTAL BURIED EXISTING


touch/in electrical contact with the pipe.

A380-DO-12"-A01BU-006
14" EXISTING WF LINE
2000.000FGL 2000.000FGL 3. Where there are branching pipes, the sock anode will run all around the branching pipe if the branch length is lower
than five meters, while the sock anode will be spliced to a branching sock anode if the pipe branch length is above five
metres.
4. Bonding cables shall be installed to maintain electrical continuity at locations such as nonwelded joints, mechanical

L OF EXISTING
(R-012-10) 8"-WF-71-0827-A01BU-N
A800-DO-MH-010 joints, flanges, couplings, concrete pits and locations where there is no electrical continuity within the piping system
EXISTING FIRE WATER
EY-DB-EXISTING EXISTING FIRE WATER TO BE
PIT to be cathodically protected. Bonding/Jumper among the pipes shall be provided outside the pits.

ROAD
WITH SPACER RING
PIT
1 2 200-PVC TO BE
DEMOLISHED 5. The piping shall be isolated with neoprene rubber from any reinforced concrete support / wall to minimize current
BD-IY-W400

C
TRENCH
1999.500 DEMOLISHED drains from rebars in reinforced concrete structures.
TOC TP 341
1999.100 BOC 6. Soil access shall be installed next to the test posts and junction boxes at paved areas.
(FV-011-01) N= 2301.150
7. The number of Permanent Magnesium Anodes at TP Type 3 locations shall be as per "DETAILED DESIGN CALCULATION
WF-VP-EXISTING 14"-WF-71-0847-A01BU-N
E= 1986.300

B.J. W400 INSTRUMENTAL BURIED EXISTING


REPORT " document no. 4058-VW-CX-00OO000013 (Ref. No. 19).
BB2-3
N= 2299.228
N= 2300.565
E= 1971.300
E= 1995.412
14" EXISTING WF LINE TRENCH 8. CP cable shall not be laid in instrument / ELECT Trench. A separate cable tray shall be used for CP at least 300mm away
14" EXISTING WF LINE
6"-WF-71-0828-A01BU-N
14" EXISTING WF LINE from ELECT cable in order to avoid the interference. All cables shall be laid without coils or kinks, buried in sand at a
(TYP.)
14" EXISTING WF LINE TP 313 6"-WF-71-0848-A01BU-N W400 INSTRUMENTAL BURIED EXISTING depth of at least 0.75 m, provided with cable protection tiles and warning tape installed 250 mm above the cable. The
TRENCH A TP25 trench shall be 300 mm wide.
INSTALL PE / PVC SHEET TO 6"-WF-71-0837-A01BU-N
705-XM-71-09
14"-WF-71-0847-A01BU-N (FV-012-02) EXISTING 9. Distance from piping to junction boxes and test posts shall be approx 1.5 m.
MITIGATE INTERFERENCE W400 ELECTRICAL BURIED EXISTING WF-VP-EXISTING
10. For the Cable Schedule, please refer to the relevant Document (Ref. No. 27).

A800-DO-12"-A01BU-002
14"-WF-71-0858-A01BU-N TRENCH

6"-WF-71-0812-A01BU-N
14"-WF-71-0051-1A01BU-N
(EXISTING)
11. For the basic requirement/guidelines to be followed by construction personnel during installation, and for brief
EXISTING LIGHT guidelines/precautions, please refer to the Intallation Specification document (Ref. No. 23) and to the Installation
(TYP.)
POLE
TP 346 Drawings (Ref. No. 24).
EXISTING LIGHT 741-XM-71-05 W400 ELECTRICAL BURIED EXISTING 14" EXISTING WF LINE 12. For the Schematic Drawing, please refer to the relevant Document (Ref. No. 25).
(TYP.)
POLE TRENCH
13. All installation works associated with the Cathodic Protection system shall be conducted in accordance with this
drawing and the complete CP design package (see documents Ref No. 16 to 29 for full list). Any conflict between this

14" EXISTING WF LINE


drawing and other CP drawings and / or other project specifications and drawings shall be brought to the attention of

EXISTING LIGHT POLE


1999.100 14" EXISTING WF LINE
LP1 EXISTING ROAD the CP Engineer in writing for clarification as soon as it is discovered.
A800-DO-12"-A01BU-002

EXISTING ROAD
BOC TP 347 14. The final location of the TR Units, Junction Boxes and Test Posts shall be checked by the CP Engineer in consultation
(TYP) with the installation Sub-contractor and client. The TR Units, Junction Boxes and Test Posts shall, where practicable, be
installed in such a fashion that safe and convenient access to them is maintained.
BD-EYL-W400
Under no circumstances shall the TR Units, Junction Boxes and Test Posts be installed in a location where they could
BD-EYL-W400 be damaged and / or cause an obstruction or interference to the regular activities of the operator.
DRAWING LIMIT

DRAWING LIMIT
(RCF-006-1) BD-EYL-W400 15. Wherever there is a pit, Electrical continuity among the pipes like DO, DOV shall be provided at all the locations using
A210-DO-SM-021
14"-WF-71-0872-A01BU-N bonding Jumper cable (1c 25 mm2) and thermite welding.
LP1 W400 ELECTRICAL BURIED EXISTING TRENCH BD-IY-W300
16. Packaged Sacrificial anodes shall be installed 1.5 m away from the pipes and shall be installed at the bottom level of

BD-IY-W300
pipe.

BD-EYL-W400

TP 355
3"-DC-57-5825-A01BUCD-N
14"-WF-71-0872-A01BU-N
17. Sacrificial anodes shall be laid horizontally. Anodes shall be soaked in water 24 hours prior to installation.
BD-IY-W300

A210-DO-12"-A01BU-001
18. Test station shall be installed 1.5 m away from the pipe.
A210-DOV-4"-A01BU-002
(FDF-006-3) INSTALL PE / PVC SHEET TO 19. AJB/PDB/BB/NDB/NJB shall be installed 1.5 m away from the pipe. Cables inside the TP/JB shall be terminated with
A210-DC-VP-003
N= 2274.599
E= 1999.430
BB1-1 proper tagging for easy identifications.
EXISTING LIGHT POLE MITIGATE INTERFERENCE

BD-IY-W300
BD-EY-W600 20. Polarisation coupon and permanent reference cells shall be installed 100 mm away from the pipe and shall be 1/3rd of
N= 2269.550
pipe depth from pipe bottom level.
E= 1977.700 6"-DC-57-0811-A01BUCD-N
BD-IY-W300

N= 2268.400
PLEASE SEE SHEET 7 FOR ADDITIONAL NOTES
N= 2269.275
E= 1968.850 6"-DC-57-0811-A01BUCD-N C TP43 E= 2089.000

CL OF ROAD 4.0M. WIDE

14"-WF-71-0874-A01BU-N
3"-DC-57-5819-A01BUCD-N
N= 2268.300
EXISTING FENCE TYPE 2 E= 2041.376 BD-EY-W800
A A210-DC-VP-004

3"-DC-57-5818-A01BUCD-N
NOTE-7
MAP VIEW
E= 1979.900

3"-DC-57-5817-A01BUCD-N
TP42 300X300 A N= 2266.000
4"-DC-57-0812-A01BUCD-N

EXTRA WIDTH
EXISTING FENCE TYPE 1
CL OF ROAD 4.0M. WIDE

E= 2052.040
3"-DC-57-0814-A01BUCD-N G01-UO-42-02 X400DEEP SUMP A
NOTE-7
TP01

EXTRA WIDTH
3"-DC-57-1001-A01BUCD-N PVC PIPE SLEEVE
EXTRA WIDTH

EXTRA WIDTH

BD-EYL-W400
CL OF OC1-VL-57-11
BD-EYL-W400

PVC PIPE SLEEVE PIPE DIA + 100mm


3"-DC-57-0813-A01BUCD-N

PIPE DIA + 100mm WITH ENCASING


A210-DO-4"-A01BU-007

BD-EY-W800 3"-DC-57-5822-A01BUCD-N DRAWING LIMIT DRAWING LIMIT

WITH ENCASING
BD-EY-W600 3"-DC-57-5823-A01BUCD-N
50 THK. GALVANIZED

DRAWING LIMIT
EXISTING LIGHT POLE (FDF-006-2)

14"-WF-71-0872-A01BU-N
GRATING COVER
3"-DC-57-1001-A01BUCD-N A210-DC-VP-002 TP 356
EXISTING WATER SUPPLY LINE (FDF-006-1)

3"-DC-57-5737-A01BUCD-N
N= 2261.300

3"-DC-57-5819-A01BUCD-N
(TO BE DISMANTLE AND RELOCATE) A210-DC-VP-001
E= 2086.518

DRAWING LIMIT
BD-EY-W1500
PVC PIPE SLEEVE
PIPE DIA + 100mm
WITH ENCASING

DRAWING
LIMIT
N= 2255600
E= 2061500

DRAWING LIMIT
N= 2253.296
E= 2068.071
TP44

N= 2254.304
E= 2062.326
LP1

3"-DC-57-5816-A01BUCD-N
AJB1-2

14" EXISTING WF LINE


AJB1-1

N= 2253.388
E= 2070.045
3"-DC-57-5832-A01BUCD-N
BD-IY-W300 N= 2254.186 N= 2253.476
E= 2072.197 E= 2079.560 A

DRAWING
N= 2252.956

LIMIT

MATCH
LINE-A
CL OF 430-VL-64-04 3"-DC-57-5816-A01BUCD-N
E= 2082.703

FUN-036-6"x4"
G09-VD-45-03
150 THK.x300H. CURB 2000.000 FGL N= 2252.020
(RD-006-1)
E= 2019.500
3"-DC-57-5812-A01BUCD-N
WALL (TYP)
EXISTING FENCE TYPE 1

EXISTING FENCE TYPE 2


(TO BE DISMANTLE AND RELOCATE)

A710-DO-CO-013
N= 2251.300 CL OF G09 CL OF G09 CL OF G09 CL OF G09 CL OF G09
THIS PAGE

DRAWING LIMIT
N= 2250.119
E= 2053.700
EXISTING WATER SUPPLY LINE

E= 2015.092 -VD-23-03 -VD-23-04 -VD-23-02 -VD-23-01 -MB-23-01

3"-DC-57-5836-A01BUCD-N
2000.000 FGL

DRAWING LIMIT
A710-DO-4"-A01BU-003
NJB1-3 N= 2251.100
LP1 (RCF-006-3) E= 2076.070

3"-DC-57-5820-A01BUCD-N

6" EXISTING WF

DRAWING LIMIT
NOTE-7

A710-DO-6"-A01BU-004
NOTE-7

CL OF 410
TP08 -MB-45-02A & B A210-DO-SM-017 N= 2251.800

BD-IY-W300
E= 2083.860

3"-DC-57-5834-A01BUCD-N
(TYP) DRAWING LIMIT

BD-EYL-W400 (TYP)
200W X 600H TR-EY-W500
BD-EYL-W200 DRAWING LIMIT DRAWING LIMIT

(TYP) CUTOUT N= 2245.400


E= 2064.440
DRAWING LIMIT

DROP AREA
C

LINE
(R-006-2)
N= 2243.620
A210-DO-MH-015
E= 2047.600
A210-DO-6"-A01BU-004 Acceptance status Eng. Dept. Date

A210-DO-6"-A01BU-003
430-UN-64-06 code
EXISTING NATURAL N= 2240.700
A710-DO-CB-001E= 2014.000
A710-DO-10"-A01BU-002 A710-DO-SM-028 N= 2243.620
N= 2240.050 N= 2240.050 N= 2237326 E= 2061.500
E= 2010.300 E= 2012.714 E= 2058425 N= 2239.550
E= 2060.200 (RD-006-5)
AC B.LENKA PROCS 14-08-2020

N= 2241.000 FOR CONTINUATION REFER SHEET 5 Comment status code:


A - Accepted CR - Commented. Resubmit for Acceptance
AC - Accepted with Comment, NA
Resubmit
- Not accepted, Resubmit
LEGEND
TRANSFORMER RECTIFIER UNIT (TRU) IMPORTANT: CONTRACTOR acceptance of this Document does not relieve the
VENDOR from full compliance with contractual obligation
NEGATIVE DISTRIBUTION BOX (NDB) - OR
NEGATIVE JUNCTION BOX (NJB) - OR 5 25MAR21 25MAR21 REVISED PER CLIENT COMMENTS N.SIPPEL A.BONETTI S.FILMORE
BOND BOX (BB)
POSITIVE DISTRIBUTION BOX (PDB) 4 10FEB21 23FEB21 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
ANODE JUNCTION BOX (AJB)
3 10FEB21 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
TEST BOX (TB) - TYPE 1 (PSP AND TCP)
TEST BOX (TB) - TYPE 2 (PSP AND TCP) 2 15DEC20 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
TEST BOX (TB) - TYPE 3 (PCP) BOND CABLE
1 23SEP20 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
TEST BOX (TB) - TYPE 4 (INTERFERENCE MITIGATION)
ANODE SOCK
TEST BOX (TB) - TYPE 5 (PVC CASING) 0 15JUL20 ISSUED FOR APPROVAL L.HULL N.SIPPEL A.BONETTI
STRUCTURE CONNECTION
SPLICE KIT
PIPE LEGEND
PERMANENT CSE REFERENCE ELECTRODE
WS: WATER SOURCE C COUPON

FD: FUEL DIESEL


AND THERMOWELD CONNECTIONS)
WF: FIRE WATER 7.7kg MAGNESIUM ANODE
A
OWS: OILY WATER SYSTEM
(TEMPORARY CP)
Realisation du 4eme Train GPL a ZCINA, Hassi Messaoud
14.5kg MAGNESIUM ANODE
DOV: VENT PIPE A
(PERMANENT CP) CT-EPC/001/SH/EPM-G/EP/18
DO: OPEN DRAIN (NON-HAZ)

DC: CLOSED DRAIN A 2x ZINC RIBBON ANODES


(PERMANENT CP)
DP: PROCESS DRAIN
NEGATIVE WELD PAD/CLEAT CONNECTION
HM: HEATING MEDIUM

GENERAL LAYOUT DRAWINGS


29 PRE-COMMISSIONING AND COMMISSIONING CHECK SHEETS 4058-VW-RC-00OO000026
14 LAYOUT OF HAZARDOUS AREA CLASSIFICATION PROCESS TRAIN 4 4058-SN-DH-00OO000003-IS0 28 PRE-COMMISSIONING AND COMMISSIONING PROCEDURE 4058-VW-PC-00OO000025
13 LAYOUT OF HAZARDOUS AREA CLASSIFICATION OVERALL LPG TRAIN 4 4058-SN-DH-00OO000001-IS0 27 CABLE SCHEDULE 4058-VW-LK-00OO000023
12 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A800 4058-AQ-DA-A800000009 26 FOUNDATION AND BASE FRAME DETAIL DRAWINGS 4058-VW-DW-00OO000022
4058-VW-DG-00OO000020 4/7
11 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A630, A710 & A720 4058-AQ-DA-A630000008 25 SCHEMATIC WIRING DRAWINGS 4058-VW-DN-00OO000021
10 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A430 4058-AQ-DA-A430000011 24 INSTALLATION DRAWINGS 4058-VW-DW-00OO000018 EPC001-00-DD-EU-CPC-00020-M 1:250 5
9 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A340 & A350 4058-AQ-DA-A340000003 23 INSTALLATION SPECIFICATION 4058-VW-SG-00OO000017
8 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A330, A360 & A380 4058-AQ-DA-A330000005 22 BILL OF MATERIAL LIST 4058-VW-LM-00OO000016
7 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A310, A320 & A370 4058-AQ-DA-A310000004 21 MATERIALS SPECIFICATION 4058-VW-SG-00OO000015 Grantham, Lincs, UK, NG31 7XS Tel. +44(0)1476 590666
6 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A210 & A220 4058-AQ-DA-A220000002 20 POWER SUPPLY REQUIREMENTS 4058-VW-LN-00OO000014 E-mail cpc@cathodic.co.uk Web www.cathodic.co.uk
5 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A100, A101 & A102 4058-AQ-DA-A100000001 19 DETAILED DESIGN CALCULATION REPORT 4058-VW-CX-00OO000013
4 UNDERGROUND GENERAL DRAWINGS - KEY PLAN 4058-AQ-DX-A100000001 18 DESIGN PHILOSOPHY & SPECIFICATION 4058-VW-SG-00OO000012
3 COATING SPECIFICATION FOR BURIED SURFACES 4058-VW-SG-0000000005 17 PRE-DESIGN SITE SURVEY REPORT 4058-VW-RT-00OO000011
2 MATERIAL SPECIFICATION AND DATASHEET 4058-VW-SG-00OO000007-IS0 16 PRE-DESIGN SITE SURVEY SPECIFICATION 4058-VW-SG-00OO000010 VENDOR DOCUMENT NO.
1 CATHODIC PROTECTION SPECIFICATION 4058-VW-SG-00OO000006-ISA 15 LAYOUT OF HAZARDOUS AREA CLASSIFICATION COMPRESSOR 4058-SN-DH-00OO000004-IS0
42119-CLO-029
REF NO. DOCUMENT TITLE DOCUMENT NUMBER REF NO. DOCUMENT TITLE DOCUMENT NUMBER
LEGEND 1. Please refer to the Coordinates Table for the Tag numbers and Coordinates of each component of CP Equipment.
TRANSFORMER RECTIFIER UNIT (TRU) 2. The ICCP continuous anode will be buried in the pipe trench at a distance of 0.5 m from the pipe at the 3 or 9 o'clock
position (i.e. halfway between bottom and top of pipe depth). Anode splicing shall be done using splice kits and shall

LIMIT
FOR CONTINUATION REFER SHEET 4
N= 2241.000 NEGATIVE DISTRIBUTION BOX (NDB) - OR be done as per approved procedure and drawings. Anode tail cables shall be terminated at designated AJB. Sufficient

A210-DO-6"-A01BU-003
NEGATIVE JUNCTION BOX (NJB) - OR watering shall be carried out after anode laid in the trench and before backfilling. In any case anodes shall not be in
touch/in electrical contact with the pipe.

DRAWING
BOND BOX (BB)

E= 2097.750
E= 2060.200 (RD-006-5)
N= 2240.375 N= 2238.595 A210-DO-CO-014
POSITIVE DISTRIBUTION BOX (PDB) 3. Where there are branching pipes, the sock anode will run all around the branching pipe if the branch length is lower

EXISTING ROAD
TP07 A710-DO-4"-A01BU-005 E= 2019.500 E= 2062.540
N= 2237856 than five meters, while the sock anode will be spliced to a branching sock anode if the pipe branch length is above five
430-UN-64-05A ANODE JUNCTION BOX (AJB)
E = 1789.500

A220-DOV-4"-A01BU-001
A N= 2236.275
E= 2091220
metres.
E= 2019.500
A710-DO-10"-A01BU-006
TEST BOX (TB) - TYPE 1 (PSP AND TCP) 4. Bonding cables shall be installed to maintain electrical continuity at locations such as nonwelded joints, mechanical

3"-DC-57-5803-A01BUCD-N
A710-DO-10"-A01BU-001
N= 2236.530 A710-DO-4"-A01BU-007 A220-DO-6"-A01BU-013 joints, flanges, couplings, concrete pits and locations where there is no electrical continuity within the piping system

3"-DC-57-5808-A01BUCD-N
E= 2010.300
TEST BOX (TB) - TYPE 2 (PSP AND TCP)

A220-DO-4"-A01BU-001
(RCF-006-2) to be cathodically protected. Bonding/Jumper among the pipes shall be provided outside the pits.

A710-DO-10"-A01BU-001

E= 2090.658
2000.000 FGL (RCF-006-4) A220-DO-2"-A01BU-002
A710-DO-SM-016 CRD-6"x4"
5. The piping shall be isolated with neoprene rubber from any reinforced concrete support / wall to minimize current

A220-DO-10"-A01BU-004
430-UN-64-05B A220-DO-SM-018N= 2236.275
TEST BOX (TB) - TYPE 3 (PCP) BOND CABLE

G09-PG-23-07
E= 2047.600
A710-DOV-4"-A01BU-002
A710-DOV-4"-A01BU-001 drains from rebars in reinforced concrete structures.
TEST BOX (TB) - TYPE 4 (INTERFERENCE MITIGATION)
FUN-053-6"x4"

A220-DO-4"-A01BU-012 ANODE SOCK 6. Soil access shall be installed next to the test posts and junction boxes at paved areas.
TEST BOX (TB) - TYPE 5 (PVC CASING) 7. The number of Permanent Magnesium Anodes at TP Type 3 locations shall be as per "DETAILED DESIGN CALCULATION
2000.000 FGL N= 2231.256
E= 2075.980 REPORT " document no. 4058-VW-CX-00OO000013 (Ref. No. 19).
(RD-006-3) STRUCTURE CONNECTION
N= 2228.110
E= 2019.778
A720-DO-CO-011
8. CP cable shall not be laid in instrument / ELECT Trench. A separate cable tray shall be used for CP at least 300mm away
BD-EY-W1000

SPLICE KIT from ELECT cable in order to avoid the interference. All cables shall be laid without coils or kinks, buried in sand at a

A220-DO-10"-A01BU-005
N= 2226.459
FUN-038-6"x4"E= 2013.000 depth of at least 0.75 m, provided with cable protection tiles and warning tape installed 250 mm above the cable. The
A720-DO-4"-A01BU-006 PERMANENT CSE REFERENCE ELECTRODE
A720-DO-6"-A01BU-007
CL OF ACCESS WAY 6.0M. WIDE trench shall be 300 mm wide.

TR-EY-W600
N= 2224.451
E= 2067.725
N= 2224.736
C COUPON 9. Distance from piping to junction boxes and test posts shall be approx 1.5 m.
E= 2067.725

A220-DO-10"-A01BU-008
CL OF 420-VL-63-04
10. For the Cable Schedule, please refer to the relevant Document (Ref. No. 27).

A220-DOV-4"-A01BU-002
EXISTING WELL
11. For the basic requirement/guidelines to be followed by construction personnel during installation, and for brief
BD-IY-W300

AND THERMOWELD CONNECTIONS)

A220-DO-SM-019
TR-EY-W600
guidelines/precautions, please refer to the Intallation Specification document (Ref. No. 23) and to the Installation

NOTE-2
CHROMATOGRAPH
A220-DO-DT-001-W400
CO2-FIRE

(RCF-006-5)
EXTINGUISHING 7.7kg MAGNESIUM ANODE
BOTTLE
A Drawings (Ref. No. 24).

GAS
BD-EY-W600 (TEMPORARY CP)
12. For the Schematic Drawing, please refer to the relevant Document (Ref. No. 25).
50 THK. A220-DO-6"-A01BU-015 14.5kg MAGNESIUM ANODE 13. All installation works associated with the Cathodic Protection system shall be conducted in accordance with this
GALVANIZED
HYDRAULIC
A220-DO-4"-A01BU-014 A
GRATING COVER
STARTING SKID
N= 2217.250
(PERMANENT CP) drawing and the complete CP design package (see documents Ref No. 16 to 29 for full list). Any conflict between this
FUN-039-6"x4" E= 2076.700
drawing and other CP drawings and / or other project specifications and drawings shall be brought to the attention of
EXTRA WIDTH

EXTRA WIDTH
N= 2217.000
A720-DO-4"-A01BU-008
the CP Engineer in writing for clarification as soon as it is discovered.

DRAWING LIMIT
E= 2091.220
CL OF ROAD 4.0M. WIDE

N= 2216.252
E= 2010.648

N= 2213.297
420-UO-63-05A A 2x ZINC RIBBON ANODES 14. The final location of the TR Units, Junction Boxes and Test Posts shall be checked by the CP Engineer in consultation

BOT OF CUT AT 1998900


E= 2011.920
A720-DO-4"-A01BU-009
TR-EY-W1500 (PERMANENT CP) with the installation Sub-contractor and client. The TR Units, Junction Boxes and Test Posts shall, where practicable, be

200Wx600H CUTOUT
(RCF-006-6)
A720-DO-SM-020 BD-EY-W600 installed in such a fashion that safe and convenient access to them is maintained.

RAMP
FUN-040-6"x4" A720-DO-10"-A01BU-003 (R-006-8)
N= 2212.024
A720-DO-CB-001
N= 2212.575
N= 2212.200
E= 2019.778
A220-DO-MH-009 NEGATIVE WELD PAD/CLEAT Under no circumstances shall the TR Units, Junction Boxes and Test Posts be installed in a location where they could
E= 2010.648
E= 2015.000
CONNECTION be damaged and / or cause an obstruction or interference to the regular activities of the operator.
420-UO-63-05B
TP02 15. Wherever there is a pit, Electrical continuity among the pipes like DO, DOV shall be provided at all the locations using

BD-IY-W800
(TYP)
N= 2207.720 N= 2207.720
A720-DOV-4"-A01BU-002
E= 2009.949 E= 2016.000 BD-EY-W400 bonding Jumper cable (1c 25 mm2) and thermite welding.
A720-DO-10"-A01BU-004 150 THK. CURB WALL (TYP)
A720-DOV-4"-A01BU-001 N= 2205.600
E= 2009.524 N= 2205.600 16. Packaged Sacrificial anodes shall be installed 1.5 m away from the pipes and shall be installed at the bottom level of
A A720-DO-10"-A01BU-001
E= 2047.600
pipe.

BD-IY-W300
17. Sacrificial anodes shall be laid horizontally. Anodes shall be soaked in water 24 hours prior to installation.

A220-DO-10"-A01BU-009
A720-DO-8"-A01BU-002 A720-DO-10"-A01BU-001

BD-EY-W1500
742-XM-71-01 18. Test station shall be installed 1.5 m away from the pipe.

A220-DO-MH-007
6"-WF-71-0834-A01BU-N

BD-IY-W800
TP32 A720-DO-MH-005 N= 2205.600 INSTALL PE / PVC SHEET TO 6" EXISTING WF 19. AJB/PDB/BB/NDB/NJB shall be installed 1.5 m away from the pipe. Cables inside the TP/JB shall be terminated with
E= 2019.778
BB1-2 proper tagging for easy identifications.
INSTALL PE / PVC SHEET TO MITIGATE INTERFERENCE LINE

EXISTING ROAD
DIESEL STORAGE
20. Polarisation coupon and permanent reference cells shall be installed 100 mm away from the pipe and shall be 1/3rd of
TANK MITIGATE INTERFERENCE BD-IY-W300
pipe depth from pipe bottom level.
A220-DO-10"-A01BU-010
A720-DO-6"-A01BU-017

N= 2200.137
E= 2014.220
A720-DO-4"-A01BU-016
AJB1-3 A220-DO-MH-016
A220-DO-10"-A01BU-006 A220-DO-10"-A01BU-006 (R-006-7) A220-DO-10"-A01BU-007 N= 2199.300
E= 2091.220
PLEASE SEE SHEET 7 FOR ADDITIONAL NOTES
A220-DO-MH-014
A220-DO-10"-A01BU-011
N= 2199.300 N= 2199.300
E= 2047.600 E= 2071.511

N= 2195.284

A220-DO-10"-A01BU-003
A720-DO-4"-A01BU-015
E= 2019.031

NJB1-1
A220-DO-SM-024
TP03 N= 2194.419 DRAWING LIMIT
MAP VIEW
NJB1-2 LP1

E = 2154.756
DRAWING LIMIT

A220-DOV-4"-A01BU-003

10" EXISTING DO LINE


N= 2191.700
E= 2018.750 DRAWING LIMIT DRAWING LIMIT

A720-DO-4"-A01BU-014
N= 2190.807
E= 2011.776
A720-DO-10"-A01BU-005 C A 2"-FD-62-0804-A01BU-N (EXISTING)
2"-FD-62-0804-A01BU-N 2"-FD-62-0804-A01BU-N

DRAWING LIMIT
A720-DO-CB-002 N= 2191.700
E= 2047.600
A720-DO-4"-A01BU-013 (R-007-2)
A720-DO-4"-A01BU-012 C N= 2188.500
420-UO-63-06A E= 2117.500

N= 2189.125

DRAWING LIMIT
E= 2011.756
TP06

DRAWING
N= 2185.895

LIMIT
E= 2011.756

2000.000 FGL

DRAWING LIMIT
CL OF EXISTING ROAD 4.0M. WIDE
2"-FD-62-0808-A01BU-N
A720-DO-4"-A01BU-011 C OF ROAD 4.0M. WIDE
L
A720-DO-4"-A01BU-010

EXTRA WIDTH
430-UO-63-06B

DRAWING
N= 2184.215

LIMIT

MATCH
LINE-A
E= 2011.756

2000.000 FGL
TP33 INSTALL PE / PVC SHEET TO

DRAWING LIMIT
N= 2183.000

MITIGATE INTERFERENCE
E= 2009.199

DRAWING LIMIT
PDB1 TRU1 N= 2176.300
E= 2052.600
N= 2177.075
E= 2076.600

DRAWING LIMIT
NDB1
A720-DO-CO-012

A630-DO-10"-A01BU-009 A630-DO-10"-A01BU-007
A630-DO-6"-A01BU-005

DRAWING LIMIT
(RD-006-4)

10" EXISTING DO LINE


BENTINI SCOPE
BD-IY-W1500
THIS PAGE

CL OF EXISTING ROAD 6.0M. WIDE


N= 2176.475 DRAWING LIMIT

EMERGENCY DIESEL GENERATOR


E= 2108.520
(R-006-10)
N= 2173.302 DRAWING LIMIT DRAWING LIMIT

E= 2119.300

EXTRA WIDTH
A630-DO-MH-021 DRAWING LIMIT

(R-006-5)

A630-DO-6"-A01BU-006

A630-DO-MH-022
EXISTING LIGHT POLE
BD-EY-W600
WATER DISTILLED ROOM

N= 2175.098
4MO-MA-50-02A A630-DOV-4"-A01BU-001
E= 2055.625 A630-DO-MH-005

(R-006-11)
14"-WF-71-0872-A01BU-N 4MO-MA-50-02B Acceptance status Eng. Dept. Date
code
FOR SUBSTATION BUILDING REFER DETAIL DRAWING NO.

6PO-EG-84-02
A630-DO-10"-A01BU-008
OBC2019-07-HMD-682ARC-LAY-0001 & 0010 BD-IY-W1000

2"-FD-62-0806-A01BU-N
SWITCHGEAR ROOM
INSTRUMENT ROOM BATTERY ROOM NOTE 8 Comment status code:
CONCRETE HOLLOW
BLOCK (EXISTING) A - Accepted CR - Commented. Resubmit for Acceptance
ECS ROOM (R-007-9)
(EXISTING)

EXTRA WIDTH
BD-IY-W400 N= 2164.540
(R-007-14)
AC - Accepted with Comment, NA
Resubmit
- Not accepted, Resubmit
E= 2046.600
DO-TIE-IN-003
EXISTING
TIE-IN TP-317 702-XM-71-01
N= 2162.409
E= 2130.115 IMPORTANT: CONTRACTOR acceptance of this Document does not relieve the
TRANSFERFOR

(R-006-9) N= 2162.409
VENDOR from full compliance with contractual obligation
E= 2119.300
TRANSFERFOR

CLEAN AGENT 6" EXISTING WF LINE A630-DO-MH-008 A630-DO-10"-A01BU-001 10" EXISTING DO LINE 12" EXISTING DO LINE
BAY
BD-IY-W400

BENTINI SCOPE SYSTEM


14" EXISTING WF LINE TIE-IN TP-348
BAY

BD-EY-W2000

14" EXISTING WF LINE


2000.200 TOC 5 25MAR21 25MAR21 REVISED PER CLIENT COMMENTS N.SIPPEL A.BONETTI S.FILMORE
4" EXISTING WF LINE TIE-IN TP-353 PAVING FOR HVAC
2000.000 FGL BENTINI SCOPE
BD-IY-W300 A630-OWS-8"-A01BU-002
(FV-006-01) 14"-WF-71-0873-A01BU-N
N= 2159.600
4 10FEB21 23FEB21 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
WF-VP-EXISTING E= 2148.650
2000.000 FGL CONCRETE HOLLOW
EXISTING FENCE
A630-OWS-8"-A01BU-001 N= 2155.550
E= 2072.130 AJB1-4 N= 2155.840
BLOCK
TYPE 3
N= 2155.550
E= 2066.130 N= 2156.650
E= 2114.840 3 10FEB21 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
LP1 (TYP.) A630-OWS-8"-A01BU-003 A630-OWS-8"-A01BU-004 E= 2079.600

(TYP.) W400 ELECTRICAL BURIED EXISTING TRENCH


BD-EYL-W200 4"-WF-71-0864-A01BU-N TP05 A A 2 15DEC20 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
BD-EYL-W400 (TYP.)
W400 ELECTRICAL BURIED EXISTING TRENCH TP04 N= 2155.840
E= 2088.250
EXTRA WIDTH
A630-DOV-4"-A01BU-003

N= 2152.600

2"-WS-62-0807-A01BU-N
E= 2046.600 EXTRA WIDTH 1 23SEP20 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
A630-OWS-MH-001 EXISTING
TIE-IN TP-349 EXISTING A630-OWS-MH-002
INSTALL PE / PVC SHEET TO N= 2152.600
E= 2035.583 LIGHT POLE LIGHT POLE
0 15JUL20 ISSUED FOR APPROVAL L.HULL N.SIPPEL A.BONETTI
(TYP.) (TYP.) 12" EXISTING DO LINE
MITIGATE INTERFERENCE A
NOTE 7 CL OF EXISTING ROAD 6.0M. WIDE

NEW ROAD EXISTING


TIE-IN TP-354
NOTE-3
EXISTING GATE
OWS COLLECTION PIT
FOR DETAILS REFER DWG.
N = 2131.000 DRAWING LIMIT DRAWING LIMIT
EXISTING FENCE
ROAD TYPE 3
NO. 4058-AADC-A630000101 PIPE LEGEND
EXTRA WIDTH
WS: WATER SOURCE
N= 2143.400
NEW FENCE TYPE 3 2000.000 FGL E= 2089.000

(NOTE 5) 14" EXISTING WF LINE


4" EXISTING WF LINE W400 ELECTRICAL BURIED EXISTING TRENCH FD: FUEL DIESEL

WF: FIRE WATER


FENCE TIE-IN
POINT J2
(SEE NOTE 4
EXISTING FENCE
TYPE 3
TO BE RETAINED
TP26 OWS: OILY WATER SYSTEM
Realisation du 4eme Train GPL a ZCINA, Hassi Messaoud
A DOV: VENT PIPE
FENCE FOUNDATION 1999.200 FGL
CT-EPC/001/SH/EPM-G/EP/18
E = 2154.756

6"-WF-71-0833-A01BU-N
14" EXISTING WF LINE
DO: OPEN DRAIN (NON-HAZ)
14" EXISTING WF LINE

(FV-002-03) (FV-002-01) TIE-IN TP-319 DC: CLOSED DRAIN


EXISTING ROAD WF-VP-EXISTING WF-VP-EXISTING
TO BE DEMOLISH 14" EXISTING WF LINE
8" EXISTING WF LINE

AND REINSTALL DP: PROCESS DRAIN


EXTRA WIDTH

EXTRA WIDTH

NEW FENCE
DRAWING LIMIT HM: HEATING MEDIUM
DRAWING LIMIT
DRAWING LIMIT N= 2131.000

GENERAL LAYOUT DRAWINGS


29 PRE-COMMISSIONING AND COMMISSIONING CHECK SHEETS 4058-VW-RC-00OO000026
14 LAYOUT OF HAZARDOUS AREA CLASSIFICATION PROCESS TRAIN 4 4058-SN-DH-00OO000003-IS0 28 PRE-COMMISSIONING AND COMMISSIONING PROCEDURE 4058-VW-PC-00OO000025
13 LAYOUT OF HAZARDOUS AREA CLASSIFICATION OVERALL LPG TRAIN 4 4058-SN-DH-00OO000001-IS0 27 CABLE SCHEDULE 4058-VW-LK-00OO000023
12 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A800 4058-AQ-DA-A800000009 26 FOUNDATION AND BASE FRAME DETAIL DRAWINGS 4058-VW-DW-00OO000022
4058-VW-DG-00OO000020 5/7
11 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A630, A710 & A720 4058-AQ-DA-A630000008 25 SCHEMATIC WIRING DRAWINGS 4058-VW-DN-00OO000021
10 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A430 4058-AQ-DA-A430000011 24 INSTALLATION DRAWINGS 4058-VW-DW-00OO000018 EPC001-00-DD-EU-CPC-00020-M 1:250 5
9 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A340 & A350 4058-AQ-DA-A340000003 23 INSTALLATION SPECIFICATION 4058-VW-SG-00OO000017
8 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A330, A360 & A380 4058-AQ-DA-A330000005 22 BILL OF MATERIAL LIST 4058-VW-LM-00OO000016
7 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A310, A320 & A370 4058-AQ-DA-A310000004 21 MATERIALS SPECIFICATION 4058-VW-SG-00OO000015 Grantham, Lincs, UK, NG31 7XS Tel. +44(0)1476 590666
6 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A210 & A220 4058-AQ-DA-A220000002 20 POWER SUPPLY REQUIREMENTS 4058-VW-LN-00OO000014 E-mail cpc@cathodic.co.uk Web www.cathodic.co.uk
5 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A100, A101 & A102 4058-AQ-DA-A100000001 19 DETAILED DESIGN CALCULATION REPORT 4058-VW-CX-00OO000013
4 UNDERGROUND GENERAL DRAWINGS - KEY PLAN 4058-AQ-DX-A100000001 18 DESIGN PHILOSOPHY & SPECIFICATION 4058-VW-SG-00OO000012
3 COATING SPECIFICATION FOR BURIED SURFACES 4058-VW-SG-0000000005 17 PRE-DESIGN SITE SURVEY REPORT 4058-VW-RT-00OO000011
2 MATERIAL SPECIFICATION AND DATASHEET 4058-VW-SG-00OO000007-IS0 16 PRE-DESIGN SITE SURVEY SPECIFICATION 4058-VW-SG-00OO000010 VENDOR DOCUMENT NO.
1 CATHODIC PROTECTION SPECIFICATION 4058-VW-SG-00OO000006-ISA 15 LAYOUT OF HAZARDOUS AREA CLASSIFICATION COMPRESSOR 4058-SN-DH-00OO000004-IS0
42119-CLO-029
REF NO. DOCUMENT TITLE DOCUMENT NUMBER REF NO. DOCUMENT TITLE DOCUMENT NUMBER
1. Please refer to the Coordinates Table for the Tag numbers and Coordinates of each component of CP Equipment.
2. The ICCP continuous anode will be buried in the pipe trench at a distance of 0.5 m from the pipe at the 3 or 9 o'clock
position (i.e. halfway between bottom and top of pipe depth). Anode splicing shall be done using splice kits and shall
be done as per approved procedure and drawings. Anode tail cables shall be terminated at designated AJB. Sufficient
watering shall be carried out after anode laid in the trench and before backfilling. In any case anodes shall not be in
N = 2423.000 DRAWING LIMIT
touch/in electrical contact with the pipe.

E = 2423.970

E = 2465.000
3. Where there are branching pipes, the sock anode will run all around the branching pipe if the branch length is lower
than five meters, while the sock anode will be spliced to a branching sock anode if the pipe branch length is above five
metres.
4. Bonding cables shall be installed to maintain electrical continuity at locations such as nonwelded joints, mechanical
W400 ELECTRICAL BURIED EXISTING joints, flanges, couplings, concrete pits and locations where there is no electrical continuity within the piping system
2000.000FGL
TRENCH to be cathodically protected. Bonding/Jumper among the pipes shall be provided outside the pits.
5. The piping shall be isolated with neoprene rubber from any reinforced concrete support / wall to minimize current
drains from rebars in reinforced concrete structures.
PIPE LEGEND 6. Soil access shall be installed next to the test posts and junction boxes at paved areas.
7. The number of Permanent Magnesium Anodes at TP Type 3 locations shall be as per "DETAILED DESIGN CALCULATION
WS: WATER SOURCE REPORT " document no. 4058-VW-CX-00OO000013 (Ref. No. 19).
8. CP cable shall not be laid in instrument / ELECT Trench. A separate cable tray shall be used for CP at least 300mm away
FD: FUEL DIESEL from ELECT cable in order to avoid the interference. All cables shall be laid without coils or kinks, buried in sand at a
depth of at least 0.75 m, provided with cable protection tiles and warning tape installed 250 mm above the cable. The
WF: FIRE WATER trench shall be 300 mm wide.
9. Distance from piping to junction boxes and test posts shall be approx 1.5 m.
OWS: OILY WATER SYSTEM
W400 ELECTRICAL BURIED EXISTING 10. For the Cable Schedule, please refer to the relevant Document (Ref. No. 27).
TRENCH
DOV: VENT PIPE 11. For the basic requirement/guidelines to be followed by construction personnel during installation, and for brief
guidelines/precautions, please refer to the Intallation Specification document (Ref. No. 23) and to the Installation
DO: OPEN DRAIN (NON-HAZ) Drawings (Ref. No. 24).

W600 ELECTRICAL BURIED EXISTING


12. For the Schematic Drawing, please refer to the relevant Document (Ref. No. 25).
DC: CLOSED DRAIN 13. All installation works associated with the Cathodic Protection system shall be conducted in accordance with this
drawing and the complete CP design package (see documents Ref No. 16 to 29 for full list). Any conflict between this
DP: PROCESS DRAIN drawing and other CP drawings and / or other project specifications and drawings shall be brought to the attention of
HM: HEATING MEDIUM the CP Engineer in writing for clarification as soon as it is discovered.
2000.000FGL
14. The final location of the TR Units, Junction Boxes and Test Posts shall be checked by the CP Engineer in consultation
with the installation Sub-contractor and client. The TR Units, Junction Boxes and Test Posts shall, where practicable, be

W400 ELECTRICAL BURIED EXISTING


installed in such a fashion that safe and convenient access to them is maintained.

TRENCH
Under no circumstances shall the TR Units, Junction Boxes and Test Posts be installed in a location where they could
be damaged and / or cause an obstruction or interference to the regular activities of the operator.
15. Wherever there is a pit, Electrical continuity among the pipes like DO, DOV shall be provided at all the locations using
24" EXISTING DO

bonding Jumper cable (1c 25 mm2) and thermite welding.


16. Packaged Sacrificial anodes shall be installed 1.5 m away from the pipes and shall be installed at the bottom level of
pipe.
TRENCH
LINE

W400 ELECTRICAL BURIED EXISTING 17. Sacrificial anodes shall be laid horizontally. Anodes shall be soaked in water 24 hours prior to installation.
(EXISTING)
(R-016-2)
A100-DO-SM-022
TRENCH 18. Test station shall be installed 1.5 m away from the pipe.
TP27 19. AJB/PDB/BB/NDB/NJB shall be installed 1.5 m away from the pipe. Cables inside the TP/JB shall be terminated with
proper tagging for easy identifications.
SHOLUDER

A100-DOV-4"-A01BU-001
2000.000FGL
20. Polarisation coupon and permanent reference cells shall be installed 100 mm away from the pipe and shall be 1/3rd of
ROAD

A100-DO-12"-A01BU-001 pipe depth from pipe bottom level.


A100-DO-6"-A01BU-003
DO-TIE-IN-004 A
A100-DO-12"-A01BU-002 ELECTRICAL PLEASE SEE SHEET 7 FOR ADDITIONAL NOTES
CONCRETE TRENCH
A (TYP.)
NOTE-3

W400 ELECTRICAL BURIED EXISTING MAP VIEW


FOR CONTINUATION REFER SHEET 4

TRENCH

35C-PA-35-04C

1789.500

1832.150

E= 2040.000

E= 2044.000
E=

E=
N=
2510.250
N= 2507.000

E= 2063.775
DRAWING LIMIT DRAWING LIMIT N= 2497.801

A100-DO-4"-A01BU-004

DRAWING LIMIT
35C-PA-35-04D

N=
2459.000

DRAWING LIMIT
FUN-049-6"x4"

E= 1936.700
N= 2446.300

N= 2445.000
24" EXISTING DO

BD-EY-W600 A100-DO-4"-A01BU-005

DRAWING LIMIT
E= 1937.010

DRAWING
N= 2383.100

LIMIT
N= 2378.700

DRAWING LIMIT
150 THK., 100 HT.
LINE

CURB WALL

THIS PAGE

DRAWING
LIMIT

MATCH
LINE-A
BD-IY-W300
BD-EY-W600

W1000 ELECTRICAL BURIED EXISTING

A100-DO-4"-A01BU-006 LEGEND

DRAWING LIMIT
TRANSFORMER RECTIFIER UNIT (TRU)

DRAWING LIMIT
W400 ELECTRICAL BURIED EXISTING NEGATIVE DISTRIBUTION BOX (NDB) - OR

DRAWING LIMIT
TRENCH
NEGATIVE JUNCTION BOX (NJB) - OR N= 2168.300

BOND BOX (BB) DRAWING LIMIT


N= 2149.446

35C-SHL-01
POSITIVE DISTRIBUTION BOX (PDB) DRAWING LIMIT
DRAWING LIMIT DRAWING LIMIT

ANODE JUNCTION BOX (AJB)


TRENCH

35C-PA-35-04A/B

35C-PA-35-04A/B

Acceptance status Eng. Dept. Date


TEST BOX (TB) - TYPE 1 (PSP AND TCP) code

TEST BOX (TB) - TYPE 2 (PSP AND TCP)


2000.000FGL
W400 ELECTRICAL BURIED EXISTING W400 ELECTRICAL BURIED EXISTING TRENCH TEST BOX (TB) - TYPE 3 (PCP) Comment status code:
TRENCH
A - Accepted CR - Commented. Resubmit for Acceptance
TEST BOX (TB) - TYPE 4 (INTERFERENCE MITIGATION)
AC - Accepted with Comment, NA
Resubmit
- Not accepted, Resubmit
TEST BOX (TB) - TYPE 5 (PVC CASING)
(R-016-4) IMPORTANT: CONTRACTOR acceptance of this Document does not relieve the
(EXISTING) 24" EXISTING DOV
24" EXISTING DO
LINE
STRUCTURE CONNECTION VENDOR from full compliance with contractual obligation
(EXISTING) LINE
(R-016-3) NEGATIVE WELD PAD/CLEAT CONNECTION
16" EXISTING DO

SPLICE KIT 5 25MAR21 25MAR21 REVISED PER CLIENT COMMENTS N.SIPPEL A.BONETTI S.FILMORE
PERMANENT CSE REFERENCE ELECTRODE

E = 2513.445
EMULSEUR MOUSSE 4 10FEB21 23FEB21 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
LINE

C COUPON
(FV-016-02)
BD-IY-W300 BD-IY-W300 WF-VP-EXISTING 3 10FEB21 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
AND THERMOWELD CONNECTIONS)
7.7kg MAGNESIUM ANODE 2 15DEC20 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
A
(TEMPORARY CP)
1 23SEP20 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI
14.5kg MAGNESIUM ANODE
A
TP28 (PERMANENT CP)
706-RA-71-20

450-PD-42-01A/B
4" EXISTING WF LINE 0 15JUL20 ISSUED FOR APPROVAL L.HULL N.SIPPEL A.BONETTI
A
24" EXISTING DO

3"-WF-71-0835-A01BU-N A 2x ZINC RIBBON ANODES


2000.000FGL (PERMANENT CP)
450-VN-42-01

L OF EXISTING
SHOLUDER
TIE-IN TP-343
LINE

14" EXISTING WF LINE

Realisation du 4eme Train GPL a ZCINA, Hassi Messaoud


450-SHL-11

24" EXISTING DO
LINE
(EXISTING) (FV-016-01)
CT-EPC/001/SH/EPM-G/EP/18
(R-016-6) WF-VP-EXISTING

BOND CABLE
N = 2316.000
DRAWING LIMIT ANODE SOCK

GENERAL LAYOUT DRAWINGS


29 PRE-COMMISSIONING AND COMMISSIONING CHECK SHEETS 4058-VW-RC-00OO000026
14 LAYOUT OF HAZARDOUS AREA CLASSIFICATION PROCESS TRAIN 4 4058-SN-DH-00OO000003-IS0 28 PRE-COMMISSIONING AND COMMISSIONING PROCEDURE 4058-VW-PC-00OO000025
13 LAYOUT OF HAZARDOUS AREA CLASSIFICATION OVERALL LPG TRAIN 4 4058-SN-DH-00OO000001-IS0 27 CABLE SCHEDULE 4058-VW-LK-00OO000023
12 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A800 4058-AQ-DA-A800000009 26 FOUNDATION AND BASE FRAME DETAIL DRAWINGS 4058-VW-DW-00OO000022
4058-VW-DG-00OO000020 6/7
11 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A630, A710 & A720 4058-AQ-DA-A630000008 25 SCHEMATIC WIRING DRAWINGS 4058-VW-DN-00OO000021
10 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A430 4058-AQ-DA-A430000011 24 INSTALLATION DRAWINGS 4058-VW-DW-00OO000018 EPC001-00-DD-EU-CPC-00020-M 1:250 5
9 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A340 & A350 4058-AQ-DA-A340000003 23 INSTALLATION SPECIFICATION 4058-VW-SG-00OO000017
8 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A330, A360 & A380 4058-AQ-DA-A330000005 22 BILL OF MATERIAL LIST 4058-VW-LM-00OO000016
7 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A310, A320 & A370 4058-AQ-DA-A310000004 21 MATERIALS SPECIFICATION 4058-VW-SG-00OO000015 Grantham, Lincs, UK, NG31 7XS Tel. +44(0)1476 590666
6 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A210 & A220 4058-AQ-DA-A220000002 20 POWER SUPPLY REQUIREMENTS 4058-VW-LN-00OO000014 E-mail cpc@cathodic.co.uk Web www.cathodic.co.uk
5 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A100, A101 & A102 4058-AQ-DA-A100000001 19 DETAILED DESIGN CALCULATION REPORT 4058-VW-CX-00OO000013
4 UNDERGROUND GENERAL DRAWINGS - KEY PLAN 4058-AQ-DX-A100000001 18 DESIGN PHILOSOPHY & SPECIFICATION 4058-VW-SG-00OO000012
3 COATING SPECIFICATION FOR BURIED SURFACES 4058-VW-SG-0000000005 17 PRE-DESIGN SITE SURVEY REPORT 4058-VW-RT-00OO000011
2 MATERIAL SPECIFICATION AND DATASHEET 4058-VW-SG-00OO000007-IS0 16 PRE-DESIGN SITE SURVEY SPECIFICATION 4058-VW-SG-00OO000010 VENDOR DOCUMENT NO.
1 CATHODIC PROTECTION SPECIFICATION 4058-VW-SG-00OO000006-ISA 15 LAYOUT OF HAZARDOUS AREA CLASSIFICATION COMPRESSOR 4058-SN-DH-00OO000004-IS0
42119-CLO-029
REF NO. DOCUMENT TITLE DOCUMENT NUMBER REF NO. DOCUMENT TITLE DOCUMENT NUMBER
1. Please refer to the Coordinates Table for the Tag numbers and Coordinates of each component of CP Equipment.
2. The ICCP continuous anode will be buried in the pipe trench at a distance of 0.5 m from the pipe at the 3 or 9 o'clock
CABLE SCHEDULE PIPE DETAIL PIPE LEGEND
position (i.e. halfway between bottom and top of pipe depth). Anode splicing shall be done using splice kits and shall
be done as per approved procedure and drawings. Anode tail cables shall be terminated at designated AJB. Sufficient
HM: HEATING MEDIUM watering shall be carried out after anode laid in the trench and before backfilling. In any case anodes shall not be in
touch/in electrical contact with the pipe.
DP: PROCESS DRAIN 3. Where there are branching pipes, the sock anode will run all around the branching pipe if the branch length is lower
than five meters, while the sock anode will be spliced to a branching sock anode if the pipe branch length is above five
DC: CLOSED DRAIN metres.
4. Bonding cables shall be installed to maintain electrical continuity at locations such as nonwelded joints, mechanical
DO: OPEN DRAIN (NON-HAZ) joints, flanges, couplings, concrete pits and locations where there is no electrical continuity within the piping system
to be cathodically protected. Bonding/Jumper among the pipes shall be provided outside the pits.
DOV: VENT PIPE
5. The piping shall be isolated with neoprene rubber from any reinforced concrete support / wall to minimize current
OWS: OILY WATER SYSTEM drains from rebars in reinforced concrete structures.
6. Soil access shall be installed next to the test posts and junction boxes at paved areas.
WF: FIRE WATER 7. The number of Permanent Magnesium Anodes at TP Type 3 locations shall be as per "DETAILED DESIGN CALCULATION
REPORT " document no. 4058-VW-CX-00OO000013 (Ref. No. 19).
FD: FUEL DIESEL 8. CP cable shall not be laid in instrument / ELECT Trench. A separate cable tray shall be used for CP at least 300mm away
from ELECT cable in order to avoid the interference. All cables shall be laid without coils or kinks, buried in sand at a
WS: WATER SOURCE depth of at least 0.75 m, provided with cable protection tiles and warning tape installed 250 mm above the cable. The
CO-ORDINATES trench shall be 300 mm wide.
9. Distance from piping to junction boxes and test posts shall be approx 1.5 m.
10. For the Cable Schedule, please refer to the relevant Document (Ref. No. 27).
11. For the basic requirement/guidelines to be followed by construction personnel during installation, and for brief
guidelines/precautions, please refer to the Intallation Specification document (Ref. No. 23) and to the Installation
Drawings (Ref. No. 24).
12. For the Schematic Drawing, please refer to the relevant Document (Ref. No. 25).
13. All installation works associated with the Cathodic Protection system shall be conducted in accordance with this
drawing and the complete CP design package (see documents Ref No. 16 to 29 for full list). Any conflict between this
TEST BOX (TB) - TEST BOX (TB) - TEST BOX (TB) - drawing and other CP drawings and / or other project specifications and drawings shall be brought to the attention of
TYPE 1 (PSP AND TCP) TYPE 2 (PSP AND TCP) TYPE 3 (PCP) the CP Engineer in writing for clarification as soon as it is discovered.
14. The final location of the TR Units, Junction Boxes and Test Posts shall be checked by the CP Engineer in consultation
with the installation Sub-contractor and client. The TR Units, Junction Boxes and Test Posts shall, where practicable, be
installed in such a fashion that safe and convenient access to them is maintained.
Under no circumstances shall the TR Units, Junction Boxes and Test Posts be installed in a location where they could
be damaged and / or cause an obstruction or interference to the regular activities of the operator.
15. Wherever there is a pit, Electrical continuity among the pipes like DO, DOV shall be provided at all the locations using
bonding Jumper cable (1c 25 mm2) and thermite welding.
16. Packaged Sacrificial anodes shall be installed 1.5 m away from the pipes and shall be installed at the bottom level of
pipe.
A A
A 17. Sacrificial anodes shall be laid horizontally. Anodes shall be soaked in water 24 hours prior to installation.
18. Test station shall be installed 1.5 m away from the pipe.
C 19. AJB/PDB/BB/NDB/NJB shall be installed 1.5 m away from the pipe. Cables inside the TP/JB shall be terminated with
proper tagging for easy identifications.
20. Polarisation coupon and permanent reference cells shall be installed 100 mm away from the pipe and shall be 1/3rd of
pipe depth from pipe bottom level.
TEST BOX (TB) -
TYPE 4 TEST BOX (TB) - PLEASE SEE BELOW FOR ADDITIONAL NOTES
(INTERFERENCE MITIGATION) TYPE 5 (PVC CASINGS)

MAP VIEW
DRAWING LIMIT DRAWING LIMIT

DRAWING LIMIT
DRAWING LIMIT
A

DRAWING
LIMIT
DRAWING LIMIT
DRAWING
LIMIT

MATCH
LINE-A
DRAWING LIMIT
ADDITIONAL NOTES

DRAWING LIMIT
21. Temporary Magnesium anodes at test station (Type 1 and 2) shall be disconnected prior to energisation of permanent cathodic

DRAWING LIMIT
protection.
22. All pipe to cable connections at TP/BB/Jumper locations shall be carried out using thermite welding connection. Pipe to cable DRAWING LIMIT

connections at all negative drain points shall be carried out using weld pad and cleat connections. All cable connections location coating DRAWING LIMIT DRAWING LIMIT

repair shall be carried out and holiday testing shall be carried out. DRAWING LIMIT

23. Carrier pipe inside the PVC casing shall be protected by Zinc ribbon anode. 2 no. Zn ribbon shall be tied to pipe at 5 & 7 O'clock position.
Acceptance status Eng. Dept. Date
Cables from Zn ribbon shall be terminated inside the Test post. Refer installation drawing no. 4058-VW-DW-00OO000018. Pipe shall be code
inserted inside the PVC sleeves along with Zn ribbon fitted to the pipe, care shall be taken while inserting the carrier inside the casing
that there shall not be any damage to Zn ribbon and cable. All 4 no. cables from Zn ribbon shall be terminated inside the test posts.
Cables shall be taken out from the casing and shall be routed to the test post and shall be terminated inside the test post. Both sides of Comment status code:
casing end shall be sealed using non metallic HDPE or other suitable sheets in order to prevent any water ingress inside the casing. A - Accepted CR - Commented. Resubmit for Acceptance
24. Cable routes shall be clearly marked using cable markers. These shall be installed every 50 m and at every change of direction of the AC - Accepted with Comment, NA
Resubmit
- Not accepted, Resubmit
cable route.
25. Linear anode routes shall be clearly marked using markers. These shall be installed every 50 m and at every change of direction of the IMPORTANT: CONTRACTOR acceptance of this Document does not relieve the
linear anode route. VENDOR from full compliance with contractual obligation
26. Prior to carry out thermite welding on existing piping,pipe thickness measurement shall be taken and necessary permission shall be
taken from the OWNER. 5 25MAR21 25MAR21 REVISED PER CLIENT COMMENTS N.SIPPEL A.BONETTI S.FILMORE

4 10FEB21 23FEB21 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI

3 10FEB21 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI

2 15DEC20 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI

1 23SEP20 REVISED PER CLIENT COMMENTS L.HULL N.SIPPEL A.BONETTI

0 15JUL20 ISSUED FOR APPROVAL L.HULL N.SIPPEL A.BONETTI

Realisation du 4eme Train GPL a ZCINA, Hassi Messaoud


CT-EPC/001/SH/EPM-G/EP/18

GENERAL LAYOUT DRAWINGS


29 PRE-COMMISSIONING AND COMMISSIONING CHECK SHEETS 4058-VW-RC-00OO000026
14 LAYOUT OF HAZARDOUS AREA CLASSIFICATION PROCESS TRAIN 4 4058-SN-DH-00OO000003-IS0 28 PRE-COMMISSIONING AND COMMISSIONING PROCEDURE 4058-VW-PC-00OO000025
NOTE: 13 LAYOUT OF HAZARDOUS AREA CLASSIFICATION OVERALL LPG TRAIN 4 4058-SN-DH-00OO000001-IS0 27 CABLE SCHEDULE 4058-VW-LK-00OO000023
Cable for Test post. 12 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A800 4058-AQ-DA-A800000009 26 FOUNDATION AND BASE FRAME DETAIL DRAWINGS 4058-VW-DW-00OO000022
4058-VW-DG-00OO000020 7/7
2 no. 1C 10 Sq.mm Cu/XLPE/PVC cable shall be connected to pipe. 11 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A630, A710 & A720 4058-AQ-DA-A630000008 25 SCHEMATIC WIRING DRAWINGS 4058-VW-DN-00OO000021
Each length shall be 10m 1:250 5
10 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A430 4058-AQ-DA-A430000011 24 INSTALLATION DRAWINGS 4058-VW-DW-00OO000018 EPC001-00-DD-EU-CPC-00020-M
9 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A340 & A350 4058-AQ-DA-A340000003 23 INSTALLATION SPECIFICATION 4058-VW-SG-00OO000017
8 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A330, A360 & A380 4058-AQ-DA-A330000005 22 BILL OF MATERIAL LIST 4058-VW-LM-00OO000016
7 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A310, A320 & A370 4058-AQ-DA-A310000004 21 MATERIALS SPECIFICATION 4058-VW-SG-00OO000015 Grantham, Lincs, UK, NG31 7XS Tel. +44(0)1476 590666
6 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A210 & A220 4058-AQ-DA-A220000002 20 POWER SUPPLY REQUIREMENTS 4058-VW-LN-00OO000014 E-mail cpc@cathodic.co.uk Web www.cathodic.co.uk
5 UNDERGROUND LAYOUT CONSTRUCTION DRAWINGS-WBS A100, A101 & A102 4058-AQ-DA-A100000001 19 DETAILED DESIGN CALCULATION REPORT 4058-VW-CX-00OO000013
4 UNDERGROUND GENERAL DRAWINGS - KEY PLAN 4058-AQ-DX-A100000001 18 DESIGN PHILOSOPHY & SPECIFICATION 4058-VW-SG-00OO000012
3 COATING SPECIFICATION FOR BURIED SURFACES 4058-VW-SG-0000000005 17 PRE-DESIGN SITE SURVEY REPORT 4058-VW-RT-00OO000011
2 MATERIAL SPECIFICATION AND DATASHEET 4058-VW-SG-00OO000007-IS0 16 PRE-DESIGN SITE SURVEY SPECIFICATION 4058-VW-SG-00OO000010 VENDOR DOCUMENT NO.
1 CATHODIC PROTECTION SPECIFICATION 4058-VW-SG-00OO000006-ISA 15 LAYOUT OF HAZARDOUS AREA CLASSIFICATION COMPRESSOR 4058-SN-DH-00OO000004-IS0
42119-CLO-029
REF NO. DOCUMENT TITLE DOCUMENT NUMBER REF NO. DOCUMENT TITLE DOCUMENT NUMBER

You might also like