EWAQ005ADVP
EWAQ006ADVP
EWAQ007ADVP
EWYQ005ADVP
EWYQ006ADVP
EWYQ007ADVP
CE - DECLARATION-OF-CONFORMITY CE - DECLARACION-DE-CONFORMIDAD CE - DECLARAÇÃO-DE-CONFORMIDADE CE - ERKLÆRING OM-SAMSVAR CE - IZJAVA-O-USKLAĐENOSTI CE - IZJAVA O SKLADNOSTI CE - ATITIKTIES-DEKLARACIJA
CE - KONFORMITÄTSERKLÄRUNG CE - DICHIARAZIONE-DI-CONFORMITA СЕ - ЗАЯВЛЕНИЕ-О-СООТВЕТСТВИИ CE - ILMOITUS-YHDENMUKAISUUDESTA CE - MEGFELELŐSÉGI-NYILATKOZAT CE - VASTAVUSDEKLARATSIOON CE - ATBILSTĪBAS-DEKLARĀCIJA
CE - DECLARATION-DE-CONFORMITE CE - ¢H§ø™H ™YMMOPºø™H™ CE - OPFYLDELSESERKLÆRING CE - PROHLÁŠENÍ-O-SHODĚ CE - DEKLARACJA-ZGODNOŚCI CE - ДЕКЛАРАЦИЯ-ЗА-СЪОТВЕТСТВИЕ CE - VYHLÁSENIE-ZHODY
CE - CONFORMITEITSVERKLARING CE - FÖRSÄKRAN-OM-ÖVERENSTÄMMELSE CE - DECLARAŢIE-DE-CONFORMITATE CE - UYUMLULUK-BİLDİRİSİ
01 are in conformity with the following standard(s) or other normative document(s), provided that these are used in accordance with our 08 estão em conformidade com a(s) seguinte(s) norma(s) ou outro(s) documento(s) normativo(s), desde que estes sejam utilizados de 16 megfelelnek az alábbi szabvány(ok)nak vagy egyéb irányadó dokumentum(ok)nak, ha azokat előírás szerint használják:
instructions: acordo com as nossas instruções: 17 spełniają wymogi następujących norm i innych dokumentów normalizacyjnych, pod warunkiem że używane są zgodnie z naszymi
02 der/den folgenden Norm(en) oder einem anderen Normdokument oder -dokumenten entspricht/entsprechen, unter der Voraussetzung, 09 соответствуют следующим стандартам или другим нормативным документам, при условии их использования согласно нашим instrukcjami:
daß sie gemäß unseren Anweisungen eingesetzt werden: инструкциям: 18 sunt în conformitate cu următorul (următoarele) standard(e) sau alt(e) document(e) normativ(e), cu condiţia ca acestea să fie utilizate în
03 sont conformes à la/aux norme(s) ou autre(s) document(s) normatif(s), pour autant qu'ils soient utilisés conformément à nos instructions: 10 overholder følgende standard(er) eller andet/andre retningsgivende dokument(er), forudsat at disse anvendes i henhold til vore conformitate cu instrucţiunile noastre
04 conform de volgende norm(en) of één of meer andere bindende documenten zijn, op voorwaarde dat ze worden gebruikt overeenkomstig instrukser: 19 skladni z naslednjimi standardi in drugimi normativi, pod pogojem, da se uporabljajo v skladu z našimi navodili:
onze instructies: 11 respektive utrustning är utförd i överensstämmelse med och följer följande standard(er) eller andra normgivande dokument, under 20 on vastavuses järgmis(t)e standardi(te)ga või teiste normatiivsete dokumentidega, kui neid kasutatakse vastavalt meie juhenditele:
05 están en conformidad con la(s) siguiente(s) norma(s) u otro(s) documento(s) normativo(s), siempre que sean utilizados de acuerdo con förutsättning att användning sker i överensstämmelse med våra instruktioner: 21 съответстват на следните стандарти или други нормативни документи, при условие, че се използват съгласно нашите
nuestras instrucciones: 12 respektive utstyr er i overensstemmelse med følgende standard(er) eller andre normgivende dokument(er), under forutssetning av at инструкции:
06 sono conformi al(i) seguente(i) standard(s) o altro(i) documento(i) a carattere normativo, a patto che vengano usati in conformità alle disse brukes i henhold til våre instrukser: 22 atitinka žemiau nurodytus standartus ir (arba) kitus norminius dokumentus su sąlyga, kad yra naudojami pagal mūsų nurodymus:
nostre istruzioni: 13 vastaavat seuraavien standardien ja muiden ohjeellisten dokumenttien vaatimuksia edellyttäen, että niitä käytetään ohjeidemme 23 tad, ja lietoti atbilstoši ražotāja norādījumiem, atbilst sekojošiem standartiem un citiem normatīviem dokumentiem:
07 Â›Ó·È Û‡Ìʈӷ Ì ÙÔ(·) ·ÎfiÏÔ˘ıÔ(·) ÚfiÙ˘Ô(·) ‹ ¿ÏÏÔ ¤ÁÁÚ·ÊÔ(·) ηÓÔÓÈÛÌÒÓ, ˘fi ÙËÓ ÚÔ¸fiıÂÛË fiÙÈ ¯ÚËÛÈÌÔÔÈÔ‡ÓÙ·È mukaisesti: 24 sú v zhode s nasledovnou(ými) normou(ami) alebo iným(i) normatívnym(i) dokumentom(ami), za predpokladu, že sa používajú v súlade
Û‡Ìʈӷ Ì ÙȘ Ô‰ËÁ›Â˜ Ì·˜: 14 za předpokladu, že jsou využívány v souladu s našimi pokyny, odpovídají následujícím normám nebo normativním dokumentům: s našim návodom:
15 u skladu sa slijedećim standardom(ima) ili drugim normativnim dokumentom(ima), uz uvjet da se oni koriste u skladu s našim uputama: 25 ürünün, talimatlarımıza göre kullanılması koşuluyla aşağıdaki standartlar ve norm belirten belgelerle uyumludur:
EN60335-2-40,
01 following the provisions of: 10 under iagttagelse af bestemmelserne i: 19 ob upoštevanju določb: 01 Directives, as amended. 10 Direktiver, med senere ændringer. 19 Direktive z vsemi spremembami.
02 gemäß den Vorschriften der: 11 enligt villkoren i: 20 vastavalt nõuetele: 02 Direktiven, gemäß Änderung. 11 Direktiv, med företagna ändringar. 20 Direktiivid koos muudatustega.
03 conformément aux stipulations des: 12 gitt i henhold til bestemmelsene i: 21 следвайки клаузите на: Low Voltage 2006/95/EC 03 Directives, telles que modifiées. 12 Direktiver, med foretatte endringer. 21 Директиви, с техните изменения.
04 overeenkomstig de bepalingen van: 13 noudattaen määräyksiä: 22 laikantis nuostatų, pateikiamų: 04 Richtlijnen, zoals geamendeerd. 13 Direktiivejä, sellaisina kuin ne ovat muutettuina. 22 Direktyvose su papildymais.
05 siguiendo las disposiciones de: 14 za dodržení ustanovení předpisu: 23 ievērojot prasības, kas noteiktas: Machinery 2006/42/EC ** 05 Directivas, según lo enmendado. 14 v platném znění. 23 Direktīvās un to papildinājumos.
06 secondo le prescrizioni per: 15 prema odredbama: 24 održiavajúc ustanovenia: Electromagnetic Compatibility 2004/108/EC * 06 Direttive, come da modifica. 15 Smjernice, kako je izmijenjeno. 24 Smernice, v platnom znení.
07 Ì ًÚËÛË Ùˆv ‰È·Ù¿Íˆv Ùˆv: 16 követi a(z): 25 bunun koşullarına uygun olarak: 07 √‰ËÁÈÒv, fiˆ˜ ¤¯Ô˘Ó ÙÚÔÔÔÈËı›. 16 irányelv(ek) és módosításaik rendelkezéseit. 25 Değiştirilmiş halleriyle Yönetmelikler.
08 de acordo com o previsto em: 17 zgodnie z postanowieniami Dyrektyw: 08 Directivas, conforme alteração em. 17 z późniejszymi poprawkami.
09 в соответствии с положениями: 18 în urma prevederilor: 09 Директив со всеми поправками. 18 Directivelor, cu amendamentele respective.
01 Note * as set out in <A> and judged positively by <B> 06 Nota * delineato nel <A> e giudicato positivamente 11 Information * enligt <A> och godkänts av <B> enligt 16 Megjegyzés * a(z) <A> alapján, a(z) <B> igazolta a megfelelést, 21 Забележка * както е изложено в <A> и оценено
according to the Certificate <C>. da <B> secondo il Certificato <C>. Certifikatet <C>. a(z) <C> tanúsítvány szerint. положително от <B> съгласно
02 Hinweis * wie in der <A> aufgeführt und von <B> positiv 07 ™ËÌ›ˆÛË * fiˆ˜ ηıÔÚ›˙ÂÙ·È ÛÙÔ <A> Î·È ÎÚ›ÓÂÙ·È ıÂÙÈο 12 Merk * som det fremkommer i <A> og gjennom positiv 17 Uwaga * zgodnie z dokumentacją <A>, pozytywną opinią Cертификата <C>.
beurteilt gemäß Zertifikat <C>. ·fi ÙÔ <B> Û‡Ìʈӷ Ì ÙÔ ¶ÈÛÙÔÔÈËÙÈÎfi <C>. bedømmelse av <B> ifølge Sertifikat <C>. <B> i Świadectwem <C>. 22 Pastaba * kaip nustatyta <A> ir kaip teigiamai nuspręsta <B>
03 Remarque * tel que défini dans <A> et évalué positivement par 08 Nota * tal como estabelecido em <A> e com o parecer 13 Huom * jotka on esitetty asiakirjassa <A> ja jotka <B> on 18 Notă * aşa cum este stabilit în <A> şi apreciat pozitiv pagal Sertifikatą <C>.
<B> conformément au Certificat <C>. positivo de <B> de acordo com o Certificado <C>. hyväksynyt Sertifikaatin <C> mukaisesti. de <B> în conformitate cu Certificatul <C>. 23 Piezīmes * kā norādīts <A> un atbilstoši <B> pozitīvajam
04 Bemerk * zoals vermeld in <A> en positief beoordeeld door 09 Примечание * как указано в <A> и в соответствии с 14 Poznámka * jak bylo uvedeno v <A> a pozitivně zjištěno <B> v 19 Opomba * kot je določeno v <A> in odobreno s strani <B> v vērtējumam saskaņā ar sertifikātu <C>.
<B> overeenkomstig Certificaat <C>. положительным решением <B> согласно souladu s osvědčením <C>. skladu s certifikatom <C>. 24 Poznámka * ako bolo uvedené v <A> a pozitívne zistené <B> v <A> DAIKIN.TCF.025E4/10-2011
05 Nota * como se establece en <A> y es valorado Свидетельству <C>. 15 Napomena * kako je izloženo u <A> i pozitivno ocijenjeno od 20 Märkus * nagu on näidatud dokumendis <A> ja heaks súlade s osvedčením <C>. <B> DEKRA (NB0344)
positivamente por <B> de acuerdo con el 10 Bemærk * som anført i <A> og positivt vurderet af <B> i strane <B> prema Certifikatu <C>. kiidetud <B> järgi vastavalt sertifikaadile <C>. 25 Not * <A>‘da belirtildiği gibi ve <C> Sertifikasına
Certificado <C>. henhold til Certifikat <C>. göre <B> tarafından olumlu olarak <C> 2082543.0551-QUA/EMC
değerlendirildiği gibi.
01 ** Daikin Europe N.V. is authorised to compile the Technical Construction File. 07 ** ∏ Daikin Europe N.V. Â›Ó·È ÂÍÔ˘ÛÈÔ‰ÔÙË̤ÓË Ó· Û˘ÓÙ¿ÍÂÈ ÙÔÓ Δ¯ÓÈÎfi Ê¿ÎÂÏÔ Î·Ù·Û΢‹˜. 13 ** Daikin Europe N.V. on valtuutettu laatimaan Teknisen asiakirjan. 19 ** Daikin Europe N.V. je pooblaščen za sestavo datoteke s tehnično mapo.
02 ** Daikin Europe N.V. hat die Berechtigung die Technische Konstruktionsakte zusammenzustellen. 08 ** A Daikin Europe N.V. está autorizada a compilar a documentação técnica de fabrico. 14 ** Společnost Daikin Europe N.V. má oprávnění ke kompilaci souboru technické konstrukce. 20 ** Daikin Europe N.V. on volitatud koostama tehnilist dokumentatsiooni.
03 ** Daikin Europe N.V. est autorisé à compiler le Dossier de Construction Technique. 09 ** Компания Daikin Europe N.V. уполномочена составить Комплект технической документации. 15 ** Daikin Europe N.V. je ovlašten za izradu Datoteke o tehničkoj konstrukciji. 21 ** Daikin Europe N.V. е оторизирана да състави Акта за техническа конструкция.
04 ** Daikin Europe N.V. is bevoegd om het Technisch Constructiedossier samen te stellen. 10 ** Daikin Europe N.V. er autoriseret til at udarbejde de tekniske konstruktionsdata. 16 ** A Daikin Europe N.V. jogosult a műszaki konstrukciós dokumentáció összeállítására. 22 ** Daikin Europe N.V. yra įgaliota sudaryti šį techninės konstrukcijos failą.
05 ** Daikin Europe N.V. está autorizado a compilar el Archivo de Construcción Técnica. 11 ** Daikin Europe N.V. är bemyndigade att sammanställa den tekniska konstruktionsfilen. 17 ** Daikin Europe N.V. ma upoważnienie do zbierania i opracowywania dokumentacji konstrukcyjnej. 23 ** Daikin Europe N.V. ir autorizēts sastādīt tehnisko dokumentāciju.
06 ** Daikin Europe N.V. è autorizzata a redigere il File Tecnico di Costruzione. 12 ** Daikin Europe N.V. har tillatelse til å kompilere den Tekniske konstruksjonsfilen. 18 ** Daikin Europe N.V. este autorizat să compileze Dosarul tehnic de construcţie. 24 ** Spoločnosť Daikin Europe N.V. je oprávnená vytvoriť súbor technickej konštrukcie.
25 ** Daikin Europe N.V. Teknik Yapı Dosyasını derlemeye yetkilidir.
Jean-Pierre Beuselinck
Director
Ostend, 2nd of January 2012
3PW33163-8K
EWAQ005ADVP EWYQ005ADVP Packaged air-cooled water chillers and
EWAQ006ADVP EWYQ006ADVP
packaged reversible air to water heat pumps
Installation manual
EWAQ007ADVP EWYQ007ADVP
T
1 2 3 4 5 6
6 7 8 9
2x 1x 1x 1x
The digital controller (DC) is installed indoors and allows the user to
turn the unit (1) ON or OFF, to select between cooling and heating
mode (only in case of a heat pump model) and to set the water
temperature. When the unit is turned on, it will provide water at the
set temperature to the fan coil units (FCU1..3).
3 1 2
4.1. Opening of the unit
To have access to all main components for installation and servicing,
the top and front cover of the unit must be removed.
10
■ To open the top cover (1), loosen the 6 screws and lift the top
cover.
11a
■ To open the front cover (2), loosen the four screws and unhitch
the front cover.
6x 6
1 7
2 18
8 9 18 9
11b
9
9
5
4
13
12
4x
1 Switch box
The switch box contains connection terminals for the power
supply and digital controller, and the main electronic and
electrical parts of the unit.
■ To gain access to the switch box’ internals – e.g. to connect the
field wiring – the switch box service panel (3) can be removed. 2 Main isolator switch
Thereto, loosen the two screws and lift the switch box service The main isolator switch allows to cut off all electrical power to
panel. the unit.
3 Heat exchanger
Switch off the power supply before removing the
switch box service panel. 4 Water inlet connection (1” MBSP)
5 Water outlet connection (1” MBSP)
2x 6 Pump
The pump circulates the water in the water circuit.
7 Expansion vessel (6 litre)
The water in the water circuit expands with rising temperatures.
The expansion vessel stabilises the pressure changes with
3 changing water temperatures by giving free space to the
changing water volume.
8 Expansion vessel service point
The service point allows connection of a dry nitrogen cylinder to
adjust the expansion vessel pre-pressure if necessary.
9 Drain and fill valve (2x)
10 Air purge valve
Remaining air in the water circuit will be automatically removed
via the air purge valve.
11 Water temperature sensors
Two temperature sensors determine the water inlet temperature
(11a) and water outlet temperature (11b).
12 Digital controller cable intake
13 Power supply intake
14 OP10 heater tape (optional, not illustrated)
The heater tape is wrapped around the pipework and protects
the evaporator and water circuit in the unit from freezing at cold
outdoor temperatures.
The pressure relief valve prevents excessive water pressure in ■ Choose a place solid enough to bear the weight and vibration of
the water circuit (≥3 bar). the unit, where the operation noise will not be amplified.
■ This appliance is intended to be used by expert or trained users
in shops, in light industry and on farms, or for commercial and
4.4. Safety devices household use by lay persons.
18 Flow switch ■ Although the noise produced by the unit during operation is low,
The flow switch checks the flow in the water circuit and protects avoid installation near to places where even low noise levels can
the heat exchanger against freezing and the pump against be disturbing (e.g., bedroom windows, terraces).
damage. In case the minimum required flow is not achieved, the ■ Choose a location where the hot air discharged from the unit will
unit will be shut down. not cause a nuisance.
■ There must be sufficient space for air passage and no
4.5. Switch box components obstructions around the air intake and the air exhaust (see
"5.1.2. Installing near a wall or obstacle" on page 4).
19 Cable tie mountings ■ The equipment is not intended for use in a potentially explosive
The cable tie mountings allow to fix the field wiring with cable atmosphere.
ties to the switch box to ensure strain relief.
■ The site must be free from the possibility of flammable gas
20 Terminal block leakage in a nearby place.
The terminal block allows easy connection of field wiring. ■ Install the unit and power cords at least 3 m away from television
and radio sets. This is to prevent interference to images and
sounds.
■ In coastal areas or other places with salty atmosphere, corrosion
19 may shorten the life of the unit. Prevent direct exposure to winds
20 coming from the sea.
■ Since drain flows out of the unit, do not place anything under the
unit which must be kept away from moisture.
>100 >100
(*) (*) >350
>350
>350
≤1200
>50
(*) For future servicing, it is recommended to foresee a larger service
space than the minimum operating space of 100 mm at the suction side
of the unit.
Install the unit high enough off the ground 3 Prepare 4 sets of M8 or M10 foundation bolts, nuts and washers
to prevent burying in snow. each (field supply).
20
>100 3
360 330
5.5. Drain work
If drain work is necessary, follow the guidelines below.
■ Two drain outlets are provided in the bottom plate of unit, see
350
"5.1.4. Unit installation drawing" on page 5 (drain plug and drain
hose are field supply).
■ In cold areas, do not use a drain hose with the unit. Otherwise,
1 2 drain water may freeze and block the drain. In case the use of a
drain hose is unavoidable for one reason or another, it is
Service space recommended to install a heater tape in order to protect drain
1 Fixation holes from freezing.
2 Drain outlets (Ø18 mm)
3 Water inlet 5.6. Water pipework
4 Water outlet
5.6.1. Checking the water circuit
Indicated distances must be respected to ensure optimal operation of The units have a water inlet and water outlet for connection to a water
the unit. For ease of access at the moment of installation or servicing, circuit. This circuit must be provided by a licensed technician and
the unit may be pushed further away from walls or obstacles. must comply with all relevant European and national regulations.
5.2. Inspecting, handling and unpacking the unit The unit is only to be used in a closed water system.
Application in an open water circuit can lead to excessive
■ The unit is packed in a cardboard box fixed by straps. corrosion of the water piping.
■ At delivery, the unit should be checked and any damage should
Before continuing the installation of the unit, beware of the following
be reported immediately to the carrier claims agent.
points:
■ Check if all unit accessories (see "2. Accessories" on page 2)
■ Two shut-off valves are delivered with the unit. To facilitate
are enclosed.
service and maintenance, install one at the water inlet and one
■ Bring the unit as close as possible to its final installation position at the water outlet of the unit.
in its original package to prevent damage during transport. ■ Drain taps must be provided at all low points of the system to
■ After unpacking, the unit can be positioned correctly using the permit complete drainage of the circuit. Two drain valves are
handles provided at both ends of the unit. provided inside the unit.
■ Air vents must be provided at all high points of the system. The
vents should be located at points which are easily accessible for
servicing. An automatic air purge is provided inside the unit.
Check that this air purge valve is not tightened too much so that
automatic release of air in the water circuit remains possible.
■ Take care that the components installed in the field piping can
withstand the water pressure.
pre-pressure [bar]
EWAQ
How to connect the accessories delivered with the unit 2 Water filter
3 Pipe nipple male/male 1/2”
Make sure the water filter, manometer and pressure relief 4 Pressure relief valve
valve (delivered with the unit) are mounted between 5 Manometer
shut-off valve and water inlet. This part of the assembly 6 Shut-off valve
must be installed indoors.
7 Water outlet
■ According to the direction of the water flow, the water filter must
5.6.5. Protecting the water circuit against freezing
be positioned as shown in the figure.
Frost can damage the unit. For this reason, in colder climates the
water circuit must be protected by means of a heater tape or by
adding glycol to the water.
In case of heater tape
■ Provide sufficient space allowing easy access to clean the water 1 Check that the unit has the option heater tape installed.
filter and regular operation check of the pressure relief valve. (Connections of the factory mounted heater tape are made on
■ The pressure relief valve must be installed in accordance with terminals 4/5 inside the switch box).
relevant local and national regulations and must be positioned
as shown in the figure. For the heater tape to operate, power to the unit must
be provided and the main isolator switch must be on.
For this reason never disconnect power and never
turn off the main isolator switch for a long time during
cold periods!
■ If a discharge pipe is connected to the pressure relief valve it 2 Install a heater tape (field supply) on the outdoor field piping.
must be installed in a continuously downward direction and in a Power supply connections for this heater tape must be made on
frost-free environment. It must be left open to the atmosphere. terminals 4/5 inside the switch box provided this heater tape is of
a type that consumes not more than 200 W.
In case of glycol
Depending on the expected lowest outdoor temperature, make sure
the water system is filled with a weight concentration of glycol as
mentioned in the table below.
Minimum
outdoor temperature 0°C –5°C –10°C –15°C
Ethylene glycol 10% 15% 25% 35%
Propylene glycol 10% 15% 25% 35%
The outdoor and indoor part of the water circuit must be insulated to Non-accessible switch box
prevent condensation during cooling operation and reduction of the AC1, AC2................Connector
cooling and heating capacity. E1, E2.....................Connector
FU1.........................Fuse 30 A 250 V
FU2,FU3.................Fuse 3.15 A 250 V
5.9. Field wiring
HR1, HR2 ...............Connector
L .............................Live
■ All field wiring entering the unit shall be double
insulated (example: H07RN-F or H07V wire inside an L1R.........................Reactor
insulation sleeve). LED A .....................Pilot lamp
■ All field wiring and components must be installed by a M1C........................Compressor motor
licensed electrician and must comply with relevant M1F ........................Fan motor
European and national regulations. MRC/W...................Magnetic relay
■ The field wiring must be carried out in accordance MRM10,MRM20 .....Magnetic relay
with the wiring diagram supplied with the unit and the N.............................Neutral
instructions given below. PCB1,2 ...................Printed circuit board
■ Be sure to use a dedicated power supply. Never use a PM1 ........................Power module
power supply shared by another appliance. Q1L.........................Overload protector
■ Be sure to establish an earth. Do not earth the unit to R1T~R3T................Thermistor
a utility pipe, surge absorber, or telephone earth. S2~S102 ................Connector
Incomplete earth may cause electrical shock.
SA2.........................Surge arrester
■ Be sure to install an earth leakage circuit breaker. SHEET METAL.......Terminal strip fixed plate
This unit uses an inverter, which means that an earth
SW1........................Forced operation ON/OFF switch
leakage circuit breaker capable of handling high
harmonics needs to be used in order to prevent SW4........................Local setting switch
malfunctioning of the earth leakage circuit breaker U, V, W, X11A .........Connector
itself. V2,V3,V5,V6,V11 ...Varistor
■ Use an all-pole disconnection type breaker with a X1M, X2M...............Terminal strip
contact separation of at least 3 mm in-between all Y1E.........................Electronic expansion valve coil
poles. Y1R ........................Reversing solenoid valve coil
Z1C~Z4C................Ferrite core
Notes
...............Field wiring
..................Terminal strip
..........................Connector
■ The field wiring on the unit is to be made on the terminal block Note: only relevant field wiring is shown.
inside the switch box. To gain access to the terminal block,
remove the unit top cover and switch box service panel, see
"4.1. Opening of the unit" on page 3.
■ Foresee the field wiring cable length to be 600 mm longer than
strictly required.
This will facilitate future servicing by allowing the switch box to
be pulled up without having to disconnect cables.
Bundle the surplus of field wiring length and keep wires together
with cable ties as shown in the figure.
Keep in mind that the main switch must stay easily accessible
and that cables must be kept away from hot piping and sharp
edges.
Wiring specifications
H C
P2 P1 P2 P1
th sw
3
2 Fix the cable with cable ties to the cable tie mountings to ensure
strain relief.
4 5
1 Chiller unit NOTE ■ When a room thermostat is connected to the unit,
2 Rear part of the digital controller the heating and cooling schedule timers are never
3 Front part of the digital controller available. Other schedule timers are not affected.
4 Wired from the rear For more information on the schedule timers, refer
5 Wired from the top to the operation manual.
6 Notch the part for the wiring to pass through with nippers, etc. ■ When a room thermostat is connected to the unit,
Connect the terminals on top of the front part of the digital and the = button or o button is pressed, the
controller and the terminals inside the unit (P1 to 6, P2 to 7). centralised control indicator e will flash to
indicate that the room thermostat has priority and
NOTE ■ When wiring, run the wiring away from the controls on/off operation and change over
power supply wiring in order to avoid operation.
receiving electric noise (external noise).
■ Peel the shield for the part The following table summarizes the required configuration and
that has to pass through the thermostat wiring at the terminal block in the switch box. Pump
inside of the digital controller operation is listed in the third column. The three last columns indicate
case ( l ). whether the following functionality is available on the user interface
(UI) or handled by the thermostat (T):
4 Reattach the upper part of the digital controller. • space heating or cooling on/off (o)
• heating/cooling changeover (=)
Be careful not to pinch the wiring when attaching. • heating and cooling schedule timers (pr)
Pump
Thermostat Configuration operation o = pr
First begin fitting from the clips at the
bottom. No thermostat wiring: on when unit is UI UI UI
on
Terminal block
H C N
8 9 10
1
Thermostat with wiring: on when T T —
5.10.2. Remote ON/OFF and cooling/heating heating/cooling heating
switch Terminal block request or
possibilities cooling request
H C N
8 9 10 by room
Remote control of the unit can be done by a voltage free contact.
thermostat
Depending on the setting on the digital controller, the unit will operate
in cooling or in heating mode. H C
th
5.10.3. Connection of the thermostat cable
Connection of the thermostat cable depends on the application.
Remote wiring: on when T — —
See also "3. Typical application examples" on page 2. ON/OFF remote on
Terminal block
Thermostat requirements H C N
■ Contact voltage: 230 V. 8 9 10
sw
th = Thermostat contact
C= Cooling contact
H= Heating contact
N= neutral
1 Field wiring 5
Make sure that the field wiring has been carried out according to
ESP [mH2O]
the instructions and guidelines given under "5.9. Field wiring" on 4
page 8.
3
2 Internal wiring
Visually check the switch box on loose connections or damaged 2
electrical components.
1
3 Fixation
0
Check that the unit is properly fixed, to avoid abnormal noises 3 7 9 111213 15 17 19 21 23 25 27 29 31 33 35 37 39
and vibrations. [l/min]
4 Damaged equipment
Check the inside of the unit on damaged components or
squeezed pipes.
5 Refrigerant leak
Check the inside of the unit on refrigerant leakage. If there is a
refrigerant leak, contact your local Daikin dealer.
6 Power supply voltage
Check the power supply voltage on the local supply panel. The
voltage must correspond to the voltage on the identification label
of the unit.
7 Shut-off valves
Make sure that the shut-off valves are correctly installed and
fully open.
8 Water pressure
Make sure the unit is filled with water and that the water
pressure is approximately 2.0 bar.
To change one or more field settings, proceed as follows. On/off button o operable operable operable
Operation changeover
button
h/c operable operable operable
Inspection/test
z operable
1 Press the z button for a minimum of 5 seconds to enter FIELD operation button
SET MODE.
[1] Weather dependent set point (heat pump models only)
The $ icon (3) will be displayed. The current selected field
setting code is indicated ; (2), with the set value displayed to The weather dependent set point field settings define the parameters
the right : (1). for the weather dependent operation of the unit. When weather
dependent operation is active, the water temperature is determined
2 Press the bgi button to select the appropriate field setting automatically depending on the outdoor temperature: colder outdoor
first code. temperatures will result in warmer water and vice versa. During
3 Press the bgj button to select the appropriate field setting weather dependent operation, the user has the possibility to shift the
second code. target water temperature up or down by a maximum of 5°C. See the
operation manual for more details on weather dependent operation.
4 Press the pfi button and pfj button to change ■ [1-00] Low ambient temperature (Lo_A): low outdoor
the set value of the select field setting. temperature.
5 Save the new value by pressing the pr button. ■ [1-01] High ambient temperature (Hi_A): high outdoor
temperature.
6 Repeat step 2 through 4 to change other field settings as
■ [1-02] Set point at low ambient temperature (Lo_Ti): the
required.
target outgoing water temperature when the outdoor
7 When finished, press the z button to exit FIELD SET MODE. temperature equals or drops below the low ambient
temperature (Lo_A).
NOTE Changes made to a specific field setting are only Note that the Lo_Ti value should be higher than Hi_Ti, as for
stored when the pr button is pressed. Navigating to a colder outdoor temperatures (i.e. Lo_A) warmer water is
new field setting code or pressing the z button will required.
discard the change made.
2 Not available
3 Auto restart
4 Not available
5 Not available
6 Not available
7 Not available
8 Not available
Before handing over the unit to the user, read following Check for correct operation of the pressure relief valve by
recommendations: turning the red knob on the valve counter-clockwise:
■ When the complete installation and all necessary settings have ■ If you do not hear a clacking sound, contact your local Daikin
been carried out, close all unit covers. dealer.
■ The service panel of the switch box may only be opened by a ■ In case the water keeps running out of the unit, close both
licensed electrician for maintenance purposes. the water inlet and outlet shut-off valves first and then contact
your local Daikin dealer.
Before contacting your local Daikin dealer, read this chapter carefully, POSSIBLE CAUSES CORRECTIVE ACTION
it will save you time and money.
Dirt is blocking the water pressure Check for correct operation of the
When carrying out an inspection on the switch box of the relief valve outlet. pressure relief valve by turning the
red knob on the valve counter-
unit, always make sure that the power supply to the unit is clockwise:
switched off. • If you do not hear a clacking
sound, contact your local Daikin
When a safety device was activated find out why the safety device dealer.
was activated before resetting it. Under no circumstances safety • In case the water keeps running
devices may be bridged or changed to a value other than the factory out of the unit, close both the
setting. If the cause of the problem cannot be found, contact your water inlet and oulet shut-off
valves first and then contact your
local Daikin dealer.
local Daikin dealer.
Symptom 1: The unit is turned on (o LED is lit) but the unit is not
heating or cooling as expected
E7 Fan lock failure (fan is locked) Check if the fan is not obstructed
by dirt. If the fan is not
obstructed, contact your local
Daikin dealer.
8.1. General