Professional Documents
Culture Documents
Preface
Introduction
This guide and the relevant operating or service manual documentation for the equipment provide
full information on safe handling, commissioning and testing of this equipment.
Documentation for equipment ordered from NR is dispatched separately from manufactured goods
and may not be received at the same time. Therefore, this guide is provided to ensure that printed
information normally present on equipment is fully understood by the recipient.
Before carrying out any work on the equipment, the user should be familiar with the contents of
this manual, and read relevant chapter carefully.
This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
When electrical equipment is in operation, dangerous voltages will be present in certain parts of
the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.
Before working in the terminal strip area, the equipment must be isolated.
Proper and safe operation of the equipment depends on appropriate shipping and handling,
proper storage, installation and commissioning, and on careful operation, maintenance and
servicing. For this reason, only qualified personnel may work on or operate the equipment.
Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected;
Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;
Are trained in the care and use of safety apparatus in accordance with safety engineering
practices;
DANGER! means that death, severe personal injury and considerable equipment damage
will occur if safety precautions are disregarded.
WARNING! means that death, severe personal and considerable equipment damage
could occur if safety precautions are disregarded.
CAUTION! means that light personal injury or equipment damage may occur if safety
precautions are disregarded.
NOTICE! is particularly applies to damage to device and to resulting damage of the protected
equipment.
DANGER!
NEVER allow a open current transformer (CT) secondary circuit connected to this
device while the primary system is live. Open CT circuit will produce a dangerously high
voltage that cause death.
WARNING!
ONLY qualified personnel should work on or in the vicinity of this device. This personnel
MUST be familiar with all safety regulations and service procedures described in this
manual. During operating of electrical device, certain part of the device is under high
voltage. Severe personal injury and significant device damage could result from
improper behavior.
WARNING!
Do NOT touch the exposed terminals of this device while the power supply is on. The
generated high voltage causes death, injury, and device damage.
WARNING!
Thirty seconds is NECESSARY for discharging the voltage. Hazardous voltage can be
present in the DC circuit just after switching off the DC power supply.
CAUTION!
Earthing
Operating environment
ONLY use the device within the range of ambient environment and in an
environment free of abnormal vibration.
Ratings
Check the input ratings BEFORE applying AC voltage/current and power supply to
the device.
Do NOT attach or remove printed circuit board if the device is powered on.
External circuit
Check the supply voltage used when connecting the device output contacts to
external circuits, in order to prevent overheating.
Connection cable
NOTICE!
We reserve all rights to this document and to the information contained herein. Improper use in particular reproduction and dissemination
to third parties is strictly forbidden except where expressly authorized.
The information in this manual is carefully checked periodically, and necessary corrections will be included in future editions. If
nevertheless any errors are detected, suggestions for correction or improvement are greatly appreciated.
Documentation Structure
The manual provides a functional and technical description of this device and a comprehensive
set of instructions for the device’s use and application.
1 Introduction
Brief introduction of the application, functions and features.
2 Technical Data
Lists of the technical data such as electrical specifications, mechanical specifications, ambient
temperature and humidity range, communication port parameters, type tests and accuracy
limits.
3 Operation Theory
Comprehensive and detailed functional description.
4 Supervision
Automatic self-supervision function of device.
5 Management
Management function (measurement, recording, metering, etc.) of this device.
6 Hardware
Description of plug-in modules and definition of pins.
7 Settings
Setting lists including system settings, communication settings and etc.
9 Configurable Function
Brief introduction of configurable functions and configuration software.
10 Communication
Supported conmmunication protocol details.
11 Installation
Recommendation for unpacking, handling, inspection and storage with a guide to the
mechanical and electrical installation. A typical wiring connection is also indicated.
12 Commissioning
Commissioning recommendation for comprising checks on the calibration and functionality of
device.
13 Maintenance
General maintenance policy.
&
AND gate
≥1
OR gate
Comparator
Timer
t
Time (optional definite-time or inverse-time characteristic)
t
10ms 0ms
Timer [delay pickup (10ms), delay drop off (0ms), non-settable]
[XXX] 0ms
Timer (delay pickup, settable)
0ms [XXX]
Timer (delay drop off, settable)
[XXX] [XXX]
Timer (delay pickup, delay drop off, settable)
Example
Ia, Ib, Ic, I0 IL1, IL2, IL3, IN IR, IY, IB, IN
Ua, Ub, Uc VL1, VL2, VL3 UR, UY, UB
Uab, Ubc, Uca VL12, VL23, VL31 URY, UYB, UBR
U0, U1, U2 VN, V1, V2 UN, U1, U2
1 Introduction
Table of Contents
1 Introduction .......................................................................................1-a
1.1 Application ....................................................................................................... 1-1
1.2 Function ........................................................................................................... 1-2
1.2.1 Measurement & Control ....................................................................................................... 1-2
List of Figures
Figure 1.1-1 Typical application................................................................................................. 1-1
Date: 2017-08-17
1 Introduction
Date: 2017-08-17
1 Introduction
1.1 Application
The PCS-9705 Bay Control & Protection Unit is used for bay level controlling, monitoring and
protection in power grid. It is suitable for applications in Substation Automation System
(abbreviated as SAS) with distributed control IEDs.
The PCS-9705 can be applied into SAS via electrical and optical communication interfaces. It can
send/receive GOOSE (Generic Object Oriented Substation Event) message in station level
network for interlocking signal and in process level network for tripping or other binary signal. The
GOOSE and SV (Sampled Value) communication scheme supports both P2P mode and
networking mode.
Process bus
Control circuit
PCS-9785
PCS-9700 HMI System PCS-9799 Satellite-
(SCADA) Station Manager Synchronized Clock
Printer
PCS-9882
Ethernet Switch
BAY 1 BAY n
Bay Level
PCS-9882 PCS-9882
Ethernet Switch Ethernet Switch
PCS-9882
Ethernet Switch
10M/100M Ethernet IEC 61850-9-2
Process Level
(Optional)
PCS-9250 Series ECT/EVT Circuit Breaker PCS-9250 Series ECT/EVT Circuit Breaker
The PCS-9705 is designed for controlling, monitoring and protection of switchgears such as
circuit breaker, disconnector, and earthing switch. Additionally, it supports tap changer control for
transformer or shunt reactor.
The PCS-9705 can be used in single bus, double bus, 3/2 CB and bus couple arrangements.
Furthermore, breaker failure protection (50BF), pole discrepancy protection (62PD), phase
overcurrent protection (50/51P), earth fault protection (50/51G), frequency protection (81), closing
synchronism check (25) and auto-reclosure (79) functions are integrated.
Date: 2017-08-17
1 Introduction
1.2 Function
1.2.1 Measurement & Control
AC analog input
DC analog input
GOOSE tripping
1.2.3 Monitoring
Switch status supervision
Conventional
PPS (RS-485): Pulse per second (PPS) via RS-485 differential level
Date: 2017-08-17
1 Introduction
PPM (DIN): Pulse per minute (PPM) via the optical coupler
PPS (DIN): Pulse per second (PPS) via the optical coupler
SAS
Advanced
PPS (Fiber) PPS: Pulse per second (PPS) via optical-fibre interface
NoTimeSyn
1.2.5 Communication
Ethernet ports conform to IEC 61850-8-1 and NR privat 103 protocols over TCP/IP
1.3 Feature
PCS-9705 adopts a fully closed chassis with a complete panel. Completely isolation for
electronic and electrical system is provided.
Back plug-in module structure is adopted. Electrical and electronic circuits are strictly
separated to enhance EMC immunity performance.
PCS-9705 adopts NR's new UAPC hardware platform, 16 bits parallel A/D converter, graphic
dot matrix LCD, and real time multi-task operating system for industrial purpose so as to
realize the high-capacity, high-precision, fast and real-time information processing. With the
high-precision parallel A/D converter, synchronization sampling can be conducted for all the
AC signals to ensure the accuracy of analog quantity measurement.
Software and hardware clock synchronization are both adopted with 1ms timing accuracy to
ensure the resolution of Sequence Of Events (abbreviated as SOE).
Large scale LCD providing graph and text makes a convenient humain-machine interaction.
Powerful PC tool software can fulfill function configuration, setting modification and waveform
analysis.
Date: 2017-08-17
1 Introduction
Date: 2017-08-17
2 Technical Data
2 Technical Data
Table of Contents
2 Technical Data ...................................................................................2-a
2.1 Electrical Specification ................................................................................... 2-1
2.1.1 AC Current Input .................................................................................................................. 2-1
Date: 2017-08-17
2 Technical Data
Date: 2017-08-17
2 Technical Data
Date: 2017-08-17
2 Technical Data
Date: 2017-08-17
2 Technical Data
Date: 2017-08-17
2 Technical Data
Date: 2017-08-17
2 Technical Data
2.6 Certifications
ISO9001:2008
ISO14001:2004
Date: 2017-08-17
2 Technical Data
OHSAS18001:2007
ISO10012:2003
CMMI L5
Date: 2017-08-17
2 Technical Data
Date: 2017-08-17
2 Technical Data
Date: 2017-08-17
2 Technical Data
2.9.9 Auto-Reclosing
Phase difference setting range 0~89 (Deg)
Accuracy 2.0Deg
Voltage difference setting range 0.02Un~0.8Un (V)
Accuracy Max(0.01Un, 2.5%)
Frequency difference setting range 0.02~1 (Hz)
Accuracy 0.01Hz
Operating time of synchronism check ≤1%×Setting+20ms
Operating time of energizing check ≤1%×Setting+20ms
Operating time of auto-reclosing ≤1%×Setting+20ms
Date: 2017-08-17
2 Technical Data
Date: 2017-08-17
3 Operation Theory
3 Operation Theory
Table of Contents
3 Operation Theory ..............................................................................3-a
3.1 AC Analog Input .............................................................................................. 3-1
3.2 DC Analog Input .............................................................................................. 3-1
3.3 Binary Input ..................................................................................................... 3-1
3.4 Binary Output .................................................................................................. 3-2
3.5 Tap Changer Control ....................................................................................... 3-3
3.6 Interlocking Logic Output ............................................................................... 3-3
3.7 Synchronism Check for Manual Closing ....................................................... 3-4
3.8 Clock Management .......................................................................................... 3-6
3.9 Circuit Breaker Wear Statistic ........................................................................ 3-6
3.9.1 Function Description ............................................................................................................ 3-6
Date: 2017-08-17
3 Operation Theory
Date: 2017-08-17
3 Operation Theory
Date: 2017-08-17
3 Operation Theory
List of Figures
Figure 3.3-1 Debouncing technique .......................................................................................... 3-2
Figure 3.7-1 Relationship between reference voltage and synchronous voltage ............... 3-4
Figure 3.7-3 Dead check logic diagram (manual closing) ...................................................... 3-6
Figure 3.11-2 Tripping & closing circuit supervision logic diagram ................................... 3-11
Date: 2017-08-17
3 Operation Theory
Figure 3.15-1 Logic diagram of earth fault protection (stage 1) .......................................... 3-35
Figure 3.15-2 Logic diagram of earth fault protection (stage x) .......................................... 3-36
Figure 3.19-1 Relationship between reference voltage and synchronism voltage............ 3-54
Figure 3.19-2 Voltage connection 1 for single busbar arrangement ................................... 3-56
Figure 3.19-3 Voltage connection 2 for single busbar arrangement ................................... 3-56
Figure 3.19-4 Voltage connection for double busbars arrangement ................................... 3-57
Figure 3.19-5 Voltage selection for double busbars arrangement ...................................... 3-57
Figure 3.19-6 Voltage connection for one and a half breakers arrangement ..................... 3-58
Figure 3.19-7 Voltage selection for bus CB of one and a half breakers arrangement....... 3-59
Figure 3.19-8 Voltage selection for tie CB of one and a half breakers arrangement ......... 3-60
Figure 3.19-9 Reference voltage circuit failure supervision logic diagram (auto-reclosure)
............................................................................................................................................. 3-61
Figure 3.19-14 Dead charge check logic diagram (auto-reclosure) .................................... 3-66
Date: 2017-08-17
3 Operation Theory
Figure 3.20-9 Extra time delay and blocking logic of AR ..................................................... 3-78
Figure 3.22-3 VT circuit supervision logic diagram for measurement ................................ 3-92
Figure 3.23-2 CT circuit supervision logic diagram for measurement ............................... 3-93
List of Tables
Table 3.10-1 I/O signals of frequency calculation function .................................................... 3-8
Date: 2017-08-17
3 Operation Theory
Date: 2017-08-17
3 Operation Theory
Date: 2017-08-17
3 Operation Theory
N
U 1 U 2 ( n)
N
n 1
N
I 1 I 2 ( n)
N
n 1
1 N
P [U ( n) I ( n) U ( n) I ( n) U ( n) I ( n)]
N n 1 a a b b c c
1 N
Q [U ( n) I ( n 3 N ) U ( n) I ( n 3 N ) U ( n) I ( n 3 N )]
N n 1 a a 4 b b 4 c c 4
Cos P
P Q2
2
The sampling rate of the measurement is 500 SPS (sample-per-second). After algorithm and
digital RC filtering, the measurement can achieve the high accuracy 0.1%.
Besides observing from the LCD of device, user can also use SAS or the auxiliary software
PCS-Explorer to supervise the measurement via communication protocol.
NOTICE!
Date: 2017-08-17
3 Operation Theory
After the filter circuit and debouncing algorithm processing, external interference can be filtered
effectively. As shown in the following figure, a well-designed debouncing technique is adopted in
this device. Binary input state change within "Debouncing time" (t0-t1 can be set 0~30s) will be
ignored, in order to ensure the accuracy of the signal status. Once there is a confirmation of
change status of signal (start from t1), a SOE record will be noted in the device.
1
Validate the binary
input state change &
write it into SOE
record
Debouncing
time Time
t0 t1
To ensure more security of this function, each binary output consists of power relay, fault detector
relay and output relay in series. An error of one or two relays will not cause the undesired output,
so as to enhance the dependability of binary output. Furthermore, each execution is controlled by
two CPU chips and the circuit to block control is also available to prevent output by mistake during
breakdown of hardware.
The control output function, which is based on the principle "Select Before Operate (abbreviated
as SBO)", can be performed from device LCD (local mode) or SCADA (remote mode).
1. Send the selection command from device LCD (local mode), or SCADA (remote mode);
2. After logic judgment function, the device returns "selection success" or "fail reason";
3. Send the execution command from device LCD (local mode), or SCADA (remote mode) if the
result "selection success" is received;
4. After logic judgment function, the device does or cancels the execution and returns
corresponding "execution success" or "fail reason";
Synchronism check function is available along with the control output function during a bay
combination to power grid.
Date: 2017-08-17
3 Operation Theory
Interlocking control function is also available and configurable logically to accomplish different
switching scheme.
If only one tap changer is required, manually operated tap points are usually made on the high
voltage (primary) or lower current winding of the transformer to minimize the current handling
requirements of the contacts. However, a transformer may include a tap changer on each winding
if there are advantages to do so. For example, in power distribution networks, a large step-down
transformer may have an off-load tap changer on the primary winding and an on-load automatic
tap changer on the secondary winding or windings. The high voltage tap is set to match long-term
system profile on the high voltage network (typically supply voltage averages) and is rarely
changed. The low voltage tap may be requested to change positions multiple times each day,
without interrupting the power delivery, to follow loading conditions on the low-voltage (secondary
winding) network.
The on-load design is also called on circuit tap changer or On Load Tap Changer (OLTC). For
many power transformer applications, a supply interruption during a tap change is unacceptable,
and the transformer is often fitted with a more expensive and complex OLTC mechanism
electronic.
The control and supervision of OLTC is treated as a special kind of binary output in this device.
The difference with an ordinary one is that, during a tap changer control process, if "running tap"
occurs, the tap position will be out of control (steps up or down continuously). An output contact
"BO_EmergStopTP" is then provided to issue an emergency stop command for this situation.
The interlocking logic function is enabled by setting the parameter [CSWI**.En_Opn_Blk] and
[CSWI**.En_Cls_Blk]. When executing a switching output, if the interlocking logical criterions are
met, besides the internal software interlock, this device also provides hardware interlock with the
help of PLC module (normally open contact output controlled by the result of interlocking logical
calculation).
Date: 2017-08-17
3 Operation Theory
This device supports synchronism check for manual closing (remote and local). Several check
modes are available, including no-check mode, synchro-check mode and dead check mode.
NOTICE!
Please refer to "25.HMI_Mode" in the chapter 7 for more details about the coordination
between the logic links and the selection of remote/local control mode.
No-Check Logic
All the logic links are disabled (i.e. "0"), and a closing command will be sent out without any
block from the synchronism check logic.
Synchro-Check Logic
The comparative relationship between the reference voltage and the incoming voltage for
synchro-check is as follow.
UL
UB
UL Line voltage
UB Bus voltage
This figure shows the characteristics of synchro-check element used for CB closing if both
line and busbar are live. The element operates if the voltage difference, frequency difference,
Date: 2017-08-17
3 Operation Theory
slip frequency difference and phase angle difference are all within their setting ranges.
[25.U_LiveChk] ≤ UB
[25.U_LiveChk] ≤ UL
|f(UB)-f(UL)| ≤ [25.f_Diff_SynChk]
df/dt ≤ [25.df/dt_SynChk]
∆δ ≤ [25.phi_Comp_Diff]
NOTICE!
This logic checks only the voltages for synchronism. Several options are supported, please
refer to "Syn Settings" in the chapter 7 for more details about these modes.
The device will calculate the measured bus voltage and line voltage at both sides of the
circuit breaker and compare them with the settings [25.U_LiveChk] and [25.U_DeadChk]. If
the voltage is higher than [25.U_LiveChk], the bus/line is regarded as live. If the voltage is
lower than [25.U_DeadChk], the bus/line is regarded as dead.
Date: 2017-08-17
3 Operation Theory
The MON module in this device has an inner real-time high-precision clock. This clock can
last for one month even if the device is switched off.
Clock Synchronization
The circuit breaker wear is caused by breaking current when a CB is tripped by a protection
operation or a control command.
During a CB tripping process, when the BCU detects a CB position change from close to open,
the CB wear statistic process starts. After a tripping execution, within 10s, if the CB open position
is detected, the CB wear statistic process will be effective. During a CB wear statistic process, the
maximal breaking current is recorded to be compared with the current in the CB wear table, which
is provided by the CB manufacturer. Then, BCU can calculate the CB wear status.
Date: 2017-08-17
3 Operation Theory
CBWear
CBWear.Ia CBWear.N_Trp
CBWear.Ib CBWear.Alm
CBWear.Ic CBWear.Stat
52a
52b
Protection device provide frequency tracing function, which can improve the accuracy of
protection algorithm and the performance of protection devices. For the power system using 50Hz
or 60Hz as reference frequency, the frequency tracing function can be disabled if the fluctuation of
the frequency range is not great. For the power system that the fluctuation of the frequency range
is great, the frequency tracing function can be enabled to improve protection performance.
Frequency tracing module adopts the positive-sequence voltage which derived from protection
used voltage as the calculation reference, the positive-sequence voltage can be calculated as
following:
Date: 2017-08-17
3 Operation Theory
When no VT is connected to the protection device, the frequency tracing function is disabled
automatically, then the protection device calculates protection algorithm using the system
reference frequency. When the protection device detects a fault happening to the power system or
the voltage is smaller than 0.15Un, the frequency tracing function is disabled.
This module, which combines all above cases, outputs system frequency to the various protection
functions.
FreqCal
FreqTrack f
fn Alm_Freq
3.10.5 Logic
SIG U3P
fn Freqence
SIG f
calulation
SIG FreqTrace
Date: 2017-08-17
3 Operation Theory
In order to prevent that wrong status of CB position is input into the device via binary input,
appropriate monitor method is used to check the rationality of the binary input. When the binary
input of CB open position is detected but there is current detected in the line, the status of CB
position will be thought as incorrect and an alarm [Alm_52b] will be issued.
Together with the status of circuit breaker and the information of external circuit, this function can
be used to supervise control circuit of circuit breaker.
CB Position Supervision
52b_PhA Alm_52b
52b_PhB
52b_PhC
CB Position Supervision
52b Alm_52b
Date: 2017-08-17
3 Operation Theory
TCCS
52a TCCS.Alm
52b
TCCS.Input
TCCS will be disabled automatically when it is used for phase-segregated circuit breaker.
NOTICE!
The signal [52a] only take effect in the tripping/closing circuit supervision and not affect
any protection function. Only if tripping/closing circuit supervision is configured, this
signal needs to be connected to the device.
Date: 2017-08-17
3 Operation Theory
3.11.5 Logic
BI [52b_PhA] >=1
&
&
BI [52b_PhB] >=1
& &
&
SIG Ia>I_Line
>=1
& >=1 10s 10s Alm_52b
SIG Ib>I_Line
&
SIG Ic>I_Line
BI [52a] >=1
>=1
BI [52b] [TCCS.t_DPU] [TCCS.t_DDO] TCCS.Alm
BI [TCCS.Input]
I_Line is the threshold value used to determine whether line is on-load or no-load. Its default value
is 0.06In.
Date: 2017-08-17
3 Operation Theory
>=1
SET
SIG Trp A S Q & Pole A open
50ms 0ms
SIG FD.Pkp R CLR Q
SIG Ia<I_Line
>=1
SET
SIG Trp B S Q & Pole B open
50ms 0ms
R CLR Q
SIG Ib<I_Line
>=1
SET
SIG Trp C S Q & Pole C open
50ms 0ms
R CLR Q
SIG Ic<I_Line
Date: 2017-08-17
3 Operation Theory
1. Fault detector based on DPFC current: DPFC current is greater than the setting value
2. Fault detector based on residual current: Residual current is greater than the setting value
4. Fault detector based on phase current: Phase current is greater than the setting value
5. Fault detector based on voltage: Phase voltage or phase-to-phase voltage is greater than the
setting value
6. Fault detector based on circuit breaker position: Circuit breaker position discrepancy
If any of the above conditions is complied, FD will operate to activate the output circuit providing
DC power supply to the output relays, then all protection functions are permitted to operate when
FD operate. The fault detector based on DPFC current and the fault detector based on residual
current are always enabled.
DPFC phase-to-phase current is obtained by subtracting the phase-to-phase current from that of
a cycle before.
ΔI = I(k)-I(k-24)
Where:
I(k-24) is the value of a sampling point before a cycle, 24 is the sampling points in one cycle.
200
100
-100
-200
0 20 40 60 80 100 120
Original Current
100
50
-50
-100
0 20 40 60 80 100 120
DPFC current
From above figures, it is concluded that DPFC can reflect the sudden change of current at the
initial stage of a fault and has a perfect performance of fault detection.
It is used to determine whether this pickup condition is met according to Equation 3.12-1.
Date: 2017-08-17
3 Operation Theory
For multi-phase short-circuit fault, the DPFC phase-to-phase current has high sensitivity to ensure
the pickup of protection device. For usual single phase to earth fault, it also has sufficient
sensitivity to pick up except the earth fault with very large fault resistance. Under this condition the
DPFC current is relative small, however, residual current is also used to judge pickup condition
(pickup condition 2).
This element adopts adaptive floating threshold varied with the change of load current
continuously. The change of load current is small and steadily under normal or power swing
condition, the adaptive floating threshold with the ΔISet is higher than the change of current under
these conditions and hence maintains the element stability.
Where:
ΔIΦΦMAX: The maximum half-wave integration value of phase-to-phase current (ΦΦ=AB, BC, CA)
The coefficient "1.25" is an empirical value which ensures the threshold always higher than the
unbalance output value of the system.
If operating condition is met, the fault detector based on DPFC current will operate to provide DC
power supply for output relays, the pickup signal will maintain 7s after the fault detector based on
DPFC current drops off.
3.12.2.2 Fault Detector Based on Residual Current (pickup condition 2)
The operation condition will be met when 3I0 is greater than the setting [FD.ROC.3I0_Set]. The
fault detector based on residual current is always in service.
Where:
3I0: residual current calculates from the vector sum of Ia, Ib and Ic
When the fault detector based on residual current operates and lasts for longer than 10 seconds,
an alarm [Alm_Pkp_I0] will be issued.
If operation condition is met, the fault detector based on residual current will operate to provide
DC power supply for output relay, and the pickup signal will maintain 7s after the fault detector
based on residual current drops off.
The operation condition will be met when negative-sequence current (I2) is greater than the
setting [FD.NOC.I2_Set]. It can be enabled or disabled by the logic setting [FD.NOC.En].
If operation condition is met, the fault detector based on negative-sequence current will operate to
provide DC power supply for output relay, and the pickup signal will maintain 7s after the fault
detector based on negative-sequence current drops off.
Date: 2017-08-17
3 Operation Theory
The fault detector based on phase current will operate to provide DC power supply for output relay
when phase overcurrent protection is enabled and meets the operation condition, and the pickup
signal will maintain 500ms after the fault detector based on phase current drops off.
This fault detector based on voltage includes the fault detectors of overvoltage protection, under
voltage protection and frequency protection. The fault detector based on voltage will operate to
provide DC power supply for output relay when corresponding voltage element is enabled and
meets the operation condition, and the pickup signal will maintain 500ms after the fault detector
based on voltage drops off.
3.12.2.6 Fault Detector Based on Circuit Breaker Position
When pole discrepancy protection is enabled, i.e. the logic setting [62PD.En] is set as "1", and if
three phases of circuit breaker are not in the same status, the fault detector based on circuit
breaker position will operate to provide DC power supply for output relays, and the pickup signal
will maintain 500ms after the the fault detector based on circuit breaker position drops off.
Under the normal state, the protection device will perform the following tasks:
3. Hardware self-check
Once the protection fault detector element in protection calculation DSP picks up, the protection
device will switch to fault calculation program, for example the calculation of phase overcurrent
protection, and to determine logic. If the fault is within the protected zone, the protection device
will send tripping command.
Date: 2017-08-17
3 Operation Theory
Main program
Sampling program
No Yes
Pickup?
The protection FD pickup conditions are the same as the FD in fault detector DSP as shown below.
The operation criteria for the conditions are also the same as that in fault detector DSP. Please
refer to section 3.12.2 for details.
FD
FD.Pkp
FD.DPFC.Pkp
FD.ROC.Pkp
FD.NOC.Pkp
Date: 2017-08-17
3 Operation Theory
3.12.6 Logic
Calculate negative-
I2>[FD.NOC.I2_Set] &
sequence current: I2
FD.NOC.Pkp
EN FD.NOC.En
Overcurrent protection is widely used in the power system as backup protection, but in some
cases, the direction of current is necessary to aid to complete the selective tripping. As shown
below:
L M N
EM C D A B EN
Fault
When line LM has an earth fault, the fault currents flowing through the relay A and the relay D are
of similar magnitude in most cases. It is desirable that the fault is isolated from the power system
by tripping the circuit breaker C and circuit breaker D. Hence, the overcurrent protection of relay A
and relay D require to associate with current direction to fulfill selective tripping.
Directional earth fault protection has a time delay due to coordinate with that of downstream so it
cannot clear the fault quickly. Pilot directional earth-fault protection, which is fulfilled by directional
earth fault element on both ends, it can maintain fast operation and achieve high sensitivity to
detect high resistance fault.
Date: 2017-08-17
3 Operation Theory
The direction of phase current and phase-to-phase current equips with an under-voltage direction
function to ensure that phase or phase-to-phase overcurrent protection has explicit directionality
when the polarized voltage is too low for close up fault.
The direction of zero-sequence current and negative-sequence current direction equips with an
impedance compensation function to ensure that zero-sequence or negative-sequence
overcurrent protection has explicit directionality when the zero-sequence voltage or the
negative-sequence voltage is too low.
By setting the characteristic angle [RCA_OC] to determine the most sensitive forward angle of
phase current and phase-to-phase current, power value is calculated using phase current with
phase polarized voltage or phase-to-phase current with phase-to-phase polarized voltage to
determine the direction of phase current or phase-to-phase current respectively in forward
direction or reverse direction. When the power value is zero, neither forward direction nor reverse
direction is considered. As shown below:
jX
U
φ
θ I
R
O
Forward direction
Reverse direction
Where:
P=U×[I×COS(θ-φ)]
Date: 2017-08-17
3 Operation Theory
From above diagram can be seen, when θ=φ, P reaches to the maximum value. It is considered
as the most sensitive forward direction. Hence, φ is called as sensitivity angle of phase
overcurrent protection.
In the event of asymmetrical fault, because phase or phase-to-phase voltage may decrease to
very low voltage whereas positive-sequence voltage does not, the polarized voltage of phase or
phase-to-phase current direction uses positive-sequence voltage to avoid wrong direction due to
too low polarized voltage. Therefore, using positive-sequence voltage as polarized voltage can
ensure that the direction determination has no dead zone for asymmetrical fault. For symmetric
fault, if positive-sequence voltage decreases to 15%Un, the device uses memorized
positive-sequence voltage as polarized voltage, the memorized positive-sequence voltage is 1.5
cycles pre-fault positive-sequence voltage.
When using normal polarized voltage to calculate phase and phase-to-phase current direction,
there are total twelve direction determination algorithm including forward direction and reverse
direction.
When the symmetrical fault occurs on a power system, positive-sequence voltage may reduce to
less than 0.15Un, the device will switch to phase or phase-to-phase current direction for
under-voltage condition. The 1.5 cycle pre-fault positive-sequence voltage is used as polarized
voltage with reverse threshold to ensure stable direction decision when three-phase voltage goes
to approximately zero due to close up fault.
At first, the threshold is forward offset before direction is determined, and the threshold will be
reversed offset after direction is determined.
Date: 2017-08-17
3 Operation Theory
By setting the characteristic angle [RCA_ROC] and [RCA_NegOC] to determine the most
sensitive forward angle of zero-sequence current and negative-sequence current, power value is
calculated using zero-sequence current with zero-sequence voltage or negative-sequence current
with negative-sequence voltage to determine the direction of zero-sequence current and
negative-sequence current respectively in forward direction or reverse direction.
When the power value is between 0 and -0.1In, neither forward direction nor reverse direction is
considered.
jX 3U0
θ-180°
-3I0
φ
R
O
3I0
θ Reverse direction
Forward direction
Where:
P=U×[I×COS(θ-φ)]
Calculating the power value using zero-sequence current (3I0) and zero-sequence voltage (3U0)
Date: 2017-08-17
3 Operation Theory
The zero-sequence current and the zero-sequence voltage can be gained by calculation
Calculating the power value using negative-sequence current (3I2) and negative-sequence
voltage (3U2) to determine the direction of negative-sequence current
The negative-sequence current and the negative-sequence voltage can be gained by calculation
is the setting [Z0_Comp], which cannot exceed the total zero-sequence impedance of
is the setting [Z2_Comp], which cannot exceed the total negative-sequence impedance
Date: 2017-08-17
3 Operation Theory
DIR
FwdDir_ROC
RevDir_ROC
FwdDir_NegOC
RevDir_NegOC
FwdDir_A
FwdDir_B
FwdDir_C
RevDir_A
RevDir_B
RevDir_C
FwdDir_AB
FwdDir_BC
FwdDir_CA
RevDir_AB
RevDir_BC
RevDir_CA
Date: 2017-08-17
3 Operation Theory
3.13.5 Settings
Table 3.13-3 Settings of current direction
1. Four-stage phase overcurrent protection with independent logic, current and time delay
settings.
3. Direction control element can be selected to control each stage phase overcurrent protection
with three options: no direction, forward direction and reverse direction.
4. Second harmonic can be selected to block each stage of phase overcurrent protection.
3.14.2.1 Overview
Date: 2017-08-17
3 Operation Theory
2. Direction control element: one direction control element shared by all overcurrent elements,
and each overcurrent element can individually select protection direction. When phase
overcurrent protection is controlled by direction control element, negative-sequence current
direction element is also effective to ensure correct operation, especially for phase-to-phase
fault.
3. Harmonic blocking element: one harmonic blocking element shared by all overcurrent
elements and each phase overcurrent element can individually enable the output signal from
harmonic element as a blocking input.
Where:
In order to prevent phase current direction element from overreaching operation characteristic for
phase-to-phase fault, negative-sequence current direction element is also used as auxiliary
direction criterion of phase overcurrent protection for asymmetric fault. Please refer to Section
3.13 for details.
When the percentage of second harmonic component to fundamental component of any phase
current is greater than the setting [50/51P.K_Hm2], harmonic blocking element operates to block
stage x overcurrent element if corresponding logic setting [50/51Px.En_Hm2_Blk] enabled.
Operation criterion:
Where:
Date: 2017-08-17
3 Operation Theory
If fundamental component of any phase current is lower than the minimum operating current
(0.1In), then harmonic calculation is not carried out and harmonic blocking element does not
operate.
Equation 3.14-3
Where:
α is a constant.
K is a constant.
C is a constant.
The user can select the operating characteristic from various inverse-time characteristic curves by
setting [50/51Px.Opt_Curve], and parameters of available characteristics for selection are shown
in the following table.
If all available curves do not comply with user application, user may set [50/51Px.Opt_Curve] as
Date: 2017-08-17
3 Operation Theory
“UserDefine” to customize the inverse-time curve characteristic with constants α, K and C. (only
stage 1)
When inverse-time characteristic is selected, if calculated operating time is less than setting
[50/51Px.tmin], then the operating time of the protection changes to the value of setting
[50/51Px.tmin] automatically.
Define-time or inverse-time phase overcurrent protection drops off instantaneously after fault
current disappears.
50/51Px
50/51Px.En1 50/51Px.On
50/51Px.En2 50/51Px.StA
50/51Px.Blk 50/51Px.StB
50/51Px.StC
50/51Px.St
50/51Px.Op
Date: 2017-08-17
3 Operation Theory
3.14.5 Logic
SET Ic>[50/51Px.I_Set]
&
SET [50/51Px.Opt_Dir]=Foward & 50/51Px.StB
Timer
EN [50/51P1.En_VTS_Blk] t
50/51Px.Op
t
SIG I3P 2nd Hm Detect & &
SET [50/51Px.En_Hm2_Blk]
EN [50/51Px.En]
&
SIG 50/51Px.En1 &
50/51Px.On
SIG 50/51Px.En2
&
SIG 50/51Px.Blk
SIG FD.Pkp
x=1, 2, 3, 4
3.14.6 Settings
Table 3.14-3 Settings of phase overcurrent protection
Date: 2017-08-17
3 Operation Theory
Date: 2017-08-17
3 Operation Theory
Date: 2017-08-17
3 Operation Theory
Date: 2017-08-17
3 Operation Theory
Date: 2017-08-17
3 Operation Theory
During normal operation of power system, there is trace residual current, whereas a fault current
flows to earth will result in greater residual current. Therefore, residual current is adopted for the
calculation of earth fault protection.
In order to improve the selectivity of earth fault protection in power grid with multiple power
sources, directional element can be selected to control earth fault protection. For application on
line-transformer unit, second harmonic also can be selected to block earth fault protection to avoid
the effect of sympathetic current on the protection.
1. Four-stage earth fault protection with independent logic, current and time delay settings.
3. Directional element can be selected to control each stage of earth fault protection with three
options: no direction, forward direction and reverse direction.
4. Second harmonic can be selected to block each stage of earth fault protection.
5. Stage 2, 3, 4 of earth fault protection can enable short time delay to improve operation speed.
3.15.2.1 Overview
1. Overcurrent element: each stage equipped with one independent overcurrent element.
2. Directional control element: one direction control element shared by all overcurrent elements,
and each overcurrent element can individually select protection direction.
3. Harmonic blocking element: one harmonic blocking element shared by all overcurrent
elements and each overcurrent element can individually enable the output signal of harmonic
blocking element as a blocking input.
The operation criterion for each stage of earth fault protection is:
Where:
Date: 2017-08-17
3 Operation Theory
In order to prevent effects of inrush current on earth fault protection, harmonic blocking function
can be selected for each stage of earth fault element by configuring logic setting
[50/51Gx.En_Hm2_Blk] (x=1, 2, 3 or 4).
Operation criterion:
Where:
If fundamental component of residual current is lower than the minimum operating current (0.1In)
then harmonic calculation is not carried out and harmonic blocking element does not operate.
All 4 stages earth fault protection can be selected as definite-time or inverse-time characteristic,
and inverse-time operating time curve is as follows.
Equation 3.15-3
Where:
K is a constant
C is a constant.
α is a constant.
Date: 2017-08-17
3 Operation Theory
The user can select the operating characteristic from various inverse-time characteristic curves by
setting [50/51Gx.Opt_Curve], and parameters of available characteristics for selection are shown
in the following table.
If all available curves do not comply with user application, user may set [50/51Gx.Opt_Curve] as
“UserDefine” to customize the inverse-time curve characteristic, and constants K, α and C with
configuration tool software. (only stage 1)
When inverse-time characteristic is selected, if calculated operating time is less than setting
[50/51Gx.tmin], then the operating time of the protection changes to the value of setting
[50/51Gx.tmin] automatically.
Define-time or inverse-time directional earth-fault protection drops off instantaneously after fault
current disappears.
50/51Gx
50/51Gx.En1 50/51Gx.On
50/51Gx.En2 50/51Gx.On_ShortDly
50/51Gx.Blk 50/51Gx.St
50/51Gx.En_ShortDly 50/51Gx.Op
50/51Gx.Blk_ShortDly
Date: 2017-08-17
3 Operation Theory
3.15.5 Logic
EN [50/51G1.En]
&
SIG 50/51G1.En1 &
50/51G1.On
SIG 50/51G1.En2
SIG 50/51G1.Blk
SET 3I0>[50/51G1.3I0_Set]
EN [50/51G1.En_Abnor_Blk] >=1
&
SET [50/51G1.Opt_Dir]=Non_Directional
EN [50/51G1.En_CTS_Blk]
>=1 >=1
SIG I3P 2nd Hm Detect & & 50/51G1.Op
[50/51G1.t_Op] 0
SET [50/51G1.En_Hm2_Blk]
SET [50/51G1.Opt_Curve]=DefTime
Date: 2017-08-17
3 Operation Theory
EN [50/51Gx.En]
&
SIG 50/51Gx.En1 &
50/51Gx.On
SIG 50/51Gx.En2
SIG 50/51Gx.Blk
SET 3I0>[50/51Gx.3I0_Set]
EN [50/51Gx.En_Abnor_Blk] >=1
&
SET [50/51Gx.Opt_Dir]=Non_Directional
EN [50/51Gx.En_CTS_Blk]
>=1
SIG I3P 2nd Hm Detect & &
[50/51Gx.t_Op] 0
SET [50/51Gx.En_Hm2_Blk]
>=1
SET [50/51Gx.Opt_Curve]=DefTime & 50/51Gx.Op
[50/51Gx.t_ShortDly] 0
EN [50/51Gx.En_ShortDly]
&
SIG [50/51Gx.En_ShortDly] 50/51Gx.On_ShortDly
SIG [50/51Gx.Blk_ShortDly]
x=2, 3, 4
Abnormal condition 1: when the system is under pole disagreement condition, for 1-pole AR, earth
fault protection will operate. If the logic setting [50/51Gx.En_Abnor_Blk] is set as “1”, the stage x
of earth fault protection will be blocked. If the logic setting [50/51Gx.En_Abnor_Blk] is set as “0”,
earth fault protection is not controlled by direction element.
Abnormal condition 2: When manually closing circuit breaker, three phases of the circuit breaker
maybe not operate simultaneously, and SOTF protection should operate. If the logic setting
[50/51Gx.En_Abnor_Blk] is set as “1”, the stage x of earth fault protection will be blocked. If the
logic setting [50/51Gx.En_Abnor_Blk] is set as “0”, earth fault protection is not controlled by
direction element.
Abnormal condition 3: VT circuit failure. If the logic setting [50/51Gx.En_Abnor_Blk] is set as “1”,
the stage x of earth fault protection will be blocked. If the logic setting [50/51Gx.En_Abnor_Blk] is
set as “0”, earth fault protection is not controlled by direction element.
Date: 2017-08-17
3 Operation Theory
3.15.6 Settings
Table 3.15-3 Settings of earth fault protection
Date: 2017-08-17
3 Operation Theory
Date: 2017-08-17
3 Operation Theory
Date: 2017-08-17
3 Operation Theory
Date: 2017-08-17
3 Operation Theory
Date: 2017-08-17
3 Operation Theory
If the power frequency of regional rises due to the active power excess demand, overfrequency
protection operates to perform generator rejection to shed part of the generators automatically
according to the rising frequency so that power supply and the load are re-balanced.
The device provides four stages overfrequency protection. When system frequency is greater
than the setting [81O.f_Pkp], overfrequency protection will put into service.
If the positive voltage U1<[81O.U1_Set], the calculation of protection is not carried out and the
output relay will be blocked.
Where:
f is system frequency.
Date: 2017-08-17
3 Operation Theory
81O.OFi
81O.En1 81O.OFi.On
81O.En2 81O.St
81O.Blk 81O.OFi.Op
3.16.1.5 Logic
SIG 81O.St2
>=1
SIG 81O.St3 >=1 81O.St
SIG 81O.St4
Date: 2017-08-17
3 Operation Theory
SIG 81O.En1
&
SIG 81O.En2 &
81O.OFi.On
EN [81O.OFi.En]
SIG 81O.Blk
&
SIG FD.Pkp
EN [81O.OFi.En]
i=1, 2, 3, 4
3.16.1.6 Settings
In case of frequency decline due to lack of active power in the power system, underfrequency
protection operates to shed part of the load according to the declined value of frequency to
re-balance the power supply and the load.
The device provides four stages underfrequency protection. When system frequency is smaller
than the setting [81U.f_Pkp], underfrequency protection will put into service.
Date: 2017-08-17
3 Operation Theory
If the positive voltage U1<[81U.U1_Set], the calculation of protection is not carried out and the
output relay will be blocked.
If -df/dt≥[81U.df/dt_Blk], the calculation of protection is not carried out and the output relay will
be blocked. The blocking element will not be released automatically until the system frequency
recovers to be less than the setting [81U.f_Pkp].
Where:
f is system frequency.
Where:
df/dt is the frequency slip speed and the time step (i.e. dt) for the calucation is equal to 5 cycle.
Underfrequency protection can be blocked by the frequency slip speed (df/dt). If the logic setting
[81U.UFi.En_df/dt_Blk] is set as “1”, when Equation 3.16-2 and Equation 3.16-3 are met, it is
decided that a fault occurred and the corresponding stage underfrequency protection is blocked at
the same time for the purpose of waiting for operation of other related protection. The blocking
signal will not reset until the system frequency recovers, i.e. the system frequency is greater than
the setting [81U.f_Pkp]. If the logic setting is set as “0”, when Equation 3.16-2 and Equation
3.16-3 are met, the stage underfrequency protection will be released to operate.
Date: 2017-08-17
3 Operation Theory
81U.UFi
81U.En1 81U.UFi.On
81U.En2 81U.St
81U.Blk 81U.UFi.Op
3.16.2.5 Logic
SIG 81U.St2
>=1
SIG 81U.St3 >=1 81U.St
SIG 81U.St4
Date: 2017-08-17
3 Operation Theory
SIG 81U.En1
&
SIG 81U.En2
EN [81U.UFi.En]
&
81U.UFi.On
SIG 81U.Blk
&
SIG FD.Pkp &
SIG U1<0.15Un >=1
EN [81U.UFi.En]
i=1, 2, 3, 4
3.16.2.6 Settings
Date: 2017-08-17
3 Operation Theory
Breaker failure protection issues a back-up trip command to trip adjacent circuit breakers in case
of a tripping failure of the circuit breaker, and clears the fault as requested by the device. To utilize
the protection information of faulty equipment and the electrical information of failure circuit
breaker to constitute the criterion of breaker failure protection, it can ensure that the adjacent
circuit breakers of failure circuit breaker are tripped with a shorter time delay, so that the affected
area is minimized, and ensure stable operation of the entire power grid to prevent generators,
transformers and other components from seriously damaged.
When both the phase-segregated tripping contact from line protection and the corresponding
phase overcurrent element operate, or both the three-phase tripping contact and any phase
overcurrent element operate, breaker failure protection will send three-phase tripping command to
trip local circuit breaker after time delay of [50BF.t1_Op] and trip all adjacent circuit breakers after
time delay of [50BF.t2_Op].
When the protection element except under voltage element within this device operates and issues
tripping signal, breaker failure protection will also be initiated.
Taking into account that the faulty current is too small for generator or transformer fault, the
sensitivity of phase current element may not meet the requirements, residual current criterion and
negative-sequence current criterion are provided in addition to the phase overcurrent element for
breaker failure protection initiated by input signal [50BF.ExTrp3P_GT] from generator and
transformer protection. They can be enabled or disabled by logic settings [50BF.En_3I0_3P] and
[50BF.En_I2_3P] respectively.
For some special fault (for example, mechanical protection or overvoltage protection operating),
maybe faulty current is very small and current criterion of breaker failure protection is not met, in
order to make breaker failure protection can also operate under the above situation, an input
signal [50BF.ExTrp_WOI] is equipped to initiate breaker failure protection, once the input signal is
energized, normally closed auxiliary contact of circuit breaker is chosen in addition to breaker
failure current check to trigger breaker failure timer. The device takes current as priority with CB
auxiliary contact (52b) as an option criterion for breaker failure check.
Date: 2017-08-17
3 Operation Theory
50BF
50BF.ExTrp3P_L 50BF.On
50BF.ExTrp3P_GT 50BF.Op_ReTrpA
50BF.ExTrp_WOI 50BF.Op_ReTrpB
50BF.ExTrpA 50BF.Op_ReTrpC
50BF.ExTrpB 50BF.Op_ReTrp3P
50BF.ExTrpC 50BF.Op_t1
50BF.En 50BF.Op_t2
50BF.Blk
Date: 2017-08-17
3 Operation Theory
3.17.5 Logic
SIG 50BF.En
&
EN [ 50BF.En] 50BF.On
SIG 50BF.Blk
SIG 50BF.On
&
SIG FD.Pkp
EN [ 50BF.En_ReTrp]
EN [ 50BF.En_3I0_1P] >=1
BI [ 50BF.ExTrpA]
BI [ 50BF.ExTrpB]
BI [ 50BF.ExTrpC] >=1
BI [ 50BF.ExTrp_WOI]
&
EN [ 50BF.En_3I0_3P] &
BI [ 52b_PhA]
&
BI [ 52b_PhB]
BI [ 52b_PhC]
SIG FD.Pkp
Where:
BFI_A, BFI_B, BFI_C: A-phase, B-phase and C-phase breaker failure protection initiating signal,
please refer to.
Date: 2017-08-17
3 Operation Theory
3.17.6 Settings
Table 3.17-2 Settings of breaker failure protection
Date: 2017-08-17
3 Operation Theory
operate. Pole discrepancy protection is required to operate before the operation of these
overcurrent elements.
62PD
62PD.En1 62PD.On
62PD.En2 62PD.Op
62PD.Blk 62PD.St
3.18.5 Logic
Pole discrepancy protection can be initiated following method.
Phase-segregated circuit breaker auxiliary contacts are connected to the device. When the state
of three phase-segregated circuit breaker auxiliary contacts are inconsistent, pole discrepancy
protection will be started and initiate output after a time delay [62PD.t_Op].
Pole discrepancy protection can be blocked by external input signal [62PD.Blk]. In general, this
input signal is usually from the output of 1-pole AR initiation, so as to prevent pole discrepancy
protection from operation during 1-pole AR initiation.
Date: 2017-08-17
3 Operation Theory
SIG 62PD.En1
&
SIG 62PD.En2 &
62PD.On
EN [62PD.En]
SIG 62PD.Blk
&
SIG FD.Pkp
EN [62PD.En_3I0/I2_Ctrl] >=1
SET 3I0>[62PD.3I0_Set] >=1
SET I2>[62PD.I2_Set]
BI [52b_PhB] &
SIG Ib<0.06In
>=1
BI [52b_PhC] &
SIG Ic<0.06In
Where:
3.18.6 Settings
Table 3.18-2 Settings of pole discrepancy protection
Date: 2017-08-17
3 Operation Theory
When two asynchronous systems are connected together, due to phase difference between the
two systems, larger impact will be led to the system during closing. Thus auto-reclosing and
manual closing are applied with the synchro-check to avoid this situation and maintain the system
stability. The synchro-check includes synchronism check and dead charge check.
The dead charge check function measures the amplitude of reference voltage and synchronism
voltage, and then compare them with the live check setting [25.U_Lv] and the dead check setting
[25.U_Dd]. The output is only given when the measured quantities comply with the criteria.
Synchro-check in this device can be used for auto-reclosing and manual closing for both
single-breaker and dual-breakers. Details are described in the following sections.
When used for the synchro-check of single-breaker, comparative relationship between reference
voltage (Uref) and synchronism voltage (Usyn) for synchro-check is as follows.
Uref Usyn
Figure 3.19-1 shows the characteristics of synchronism check element used for the auto-reclosing
if both reference voltage and synchronism voltage are live. The synchronism check element
operates if voltage difference, phase angle difference and frequency difference are all within their
setting values.
Usyn≥[25.U_Lv]
Uref≥[25.U_Lv]
Date: 2017-08-17
3 Operation Theory
|Usyn- Uref|≤[25.U_Diff]
Usyn×Uref×cosØ≥0
Usyn×Uref×sin([25.phi_Diff]) ≥Usyn×Uref×|sinØ|
Where,
|f(Usyn)-f(Uref)|≤[25.f_Diff]
If frequency check is disabled (i.e. [25.En_fDiffChk] is set as "0"), a detected maximum slip cycle
can also be determined by the following equation based on phase difference setting and the
synchronism check time setting:
f =[25.phi_Diff]/(180×[25.t_SynChk])
Where:
f is slip cycle
If frequency check is enabled (i.e. [25.En_fDiffChk] is set as "1"), then [25.t_SynChk] can be set to
be a very small value (default value is 50ms).
This function module supports voltage switching. In general, voltage switching is fulfilled by
external circuit, and the busbar arrangement should be determined, including three options, single
busbar arrangement, double busbars arrangement and 1½ breakers arrangement, if using this
module to fulfill voltage switching.
Analog input defines four voltage inputs, UL1, UB1, UL2, UB2, and their usage are as follow:
UL1: it connects with three-phase protection voltages (from line or busbar), which mainly are used
by distance protection, voltage protection and so on.
UL2: it connects with single synchronism voltage (from the other line of the same diameter in 1½
breakers arrangement). When voltage switching is available, it is only used by 1½ breakers
arrangement.
UB2: it connects with single synchronism voltage (from busbar). When voltage switching is
available, it is only used by double busbars arrangement and 1½ breakers arrangement.
The reference voltage (Uref) is determined to use phase voltage or phase-to-phase voltage (UL1)
from three-phase protection voltages and by the setting [25.Opt_Source_UL1].
The synchronism voltage (Usyn) always connects with UB1 if not adopting voltage switching. It
connects with one of UB1, UL2 and UB2 according to the result of voltage switching if adopting
voltage switching.
Date: 2017-08-17
3 Operation Theory
Voltage selection function is not required for this busbar arrangement, the connection of the
voltage signals and respective VT MCB auxiliary contacts to the device is shown in the Figure
3.19-2 and Figure 3.19-3.
Bus
Ua
UL1 Ub CB
Uc
25.MCB_VT_UL1
UB1
25.MCB_VT_UB1
Line
Three-phase protection voltages are from busbar VT. As shown in above figure, the reference
voltage (Uref) is selected among three-phase protection voltages, and synchronism voltage (Usyn)
is from line VT.
Bus
UB1 CB
25.MCB_VT_UB1
Ua
UL1 Ub
Uc
25.MCB_VT_UL1 Line
In the figures, the setting [VTS.En_LineVT] is used to determine protection voltage signals (Ua,
Ub, Uc) from line VT or bus VT according to the condition. This setting is only used for VT circuit
failure logic, and it does not affect the synchro-check mode. Three-phase protection voltages are
from line VT, as shown in above figure, the reference voltage (Uref) is selected among UL1
three-phase protection voltages, and synchronism voltage (Usyn) is from busbar VT.
Date: 2017-08-17
3 Operation Theory
Bus2
Bus1
B1D B2D
UB1
25.MCB_VT_UB1
UB2
25.MCB_VT_UB2
25.NC_UB1DS
25.NO_UB1DS CB
25.NC_UB2DS
25.NO_UB2DS
Ua
UL1 Ub
Line
Uc
25.MCB_VT_UL1
For double busbars arrangement, selection of appropriate voltage signals from Bus 1 and Bus 2
for synchronizing are required. Line VT signal is taken as reference to check synchronizing with
the voltage after voltage selection function. Selection approach is as follows.
For the disconnector positions, the normally open (NO) and normally closed (NC) contacts of the
disconnector for bus 1 and bus 2 are required to determine the disconnector open and closed
positions. The voltage selection logic is as follows.
BI 25.NC_UB1DS &
Voltage Selection Logic
UB1_Sel
BI 25.NO_UB1DS
BI 25.NC_UB2DS &
UB2_Sel
BI 25.NO_UB2DS
&
Alm_Invalid_Sel
UB1 Usyn
UB2
After acquiring the disconnector open and closed positions of double busbars, use the following
Date: 2017-08-17
3 Operation Theory
If voltage selection is invalid (Alm_Invalid_Sel=1), keep original selection and without switchover.
For one and a half breakers arrangement, selection of appropriate voltage signals among Line1
VT, Line2 VT and Bus 2 VT as reference voltage to check synchronizing with Bus 1 voltage signal
for closing breaker at Bus 1 side.
Bus1
UB1
25.MCB_VT_UB1
25.NC_UB1DS
B1D
25.NO_UB1DS
Ua Line 1
UL1 Ub
Uc
25.MCB_VT_UL1
L1D
25.NC_UL1DS
25.NO_UL1DS
Line 2
UL2
25.MCB_VT_UL2
25.NC_UL2DS
25.NO_UL2DS
L2D
25.NC_UB2DS
25.NO_UB2DS
UB2
25.MCB_VT_UB2
B2D
Bus2
Figure 3.19-6 Voltage connection for one and a half breakers arrangement
For the circuit breaker at bus side (take bus breaker of bus 1 as an example), the device acquires
the disconnector open and closed positions of two feeders and bus 2. The voltage selection logic
Date: 2017-08-17
3 Operation Theory
is as follows.
BI 25.NC_UL1DS &
UL1_Sel
BI 25.NO_UL1DS
&
BI 25.NC_UL2DS & UL2_Sel
BI 25.NO_UL2DS
&
BI 25.NC_UB2DS & UB2_Sel
BI 25.NO_UB2DS
&
Alm_Invalid_Sel
UL1 Uref
UL2
UB2
UB1 Usyn
Figure 3.19-7 Voltage selection for bus CB of one and a half breakers arrangement
For the tie breaker, the device acquires the disconnector open and closed positions of two feeders
and two busbars. Either Line 1 VT or Bus 1 VT signal is selected as reference voltage to check
synchronizing with the selected voltage between Line 2 VT and Bus 2 VT. The voltage selection
logic is as follows.
Date: 2017-08-17
3 Operation Theory
BI 25.NC_UL1DS &
UL1_Sel
BI 25.NO_UL1DS
&
BI 25.NC_UB1DS & UB1_Sel
BI 25.NO_UB1DS
&
UL1 Uref
UB1
BI 25.NC_UL2DS &
UL2_Sel
BI 25.NO_UL2DS
&
BI 25.NC_UB2DS & UB2_Sel
BI 25.NO_UB2DS
>=1
& Alm_Invalid_Sel
UL2 Usyn
UB2
Figure 3.19-8 Voltage selection for tie CB of one and a half breakers arrangement
When the voltage selection fails (including VT circuit failure and MCB failure), the device will issue
the corresponding failure signal. If the voltage selection is invalid (Alm_Invalid_Sel=1), keep
original selection and without switchover.
In order to simplify description, one of the two voltages used in the synchro-check (synchronism check
and dead charge check) which obtained after voltage selection function is regarded as line voltage,
and another is bus voltage.
3.19.2.4 Synchronism Voltage Circuit Failure Supervision
If voltage from synchronism voltage VT or reference voltage VT is used for auto-reclosing with
synchronism or dead reference voltage or synchronism voltage check, the synchronism voltage
circuit and reference voltage circuit are monitored.
During normal operation, the circuit breaker is in closed state (52b of three phases are
de-energized), if automatic reclosing cycle is in progress and no fault detector operates, then the
synchronism voltage is lower than the setting [25.U_Lv], it means that synchronism voltage circuit
fails and the synchronism voltage alarm [25.Alm_VTS_Usyn] or reference voltage alarm
[25.Alm_VTS_Uref] will be issued with a time delay of 10s. If the MCB of synchronism voltage or
reference voltage is open, the corresponding alarm signal [25.Alm_VTS_Usyn] or
[25.Alm_VTS_Uref] will be issued instantaneously.
If no check mode is enabled (the signal [25.On_NoChk] is "1"), synchro-check used voltage circuit
Date: 2017-08-17
3 Operation Theory
When synchronism voltage circuit failure is detected, function of dead check in auto-reclosing
logic will be disabled.
After synchronism voltage reverted to normal condition, the alarm will be reset automatically with
a time delay of 10s.
SIG 79.Inprog
&
10s 10s
SIG Uref<[25.U_Lv]
>=1
&
BI 25.MCB of Uref 25.Alm_VTS_Uref
EN 25.En_SynChk >=1
SIG 25.En_DdL_DdB &
SIG 25.En_DdL_LvB
SIG 25.En_LvL_DdB
SIG 25.Blk_VTS_UL
Figure 3.19-9 Reference voltage circuit failure supervision logic diagram (auto-reclosure)
SIG 79.Inprog
&
10s 10s >=1
SIG Usyn<[25.U_Lv] &
25.Alm_VTS_Usyn
BI 25.MCB of Usyn
EN 25.En_SynChk >=1
SIG 25.En_DdL_DdB &
SIG 25.En_DdL_LvB
SIG 25.En_LvL_DdB
SIG 25.Blk_VTS_UB
Figure 3.19-10 Synchronism voltage circuit failure supervision logic diagram (auto-reclosure)
Where:
"25.MCB of Uref" means binary input for VT MCB auxiliary contact of the reference voltage after
voltage switching.
"25.MCB of Usyn" means binary input for VT MCB auxiliary contact of the synchronism voltage
after voltage switching.
Date: 2017-08-17
3 Operation Theory
25
25.Blk_Chk UL1_Sel
UL2_Sel
25.Blk_SynChk
UB1_Sel
25.Blk_DdChk UB2_Sel
Alm_Invalid_Sel
25.Start_Chk
25.On_SynChk
25.Start_3PLvChk 25.On_DdL_DdB
25.Sel_SynChk 25.On_DdL_LvB
25.On_LvL_DdB
25.Sel_DdL_DdB
25.On_NoChk
25.Sel_DdL_LvB 25.Ok_fDiffChk
25.Ok_UDiffChk
25.Sel_LvL_DdB
25.Ok_phiDiffChk
25.Sel_NoChk
25.Ok_DdL_DdB
25.Blk_VTS_Uref 25.Ok_DdL_LvB
25.Ok_LvL_DdB
25.Blk_VTS_Usyn
25.Chk_LvL
25.MCB_VT_UL1 25.Chk_DdL
25.MCB_VT_UL2 25.Chk_LvB
25.Chk_DdB
25.MCB_VT_UB1
25.Ok_DdChk
25.MCB_VT_UB2 25.Ok_SynChk
25.NC_UL1DS 25.Ok_Chk
25.Ok_3PLvChk
25.NO_UL1DS
25.Alm_VTS_Uref
25.NC_UB1DS
25.Alm_VTS_Usyn
25.NO_UB1DS
25.f_Ref
25.NC_UL2DS 25.f_Syn
25.NO_UL2DS 25.U_Diff
25.f_Diff
25.NC_UB2DS
25.Phi_Diff
25.NO_UB2DS
Date: 2017-08-17
3 Operation Theory
Date: 2017-08-17
3 Operation Theory
3.19.5 Logic
3.19.5.1 Synchronism Check Logic
The frequency difference, voltage difference, and phase difference of voltages from both sides of
the circuit breaker are calculated in the device, they are used as input conditions of the
synchronism check. When the synchronism check function is enabled and the voltages of both
ends meets the requirements of the voltage difference, phase difference, and frequency
difference, and there is no synchronism check blocking signal, it is regarded that the synchronism
check conditions are met.
Synchronism check logic is usually used for 3-pole AR, and 1-pole AR is usually adopts no check
logic. However, the circuit breaker at local end cannot reclosed unless the circuit breaker at
remote end is reclosed successfully. In order to meet this requirement, live three-phase check can
be used for 1-pole AR, determined by the setting [25.En_3PLvChk], ensure that three-phase
voltages is restored to normal at local end after the circuit breaker at remote end is reclosed.
Date: 2017-08-17
3 Operation Theory
1
EN [25.En_SynChk]
25.On_SynChk
SIG 25.Sel_SynChk
0
EN [25.SetOpt]
EN [25.En_3PLvChk]
SIG Uref.a>[25.U_Lv]
>=1
&
SIG Uref.b>[25.U_Lv]
SIG Uref.c>[25.U_Lv]
&
SIG 25.Start_3PLvChk 200ms 0ms 25.Ok_3PLvChk
SIG 25.Blk_SynChk
&
SIG [25.On_SynChk]
&
SIG 25.Start_Chk
SIG Usyn>[25.U_Lv]
& &
SIG Uref>[25.U_Lv] 50ms 0ms & [25.t_SynChk] 0ms 25.Ok_SynChk
SIG 25.Ok_UdiffChk
SIG 25.Ok_phiDiffChk
SIG 25.Ok_fDiffChk
The dead charge check conditions have three types, namely, live-synchronism voltage and
dead-reference voltage check, dead-synchronism voltage and live-reference voltage check and
dead-synchronism voltage and dead-reference voltage check. The above three modes can be
enabled and disabled by the corresponding logic settings ([25.En_DdL_DdB], [25.En_LvL_DdB]
and [25.En_DdL_LvB]) or external signal, when the setting [25.SetOpt] is set as "1", dead charge
check mode is determined by corresponding logic settings. Otherwise, dead charge check mode
is determined by external signal.
The device can calculate the measured synchronism voltage and reference voltage and compare
them with the settings [25.U_Lv] and [25.U_Dd]. When the voltage is higher than [25.U_Lv], the
synchronism voltage/reference voltage is regarded as live. When the voltage is lower than
[25.U_Dd], the synchronism voltage/reference voltage is regarded as dead.
Date: 2017-08-17
3 Operation Theory
1
EN [25.En_DdL_DdB]
25.On_DdL_DdB
SIG 25.Sel_SynChk
0
EN [25.SetOpt]
1
EN [25.En_LvL_DdB]
25.On_LvL_DdB
SIG 25.Sel_LvL_DdB
0
EN [25.SetOpt]
1
EN [25.En_DdL_LvB]
25.On_DdL_LvB
SIG 25.Sel_DdL_LvB
0
EN [25.SetOpt]
SIG Usyn>[25.U_Lv]
SIG Usyn>[25.U_Lv]
SIG Usyn<[25.U_Dd]
SIG 25.Alm_VTS_Uref
Date: 2017-08-17
3 Operation Theory
1
EN [25.En_NoChk]
25.On_NoChk
SIG 25.Sel_NoChk
0
EN [25.SetOpt]
SIG 25.Ok_SynChk
>=1
EN 25.On_NoChk 25.Ok_Chk
SIG 25.Ok_DdChk
3.19.6 Settings
Table 3.19-2 Synchro-check settings
Date: 2017-08-17
3 Operation Theory
Date: 2017-08-17
3 Operation Theory
Besides overhead lines, other equipment failure, such as cables, busbar, transformer fault and so
on, are generally permanent fault, and auto-reclosing is not initiated after faulty feeder is tripped.
For some mixed circuits, such as overhead line with a transformer unit, hybrid transmission lines,
etc., it is required to ensure that auto-reclosing is only initiated for faults overhead line section, or
make a choice according to the situation.
When external auto-reclosure is used, the device can output some configurable output to initiate
external AR, such as, contact of initiating AR, phase-segregated tripping contact, single-phase
tripping contact, three-phase tripping contact and contact of blocking AR. According to
requirement, these contacts can be selectively connected to external auto-reclosure device to
initiate AR.
For phase-segregated circuit breaker, AR mode can be 1-pole AR for single-phase fault and
3-pole AR for multi-phase fault, or always 3-pole AR for any kinds of fault according to system
requirement. For persistent fault or multi-shot AR number preset value is reached, the device will
send final tripping command. The device will provide appropriate tripping command based on
faulty phase selection if adopting 1-pole AR.
AR can be enabled or disabled by logic setting or external signal via binary input. When AR is
enabled, the device will output contact [79.On], otherwise, output contact [79.Off]. After some
reclosing conditions, such as, CB position, CB pressure and so on, is satisfied, the device will
output contact [79.Ready].
According to requirement, the device can be set as one-shot or multi-shot AR. When adopting
Date: 2017-08-17
3 Operation Theory
multi-shot AR, the AR mode of first time reclosing can be set as 1-pole AR, 3-pole AR or 1/3-pole
AR. The rest AR mode is only 3-pole AR and its number is determined by the maximum 3-pole
reclosing number.
For one-shot AR or first reclosing of multi-shot AR, AR mode can be selected by logic setting
[79.En_1PAR], [79.En_3PAR] and [79.En_1P/3PAR] or external signal via binary inputs. When
3-pole or 1/3-pole AR mode is selected, the following three types of check modes can be selected:
dead charge check, synchronism check and no check.
79
79.En 79.On
79.Blk 79.Off
79.Sel_1PAR 79.Close
79.Sel_3PAR 79.Ready
79.Sel_1P/3PAR 79.AR_Blkd
79.Trp 79.Active
79.Trp3P 79.Inprog
79.TrpA 79.Inprog_1P
79.TrpB 79.Inprog_3P
79.TrpC 79.Inprog_3PS1
79.LockOut 79.Inprog_3PS2
79.PLC_Lost 79.Inprog_3PS3
79.WaitMaster 79.Inprog_3PS4
79.CB_Healthy 79.WaitToSlave
79.Clr_Counter 79.Perm_Trp1P
79.Ok_Chk 79.Perm_Trp3P
79.Ok_3PLvChk 79.Rcls_Status
79.Fail_Rcls
79.Succ_Rcls
79.Fail_Chk
79.Mode_1PAR
79.Mode_3PAR
79.Mode_1/3PAR
Date: 2017-08-17
3 Operation Theory
Date: 2017-08-17
3 Operation Theory
3.20.5 Logic
3.20.5.1 AR Ready
For the first reclosing of multi-shot AR, AR mode can be 1-pole AR or 3-pole AR, however, the
selection is valid only to the first reclosing, after that it can only be 3-pole AR.
When logic setting [79.SetOpt] is set as "1", AR mode is determined by logic settings. When logic
setting [79.SetOpt] is set as "0", AR mode is determined by external signal via binary inputs.
An auto-reclosure must be ready to operate before performing reclosing. The output signal
[79.Ready] means that the auto-reclosure can perform at least one time of reclosing function, i.e.,
breaker open-close-open.
When the device is energized or after the settings are modified, the following conditions must be
met before the reclaim time begins:
1. AR function is enabled.
2. The circuit breaker is ready, such as, normal storage energy and no low pressure signal.
3. The duration of the circuit breaker in closed position before fault occurrence is not less than
the setting [79.t_CBClsd].
Date: 2017-08-17
3 Operation Theory
After the auto-reclosure operates, the auto-reclosure must reset, i.e., [79.Active]=0, in addition to
the above conditions for reclosing again.
When there is a fault on an overhead line, the concerned circuit breakers will be tripped normally.
After fault is cleared, the tripping command will drop off immediately. In case the circuit breaker is
in failure, etc., and the tripping signal of the circuit breaker maintains and in excess of the time
delay [79.t_PersistTrp], AR will be blocked, as shown in the following figure.
En [79.En_PDF_Blk]
En [79.N_Rcls]=1
>=1
& 79.AR_Blkd
SIG Three phase trip
& >=1
&
The input signal [79.CB_Healthy] must be energized before auto-reclosure gets ready. Because
most circuit breakers can finish one complete process: open-closed-open, it is necessary that
circuit breaker has enough energy before reclosing. When the time delay of AR is exhausted, AR
will be blocked if the input signal [79.CB_Healthy] is still not energized within time delay
[79.t_CBReady]. If this function is not required, the input signal [79.CB_Healthy] can be not to
configure, and its state will be thought as "1" by default.
In order to block AR reliably even if the signal of manually open circuit breaker not connected to
the input of blocking AR, when the circuit breaker is open by manually and there is CB position
input under normal conditions, AR will be blocked with the time delay of 100ms if AR is not
initiated and no any trip signal.
Date: 2017-08-17
3 Operation Theory
protection operates, the device operates for multi-phase fault, three-phase fault and so on. These
flags of blocking AR have been configured in the device, additional configuration is not required.),
auto-reclosure will be discharged immediately and next auto-reclosing will be disabled.
When the input signal [79.LockOut] is energized, auto-reclosure will be blocked immediately. The
blocking flag of AR will be also controlled by the internal blocking condition of AR. When the
blocking flag of AR is valid, auto-reclosure will be blocked immediately.
EN [79.En] &
EN [79.En_ExtCtrl]
>=1
79.On
&
SIG 79.En &
SIG 79.Blk
When a fault occurs under pole disagreement condition, blocking AR can be enabled or disabled.
The time delay [79.t_SecFault] is used to discriminate another fault which begins after 1-pole AR
initiated. AR will be blocked if another fault happens after this time delay if the logic setting
[79.En_PDF_Blk] is set as "1", and 3-pole AR will be initiated if [79.En_PDF_Blk] is set as "1".
AR will be blocked immediately once the blocking condition of AR appears, but the blocking
condition of AR will drop off with a time delay [79.t_DDO_BlkAR] after blocking signal disappears.
When one-shot and 1-pole AR is enabled, auto-reclosure will be blocked immediately if there are
binary inputs of multi-phase CB position is energized.
When any protection element operates to trip, the device will output a signal [79.Active] until AR
drop off (Reset Command). Any tripping signal can be from external protection device or internal
protection element.
Date: 2017-08-17
3 Operation Theory
AR function can be enabled by internal logic settings of AR mode or external signal via binary
inputs in addition to internal logic setting [79.En]. When logic setting [79.En_ExtCtrl] is set as "1",
AR enable are determined by external signal via binary inputs and logic settings. When logic
setting [79.En_ExtCtrl] set as "0", AR enable are determined only by logic settings.
For one-shot reclosing, if 1-pole AR mode is selected, auto-reclosure will reset when there is
three-phase tripping signal or input signal of multi-phase open position.
SIG 79.On
SIG 79.Mode_3PAR
SIG 79.Ready
SIG 79.Trp
SIG 79.Trp3P
SIG 79.TrpC
When AR is enabled, the device will output the signal [79.Perm_Trp3P] if AR is not ready, or AR
mode is set as 3-Pole AR, or another fault occurs after the circuit breaker is open.
3.20.5.2 AR Initiation
AR mode can be selected by external signal via binary inputs or internal logic settings. If the logic
setting [79.SetOpt] set as "1", AR mode is determined by the internal logic settings. If the logic
settings [79.SetOpt] set as "0", AR mode is determined by the external inputs.
AR can be initiated by tripping signal of line protection, and the tripping signal may be from
internal trip signal or external trip signal.
When selecting 1-pole AR or 1/3-pole AR, line single-phase fault will trigger 1-pole AR. When AR
is ready to reclosing ("79.Ready"=1) and the single-phase tripping command is received, this
single-phase tripping command will be kept in the device, and 1-pole AR will be initiated after the
single-phase tripping command drops off. The single-phase tripping command kept in the device
will be cleared after the completion of auto-reclosing sequence (Reset Command). Its logic is
shown in Figure 3.20-4.
Date: 2017-08-17
3 Operation Theory
&
SIG 79.Ready
&
1-pole AR Initiation
SIG 79.Sel_1PAR >=1
SIG 79.Sel_1P/3PAR
When selecting 3-pole AR or 1/3-pole AR, three-phase tripping will trigger 3-pole AR. When AR is
ready to reclosing ("79.Ready"=1) and the three-phase tripping command is received, this
three-phase tripping command will be kept in the device, and 3-pole AR will be initiated after the
three-phase tripping command drops off. The three-phase tripping command kept in the device
will be cleared after the completion of auto-reclosing sequence. (Reset Command) Its logic is
shown in Figure 3.20-5.
&
SIG 79.Ready
&
3-pole AR Initiation
SIG 79.Sel_3PAR >=1
SIG 79.Sel_1P/3PAR
2. AR initiated by CB state
A logic setting [79.En_CBInit] is available for selection that AR is initiated by CB state. Under
normal conditions, when AR is ready to reclosing ("79.Ready"=1), AR will be initiated if circuit
breaker is open and corresponding phase current is nil. AR initiated by CB state can be divided
into initiating 1-pole AR and 3-pole AR, their logics are shown in Figure 3.20-6 and Figure 3.20-7
respectively. Usually normally closed contact of circuit breaker is used to reflect CB state.
Date: 2017-08-17
3 Operation Theory
EN [79.En_CBInit]
SIG 79.Ready
SIG 79.Sel_1P/3PAR
EN [79.Sel_1PAR] >=1
EN [79.Sel_1P/3PAR]
3.20.5.3 AR Reclosing
After AR is initiated, the device will output the initiating contact of AR. For 1-pole AR, in order to
prevent pole discrepancy protection from maloperation under pole discrepancy conditions, the
contact of "1-pole AR initiation" can be used to block pole discrepancy protection.
When the dead time delay of AR expires after AR is initiated, as for 1-pole AR, when the setting
[25.En_3PLvChk] is set as "0", the result of synchronism check will not be judged, and reclosing
command will be output directly. When the setting [25.En_3PLvChk] is set as "1", the reclosing is
not permissible unless live three-phase check is met. As far as the 3-pole AR, if the synchronism
check is enabled, the release of reclosing command shall be subject to the result of synchronism
check. After the dead time delay of AR expires, if the synchronism check is still unsuccessful
within the time delay [79.t_wait_Chk], the signal of synchronism check failure (79.Fail_Syn) will be
output and the AR will be blocked. If 3-pole AR with no-check is enabled, the condition of
synchronism check success (25.Ok_Chk) will always be established. And the signal of
synchronism check success (25.Ok_Chk) from the synchronism check logic can be applied by
auto-reclosing function inside the device or external auto-reclosure device.
Date: 2017-08-17
3 Operation Theory
79.Inprog_1P
SIG 1-pole AR Initiation >=1
79.Inprog
SIG 3-pole AR Initiation
79.Inprog_3P
&
SIG 79.Ok_3PLvChk
>=1
& [79.t_Wait_Chk] 0ms 79.Fail_Chk
SIG 79.Ok_Chk
In case pilot protection adopting permissive scheme, when the communication channel is
abnormal, pilot protection will be disabled. In the process of channel abnormality, an internal fault
occurs on the transmission line, backup protection at both ends of line will operate to trip the
circuit breaker of each end. The operation time of backup protection at both ends of the line is
possibly non-accordant, whilst the time delay of AR needs to consider the arc-extinguishing and
insulation recovery ability for transient fault, so the time delay of AR shall be considered
comprehensively according to the operation time of the device at both ends. When the
communication channel of main protection is abnormal (input signal [79.PLC_Lost] is energized),
and the logic setting [79.En_AddDly] is set as "1", then the dead time delay of AR shall be equal to
the original dead time delay of AR plus the extra time delay [79.t_AddDly], so as to ensure the
recovery of insulation intensity of fault point when reclosing after transient fault. This extra time
delay [79.t_AddDly] is only valid for the first shot AR.
>=1
BI [79.PLC_Lost]
&
SIG 79.Active
&
Extend AR time
EN [79.En_AddDly]
Reclosing pulse length may be set through the setting [79.t_PW_AR]. For the circuit breaker
Date: 2017-08-17
3 Operation Theory
without anti-pump interlock, a logic setting [79.En_CutPulse] is available to control the reclosing
pulse. When this function is enabled, if the device operates to trip during reclosing, the reclosing
pulse will drop off immediately, so as to prevent multi-shot reclosing onto fault. After the reclosing
command is issued, AR will drop off with time delay [79.t_Reclaim], and can carry out next
reclosing.
EN [79.En_CutPulse]
>=1
&
SIG 79.AR_Out [79.t_Reclaim] 0ms Reset Command
The reclaim timer defines a time from the issue of the reclosing command, after which the
reclosing function resets. Should a new trip occur during this time, it is treated as a continuation of
the first fault. The reclaim timer is started when the CB closing command is given.
SET [79.Opt_Priority] =1
The output signal "79.WaitToSlave" is usually configured to the signal "79.WaitMaster" of slave AR.
Slave AR is permissible to reclosing only if master AR is reclosed successfully.
For transient fault, the fault will be cleared after the device operates to trip. After the reclosing
command is issued, AR will drop off after time delay [79.t_Reclaim], and can carry out next
reclosing. When the reclosing is unsuccessful or the reclosing condition is not met after AR
initiated, the reclosing will be considered as unsuccessful, including the following cases.
1. If any protection element operates to trip when AR is enabled ([79.On]=1) and AR is not
Date: 2017-08-17
3 Operation Theory
2. For one-shot AR, if the tripping command is received again within reclaim time after the
reclosing pulse is issued, the reclosing shall be considered as unsuccessful.
3. For multi-shot AR, if the reclosing times are equal to the setting value of AR number and the
tripping command is received again after the last reclosing pulse is issued, the reclosing shall
be considered as unsuccessful.
4. The logic setting [79.En_FailCheck] is available to judge whether the reclosing is successful
by CB state, when it is set as "1". If CB is still in open position with a time delay [79.t_Fail]
after the reclosing pulse is issued, the reclosing shall be considered as unsuccessful. For this
case, the device will issue a signal (79.Fail_Rcls) to indicate that the reclosing is
unsuccessful, and this signal will drop off after (Reset Command). AR will be blocked if the
reclosing shall be considered as unsuccessful.
SIG 79.On
&
SIG 79.Ready
SIG 79.AR_Blkd
>=1
SIG AR Pulse
&
[79.t_Fail] 0ms &
SIG CB closed
EN [79.En_FailCheck] &
& 79.Succ_Rcls
0 [79.t_Fail]
After unsuccessful AR is confirmed, AR will be blocked. AR will not enter into the ready state
unless the circuit breaker position drops off , and can only begin to enter into the ready state again
after the circuit breaker is closed.
3.20.5.5 Reclosing Numbers Control
The device may be set up into one-shot or multi-shot AR. Through the setting [79.N_Rcls], the
Date: 2017-08-17
3 Operation Theory
maximum number of reclosing attempts may be set up to 4 times. Generally, only one-shot AR is
selected. Some corresponding settings may be hidden if one-shot AR is selected.
1. 1-pole AR
[79.N_Rcls]=1 means one-shot reclosing. For one-shot 1-pole AR mode, 1-pole AR will be
initiated only for single-phase fault and respective faulty phase selected, otherwise, AR will be
blocked. For single-phase transient fault on the line, line protection device will operate to trip and
1-pole AR is initiated. After the dead time delay for 1-pole AR is expired, the device will send
reclosing pulse, and then the auto-reclosure will drop off after the time delay [79.t_Reclaim] to
ready for the next reclosing. For permanent fault, the device will operate to trip again after the
reclosing is performed, and the device will output the signal of reclosing failure [79.Fail_Rcls].
[79.N_Rcls]>1 means multi-shot reclosing. For multi-shot reclosing in 1-pole AR mode, the first
reclosing is 1-pole AR, and the subsequent reclosing can only be 3-pole AR. For single-phase
transient fault on the line, line protection device will operate to trip and then 1-pole AR is initiated.
After the dead time delay of the first reclosing is expired, the device will send reclosing pulse, and
then the auto-reclosure will drop off after the time delay [79.t_Reclaim] to ready for the next
reclosing. For permanent fault, the device will operate to trip again after the reclosing is performed,
and then 3-pole AR is initiated. At this time, the time delay applies the setting [79.t_Dd_3PS2].
After the time delay is expired, if the reclosing condition is met, the device will send reclosing
pulse. The sequence is repeated until the reclosing is successful or the maximum permit reclosing
number [79.N_Rcls] is reached. If the first fault is multi-phase fault, the device operates to trip
three-phase and initiate 3-pole AR. At this time, the time delay applies the setting [79.t_Dd_3PS1].
For the possible reclosing times of 3-pole AR in 1-pole AR mode, please refer to Table 3.20-2.
2. 3-pole AR
[79.N_Rcls]=1 means one-shot reclosing. For one-shot 3-pole AR mode, line protection device
will operate to trip when a transient fault occurs on the line and 3-pole AR will be initiated. After the
dead time delay for 3-pole AR is expired, the device will send reclosing pulse, and then the
auto-reclosure will drop off after the time delay [79.t_Reclaim] to ready for the next reclosing. For
permanent fault, the device will operate to trip again after the reclosing is performed, and the
device will output the signal of reclosing failure [79.Fail_Rcls].
[79.N_Rcls]>1 means multi-shot reclosing. For multi-shot reclosing in 3-pole AR mode, line
protection device will operate to trip when a transient fault occurs on the line and 3-pole AR will be
initiated. After the dead time delay of the first reclosing is expired, the device will send reclosing
pulse, and then the auto-reclosure will drop off after the time delay [79.t_Reclaim] to ready for the
next reclosing. For permanent fault, the device will operate to trip again after the reclosing is
performed, and then 3-pole AR is initiated after the tripping contact drops off. After the time delay
for AR is expired, the device will send reclosing pulse. The sequence is repeated until the
reclosing is successful or the maximum permit reclosing number [79.N_Rcls] is reached.
3. 1/3-pole AR
[79.N_Rcls]=1 means one-shot reclosing. For one-shot 1/3-pole AR mode, line protection device
will operate to trip when a transient fault occurs on the line and 1-pole AR will be initiated for
Date: 2017-08-17
3 Operation Theory
single-phase fault and 3-pole AR will be initiated for multi-phase fault. After respective dead time
delay for AR is expired, the device will send reclosing pulse, and then the auto-reclosure will drop
off after the time delay [79.t_Reclaim] to ready for the next reclosing. For permanent fault, the
device will operate to trip again after the reclosing is performed, and the device will output the
signal of reclosing failure [79.Fail_Rcls].
[79.N_Rcls]>1 means multi-shot reclosing. For multi-shot reclosing in 1/3-pole AR mode, line
protection device will operate to trip when a transient fault occurs on the line and AR will be
initiated. After the dead time delay of the first reclosing is expired, the device will send reclosing
pulse, and then the auto-reclosure will drop off after the time delay [79.t_Reclaim] to ready for the
next reclosing. For permanent fault, the device will operate to trip again after the reclosing is
performed, and then 3-pole AR is initiated after the tripping contact drops off. After the time delay
for AR is expired, the device will send reclosing pulse. The sequence is repeated until the
reclosing is successful or the maximum permit reclosing number [79.N_Rcls] is reached. For the
possible reclosing times of 3-pole AR in 1/3-pole AR mode, please refer to Table 3.20-2 .
The table below shows the number of reclose attempts with respect to the settings and AR
modes.
Duplicated protection configurations are normally applied for UHV lines. If reclosing function is
integrated within line protections, the auto-reclosing function can be enabled in any or both of the
line protections without coordination.
If both sets of reclosing functions are enabled, when one of them first recloses onto a permanent
fault, the other will block the reclosing pulse according to the latest condition of the faulty phase.
For one-shot AR mode, if the current is detected in the faulty phase, AR will be blocked
immediately to prevent the circuit breaker from repetitive reclosing. For multi-shot AR mode, if the
current is detected in the faulty phase, the current reclosing pulse will be blocked and go into the
next reclosing pulse logic automatically. If the maximum permitted reclosing number [79.N_Rcls]
is reached, the auto-reclosure will drop off after the time delay [79.t_Reclaim].
For one-shot or multi-shot AR, there is a corresponding reclosing counter at each stage. After
reclosing pulse is sent, the corresponding reclosing counter will plus 1 and the reclosing counter
may be cleared by the submenu "Clear Counter". If the circuit breaker is reclosed by other
Date: 2017-08-17
3 Operation Theory
devices during AR initiation, the auto-reclosure will go into the next reclosing pulse logic.
The following two examples indicate typical time sequence of AR process for transient fault and
permanent fault respectively.
Signal
Fault
Trip
CB 52b
Open
79.t_Reclaim [79.t_Reclaim]
79.Active
79.Inprog [79.t_Dd_1PS1]
79.Inprog_1P [79.t_Dd_1PS1]
79.Ok_Chk
AR Out [79.t_PW_AR]
79.Perm_Trp3P
79.Fail_Rcls
Time
Date: 2017-08-17
3 Operation Theory
Signal
Fault
Trip
Open Open
52b
79.t_Reclaim [79.t_Reclaim]
79.Active
79.Inprog
79.Inprog_1P [79.t_Dd_1PS1]
79.Inprog_3PS2 [79.t_Dd_3PS2]
79.Ok_Chk
79.Perm_Trp3P
79.Fail_Rcls 200ms
Time
3.20.6 Settings
Table 3.20-3 Settings of auto-reclosing
Date: 2017-08-17
3 Operation Theory
Date: 2017-08-17
3 Operation Theory
Date: 2017-08-17
3 Operation Theory
3.21.4 Logic
After tripping signal is issued, the tripping pulse will be kept as same as the setting [t_Dwell_Trp]
at least. When the time delay is expired, for phase-segregated tripping, the tripping signal will
drop off immediately if the faulty current of corresponding phase is less than 0.06In (In is
secondary rated current), otherwise the tripping signal will be always kept until the faulty current of
corresponding phase is less than 0.06In. For three-phase tripping, the tripping signal will drop off
immediately if three-phase currents are all less than 0.06In, otherwise the tripping signal will be
always kept until three-phase currents are all less than 0.06In.
Date: 2017-08-17
3 Operation Theory
SIG Ia>0.06In
0 t_Dwell_Trp
&
&
>=1 TrpB
50BF.Op_ReTrpB t_Dwell_Trp 0
SIG &
SIG Ib>0.06In
0 t_Dwell_Trp
&
&
>=1 TrpC
50BF.Op_ReTrpC t_Dwell_Trp 0
SIG &
SIG Ic>0.06In
>=1
>=1 Trp
0 t_Dwell_Trp
&
&
SIG 62PD.Op
All operation elements (except for re-tripping element) are 3 phase tripping elements.
Date: 2017-08-17
3 Operation Theory
EN [50/51Px.En_BlkAR]
>=1
EN 50/51Gx.En_BlkAR
SIG 62PD.Op
>=1 >=1
SIG 81U.UFx.Op TRP.BlkAR
SIG 81O.OFx.Op
SIG 50BF.Op_t2
3.21.5 Settings
Table 3.21-2 Settings of trip logic
VT circuit failure can be caused by many reasons, such as fuse blown due to short-circuit fault,
poor contact of VT circuit, VT maintenance and so on. The device can detect them and issue an
alarm signal to block relevant protection functions. However, the alarm of VT circuit failure should
not be issued when the following cases happen.
2. Only current protection functions are enabled and VT is not connected to the device.
Date: 2017-08-17
3 Operation Theory
Under normal conditions, the device detect residual voltage greater than 8% of Unn to determine
single-phase or two-phase VT circuit failure, and detect three times positive-sequence voltage
less than Unn to determine three-phase VT circuit failure. Upon detecting abnormality on VT
circuit, an alarm will comes up after a time delay of [VTS.t_DPU] and drop off with a time delay of
[VTS.t_DDO] after VT circuit restored to normal.
VT (secondary circuit) MCB auxiliary contact as a binary input can be connected to the binary
input circuit of the device. If MCB is open (i.e. [VTS.MCB_VT] is energized), the device will
consider the VT circuit is not in a good condition and issues an alarm without a time delay. If the
auxiliary contact is not connected to the device, VT circuit supervision will be issued with time
delay as mentioned in previous paragraph.
When VT is not connected into the device, the alarm will be not issued if the logic setting
[VTS.En_Out_VT] is set as "1". However, the alarm is still issued if the binary input [VTS.MCB_VT]
is energized, no matter that the logic setting [VTS.En_Out_VT] is set as "1" or "0".
When VT neutral point fails, third harmonic of residual voltage is comparatively large. If third
harmonic amplitude of residual voltage is larger than 0.2Unn and without operation of fault
detector element, VT neutral point failure alarm signal [VTNS.Alm] will be issued after a time delay
of [VTS.t_DPU] and drop off with a time delay of [VTS.t_DDO] after three phases voltage restored
to normal.
VTS VTNS
VTS.Blk VTNS.Blk
VTS.MCB_VT
Date: 2017-08-17
3 Operation Theory
logic etc.
VT neutral point supervision enabling input, it is triggered from binary input or
3 VTNS.En
programmable logic etc.
VT neutral point supervision blocking input, it is triggered from binary input or
4 VTNS.Blk
programmable logic etc.
5 VTS.MCB_VT Binary input for VT MCB auxiliary contact
No. Output Signal Description
1 VTS.Alm Alarm signal to indicate VT circuit fails
2 VTNS.Alm Alarm signal to indicate VT neutral point fails
3.22.5 Logic
SIG 3U0>0.08Unn
>=1
SIG 3U1<Unn &
>=1 If FD.Pkp OR 79.Inprog operate, then
EN [VTS.En_LineVT] & circuit of time delay will be interrupted.
BI [VTS.MCB_VT]
>=1
& VTS.Alm
EN [VTS.En]
&
SIG [VTS.En]
SIG [VTS.Blk]
&
SIG FD.Pkp >=1
SIG 79.Inprog
If FD.Pkp OR 79.Inprog operate, then
circuit of time delay will be interrupted.
OTH U03>0.2Unn & >=1
[VTS.t_DPU] [VTS.t_DDO] & VTNS.Alm
EN [VTS.En_Out_VT]
EN [VTS.En]
&
SIG [VTNS.En]
SIG [VTNS.Blk]
If fault detector element operates or automatic reclosing cycle is in progress, and VT circuit failure
signal have been detected, then the VT circuit failure signal will be maintained, only when the fault
detector element and automatic reclosing element are all drop-off, VT circuit supervision will
return to normal operation.
Date: 2017-08-17
3 Operation Theory
SIG U2 > 8V
≥1
SIG U1 < 30V
&
SIG Ia > 0.04In
SIG Ib > 0.04In ≥1
SIG Ic > 0.04In
& 1.25s 0
[YYYY.Alm_VTS_Measmt]
EN [YYYY.En_Alm_VTS]
3.22.6 Settings
Table 3.22-2 VTS settings
Under a normal condition, secondary current input for measurement is continuously supervised by
detecting the residual and negative-sequence current. If the residual current is larger than 0.06A
Date: 2017-08-17
3 Operation Theory
or the negative-sequence current is greater than 0.10A, a CT circuit error is considered. The
related functions are going to be blocked and an alarm will be issued with a time delay of 1.25s
and drop off with a time delay of 10s after the error disappears.
CTS
CTS.En CTS.Alm
CTS.Blk
3.23.5 Logic
SIG 3I0>0.1In
&
SIG 3U0<3V
SIG IA<0.06In
>=1
SIG IB<0.06In
SIG IC<0.06In
EN [YYYY.En_Alm_CTS]
Date: 2017-08-17
3 Operation Theory
Date: 2017-08-17
4 Supervision
4 Supervision
Table of Contents
4 Supervision ........................................................................................ 4-a
4.1 BCU Supervision Alarm ................................................................................... 4-1
4.2 GOOSE Alarm ................................................................................................... 4-6
List of Tables
Table 4.1-1 BCU supervision alarm ........................................................................................... 4-1
Date: 2017-08-17
4 Supervision
Date: 2017-08-17
4 Supervision
A minor abnormality may block a certain number of functions while the other functions can still
work. However, if a severe hardware failure is detected, all functions will be blocked, the LED
“HEALTHY” will be extinguished, and the output contact “BO_FAIL”, which locates in the PWR
module, will be electrified. Therefore, this device can no longer be in service and maintenance is
required to eliminate the failure. The alarm signals and their corresponding troubleshooting
suggestions are listed below.
NOTICE!
If the device is blocked or an alarm signal is issued, please find out its reason with the
help of self-diagnostic record. If the reason cannot be found at site, please inform the
local service or the manufacturer.
NOTICE!
"YYYY" is the function name substitution for bay identification such as "BayMMXU",
"Bus1_MMXU", "Bay1_MMXU", "Sum_MMXU", etc.
Access Path: “MainMenu” -> “Status” -> “Superv State” -> “BCU Superv".
Date: 2017-08-17
4 Supervision
Date: 2017-08-17
4 Supervision
Date: 2017-08-17
4 Supervision
Date: 2017-08-17
4 Supervision
Date: 2017-08-17
4 Supervision
Date: 2017-08-17
4 Supervision
Access Path: “MainMenu” -> “Status” -> “Superv State” -> “GOOSE Superv”.
NOTICE!
"ZZZZ" refers to the a link identification name which can be configured through the
corresponding label setting (Access path: “MainMenu” -> “Settings” -> “Device Setup” ->
“Label Settings”).
Date: 2017-08-17
4 Supervision
Date: 2017-08-17
5 Management
5 Management
Table of Contents
5 Management ......................................................................................5-a
5.1 Protection Measurement ................................................................................ 5-1
5.2 BCU Measurement .......................................................................................... 5-1
5.3 Event Recording .............................................................................................. 5-1
5.3.1 Overview .............................................................................................................................. 5-1
Date: 2017-08-17
5 Management
Date: 2017-08-17
5 Management
The menu "Measurement2" is used to display measured values from fault detector DSP in
secondary value.
This device performs continuous measurement of the analogue input quantities. The current full
scale of relay is 40 times of rated current, and there is no effect to the performance of IED due to
overflowing of current full scale. The device samples 24 points per cycle and calculates the RMS
value in each interval and updated the LCD display in every 0.5 second. The measurement data
can be displayed on the LCD of the relay front panel or on the local/remote PC via software tool.
Navigate the menu to view the sampling value through LCD screen.
This device performs continuous measurement of analog inputs. The device samples multiple
points per cycle, calculates RMS values in each interval, and updates the LCD display in every
0.5s. The measurement can be displayed on the LCD of the device HMI panel and transmitted to
local/remote control centre.
Date: 2017-08-17
5 Management
5.4.2 Design
A disturbance record consists of fault record and fault waveform. A disturbance record can be
initiated by fault detector element, tripping element, reclosing element or configurable signal
[BI_TrigDFR].
1. Sequence number
Each operation will be recorded with a sequence number in the record and displayed on LCD
screen.
The time resolution is 1ms using the relay internal clock synchronized via clock synchronized
device if connected. The date and time is recorded when a system fault is detected.
An operating time (not including the operating time of output relays) is recorded in the record.
4. Faulty phase
5. Protection elements
Date: 2017-08-17
5 Management
Each fault record consists of all analog and digital quantities related to protection, such as original
current and voltage, differential current, alarm elements, and binary inputs and etc.
Each time recording includes 12-cycle pre-fault waveform, and 250 cycles at least and 500 cycles
at most can be recorded. Each cycle waveform is high-frequency recording at a rate of 1200Hz
(24 poingts per cycle).
Each time recording includes several-cycle waveform before triggering (the waveform cycle
number is configured via the communication setting [Num_Cyc_PreTrigDFR], the default value is
12-cycle), and 250 cycles at most can be recorded. Each cycle waveform is high-frequency
recording at a rate of 1200Hz or 1440Hz (24 poingts per cycle).
Date: 2017-08-17
5 Management
Date: 2017-08-17
6 Hardware
6 Hardware
Table of Contents
6 Hardware ............................................................................................6-a
6.1 Overview .......................................................................................................... 6-1
6.2 Module Configuration (for EXAMPLE only)................................................... 6-2
6.3 Plug-In Module Description ............................................................................ 6-3
6.3.1 MON Module (Management & Monitoring) .......................................................................... 6-3
List of Figures
Figure 6.1-1 Hardware diagram ................................................................................................. 6-1
Date: 2017-08-17
6 Hardware
Date: 2017-08-17
6 Hardware
6.1 Overview
PCS-9705 adopts 32-bit microchip processor as the control core for management and monitoring
function, meanwhile, adopts high-speed digital signal processor DSP for calculation. 80 points are
sampled in every cycle and parallel processing of sampled data can be realized in each sampling
interval to ensure ultrahigh reliability and safety of the device.
This device is developed on the basis of NR's latest software and hardware platform, and this new
platform provides high reliability, networking and great capability for anti-interference.
Output Relay
Binary Input
External
Protection
Conventional CT/VT A/D Calculation
DSP
ECVT
Fault
A/D Detector Pickup
DSP Relay
ECVT
ETHERNET
LCD +E
Clock SYN
Power
Uaux LED CPU
Supply
RJ45
Keypad
PRINT
The working process of the device is shown in above figure: current and voltage from
conventional CT/VT are converted into small voltage signal and sent to DSP module after filtered
and A/D conversion for calculation (ECVT signal is sent to the device without any conversion).
When DSP module completes all the calculation, the result will be recorded in the CPU on MON
module. DSP module carries out fault detector, logic calculation, tripping output, and MON module
perfomes SOE (Sequence Of Event) recording, waveform recording, printing, device internal and
external communication. When fault detector detects a fault and picks up, the positive power
supply for output relay will be available.
The items can be flexibly configured depending on the situations like sampling method of the
device (conventional CT/VT or ECT/EVT), and the mode of binary output (conventional binary
output or GOOSE binary output). The configurations for PCS-9705 based on microcomputer are
classified into standard and optional modules.
Date: 2017-08-17
6 Hardware
MON module provides management and monitoring functions, such as SAS communication,
event recording, setting modification, etc. Station level GOOSE message can also be
received by MON module.
DSP module performs filtering, sampling, protection and fault detector calculation.
AC AI module converts AC current and voltage from CT/VT to small voltage signal.
BO module provides output contacts assigned for protection tripping, remote control and
signalisation.
PWR module converts 110~250Vdc into various low level DC voltage for modules and
electronic components.
NOTICE!
This section shows several examples of device terminal view and module
arrangement.
The following figures should NOT be used as reference for device configuration or
wiring design. For such purpose, please use the latest corresponding Manufacture
Ordering Table and consult our design department.
Date: 2017-08-17
6 Hardware
DSP module 2
DSP module 1
DC AI module
AC AI module
MON module
PWR module
BO module
BI module
Slot No.
B01 B02 B03 B04 B05 B06 B07 B08 B09 B10 B11 B12 B13 B14 B15 P1
CAUTION!
Do NOT look into the end of an optical fiber connected to an optical port.
Date: 2017-08-17
6 Hardware
NR1110B
The BCU-DSP module (NR1115) is resposible for remote and manual closing with synchronism
check. It is fixed at the slot 03.
The PROT-DSP module (NR1161) is fixed at the slot 04. It consists of double high-performance
digital signal processors, 16-digit high-accuracy A/D converter that can perform synchronous
sampling and manage other peripherals. One of double DSP is responsible for protection
calculation, and can fulfill analog data acquisition, protection logic calculation and tripping output.
The other is responsible for fault detector, and can fulfill analog data acquisition, fault detector and
providing power supply to output relay.
If the DSP module is connected with conventional CT/VT, it can perform the synchronous data
acquisition through AC AI module. if the module is connected with ECT/EVT, it can receive
real-time synchronous sampled value from merging unit through NET-DSP module.
Date: 2017-08-17
6 Hardware
NR1115 NR1161
For AC AI module, if the plug is not put in the socket, external CT circuit is closed itself as shown
below.
Plug
Socket
In
Out
Date: 2017-08-17
6 Hardware
In
Out
NOTICE!
The rated value and the linear range of the input current transformer are optional: 1A or
5A. Please declare the CT rated value and linear range when placing the order. It is
necessary to check whether the current transformer inputs are in accordance with the
demand of practical engineering before putting the device into operation.
NOTICE!
CT Requirement
Date: 2017-08-17
6 Hardware
Rated short-time thermal current Ith and rated dynamic current Idyn
Performance verification
Date: 2017-08-17
6 Hardware
For example:
= 30×5×(1+60/25)=510V
Esl′ = 2×Ipcf×Isn×(Rct+Rb)/Ipn
= 2×Ipcf ×Isn×(Rct+(Rr+2×RL+Rc))/Ipn
= 2×40000×5×(1+(0.1+2×0.5+0.1))/2000=440V
The NR1425B provides 6 channels of 20mA/10V inputs. The NR1425C provides 4 channels of
20mA/10V and 2 channels of 220V inputs.
The different input ranges of DC analog input can be selected in using the corresponding jumpers
(short-circuit link) on the module.
X = A, B, C, D, E, F
Date: 2017-08-17
6 Hardware
01
NR1425 02
+ 03
DC input 1
- 04
05
06
+ 07
DC input 2
- 08
09
10
+ 11
DC input 3
- 12
13
+ 14
DC input 4
- 15
16
+ 17
DC input 5
- 18
19
DC input 6 + 20
- 21
22
NOTICE!
NR1503
Each BI module is with a 22-pin connector for 11 binary inputs, and its rated voltage can be
selected to be 110Vdc, 125Vdc, 220Vdc. Each binary input of NR1503 has independent
negative power input of opto-coupler and can be configurable. NR1503A′s pickup voltage and
dropoff voltage are fixed value, and the range is from 55%Un to 70%Un.
Date: 2017-08-17
6 Hardware
BI_01 01
NR1503 Opto01- 02
BI_02 03
Opto02- 04
BI_03 05
Opto03- 06
BI_04 07
Opto04- 08
BI_05 09
Opto05- 10
BI_06 11
Opto06- 12
BI_07 13
Opto07- 14
BI_08 15
Opto08- 16
BI_09 17
Opto09- 18
BI_10 19
Opto10- 20
BI_11 21
Opto11- 22
Date: 2017-08-17
6 Hardware
NR1504
Each BI module is with a 22-pin connector for 18 binary inputs, and its rated voltage can be
selected to be 110Vdc, 125Vdc, 220Vdc. All binary inputs of NR1504A share one common
negative power input and can be configurable. NR1504A′s pickup voltage and dropoff voltage
are fixed value, and the range is from 55%Un to 70%Un.
Opto+ 01
NR1504 BI_01 02
BI_02 03
BI_03 04
BI_04 05
BI_05 06
BI_06 07
08
BI_07 09
BI_08 10
BI_09 11
BI_10 12
BI_11 13
BI_12 14
15
BI_13 16
BI_14 17
BI_15 18
BI_16 19
BI_17 20
BI_18 21
COM- 22
[BI_n] can be configured as a specified binary input by PCS-Explorer software (n=01, 02, ……).
Terminal description for NR1504 is shown as follows.
Date: 2017-08-17
6 Hardware
01
BO_01
NR1521 02
03
BO_02
04
05
BO_03
06
07
BO_04
08
09
BO_05
10
11
BO_06
12
13
BO_07
14
15
BO_08
16
17
BO_09
18
19
BO_10
20
21
BO_11
22
Date: 2017-08-17
6 Hardware
NOTICE!
NOTICE!
However, the signals which will control the circuit breaker directly or initate breaker
failure protection can be configured to output contacts that are NOT controlled by fault
detector:
Related signals with voltage switchover and synchrocheck and related signals with
AR except reclosing signal and AR failure signal.
The use of an external miniature circuit breaker is recommended. The miniature circuit breaker
must be in the on position when the device is in operation and in the off position when the device
is in cold reserve.
NOTICE!
The standard rated voltage of PWR module is self-adaptive to 88~300Vdc. If the input
voltage is out of range, an alarm signal (Fail_Device) will be issued. For a non-standard
rated voltage PWR module, please specify when placing order and check if the rated
voltage is the same before putting the device into service.
NOTICE!
The PWR module provides the pin No.12 and a grounding screw for device grounding.
The pin shall be connected to grounding screw and then connected to the earth copper
bar of panel via dedicated grounding wire. Effective grounding is the most important
Date: 2017-08-17
6 Hardware
measure for a device to prevent EMI, so effective grounding must be ensured before
the device is put into service.
NOTICE!
This device, like almost all electronic equipments, contains electrolytic capacitors.
These capacitors are well known to be subject to deterioration over time if voltage is
not applied periodically. Deterioration can be avoided by powering the device up at
least once a year.
NR1301
5V OK ALM
BO_ALM BO_FAI L
1 BO_COM1
2 BO_FAIL
3 BO_ALM
4 BO_COM2
5 BO_FAIL
6 BO_ALM
7 OPTO+
8 OPTO-
9
10 PWR+
11 PWR-
12 GND
The pin definition of the connector fixed on the PWR module is described as below.
9 Empty
Date: 2017-08-17
6 Hardware
Date: 2017-08-17
6 Hardware
Date: 2017-08-17
7 Settings
7 Settings
Table of Contents
7 Settings ..............................................................................................7-a
7.1 System Settings .............................................................................................. 7-1
7.1 Protection Settings ......................................................................................... 7-1
7.1.1 FD Settings .......................................................................................................................... 7-2
Date: 2017-08-17
7 Settings
Date: 2017-08-17
7 Settings
NOTICE!
NOTICE!
"YYYY" in the following tables is the wildcard of bay identification that can be set by the
software PCS-Explorer.
NOTICE!
"BXX" in the following tables signifies the module at the No.XX slot.
Date: 2017-08-17
7 Settings
7.1.1 FD Settings
No. Name Range Step Unit Remark
Current setting of DPFC current fault detector
1 FD.DPFC.I_Set (0.050~30.000)×In 0.001 A
element
Current setting of residual current fault detector
2 FD.ROC.3I0_Set (0.050~30.000)×In 0.001 A
element
Current setting of negative-sequence current fault
3 FD.NOC.I2_Set (0.050~30.000)×In 0.001 A
detector element
Enabling/disabling negative-sequence current
fault detector element
4 FD.NOC.En 0 or 1
0: disable
1: enable
Date: 2017-08-17
7 Settings
Date: 2017-08-17
7 Settings
Date: 2017-08-17
7 Settings
Date: 2017-08-17
7 Settings
Date: 2017-08-17
7 Settings
7.1.4 OC Settings
No. Name Range Step Unit Remark
Setting of second harmonic component for
1 50/51P.K_Hm2 0.000~1.000 0.001
blocking phase overcurrent elements
Current setting for stage 1 of phase
2 50/51P1.I_Set (0.050~30.000)×In 0.001 A
overcurrent protection
Time delay for stage 1 of phase overcurrent
3 50/51P1.t_Op 0.000~20.000 0.001 s
protection
Enabling/disabling stage 1 of phase
overcurrent protection
4 50/51P1.En 0 or 1
0: disable
1: enable
5 50/51P1.En_BlkAR 0 or 1 Enabling/Disabling auto-reclosing blocked
Date: 2017-08-17
7 Settings
Date: 2017-08-17
7 Settings
Date: 2017-08-17
7 Settings
Date: 2017-08-17
7 Settings
Date: 2017-08-17
7 Settings
7.1.6 PD Settings
No. Name Range Step Unit Remark
Current setting of residual current criterion
1 62PD.3I0_Set (0.050~30.000)×In 0.001 A
for pole discrepancy protection
Current setting of negative-sequence current
2 62PD.I2_Set (0.050~30.000)×In 0.001 A
criterion for pole discrepancy protection
3 62PD.t_Op 0.000~600.000 0.001 s Time delay of pole discrepancy protection
Enabling/disabling pole discrepancy
protection
4 62PD.En 0 or 1
0: disable
1: enable
Date: 2017-08-17
7 Settings
Date: 2017-08-17
7 Settings
Date: 2017-08-17
7 Settings
Date: 2017-08-17
7 Settings
Date: 2017-08-17
7 Settings
Date: 2017-08-17
7 Settings
Date: 2017-08-17
7 Settings
2 YYYY.En_Alm_ROV 0 or 1 1
4 YYYY.En_Alm_UV 0 or 1 1
6 Cur3P.Opt_CT_Measmt 0 or 1 1
7 Vol3P.Opt_UN 0 or 1 1
8 Cur3P.Opt_IN 0 or 1 1
9 YYYY.En_Alm_VTS 0 or 1 1
10 YYYY.En_Alm_CTS 0 or 1 1
YYYY.Th_ZeroDrift
Zero drift threshold to limit the variation influence (of voltage and current) due to temperature
or other environmental factor. Variation less than this setting will be regarded as a zero drift
and ignored.
YYYY.En_Alm_ROV
YYYY.UN_Alm_ROV
This setting is expressed as a percentage for the emission threshold of the alarm
[YYYY.Alm_ROV].
If (
[YYYY.En_Alm_ROV] = 1,
If (
[YYYY.Alm_ROV] = 1,
Date: 2017-08-17
7 Settings
YYYY.En_Alm_UV
YYYY.U_Alm_UV
This setting is expressed as a percentage for the emission threshold of the alarm
[YYYY.Alm_UV].
If (
[YYYY.En_Alm_UV] = 1,
If (
[YYYY.Alm_UV] = 1,
Cur3P.Opt_CT_Measmt
"1": Inputs Ia and Ic are enough for current measurement (i.e.: Ib is unnecessary).
"0": Inputs Ia, Ib & Ic are all necessary for current measurement.
Vol3P.Opt_UN
If (
[Vol3P.Opt_UN] = 0
Else if (
Date: 2017-08-17
7 Settings
[Vol3P.Opt_UN] = 1
/* Vector summation */
Cur3P.Opt_IN
If (
[Cur3P.Opt_IN] = 0
Else if (
[Cur3P.Opt_IN] = 1
/* Vector summation */
YYYY.En_CTRevPolarity
YYYY.En_Alm_VTS
YYYY.En_Alm_CTS
DPOS.t_Alm
If alarm function for [DPOS**] is enabled, and corresponding NO contact & NC contact are
Date: 2017-08-17
7 Settings
both open or close for the duration which is greater than "[DPOS.t_DPU_**] + [DPOS.t_Alm]",
an alarm signal named [DPOS.Alm] will be issued.
1 25.Opt_Mode_SynChk 0 or 1 1
7 25.Opt_Mode_DdChk 1~7 1
8 25.En_VTS_Blk_DdChk 0 or 1 1
9 25.En_VTS_Blk_SynChk 0 or 1 1
NoVoltSel, DblBusOneCB,
16 CBConfigMode
3/2BusCB, 3/2TieCB
25.Opt_Mode_SynChk
"0" Normal;
"1" The phase difference is fixed at 1 degree for the synchronization check
25.U_UV
If either side of CB voltage for synchronization check is less than this setting, CB closing will
be disabled.
Date: 2017-08-17
7 Settings
25.U_UH
If either side of CB voltage for synchronization check is more than this setting, CB closing will
be disabled.
25.U_Diff
If the voltage difference between both sides of the CB for synchronization check is greater
than this setting, CB closing will be disabled.
Date: 2017-08-17
7 Settings
25.f_Diff
Threshold of frequency difference between both sides of the CB (Δf = |f-fsyn|) for
synchronization check.
If the Δf between both sides of the CB is greater than this setting, CB closing will be disabled.
25.df/dt
Threshold of df/dt (change rate of frequency difference) between both sides of the CB for
synchronization check.
If the df/dt between both sides of the CB is greater than this setting, CB closing will be
disabled.
25.Opt_Mode_DdChk
1 Both the incoming side and the reference side adopt dead check.
2 The incoming side adopts live check and the reference side adopts dead check.
3 The incoming side adopts dead check and the reference side adopts live check.
The incoming side adopts live check and the reference side adopts dead check.
6 Or:
The incoming side adopts dead check and the reference side adopts live check.
The incoming side adopts live check and the reference side adopts dead check.
Or:
7 The incoming side adopts dead check and the reference side adopts live check.
Or:
Both the incoming side and the reference side adopt dead check.
[25.Opt_Mode_DeadChk] will only be valid when this device is set to work in "dead check
mode".
In the above table, the criterion for dead check is: a voltage will be regarded as dead if it is
less than [25.U_DeadChk]. The criterion for live check is: a voltage will be regarded as live if it
is greater than [25.U_LiveChk].
25.phi_Diff
Threshold of phase-angle difference between both sides of the CB for synchronization check.
If the phase-angle difference between the 2 voltages on both sides of the CB is greater than
this setting, CB closing will be disabled.
Date: 2017-08-17
7 Settings
25.En_VTS_Blk_DdChk
"1/0": Enable/Disable the block function of dead check mode if there is alarm of VT circuit
failure.
25.En_VTS_Blk_SynChk
"1/0": Enable/Disable the block function of synchronization check mode if there is alarm of VT
circuit failure.
25.t_Reset
Duration of synchronization check. The check will not precede any longer out of this range.
25.U_DdChk
In "dead check mode", a voltage will be regarded as dead if it is less than this setting.
25.U_LvChk
In "dead check mode", a voltage will be regarded as live if it is greater than this setting.
25.phi_Comp
Compensation angle for incoming voltage during synchronization check. The summation of
the reference voltage angle and this setting will be compared with the incoming voltage angle.
3) Other factors.
25.t_Close_CB
It is the time from receiving closing command pulse until the CB is completely closed.
CBConfigMode
3/2BusCB: bus side circuit breaker for one and a half breakers
3/2TieCB: line side circuit breaker for one and a half breakers
Date: 2017-08-17
7 Settings
7.2.3 BI Settings
"DPU" is the abbreviation of "Delay Pick Up". "t_DPU" refers to "debouncing time".
CSWI**.t_DPU_DPS
In order to prevent the situation that NO contact & NC contact are both opened or closed
during CB/DS/ES operation process, these debouncing time settings should be configured
to be greater than the duration.
Access path of [DPOS**] is "MainMenu" -> "Status" -> "Inputs" -> "DPS Inputs".
For CB: NO contact refers to 52a contact; NC contact refers to 52b contact;
For DS: NO contact refers to 89a contact; NC contact refers to 89b contact;
For ES: NO contact refers to 57a contact; NC contact refers to 57b contact.
Bxx.t_DPU_BI_**
In this device, each binary input has an independent debouncing time setting.
The debouncing time (also called delay pickup time) of binary input is the duration for
confirming binary input state, i.e.: if binary input state changes and remains unchanged
during the duration, and then the binary input state will be confirmed by the device.
7.2.5 TP Settings
1 84.Num_Tap_Pos 0~26 1
2 84.Code_Tap_Pos 0~3 1
4 84.En_EmergStop_Tap_Pos 0 or 1 1
Date: 2017-08-17
7 Settings
84.Num_Tap_Pos
The maximum number of transformer’s tap position, it will take effect only when
[84.Code_Tap_Pos] =3:
84.Code_Tap_Pos
This is the access mode selection of the tap position of the transformer.
1) "0": No binary inputs will be used for Tap Position Indication (abbreviated as TPI).
Binary input 15 is the least significant bit however binary input 20 is the most significant
bit. The first 4 bits are for binary numbers while the 5th bit and the 6th bit represent ten
and twenty respectively.
a) If the transformer tap position is 5, then binary inputs 20 to 15 indicate as "00 0101".
b) If the transformer tap position is 15, then binary inputs 20 to 15 indicate as "01 0101".
c) If the transformer tap position is 25, then binary inputs 20 to 15 indicate as "10 0101".
3) "2": Binary inputs 15 to 24 will be used to indicate "0~9", binary inputs 25, 26 and 27
denote the tap position lower than 10 or between 10 to 19 or over 19 respectively. Binary
inputs 28 to 40 will not be used.
4) "3": Binary inputs 15 to 40 represent tap positions 1 to 26 respectively. Only one binary
input would be set as 1 among binary inputs 15 to 40.
Date: 2017-08-17
7 Settings
84.t_DPU_Tap_Pos
This is the duration for confirming transformer tap position (abbreviated as TP). If TP changes
and remains unchanged for this duration, the TP will be confirmed. Otherwise, the binary
input state will not be confirmed.
84.En_EmergStop_Tap_Pos
Enable/Disable the function to stop slip of TP immediately. During tap changer control
process, if "slip TP" occurs, the TP will be out of control, and it will step up or down
continuously.
84.t_EmergStop_Tap_Pos
NOTICE!
The function is used to maintain this device and has already been configured by the
manufacturer. It is strongly recommended NOT to adjust it.
Date: 2017-08-17
7 Settings
19 CBWear.Wear_01 0 0~10000 1
20 CBWear.Wear_02 4 0~10000 1
21 CBWear.Wear_03 33 0~10000 1
22 CBWear.Wear_04 92 0~10000 1
CBWear.Th_Wear
This is the CB wear alarm threshold. If one of the wear statistic status (i.e.: "CBWear.Stat",
"CBWear.Stat_A", "CBWear.Stat_B" and "CBWear.Stat_C") is greater than the threshold, the
alarm will be issued.
CBWear.t_Stat
This is the CB position changing period (from closing to opening). It should be greater than
the arc-suppression time.
Date: 2017-08-17
7 Settings
CBWear.Ibrk_**
CBWear.Wear_**
1 Link_BO 0 or 1 1
2 Link_IgnExtIntlck 0 or 1 1
3 25.Link_DdChk 0 or 1 1
4 25.Link_SynChk 0 or 1 1
5 Link_** 0 or 1 1
Link_BO
Link_IgnExtIntlck
Enable/Disable interlock logic from external bay. If this setting is "0", all the interlock logic
from external bay will be considered as satisfied.
These logic links cooperate to determine Synchronism check mode for CB closing. Please
refer to "Synchronism check (25)" in Chapter 3 for more details.
Link_**
Date: 2017-08-17
7 Settings
process layer.
NOTICE!
These links are aim to avoid issuing disconnection alarms if the relevant GOOSE
channel is empty due to some situations such as remote device is out of service.
1 Link_Spare* 0 or 1 Enable/Disable the corresponding customized logic link for BCU functions.
Opt_Caption_103
Select the caption language sent to SAS via IEC 103 protocol.
En_RevCT_Prot
En_RevCT_Measmt
Un_BinaryInput
This setting is used to set the voltage level of binary input module.
En_MDisk
A moveable mdisk is implemented on the MON plug-in module to backup and restore
programs, settings and configurations.
Date: 2017-08-17
7 Settings
If MON plug-in module is broken, remove the mdisk and put it into a new MON plug-in
module, use the menu on HMI to restore the backup programs and configurations. If DSP
plug-in module is broken, after a new DSP plug-in module is installed, use the menu on HMI
to restore the backup programs and configurations. If the moveable mdisk is broken, after a
new mdisk is installed on the MON plug-in module, use the menu on HMI to back up the
current programs and configurations into the new mdisk. The default setting is 0
9 IP_LAN4 000.000.000.000~255.255.255.255
10 Mask_LAN4 000.000.000.000~255.255.255.255
11 En_LAN4 Disable or enable
12 Gateway 000.000.000.000~255.255.255.255
13 En_Broadcast Disable or enable
14 Addr_RS485A 0~255
15 Baud_RS485A 4800,9600,19200,38400,57600,115200 (bps)
16 Protocol_RS485A IEC103, Modbus, DNP, DLT645, Resv*
17 Addr_RS485B 0~255
18 Baud_RS485B 4800,9600,19200,38400,57600,115200 (bps)
20 Threshold_Measmt_Net 0~100%
21 Period_Measmt_Net 0~65535s
22 Format_Measmt 0, 1
23 Cfg_NetPorts_Bond 0, 3, 5, 6, 9, 10, 12
25 IP_Server_SNTP 000.000.000.000~255.255.255.255
26 IP_StandbyServer_SNTP 000.000.000.000~255.255.255.255
27 En_Server_SNTP 0 or 1
28 OffsetHour_UTC -12~+12 (hrs)
29 OffsetMinute_UTC 0~60 (min)
30 Opt_Display_Status PriValue, SecValue
31 Num_Cyc_PreTrigDFR 0~140 (cycles)
32 Opt_NetMode STP, PRP, HSR, Resv*
Date: 2017-08-17
7 Settings
Date: 2017-08-17
7 Settings
They are used for Ethernet communication based on the IEC 60870-5-103 protocol. When
the IEC 61850 protocol is applied, the IP address of Ethernet A will be GOOSE source MAC
address.
Gateway
En_Broadcast
This setting is only used only for IEC 60870-5-103 protocol. If NR network IEC 60870-5-103
protocol is used, the setting must be set as "1".
Addr_RS485A, Addr_RS485B
They are the device′s communication addresses via serial ports (port A and port B).
Baud_RS485A, Baud_RS485B
Protocol_RS485A, Protocol_RS485B
NOTICE!
Above table listed all the communication settings, the device delivered to the user
maybe only show some settings of them according to the communication interface
configuration. If only the Ethernet ports are applied, the settings about the serial ports
(port A and port B) are not listed in this submenu. And the settings about the Ethernet
ports only listed in this submenu according to the actual number of Ethernet ports.
The standard arrangement of the Ethernet port is two, at most four (predetermined
when ordering). Set the IP address according to actual arrangement of Ethernet
numbers and the un-useful port/ports need not be configured. If PCS-Explorer
configuration tool is connected with this device through the Ethernet, the IP address of
PCS-Explorer must be set as one of the available IP address of this device.
Threshold_Measmt_Net
This is the threshold to send measurement values to SCADA or gateway through IEC
60870-5-103 or IEC61850 protocol.
Period_Measmt_Net
This is the timing period for this device to send measurement data to SCADA or gateway
Date: 2017-08-17
7 Settings
Format_Measmt
The setting is used to select the format of measurement data sent to SCADA through IEC
60870-5-103 protocol.
1: GDD data type through IEC103 protocol is 7, i.e. 754 short real number of IEEE standard
Cfg_NetPorts_Bond
Use this setting to set the channel bonding arrangement of two Ethernet ports in station level
communication link.
For redundancy or increased throughput of the communication, dual network structure may
be adopted along with channel bonding technology. These two bonded interfaces, who share
the identical IP address and MAC address, work in Active-Standby mode. If the link via active
interface fails, the link via original standby interface will be activated automatically to ensure a
reliable communication.
The value of this setting represents a 4-bits binary number. Each bit represents a
corresponding Ethernet port's bonding status. Use the following map to decide the specific
setting value. Additionally, the default value "0" means the channel bonding function is
deactivated.
Ethernet port 1 Ethernet port 2 Ethernet port 1 Ethernet port 3 Ethernet port 1 Ethernet port 4
0 0 1 1 3 0 1 0 1 5 1 0 0 1 9
Bonding Bonding Bonding
Ethernet port 2 Ethernet port 3 Ethernet port 2 Ethernet port 4 Ethernet port 3 Ethernet port 4
0 1 1 0 6 1 0 1 0 10 1 1 0 0 12
Ethernet port 1: Bit0, Ethernet port 2: Bit1, Ethernet port 3: Bit2, Ethernet port 4: Bit3
Take the device Ethernet ports 1 & 2 for example and assume that P1 is connected to NET1
while P2 is connected to NET2.
After the device is powered on, only P1 is activated when both NET1 and NET2 are
Date: 2017-08-17
7 Settings
normal.
If NET1 is abnormal, P2 cannot be activated if NET2 is also abnormal. The device will
keep trying on P1.
If P2 is working, the device will maintain this state even if NET1 has been restored to
normal. It will be switched to P1 only if NET2 is abnormal.
Opt_TimeSyn
Conventional
PPS (RS-485): Pulse per second (PPS) via RS-485 differential level
PPM (DIN): Pulse per minute (PPM) via a configurable binary input
PPS (DIN): Pulse per second (PPS) via a configurable binary input
SAS
Advanced
NoTimeSyn
When no time synchronization signal is connected to the device, please select this
option and the alarm message [Alm_TimeSyn] will not be issued anymore.
"Conventional" mode and "SAS" mode are always supported, but "Advanced" mode is only
supported when NET-DSP module is equipped.
Date: 2017-08-17
7 Settings
When "NoTimeSyn" mode is selected, the device will not send alarm signals without time
synchronization signal. However, the device can still be synchronized when receiving
time synchronization signal.
IP_Server_SNTP
This is the address of the SNTP time synchronization server which sends SNTP timing
messages to the device.
IP_StandbyServer_SNTP
OffsetHour_UTC, OffsetMinute_UTC
If the IEC61850 protocol is adopted, the time tags of communication message are required
according to UTC (Universal Time Coordinated) time.
The setting [OffsetHour_UTC] is used to set the hour offset of the current time zone to the
GMT (Greenwich Mean Time) zone; for example, if the device is applied in China, the time
zone of China is east 8th time zone, so this setting will be "8".
The setting [OffsetMinute_UTC] is used to set the minute offset of the current time zone to
the GMT zone.
Time zone GMT zone East 1st East 2nd East 3rd East 4th East 5th
Setting 0 1 2 3 4 5
Time zone East 6th East 7th East 8th East 9th East 10th East 11th
Setting 6 7 8 9 10 11
Time zone East/West 12th West 1st West 2nd West 3rd West 4th West 5th
Setting 12/-12 -1 -2 -3 -4 -5
Time zone West 6th West 7th West 8th West 9th West 10th West 11th
Setting -6 -7 -8 -9 -10 -11
Date: 2017-08-17
7 Settings
Opt_Display_Status
This setting is used to set display mode of current and voltage in fault records, primary value
or secondary value. The sampled values of current and voltage are displayed as secondary
value by default. When it is set as primary value, both secondary voltage and secondary
current are converted into primary voltage and primary current according to rated secondary
and primary value of VT and CT respectively.
Num_Cyc_PreTrigDFR
The setting is used to set the cycle number recorded by the device before the trigger element
operating.
Opt_NetMode
Resv: Reserved
During the device initialization, the network mode is checked. If the actual network mode is
different with the setting, the alarm "Alm_Version" will be issued. When actual network mode
is correct, please modify the setting to the correct value. When actual network mode is wrong,
please modify the setting as “Resv” firstly and then modify the setting to the correct value.
NOTICE!
IEDNAME
IED name of this device. If this setting is modified, the IED name in ".cid" file will be changed
simultaneously and vice versa.
Opt_DualNetMode_MMS
0: Single network;
En_DualNet_SL_GOOSE
En_ComplexNet_GOOSE
Enable/Disable mixed GOOSE network (especially for the condition that certain IEDs adopt
single network while others adopt dual network) for process layer.
Date: 2017-08-17
7 Settings
En_TCP*_DNP
The logic setting is used to enable or disable network No.* DNP client. (x=1, 2, 3, 4)
1: enable
0: disable
When network No.* DNP client is not configured to be in service by PCS-Explorer, DNP client
settings corresponding to network No.* will be hidden.
Addr_Slave_TCP*_DNP
Addr_Master_TCP*_DNP
IP_Master_TCP*_DNP
Opt_Map_TCP*_DNP
Obj01DefltVar_TCP*_DNP
Obj02DefltVar_TCP*_DNP
Obj30DefltVar_TCP*_DNP
AI32Int: Analog Input with a flag octet and a 32-bit, signed integer value
AI16Int: Analog Input with a flag octet and a 16-bit, signed integer value
AI32IntWoutF: Analog Input with a 32-bit, signed integer value (but without flags)
AI16IntWoutF: Analog Input with a 16-bit, signed integer value (but without flags)
AI32Flt: Analog Input with a flag octet and a single-precision, floating-point value
Date: 2017-08-17
7 Settings
Obj32DefltVar_TCP*_DNP
AI32IntEvWoutT: Analog Input Event with a flag octet and a 32-bit, signed integer value (but
without time-of-occurence)
AI16IntEvWoutT: Analog Input Event with a flag octet and a 16-bit, signed integer value (but
without time-of-occurence)
AI32FltEvWoutT: Analog Input Event with single-precision, floating-point value (but without
time-of-occurence)
Obj40DefltVar_TCP*_DNP
AO32Int: Analog Output with a flag octet and a 32-bit, signed integer value
AO16Int: Analog Output with a flag octet and a 16-bit, signed integer value
AO32Flt: Analog Output with a flag octet and a single-precision, floating-point value
t_AppLayer_TCP*_DNP
t_KeepAlive_TCP*_DNP
En_UR_TCP*_DNP
The logic setting is used to enable or disable the unsolicited message function of network
No.* DNP client.
1: enable
0: disable
Num_URRetry_TCP*_DNP
It is the online retransmission number of the unsolicited message of network No.* DNP client.
(x=1, 2, 3, 4)
t_UROfflRetry_TCP*_DNP
It is the offline timeout of the unsolicited message of network No.* DNP client.
Class_BI_TCP*_DNP
It is the class level of the “Binary Input” of network No.* DNP client.
Class_AI_TCP*_DNP
It is the class level of the “Analog Input” of network No.* DNP client.
Date: 2017-08-17
7 Settings
t_Select_TCP*_DNP
t_TimeSynIntvl_TCP*_DNP
It is the time interval of the time synchronization function of network No.* DNP client.
Date: 2017-08-17
7 Settings
Date: 2017-08-17
8 Human Machine Interface
Table of Contents
8 Human Machine Interface .................................................................8-a
8.1 Overview .......................................................................................................... 8-1
8.1.1 Design .................................................................................................................................. 8-1
Date: 2017-08-17
8 Human Machine Interface
List of Figures
Figure 8.2-1 Main menu example (LCD 320×240) .................................................................... 8-4
List of Tables
Table 8.2-1 Menu description of "Measurements" .................................................................. 8-5
Date: 2017-08-17
8 Human Machine Interface
Date: 2017-08-17
8 Human Machine Interface
Date: 2017-08-17
8 Human Machine Interface
8.1 Overview
Operator can access this device from the HMI panel. Local communication with the device is
possible in using a computer via the multiplex RJ-45 debugging port. Furthermore, remote
communication is also possible in using the SAS via communication ports in the MON module.
This chapter describes the human machine interface (HMI), and gives operator an instruction
about how to display or print event report, setting and so on through menu tree and display
metering value, including r.m.s. current, voltage, frequency, etc. through LCD. Procedure to
change active setting group or a settable parameter value through keypad is also described in
detail.
8.1.1 Design
The human-machine interface consists of a human-machine interface (HMI) module which allows
a communication to be as simple as possible for the user. The HMI module helps to draw your
attention to something that has occurred which may activate an LED or a report displayed on the
LCD. Operator can locate the data of interest by navigating the keypad.
8.1.2 Keypad
FUN
ENT
ESC
"ESC"
"ENT"
Date: 2017-08-17
8 Human Machine Interface
"FUN"
Page up/down
01 HEALTHY 11
02 ALARM 12
03 13
04 14
05 15
06 16
07 17
08 18
09 19
10 20
Off Device is out of service or any hardware error is defected during self-check.
HEALTHY
Steady Green Device is in service and ready for operating.
"HEALTHY" LED can only be turned on by energizing the device and no abnormality detected.
"ALARM" LED is turned on as long as alarm exists. When all alarm signals disappear, it will be
turned off.
Date: 2017-08-17
8 Human Machine Interface
Other 18 LED indicators with no labels are configurable and user can configure them to be lit by
signals of operation element, alarm element and binary output contact according to requirement
through PCS-Explorer software. These 18 LEDs are configurable with selectable color among
green, yellow and red.
All the 20 LED indicators refresh every 30s if there is no change of status.
P2
P1
P3
P1: To connect the multiplex RJ45 port. An 8-core cable is applied here.
The definition of the 8-core cable in the above figure is introduced in the following table.
It should be ensured that the device and PC are in the same network segment.
Date: 2017-08-17
8 Human Machine Interface
The IP address and subnet mask of the device Ethernet port 1 (if connected) should be [IP_LAN1]
= 198.87.96.***, [Mask_LAN1] =255.255.255.0. (*** can be any value from 0 to 255 except 102)
For using a Ethernet port, the corresponding logic setting [En_LANx] (x = 2, 3, 4, etc.) must be "1".
"YYYY" is the function name substitution for bay identification such as "BayMMXU",
"Bus1_MMXU", "Bay1_MMXU", "Sum_MMXU", etc.
"BXX" in the following tables signifies the module at the No.XX slot.
Press "▲" to enter the main menu with the interface as shown in the following diagram:
Measurements
Status
Records
Settings
Local Cmd
Information
Test
Clock
Language
Date: 2017-08-17
8 Human Machine Interface
Main Menu
Measurements
Status
Records
Settings
Local Cmd
Information
Test
Clock
Language
8.2.2 Measurements
Main Menu
Measurements
Measurements1
Measurements2
Measurements3
This menu is used to display real-time measured values, including AC voltage, AC current, phase
angle and calculated quantities. These data can help users to acquaint the device′s status. This
menu comprises following submenus.
Date: 2017-08-17
8 Human Machine Interface
19 Ang (Ua-Ub) Phase angle between phase-A voltage and phase-B voltage 0 Deg
20 Ang (Ub-Uc) Phase angle between phase-B voltage and phase-C voltage 0 Deg
21 Ang (Uc-Ua) Phase angle between phase-C voltage and phase-A voltage 0 Deg
22 Ang (Ua-Ia) Phase angle between phase-A voltage and phase-A current 0 Deg
23 Ang (Ub-Ib) Phase angle between phase-B voltage and phase-B current 0 Deg
24 Ang (Uc-Ic) Phase angle between phase-C voltage and phase-C current 0 Deg
25 Ang (Ia-Ib) Phase angle between phase-A current and phase-B current 0 Deg
26 Ang (Ib-Ic) Phase angle between phase-B current and phase-C current 0 Deg
27 Ang (Ic-Ia) Phase angle between phase-C current and phase-A current 0 Deg
Date: 2017-08-17
8 Human Machine Interface
1 YYYY.Ia_Pri
3 YYYY.Ic_Pri
5 YYYY.Ua_Pri
7 YYYY.Uc_Pri
Date: 2017-08-17
8 Human Machine Interface
11 YYYY.Uab_Pri
13 YYYY.Uca_Pri
1 YYYY.Ia_Sec
3 YYYY.Ic_Sec
Date: 2017-08-17
8 Human Machine Interface
5 YYYY.Ua_Sec
7 YYYY.Uc_Sec
11 YYYY.Uab_Sec
13 YYYY.Uca_Sec
Date: 2017-08-17
8 Human Machine Interface
1 YYYY.Pa_Pri
3 YYYY.Pc_Pri
4 YYYY.Qa_Pri
6 YYYY.Qc_Pri
7 YYYY.Sa_Pri
The primary values of three-phases apparent
8 YYYY.Sb_Pri 0.00 MVA
powers.
9 YYYY.Sc_Pri
10 YYYY.Cosa
12 YYYY.Cosc
Date: 2017-08-17
8 Human Machine Interface
3 YYYY.Pc_Sec
4 YYYY.Qa_Sec
The secondary values of three-phases reactive
5 YYYY.Qb_Sec 0.00 Var
powers.
6 YYYY.Qc_Sec
7 YYYY.Sa_Sec
The secondary values of three-phases apparent
8 YYYY.Sb_Sec 0.00 VA
powers.
9 YYYY.Sc_Sec
10 YYYY.Cosa
12 YYYY.Cosc
Date: 2017-08-17
8 Human Machine Interface
8.2.3 Status
Main Menu
Status
Inputs
Contact Inputs
GOOSE Inputs
Tap Position
DPS Inputs
Outputs
Contact Outputs
Interlock Status
Trip Counter
CBWear
Superv State
Prot Superv
GOOSE Superv
BCU Superv
BCU Links
This menu is used to display real-time input signals, output signals and alarm signals of the device.
These data can help users to acquaint the device′s status. This menu comprises following
submenus.
Date: 2017-08-17
8 Human Machine Interface
8.2.3.1 Inputs
1 Contact Inputs Display states of binary inputs derived from opto-isolated channels
2 GOOSE Inputs Display state and quality of binary inputs via GOOSE communication.
The binary input indicates that the power supply of BI module in slot XX is
1 BXX.Alm_OptoDC
abnormal.
8.2.3.2 Outputs
Date: 2017-08-17
8 Human Machine Interface
During tap changer control process, if "running tap" occurs, transformer tap
position will be out of control, and it will step up or down continuously.
This device provides an output contact "BO_EmergStopTP" to issue an
emergency stop command for transformer tap position control. Therefore,
1 84.BO_EmergStop_Tap_Pos
"running tap" can be avoided. Select-Before-Operate (abbreviated as SBO)
process is cancelled here so as to stop "running tap" immediately.
State of the output contact "BO_EmergStopTP" is displayed as
[84.BO_EmergStop_Tap_Pos].
1 CSWI**.CILO.EnaOpn State "1" indicates satisfaction of all interlock logics for remote opening
2 CSWI**.CILO.EnaCls State "1" indicates satisfaction of all interlock logics for remote closing
Date: 2017-08-17
8 Human Machine Interface
8.2.4 Records
Main Menu
Records
Disturb Records
Superv Events
IO Events
Device Logs
Control Logs
Clear Records
This menu is used to display all kinds of records, including the disturbance records, supervision
events, binary events and device logs, so that the operator can load to view and use as the
reference of analyzing accidents and repairing the device. All records are stored in non-volatile
memory, it can still record them even if it loses its power.
Date: 2017-08-17
8 Human Machine Interface
8.2.5 Settings
Main Menu
Settings
System Settings
Prot Settings
BCU Settings
Logic Links
Device Setup
NOTICE!
Check or modify the logic links settings, including function links and GOOSE
4 Logic Links
links.
The menu is hidden by default, and when itis visible, it can be used to
6 Confirm Settings
confirm all settings of this device.
2 Direction Settings Check or modify direction settings for ROC and OC protections
8 VTS/CTS Settings Check or modify VT circuit supervision and CT circuit supervision settings
Date: 2017-08-17
8 Human Machine Interface
Date: 2017-08-17
8 Human Machine Interface
Main Menu
Local Cmd
Reset Target
Trig Oscillograph
Download
Clear Counter
Manual Control
Clear AR Counter
1 Reset Target Reset the local signal, indicator LED, LCD display, etc.
8.2.7 Information
Main Menu
Information
Version Info
Board Info
In this menu, the LCD displays software information and the configuration of all kinds of intelligent
plug-in modules.
Display software information of DSP module, MON module and HMI module,
1 Version Info
which consists of version, creating time of software, CRC codes and
Date: 2017-08-17
8 Human Machine Interface
2 Board Info
8.2.8 Test
Main Menu
Test
Device Test
+ Disturb Events
+ Superv Events
+ IO Events
GOOSE Outputs
Internal Signal
AR Counter
AC Auto Calbr
Interlock Info
GOOSE Interlock
HMI Setup
Contrast
BacklitDur
SupervLCD
SupervLED
This menu is mainly used for developers to debug the program and for engineers to maintain the
device.
Date: 2017-08-17
8 Human Machine Interface
3 N_GS_DecodeErr Failure times to decode the received data via GOOSE network.
1 Disturb Events Simulate and issue disturbance event for protection element
Date: 2017-08-17
8 Human Machine Interface
NOTICE!
8.2.9 Clock
The current time of the internal clock can be viewed and modified here.
8.2.10 Language
This menu is mainly used to set LCD display language.
3. Event display.
If LCD configuration file has been downloaded successfully to this device, SLD will be displayed in
normal display. Otherwise, SLD will not be displayed. If any event is detected, the corresponding
event display will pop up automatically.
If SLD is not involved in normal display, user can keep pressing "ENT" and then press "ESC" to
switch between normal display (without SLD) and event display.
Date: 2017-08-17
8 Human Machine Interface
If SLD is involved in normal display, user can keep pressing "ENT" and then press "ESC" to
switch between normal display (with SLD) and event display.
Event display of disturbance records can be cleared manually in this way: keep pressing "ESC"
and then press "ENT";
Event display of supervision events cannot be cleared manually, and it will not be cleared until the
corresponding supervision events have disappeared;
Event display of IO events only keeps for several seconds and then it will disappear and return to
normal display automatically.
An example of normal display without SLD is shown in the following figure. The LCD adopts white
color as its backlight that will be activated in case of any keyboard operation. Moreover, the
backlight will be extinguished automatically if no keyboard operation is detected for duration.
S 2013-01-15 13:22:23
BayMMXU.Ia_Sec 0.0000 A
BayMMXU.Ib_Sec 0.0000 A
BayMMXU.Ic_Sec 0.0000 A
BayMMXU.Uab_Sec 0.10 V
BayMMXU.Ubc_Sec 0.10 V
BayMMXU.Uca_Sec 0.10 V
BayMMXU.Usyn_Sec 0.10 V
BayMMXU.f 0.000 Hz
BayMMXU.fsyn 0.000 Hz
Addr 24343
Date: 2017-08-17
8 Human Machine Interface
2013-01-15 13:22:23 shows current date and time of this device, the format is
"yyyy-mm-dd hh:mm:ss".
M0131
M01
M0151
M0171
Feeder M01
Signs for the circuit breaker (abbreviated as CB) and switch (DS or ES) are listed in the following
table.
Date: 2017-08-17
8 Human Machine Interface
In SLD display, press "▼" continuously to select a CB/switch to be opened/closed, and then press
key "ENT" to control selected CB/switch. The control operation window will be valid for duration
after inputting correct password as shown in the following figure. The password for control
operation is fixed as "111".
Please refer to "Remote Control" (from the 4th step) for the following steps of control.
Please make sure that the switch is on the right position "Local" when operating;
Password:
0 00
This device can store up to 1024 supervision events. During the operation of the device, the
supervision event of hardware self-check errors or system operation abnormity will be displayed
immediately.
Date: 2017-08-17
8 Human Machine Interface
S Superv Events
Alm_Device
Alm_Version
This device can store up to 1024 IO events (i.e.: binary events). During the operation of the device,
the binary input will be displayed once its state has changed, i.e.: from "0" to "1" or from "1" to "0".
BI_Maintenance 0 1
Date: 2017-08-17
8 Human Machine Interface
2013-01-15 13:31:23:669 shows date and time when the report occurred, the format is
"yyyy-mm-dd hh:mm:ss:fff".
BI_Maintenance 0→1 shows the state change of binary input, including binary input
name, original state and final state.
2. Press the "▲" or "▼" to move the cursor to the "Measurements" menu, and then press
"ENT" or "►" to enter the menu;
3. Press "▲" or "▼" to move the cursor to any command menu, and then press "ENT" to enter
the menu;
4. Press "▲" or "▼" to page up/down (if all information cannot be displayed in one display
screen, one screen can display 14 lines of information at most);
6. Press "ENT" or "ESC" to exit this menu (returning to the "Measurements" menu);
2. Press "▲" or "▼" to move the cursor to the "Status" menu, and then press "ENT" or "►" to
enter the menu.
3. Press "▲" or "▼" to move the cursor to any command menu item, and then press "ENT" to
enter the submenu.
4. Press "▲" or "▼" to page up/down (if not all information can be displayed in one display
screen, one screen can display 14 lines of information at most).
6. Press "ENT" or "ESC" to exit this menu (returning to the "Status" menu).
2. Press "▲" or "▼" to move the cursor to the "Records" menu, and then press "ENT" or "►" to
enter the menu;
3. Press "▲" or "▼" to move the cursor to any command menu, and then press "ENT" to enter
the menu;
Date: 2017-08-17
8 Human Machine Interface
7. Press "ENT" or "ESC" to exit this menu (returning to the "Records" menu).
An example of the command menu "Device Logs" is shown in the following figure. Displays of
other command menus (for example, "Disturb Records") are similar.
Device Logs NO. 60 shows the title and the No. of the device log. This device can
store up to 1024 device logs.
2013-01-28 10:18:47:569ms shows date and time when the report occurred, the format is
"yyyy-mm-dd hh:mm:ss:fff".
Date: 2017-08-17
8 Human Machine Interface
2. Press "▲" or "▼" to move the cursor to the "Settings" menu, and then press "ENT" or "►" to
enter the menu;
3. Press "▲" or "▼" to move the cursor to any command menu, and then press "ENT" to enter
the menu;
If the displayed information exceeds 14 lines, the scrollbar will appear on the right side of the
LCD to indicates the quantity of all displayed information of the command menu and the
relative location of information where the current cursor is pointing at.
2. Press "▲" or "▼" to move the cursor to the "Settings" menu, and then press "ENT" or "►" to
enter the menu;
3. Press "▲" or "▼" to move the cursor to any command menu, and then press "ENT" to enter
the menu;
8. If selecting the command menu "System Settings", move the cursor to the setting item to be
modified, and then press "ENT".
Press "+" or "-" to modify the value (if the modified value is of multi-bit, press "◄" or "►" to
move the cursor to the digit bit, and then press "+" or "-" to modify the value), press "ESC"
to cancel the modification and return to the displayed interface of the command menu
"System Settings". Press "ENT" to automatically exit this menu (returning to the displayed
interface of the command menu "System Settings").
Move the cursor to continue modifying other setting items. After all setting values are
modified, press "◄", "►" or "ESC", and the LCD will display "Save or Not?". Directly Press
"ESC" or Press "◄" or "►" to move the cursor. Select the "Cancel", and then press "ENT" to
automatically exit this menu (returning to the displayed interface of the command menu
"System Settings").
Press "◄" or "►" to move the cursor. Select "No" and Press "ENT", all modified setting item
will restore to its original value, exit this menu (returning to the menu "Settings").
Date: 2017-08-17
8 Human Machine Interface
Press "◄" or "►" to move the cursor to select "Yes", and then press "ENT", the LCD will
display password input interface.
Password:
____
Input a 4-bit password ("+", "◄", "▲" and "-"). If the password is incorrect, continue
inputting it, and then press "ESC" to exit the password input interface and return to the
displayed interface of the command menu "System Settings". If the password is correct,
LCD will display "Save Setting …", and then exit this menu (returning to the displayed
interface of the command menu "System Settings"), with all modified setting items as
modified values.
NOTICE!
After modifying settings of the device, the "HEALTHY" LED indicator of the device will
be off, and the device will automatically restart and re-check them. If the check does
not pass, the device will be blocked.
2. Press the "▲" or "▼" to move the cursor to the "Settings" menu, and then press the "ENT" or
"►" to enter the menu;
3. Press the "▲" or "▼" to move the cursor to the command menu "Copy Settings", and then
press the "ENT" to enter the menu.
Date: 2017-08-17
8 Human Machine Interface
Copy Settings
Active Group: 01
Copy To Group: 02
Press the "+" or "-" to modify the value. Press the "ESC", and return to the menu "Settings".
Press the "ENT", the LCD will display the interface for password input, if the password is
incorrect, continue inputting it, press the "ESC" to exit the password input interface and return
to the menu "Settings". If the password is correct, the LCD will display "copy setting OK!",
and exit this menu (returning to the menu "Settings").
Active Group: 01
Change To Group: 02
Press the "+" or "-" to modify the value, and then press the "ESC" to exit this menu
(returning to the main menu). After pressing the "ENT", the LCD will display the password
input interface. If the password is incorrect, continue inputting it, and then press the "ESC" to
exit the password input interface and return to its original state. If the password is correct, the
Date: 2017-08-17
8 Human Machine Interface
"HEALTHY" indicator lamp of the protection device will go out, and the protection device will
re-check the protection setting. If the check doesn’t pass, the protection device will be
blocked. If the check is successful, the LCD will return to its original state.
2. Press "+", "-", "+", "-" and "ENT"; Press "ESC" to exit this menu (returning to the original
state). Press "ENT" to carry out the deletion.
NOTICE!
The operation of deleting device message will delete all messages saved by the device,
including disturbance records, supervision events, IO events, but not including device
logs. Furthermore, the message is irrecoverable after deletion, so the application of the
function shall be cautious.
2. Press "▲" or "▼" to move the cursor to the command menu "Local Cmd", and then press
"ENT" to enter submenus. Press "▲" or "▼" to move the cursor to the command menu
"Control", and then press "ENT" to enter the password.
3. Input a 3-bit password ("111"). If the password is incorrect, continue inputting it, and then
press "ESC" to exit the password input interface and return to the displayed interface of the
command menu "Control". If the password is correct, it will go to the following step.
4. Press "▲" or "▼" to move the cursor to the control object and press "ENT" to select the
control object.
5. Press "◄" or "►" to select control command press "ENT" or "ESC" to the next/previous step.
Date: 2017-08-17
8 Human Machine Interface
6. Press "◄" or "►" to select RSYN check mode and Press "ENT" or "ESC" to the next/previous
step.
4) LoopCheck Reserved
7. Press "◄" or "►" to select interlock mode and Press "ENT" or "ESC" to the next/previous
step.
8. Press "◄" or "►" to select control type and Press "ENT" or "ESC" to the next/previous step.
9. The result of control operation will be shown on LCD. Press "ESC" to return to the 7th step.
NOTICE!
"Execute" operation must be operated after "Select" operation in manual control mode.
2. Press "▲" or "▼" to move the cursor to the "Clock" menu, and then press "ENT" to enter
clock display
Date: 2017-08-17
8 Human Machine Interface
3. Press "▲" or "▼" to move the cursor to the date or time to be modified;
4. Press "+" or "-" to modify value, and then press "ENT" to save the modification and return to
the main menu;
5. Press "ESC" to cancel the modification and return to the main menu.
Clock
Year: 2012
Month: 12
Day: 25
Hour: 14
Minute: 26
Second: 54
2. Press "▲" or "▼" to move the cursor to the "Information" menu, and then press "ENT" or
"►" to enter the menu.
3. Press "▲" or "▼" to move the cursor to the command menu "Board Info", and then press
"ENT" to enter the menu.
2. Press "▲" or "▼" to move the cursor to the "Information" menu, and then press "ENT" to
enter the submenu.
3. Press "▲" or "▼" to move the cursor to the command menu "Version Info", and then press
"ENT" to display the software version.
4. Press "▲" or "▼" to check all the relative information about the software version (CRC code,
management code, programme time, etc.).
Date: 2017-08-17
8 Human Machine Interface
2. Press "▲" or "▼" to move the cursor to the "Test" menu, and then press "ENT" or "►" to
enter the menu.
3. Press "▲" or "▼" to move the cursor to the submenu "Device Test", and then press "ENT" to
enter the submenu and select test item. If "Disturb Events", "Superv Events" or "IO Events"
is selected, two options "All Test" and "Select Test" are provided.
4. Press "▲" or "▼" to move the cursor to select the corresponding command menu "All Test"
or "Select Test".
5. If selecting the "All Test", press "ENT", and the device will successively carry out all
operation element message test one by one.
6. If "Select Test" is selected, press "ENT". Press "+" or "-" to page up/down, and then press
"▲" or "▼" to move the scrollbar. Move the cursor to select the corresponding item. Press
"ENT" to execute the communication test of this item, station control or control center will
receive corresponding message.
7. Press "ESC" to exit this menu (returning to the menu "Select Test"), at this moment, the LCD
will display "Communication Test Exiting…".
NOTICE!
If no input operation is carried out within 60s, the communication test will exit and
return to the "Select Test" menu automatically, at this moment, the LCD will display
"Communication Test Timeout and Exiting...".
2. Press "▲" or "▼" to move the cursor to the command menu "Language", and then press
"ENT" to enter the menu and the following display will be shown on LCD.
Date: 2017-08-17
8 Human Machine Interface
1. 中文
2. English
3. Press "▲" or "▼" to move the cursor to the language user preferred and Press "ENT" to
execute language switching. After language switching is finished, LCD will return to defaul
display. Otherwise, press "ESC" to cancel language switching and return to the menu
"Language".
Date: 2017-08-17
8 Human Machine Interface
Date: 2017-08-17
9 Configurable Function
9 Configurable Function
Table of Contents
9 Configurable Function ......................................................................9-a
9.1 Overview .......................................................................................................... 9-1
9.2 Configurable Function of PCS-Explorer ........................................................ 9-1
9.3 Configurable Function of SCL Configurator ................................................. 9-1
Date: 2017-08-17
9 Configurable Function
Date: 2017-08-17
9 Configurable Function
9.1 Overview
Two configuration tools are designed to realize the configurable functions of PCS-9705.
PCS-Explorer
Support of device configuration, function configuration, LCD configuration, binary input and
binary output configuration, LED indicator configuration and programmable interlocking logic
SCL Configurator:
After function configuration is finished, disabled function will be hidden in the device and in setting
configuration list of PCS-Explorer Software. The user can select to show or hide some setting by
this way, and modify the setting vale.
Please refer to the instruction manual “PCS-Explorer Auxiliary Software” for details.
Functions:
Programmable logic
Device configuration
Function configuration
LCD configuration
Setting configuration
Analysis of waveform
File downloading/uploading
Date: 2017-08-17
9 Configurable Function
SCL configuration tool is developed for the engineered implementation IEC61850. It can be used
to create, edit and view SCL files which conform to IEC61850-6 regulations, and then construct
the substation configuration, structures, models, etc. Specially, it can be used to define the
message transmitted inter-bay (useful for interlocking).
Please refer to the instruction manual “SCL Configurator Auxiliary Software” for details.
Functions:
Import of IED file into ICD file which conforms to IEC 61850-6
Association of different intelligent electronic devices and their logical nodes (LN) to substation
details, and completion of substation system configuration according to IEC61850-6
Date: 2017-08-17
10 Communication
10 Communication
Table of Contents
10 Communication ............................................................................ 10-a
10.1 Overview ...................................................................................................... 10-1
10.2 Rear Communication Port .......................................................................... 10-1
10.2.1 Ethernet Interface ............................................................................................................ 10-1
List of Figures
Figure 10.2-1 Ethernet communication cable ........................................................................ 10-1
Figure 10.3-1 Dual-net full duplex mode sharing the RCB block instance......................... 10-4
Figure 10.3-2 Dual-net hot-standby mode sharing the same RCB instance ...................... 10-5
Figure 10.3-3 Dual-net full duplex mode with 2 independent RCB instances .................... 10-6
Date: 2017-08-17
10 Communication
Date: 2017-08-17
10 Communication
10.1 Overview
This section outlines the remote communications interfaces of this device. This device supports a
choice of 2 protocols via the rear communication interface, selected via the model number by
setting. The protocol provided by the device can be chosen from the menu “Settings→Device
Setup→Comm Settings”.
It should be noted that the descriptions contained within this section do not aim to fully detail the
protocol itself. The relevant documentation for the protocol should be referred to for this
information. This section serves to describe the specific implementation of the protocol in the
device.
It is recommended to use twisted shielded eight-core cable as the communication cable. A picture
is shown below.
Each equipment is connected with an exchanger via communication cable, and thereby it forms a
star structure network. Dual-network is recommended in order to increase reliability. SCADA is
connected to the exchanger and will play a role as master station, other equipment connected to
the exchanger will play a role as slave unit.
Date: 2017-08-17
10 Communication
SCADA
Switch: Net A
Switch: Net B
……
10.3.1 Overview
The IEC61850 software module is adopted in the device.
The IEC61850 standard is the result of years of work by electric utilities and vendors of electronic
equipment to produce standardized communications systems. IEC61850 is a series of standards
describing client/server and peer-to-peer communications, substation design and configuration,
testing, environmental and project standards. The complete set includes:
IEC 61850-5: Communications and requirements for functions and device models
IEC 61850-7-1: Basic communication structure for substation and feeder equipment–
Principles and models
IEC 61850-7-2: Basic communication structure for substation and feeder equipment -
Abstract communication service interface (ACSI)
IEC 61850-7-3: Basic communication structure for substation and feeder equipment–
Common data classes
IEC 61850-7-4: Basic communication structure for substation and feeder equipment–
Compatible logical node classes and data classes
IEC 61850-8-1: Specific Communication Service Mapping (SCSM) – Mappings to MMS (ISO
9506-1 and ISO 9506-2) and to ISO/IEC 8802-3
Date: 2017-08-17
10 Communication
IEC 61850-9-1: Specific Communication Service Mapping (SCSM) – Sampled values over
serial unidirectional multidrop point to point link
IEC 61850-9-2: Specific Communication Service Mapping (SCSM) – Sampled values over
ISO/IEC 8802-3
These documents can be obtained from the IEC (http://www.iec.ch). It is strongly recommended
that all those involved with any IEC61850 implementation obtain this document set.
MMS protocol
IEC61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper
(application) layer for transfer of real-time data. This protocol has been in existence for a number
of years and provides a set of services suitable for the transfer of data within a substation LAN
environment. IEC 61850-7-2 abstract services and objects are mapped to actual MMS protocol
services in IEC61850-8-1.
Client/server
Please note that gateways can be considered as clients and servers subject to the communication
object. When retrieving data from IEDs within the substation, the gateways are considered as
servers whereas transmitting data to control centers, the gateways are considered as clients.
Peer-to-peer
A substation configuration language is a number of files used to describe IED configurations and
communication systems according to IEC 61850-5 and IEC 61850-7. Each configured device has
an IED Capability Description (ICD) file and a Configured IED Description (CID) file. The
substation single line information is stored in a System Specification Description (SSD) file. The
entire substation configuration is stored in a Substation Configuration Description (SCD) file. The
SCD file is the combination of the following items: individual ICD files, SSD file, communication
system parameters (MMS, GOOSE control block, SV control block), as well as GOOSE/SV
Date: 2017-08-17
10 Communication
Client-server mode is adopted: clients (SCADA, control center and etc.) communicate with the
IEDs via MMS communication network, and the IEDs operate as the servers. IEDs are connected
to clients passively, and they can interact with the clients according to the configuration and the
issued command of the clients.
Three modes for dual-MMS Ethernet (abbreviated as dual-net) are provided as below.
NOTICE!
Hereinafter, the normal operation status of net means the physical link and TCP link are
both ok. The abnormal operation status of net means physical link or TCP link is
broken.
Mode 1: Dual-net full duplex mode sharing the same RCB instance
Client Client
TCP Link
MMS Link
Figure 10.3-1 Dual-net full duplex mode sharing the RCB block instance
Net A and Net B share the same report control block (abbreviated as RCB) enabled by the client.
IED sends undifferentiated date through dual-net to the clients. If one net is physically
disconnected, the flag of RCB instance (i.e.: “RptEna” in above figure) is still “true”. Only when
Date: 2017-08-17
10 Communication
both Net A and Net B are disconnected, the flag of the RCB instance will automatically change to
“false”.
In normal operation status of mode 1, IED provides the same MMS service for Net A and Net B. If
one net is physically disconnected (i.e.: “Abnormal operation status” in above figure), the working
mode will switch to single-net mode seamlessly and immediately. Network communication
supervision is unnecessary here, and Buffered Report Control Block (abbreviated as BRCB) need
not to be used. On the other net, date alternation works normally. Therefore, MMS service can
interact normally without interruption. This mode ensures no data loss during one net is in
abnormal operation status.
In mode 1, one report will be transmitted twice via dual nets for the same report instance, so the
client needs to distinguish whether two reports are same according to corresponding EntryIDs.
Client Client
TCP Link
Figure 10.3-2 Dual-net hot-standby mode sharing the same RCB instance
In mode 2, the MMS service is provided on main MMS link, no MMS service interacts on the
standby MMS link. The definitions of two links are as follows:
Main MMS Link: Physically connected, TCP level connected, MMS report service
available.
Standby MMS Link: Physically connected, TCP level connected, MMS report service not
available.
If the main net fails to operate (i.e.: “Abnormal operation status” in the above figure), the IED will
Date: 2017-08-17
10 Communication
set “RptEna” to “false”. Meanwhile the client will detect the failure by heartbeat message or
“keep-alive”, it will automatically enable the RCB instance by setting “RptEna” back to “true”
through standby MMS link. By the buffer function of BRCB, the IED can provide uninterrupted
MMS service on the standby net. However, the differences of BRCB standards among different
manufacturers may cause data loss. Moreover, if duration of net switch is too long, the data loss is
positively as the capacity of BRCB’s buffer function is limited.
NOTICE!
In mode 1 and mode 2, Net A IED host address and Net B IED host address must be
the same. E.g.: if the subnet mask is 255.255.0.0, network prefix of Net A is
198.120.0.0, network prefix of Net B is 198.121.0.0, Net A IP address of the IED is
198.120.1.2, and then Net B IP address of the IED must be configured as 198.121.1.2,
i.e.: Net A IED host address =1x256+2=258, Net B IED host address =1x256+2=258,
Net A IED host address equals to Net B IED host address.
Client Client
TCP Link
MMS Link
Figure 10.3-3 Dual-net full duplex mode with 2 independent RCB instances
In mode 3, IED provides 2 report instances for each RCB, Net A and Net B work independently
from each other, failures of one net will not affect the other net at all.
In this mode, 2 report instances are required for each client. Therefore, the IED may be unable to
provide enough report instances if there are too many clients.
Net A and Net B send the same report separately when they operates normally, To ensure no
repeated data is saved into database, massive calculation is required for the client.
Date: 2017-08-17
10 Communication
Moreover, accurate clock synchronization of the IED is required to distinguish whether 2 reports
are the same report according to the timestamps. Clock synchronization error of the IED may lead
to report loss/redundancy.
As a conclusion:
In mode 3, the IED may be unable to provide enough report instances if too many clients are
applied on site.
For the consideration of client treatment and IED implementation, mode 1 (Dual-net full duplex
mode sharing the same report instance) is recommended for MMS communication network
deployment.
Each IED represents one IEC61850 physical device. The physical device contains one or more
logical device(s), and the logical device contains many logical nodes. The logical node LPHD
contains information about the IED physical device. The logical node LLN0 contains common
information about the IED logical device.
The GGIO logical node is available in this device to provide access to digital status points
(including general I/O inputs and warnings) and associated timestamps and quality flags. The
data content must be configured before the data can be used. GGIO provides digital status points
for access by clients. It is intended that clients use GGIO in order to access digital status values
from in this device. Clients can utilize the IEC61850 buffered reporting features available from
GGIO in order to build sequence of events (abbreviated as SOE) logs and HMI display screens.
Buffered reporting should generally be used for SOE logs since the buffering capability reduces
the chances of missing data state changes. All needed status data objects are transmitted to HMI
clients via buffered reporting, and the corresponding buffered reporting control block (abbreviated
as BRCB) is defined in LLN0.
Most of analog measured values are available through the MMXU logical nodes, and metering
values in MMTR, the others in MMXN, MSQI and so on. Each MMXU logical node provides data
from an IED current/voltage “source”. There is one MMXU available for each configurable source.
MMXU1 provides data from CT/VT source 1(usually for protection purpose), and MMXU2
provides data from CT/VT source 2 (usually for monitor and display purpose). All these analog
data objects are transmitted to HMI clients via unbuffered reporting periodically, and the
corresponding unbuffered reporting control block (URCB) is defined in LLN0. MMXUx logical
Date: 2017-08-17
10 Communication
MMXU.MX.Hz: frequency
PTOF: Overfrequency
PTUF: Underfrequency
RBRF:Breaker failure
RSYN: Synchronism-check
The protection elements listed above contain start (pickup) and operate flags, instead of any
element has its own start (pickup) flag separately, all the elements share a common start (pickup)
flags “PTRC.ST.Str.general”. These flags take their values from related module for the
corresponding element. Similar to digital status values, the protection trip information is reported
via BRCB, and BRCB also locates in LLN0.
Logical node LLN0 is essential for an IEC61850 based IED. This LN shall be used to address
Date: 2017-08-17
10 Communication
common issues for Logical Devices. In this device, most of the public services, the common
settings, control values and some device oriented data objects are available here. The public
services may be BRCB, URCB and GSE control blocks and similar global defines for the whole
device; the common settings include all the setting items of communication settings, system
settings and some of the setting items, which can be configured to 2 or more logical nodes. In
LLN0, the item Loc is a device control object, this Do item indicates the local operation for
complete logical device, when it is true, all the remote control commands to the IED will be
blocked and those commands make effective until the item Loc is changed to false. Besides the
logical nodes we describe above, there are some other logical nodes below in the IEDs.
MMXU: This LN shall be used to acquire values from CTs and VTs and calculate measurands
such as RMS values for current and voltage or power flows out of the acquired voltage and
current samples. These values are normally used for operational purposes such as power
flow supervision and management, screen displays, state estimation, etc. The requested
accuracy for these functions has to be provided.
CILO: This LN shall be used to “enable” a switching operation if the interlocking conditions
are fulfilled. One instance per switching device is needed. At least all related switchgear
positions have to be subscribed. The interlocking algorithm is a local issue.
This LN is used for the interlocking function at station level and/or at bay level.
Interlocking may be totally centralized or totally decentralized. Since the interlocking rules are
basically the same on bay and station level and based on all related position indications, the
different interlocking LNs may be seen as instances of the same LN class Interlocking (IL).
All interlocking rules referring to a bay are included in this LN. Releases or blockings of
requested commands are issued. In the case of status changes affecting interlocking,
blocking commands are issued.
All interlocking rules referring to the station are included in this LN. Releases or
blockings of requested commands are issued. Information with the LN bay interlocking is
exchanged.
MSQI: This LN is used for the sequences and imbalances, for example for stability purpose.
This LN is used to acquire values from CTs and VTs and to calculate the sequences and
imbalances in a three/multi-phase power system.
The voltage phasor difference from both sides of an open breaker is calculated and
compared with predefined switching conditions (synchrocheck). Included is the case that one
side is dead (example: energizing a dead line) and the case that the phasor on one side can
be actively controlled by “higher” or “lower” (means synchronizing).
Date: 2017-08-17
10 Communication
are within the desired limits of frequency, phase-angle and voltage, to permit or to cause the
paralleling of these two circuits (IEEE C37.2-1996).
To avoid stress for the switching device and the network, closing of the circuit breaker is
allowed by the synchrocheck only, if the differences of voltage, frequency and phase angle
are within certain limits.
Device allocated to YPTR allowing changing taps of the winding for voltage regulation.
This LN provides automatic function to keep the voltage of a busbar within a specific range
using tap changers. This node operates the tap changer automatically according to given
setpoints or by direct operator commands (manual mode).
LPHD: Physical device information, the logical node to model common issues for physical
device.
GAPC: Generic automatic process control, it is used to model in a generic way the
processing/automation of functions, for example the sequence control functions for this
device.
CSWI: Switch controller. This class is used to control all switching conditions of XCBR and
XSWI. A remote switching command (for example Select-Before-Operate) arrives here firstly.
XCBR: Breaker control. The XCBR logical node is directly associated with the breaker control
feature.
XCBR1.ST.Pos: This is the position of the breaker. If the breaker control logic indicates that
the breaker, or any single pole of the breaker, is closed, then the breaker position state is “on”.
If the breaker control logic indicates that the breaker is open, then the breaker position state
is “off”.
XCBR1.ST.BlkOpn: This is the state of the block open command logic. When true, breaker
open commands from IEC61850 clients will be rejected.
XCBR1.ST.BlkCls: This is the state of the block close command logic. When true, breaker
close commands from IEC61850 clients will be rejected.
XCBR1.CO.Pos: This is where IEC61850 clients can issue open or close commands to the
breaker. Select-Before-Operate (abbreviated as SBO) with enhanced security is the only
supported IEC61850 control model.
PTRC: Protection trip conditioning, it shall be used to connect the “operate” outputs of one or
more protection functions to a common “trip” to be transmitted to XCBR. In addition or
alternatively, any combination of “operate” outputs of protection functions may be combined
to a new “operate” of PTRC.
RDRE: Disturbance recorder function. It triggers fault wave recorder and its output refers to
the “IEEE Standard Format for Transient Data Exchange (COMTRADE) for Power System”
Date: 2017-08-17
10 Communication
(IEC 60255-24). All enabled channels are included in the recording and independent of the
trigger mode.
IEC61850 buffered and unbuffered reporting control blocks locate in LLN0, they can be configured
to transmit information of protection trip information (in the Protection logical nodes), binary status
values (in GGIO) and analog measured/calculated values (in MMXU, MMTR and MSQI). The
reporting control blocks can be configured in CID files, and then be sent to the IED via an
IEC61850 client. The following items can be configured.
- Bit 1: Data-change
- Bit 4: Integrity
- Bit 1: Sequence-number
- Bit 2: Report-time-stamp
- Bit 3: Reason-for-inclusion
- Bit 4: Data-set-name
- Bit 5: Data-reference
- Bit 8: Conf-revision
- Bit 9: Segmentation
MMS file services are supported to allow transfer of oscillography, event record or other files from
this device.
10.3.5.3 Timestamps
The Universal Time Coordinated (abbreviated as UTC) timestamp associated with all IEC61850
Date: 2017-08-17
10 Communication
data items represents the latest change time of either the value or the quality flags of the data
item.
IEC61850 specifies that each logical node can have a name with a total length of 11 characters.
The name is composed of:
Complete names are of the form xxxxxxPTOC1, where the xxxxxx character string is configurable.
Details regarding the logical node naming rules are given in IEC61850 parts 6 and 7-2. It is
recommended that a consistent naming convention be used for an entire substation project.
IEC61850 specifies the type of broadcast data transfer services: Generic Object Oriented
Substation Events (GOOSE). IEC61850 GOOSE services provide virtual LAN (VLAN) support,
Ethernet priority tagging, and Ether-type Application ID configuration. The support for VLANs and
priority tagging allows for the optimization of Ethernet network traffic. GOOSE messages can be
given a higher priority than standard Ethernet traffic, and they can be separated onto specific
VLANs. Devices that transmit GOOSE messages also function as servers. Each GOOSE
publisher contains a “GOOSE control block” to configure and control the transmission.
The GOOSE transmission (including subscribing and publishing) is controlled by GOOSE logic
link settings in device.
This device supports IEC61850 Generic Object Oriented Substation Event (GOOSE)
communication. All GOOSE messages contain IEC61850 data collected into a dataset. It is this
dataset that is transferred using GOOSE message services. The GOOSE related dataset is
configured in the CID file and it is recommended that the fixed GOOSE be used for
implementations that require GOOSE data transfer between PCS-9705 series bay control units.
IEC61850 GOOSE messaging contains a number of configurable parameters, all of which must
be correct to achieve the successful transfer of data. It is critical that the configured datasets at
the transmission and reception devices are an exact match in terms of data structure, and that the
GOOSE addresses and name strings match exactly.
Client/ Server
Services PCS-9705
Subsrciber /Publisher
Client-Server Roles
Date: 2017-08-17
10 Communication
Client/ Server
Services PCS-9705
Subsrciber /Publisher
SCSMS Supported
Where:
C1: Shall be "M" if support for LOGICAL-DEVICE model has been declared
O: Optional
M: Mandatory
M1 Logical device C2 C2 Y
M2 Logical node C3 C3 Y
M3 Data C4 C4 Y
M4 Data set C5 C5 Y
M5 Substitution O O Y
Reporting
M7-1 sequence-number Y Y Y
M7-2 report-time-stamp Y Y Y
M7-3 reason-for-inclusion Y Y Y
M7-4 data-set-name Y Y Y
M7-5 data-reference Y Y Y
Date: 2017-08-17
10 Communication
M7-6 buffer-overflow Y Y Y
M7-7 entryID Y Y Y
M7-8 BufTm N N N
M7-9 IntgPd Y Y Y
M7-10 GI Y Y Y
M8-1 sequence-number Y Y Y
M8-2 report-time-stamp Y Y Y
M8-3 reason-for-inclusion Y Y Y
M8-4 data-set-name Y Y Y
M8-5 data-reference Y Y Y
M8-6 BufTm N N N
M8-7 IntgPd N Y Y
Logging
M9 Log control O O N
M9-1 IntgPd N N N
M10 Log O O N
GSE
M12 GOOSE O O Y
M13 GSSE O O N
M16 Time M M Y
Where:
C2: Shall be "M" if support for LOGICAL-NODE model has been declared
C3: Shall be "M" if support for DATA model has been declared
C4: Shall be "M" if support for DATA-SET, Substitution, Report, Log Control, or Time models has
been declared
C5: Shall be "M" if support for Report, GSE, or SMV models has been declared
M: Mandatory
Date: 2017-08-17
10 Communication
Server
S1 ServerDirectory M Y
Application association
S2 Associate M Y
S3 Abort M Y
S4 Release M Y
Logical device
S5 LogicalDeviceDirectory M Y
Logical node
S6 LogicalNodeDirectory M Y
S7 GetAllDataValues M Y
Data
S8 GetDataValues M Y
S9 SetDataValues M Y
S10 GetDataDirectory M Y
S11 GetDataDefinition M Y
Data set
S12 GetDataSetValues M Y
S13 SetDataSetValues O Y
S14 CreateDataSet O N
S15 DeleteDataSet O N
S16 GetDataSetDirectory M Y
Substitution
S17 SetDataValues M Y
Reporting
S24 Report M Y
Date: 2017-08-17
10 Communication
S24-1 data-change M Y
S24-2 qchg-change M Y
S24-3 data-update M Y
S25 GetBRCBValues M Y
S26 SetBRCBValues M Y
S27 Report M Y
S27-1 data-change M Y
S27-2 qchg-change M Y
S27-3 data-update M N
S28 GetURCBValues M Y
S29 SetURCBValues M Y
Logging
S30 GetLCBValues O N
S31 SetLCBValues O N
Log
S32 QueryLogByTime O N
S33 QueryLogAfter O N
S34 GetLogStatusValues O N
S35 SendGOOSEMessage M Y
S36 GetGoReference O Y
S37 GetGOOSEElementNumber O N
S38 GetGoCBValues M Y
S39 SetGoCBValuess M Y
Control
S51 Select O N
S52 SelectWithValue M Y
S53 Cancel M Y
S54 Operate M Y
S55 Command-Termination O Y
S56 TimeActivated-Operate O N
File transfer
Date: 2017-08-17
10 Communication
S58 SetFile O Y
S59 DeleteFile O N
Time
SNTP M Y
This device supports IEC61850 logical nodes as indicated in the following table. Note that the
actual instantiation of each logical node is determined by the product order code.
Nodes PCS-9705
PDIF: Differential -
PDIS: Distance -
Date: 2017-08-17
10 Communication
Nodes PCS-9705
PTUC: Undercurrent -
IARC: Archiving -
Date: 2017-08-17
10 Communication
Nodes PCS-9705
ZBAT: Battery -
ZBSH: Bushing -
ZCON: Converter -
ZGEN: Generator -
ZMOT: Motor -
Date: 2017-08-17
10 Communication
Nodes PCS-9705
ZREA: Reactor -
10.4.1 Overview
The DNP3.0 (Distributed Network Protocol) protocol can support the OSI/EPA model of the ISO
(International Organization for Standards), and it includes four parts: application layer protocol,
transport functions, data link layer protocol and data object library. The DNP3.0 protocol is
recommended to use the Ethernet network. This relay operates as a slave in the system,
responding to commands from a master station.
NOTICE!
For the use of DNP3.0 protocol in this device, please make sure that this protocol is
enabled in device configuration file (DEV) to view and set all the related DNP3.0
communication settings via the menu "Settings" -> "Device Setup" -> "Comm
Settings".
Date: 2017-08-17
10 Communication
The descriptions given here are intended to accompany this relay. The DNP3.0 protocol is not
described here; please refer to the DNP3.0 protocol standard for the details about the DNP3.0
implementation. This manual only specifies which objects, variations and qualifiers are supported
in this relay, and also specifies what data is available from this relay via DNP3.0.
The relay operates as a DNP3.0 slave and supports subset level 3 of the protocol, plus some of
the features from level 4. The DNP3.0 communication uses the Ethernet ports (electrical or optical)
at the rear side of this relay.
The supported object groups and object variations are show in the following table.
Date: 2017-08-17
10 Communication
Date: 2017-08-17
10 Communication
Date: 2017-08-17
10 Communication
Date: 2017-08-17
10 Communication
Analog Input Deadband: Single ~ prec flt 129 (response) 00, 01 (start ~ stop)
34 3
~ pt
40 0 Analog Output Status: Any Variation
40 1 Analog Output Status: 32 ~ bit with flag 129 (response) 00, 01 (start ~ stop)
40 2 Analog Output Status: 16 ~ bit with flag 129 (response) 00, 01 (start ~ stop)
Analog Output Status: single ~ prec flt ~
40 3 129 (response) 00, 01 (start ~ stop)
pt with flag
Analog Output: 129 (response) echo of request
41 1
32 ~ bit
Analog Output: 129 (response) echo of request
41 2
16 ~ bit
Analog Output: 129 (response) echo of request
41 3
Single ~ prec ft ~ pt
129 (response) 07 (limited qty = 1)
50 1 Time and Data: Absolute time
Date: 2017-08-17
10 Communication
This relay now supports 4 Ethernet clients and 2 serial port clients. Each client can be set the DNP
related communication parameters respectively and be selected the user-defined communication
table. This relay supports a default communication table and 4 user-defined communication tables,
and the default communication table is fixed by the manufacturer and not permitted to configure
by the user.
The user can configure the user-defined communication table through the PCS-Explorer
configuration tool auxiliary software. The object groups “Binary Input”, “Binary Output”, “Analog
Input” and “Analog Output” can be configured according to the practical engineering demand.
To the analog inputs, the attributes “deadband” and “factor” of each analog input can be
configured independently. To the analog outputs, only the attribute “factor” of each analog output
needs to be configured. If the integer mode is adopted for the data formats of analog values (to
“Analog Input”, “Object Variation” is 1, 2 and 3; to “Analog Output”, “Object Variation” is 1 and 2.),
the analog values will be multiplied by the “factor” respectively to ensure their accuracy. And if the
float mode is adopted for the data formats of analog values, the actual float analog values will be
sent directly.
The judgment method of the analog input change is as below: Calculate the difference between
the current new value and the stored history value and make the difference value multiply by the
“factor”, then compare the result with the “deadband” value. If the result is greater than the
“deadband” value, then an event message of corresponding analog input change will be created.
In normal communication process, the master can online read or modify a “deadband” value by
reading or modifying the variation in “Group34”.
The remote control signals, logic links and external extended output commands can be configured
into the “Binary Output” group. The supported control functions are listed as below.
Information Point Pulse On/Null Pulse On/Close Pulse On/Trip Latch On/Null Latch Off/Null
Remote Control Not supported Close Trip Close Trip
Logic Link Not supported Set Clear Set Clear
Extended Output See following description
Date: 2017-08-17
10 Communication
This relay does not transmit the unsolicited messages if the related logic setting is set as “0”. If the
unsolicited messages want to be transmitted, the related logic setting should be set as “1” or the
DNP3.0 master will transmit “Enable Unsolicited” command to this relay through “Function Code
20” (Enable Unsolicited Messages). If the “Binary Input” state changes or the difference value of
the “Analog Input” is greater than the “deadband” value, this device will transmit unsolicited
messages. If the DNP3.0 master needs not to receive the unsolicited messages, it should forbid
this relay to transmit the unsolicited messages by setting the related logic setting as “0” or through
the “Function Code 21” (Disable Unsolicited Messages).
If the DNP3.0 master calls the Class0 data, this relay will transmit all actual values of the “Analog
Input”, “Binary Input” and “Analog Output”. The classes of the “Analog Input” and “Binary Input”
can be defined by modifying relevant settings. In communication process, the DNP3.0 master can
online modify the class of an “Analog Input” or a “Binary Input” through “Function Code 22”
(Assign Class).
Date: 2017-08-17
10 Communication
Date: 2017-08-17
11 Installation
11 Installation
Table of Contents
11 Installation ...................................................................................... 11-a
11.1 Overview ...................................................................................................... 11-1
11.2 Safety Information ....................................................................................... 11-1
11.3 Check Shipment .......................................................................................... 11-2
11.4 Material and Tools Required ....................................................................... 11-2
11.5 Device Location and Ambient Conditions ................................................. 11-2
11.6 Mechanical Installation ............................................................................... 11-3
11.7 Electrical Installation and Wiring ............................................................... 11-4
11.7.1 Grounding Guidelines ...................................................................................................... 11-4
List of Figures
Figure 11.6-1 Dimensions of full width PCS-9705 (unit: mm)............................................... 11-3
Figure 11.6-3 Demonstration of plugging a board into its corresponding slot .................. 11-3
Figure 11.7-4 Glancing demo about the wiring for electrical cables ................................... 11-7
Date: 2017-08-17
11 Installation
Date: 2017-08-17
11 Installation
11.1 Overview
The device must be shipped, stored and installed with the greatest care.
Choose the place of installation such that the communication interface and the controls on the
front of the device are easily accessible.
Air must circulate freely around the equipment. Observe all the requirements regarding place of
installation and ambient conditions given in this instruction manual.
Take care that the external wiring is properly brought into the equipment and terminated correctly
and pay special attention to grounding. Strictly observe the corresponding guidelines contained in
this section.
In certain cases, the settings have to be configured according to the demands of the engineering
configuration after replacement. It is therefore assumed that the personnel who replace modules
and units are familiar with the use of the operator program on the service PC.
WARNING!
ONLY insert or withdraw a module while the device power supply is switched off. To
this end, disconnect the power supply cable that connects with the PWR module.
NOTICE!
Industry packs and ribbon cables may ONLY be replaced on a workbench for electronic
equipment. Electronic components are sensitive to electrostatic discharge when not in
the unit's housing.
NOTICE!
NOTICE!
A module can ONLY be inserted in the slot designated in the chapter 6. Components
can be damaged or destroyed by inserting module in a wrong slot.
Should boards have to be removed from this device installed in a grounded cubicle in an HV
switchgear installation, please discharge yourself by touching station ground (the cubicle)
beforehand.
Date: 2017-08-17
11 Installation
Only hold electronic boards at the edges, taking care not to touch the components.
Only works on the board which has been removed from the cubicle on a workbench designed
for electronic equipment and wear a grounded wristband. Do not wear a grounded wristband,
however, while inserting or withdrawing units.
Always store and ship the electronic boards in their original packing. Place electronic parts in
electrostatic screened packing materials.
Visually inspect all the material when unpacking it. When there is evidence of transport damage,
lodge a claim immediately in writing with the last carrier and notify the nearest NR Company or
agent.
If the equipment is not going to be installed immediately, store all the parts in their original packing
in a clean dry place at a moderate temperature. The humidity at a maximum temperature and the
permissible storage temperature range in dry air are listed in Chapter “Technical Data”.
A suitable drill and spanners are required to secure the cubicles to the floor using the plugs
provided (if this device is mounted in cubicles).
Excessively high temperature can appreciably reduce the operating life of this device.
The place of installation should permit easy access especially to front of the device, i.e. to the
human machine interface of the equipment.
There should also be free access at the rear of the equipment for additions and replacement of
electronic boards.
Since every piece of technical equipment can be damaged or destroyed by inadmissible ambient
conditions, such as:
The location should not be exposed to excessive air pollution (dust, aggressive substances).
Surge voltages of high amplitude and short rise time, extreme changes of temperature, high
levels of humidity, severe vibration and strong induced magnetic fields should be avoided as
far as possible.
Date: 2017-08-17
11 Installation
The equipment can in principle be mounted in any attitude, but it is normally mounted vertically
(visibility of markings).
It is necessary to leave enough space top and bottom of the cut-out in the cubicle for
heat emission of this device.
This device is made of a single layer 4U chassis. Following figure shows the dimensions and
cut-out size in the cubicle of this device for reference in mounting.
482.6 290
465
Front Side
101.6
177
465±0.2
451+0.4
-0
4-Φ 6.8
101.6±0.1
Cut-Out
179 -0
+0.4
The Gollowing figure shows the installation way of a module being plugged into a corresponding
slot.
Date: 2017-08-17
11 Installation
In the case of equipment supplied in cubicles, place the cubicles on the foundations that have
been prepared. Take care while doing so not to jam or otherwise damage any of the cables that
have already been installed. Secure the cubicles to the foundations.
All these precautions can only be effective if the station ground is of good quality.
Switching operations in HV installations generate transient over voltages on control signal cables.
There is also a background of electromagnetic RF fields in electrical installations that can induce
spurious currents in the devices themselves or the leads connected to them.
On the other hand, electronic apparatus can transmit interference that can disrupt the operation of
other apparatus.
In order to minimize these influences as far as possible, certain standards have to be observed
with respect to grounding, wiring and screening.
Metal accessories such as side plates, blanking plates etc., must be effectively connected
surface-to-surface to the grounded frame to ensure a low-impedance path to ground for RF
interference. The contact surfaces must not only conduct well, they must also be non-corroding.
NOTICE!
If the above conditions are not fulfilled, there is a possibility of the cubicle or parts of it
forming a resonant circuit at certain frequencies that would amplify the transmission of
interference by the devices installed and also reduce their immunity to induced
interference.
Movable parts of the cubicle such as doors (front and back) or hinged equipment frames must be
effectively grounded to the frame by three braided copper strips (see Figure 11.7-1).
The metal parts of the cubicle housing and the ground rail are interconnected electrically
conducting and corrosion proof. The contact surfaces shall be as large as possible.
NOTICE!
For metallic connections please observe the voltage difference of both materials
according to the electrochemical code.
The cubicle ground rail must be effectively connected to the station ground rail by a
grounding strip (braided copper).
Date: 2017-08-17
11 Installation
Door or hinged
equipment frame
Cubicle ground
rail close to floor
Braided
copper strip
Station
ground
Conducting
connection
There are some ground terminals on some connectors of this device, and the sign is “GND”. All
the ground terminals are connected in the cabinet of this device. Therefore, the ground terminal
on the rear panel (see Figure 11.7-2) is the only ground terminal of this device.
The grounding strips must therefore be of (preferably tinned) braided copper and not round
copper conductors, as the cross-section of round copper would have to be too large.
Proper terminations must be fitted to both ends (press/pinch fit and tinned) with a hole for bolting
them firmly to the items to be connected.
Date: 2017-08-17
11 Installation
The surfaces to which the grounding strips are bolted must be electrically conducting and
non-corroding.
Press/pinch fit
cable terminal
Braided
copper strip Terminal bolt
Contact surface
Power supply, binary inputs & outputs: stranded conductor, 1.0mm 2 ~ 2.5mm 2
DANGER!
NEVER allow a open current transformer (CT) secondary circuit connected to this
device while the primary system is live. Open CT circuit will produce a dangerously
high voltage that cause death.
A female connector is used for connecting the wires with it, and then a female connector plugs
into a corresponding male connector that is in the front of one board. See Chapter “Hardware” for
further details about the pin defines of these connectors.
The following figure shows the glancing demo about the wiring for the electrical cables.
Date: 2017-08-17
11 Installation
01 02
03 04
Tighten 05 06
07 08
09 10
11 12
01
13 14
15 16
17 18
19 20
21 22
23 24
Figure 11.7-4 Glancing demo about the wiring for electrical cables
Date: 2017-08-17
11 Installation
Date: 2017-08-17
12 Commissioning
12 Commissioning
Table of Contents
12 Commissioning ............................................................................ 12-a
12.1 Overview ...................................................................................................... 12-1
12.2 Safety Instructions ...................................................................................... 12-1
12.3 Commission Tools ...................................................................................... 12-2
12.4 Setting Familiarization ................................................................................ 12-2
12.5 Product Checks ........................................................................................... 12-3
12.5.1 With the Device De-energized ......................................................................................... 12-3
Date: 2017-08-17
12 Commissioning
Date: 2017-08-17
12 Commissioning
12.1 Overview
This device is numerical in their design, implementing all functions in software. The device
employs a high degree self-checking so in the unlikely event of a failure, it will give an alarm.
Blank commissioning test and setting records are provided at the end of this manual for
completion as required.
Before carrying out any work on the equipment, the user should be familiar with the contents of
the safety and technical data sections and the ratings on the equipment’s rating label.
DANGER!
WARNING!
ONLY qualified personnel should work on or in the vicinity of this device. This
personnel MUST be familiar with all safety regulations and service procedures
described in this manual. During operating of electrical device, certain part of the
device is under high voltage. Severe personal injury and significant device damage
could result from improper behavior.
The earthing screw of the device must be connected solidly to the protective earth conductor
before any other electrical connection is made.
Hazardous voltages can be present on all circuits and components connected to the supply
voltage or to the measuring and test quantities.
Hazardous voltages can be present in the device even after disconnection of the supply
voltage (storage capacitors!)
The limit values stated in the Chapter “Technical Data” must not be exceeded at all, not even
during testing and commissioning.
When testing the device with secondary test equipment, make sure that no other
measurement quantities are connected. Take also into consideration that the trip circuits and
may be close commands to the circuit breakers and other primary switches are disconnected
from the device unless expressly stated.
Date: 2017-08-17
12 Commissioning
Modern test set may contain many of the above features in one unit.
Multifunctional dynamic current and voltage injection test set with interval timer.
Multimeter with suitable AC current range and AC/DC voltage ranges of 0~440V and
0~250V respectively.
Optional equipment:
An electronic or brushless insulation tester with a DC output not exceeding 500V (for
insulation resistance test when required).
A portable PC, with appropriate software (this enables the rear communications port to
be tested, if this is to be used, and will also save considerable time during
commissioning).
EIA RS-485 to EIA RS-232 converter (if EIA RS-485 IEC60870-5-103 port is being
tested).
Tester: HELP-9000.
With the front cover in place all keys are accessible. All menu cells can be read. The LED
indicators and alarms can be reset. Protection or configuration settings can be changed, or fault
and event records cleared. However, menu cells will require the appropriate password to be
entered before changes can be made.
Date: 2017-08-17
12 Commissioning
If the application-specific settings have been applied to the device prior to commissioning, it is
advisable to make a copy of the settings so as to allow them restoration later. This could be done
by extracting the settings from the device itself via printer or manually creating a setting record.
This device is fully numerical and the hardware is continuously monitored. Commissioning tests
can be kept to a minimum and need only include hardware tests and conjunctive tests. The
function tests are carried out according to user’s correlative regulations.
The following tests are necessary to ensure the normal operation of the equipment before it is first
put into service.
Hardware tests
These tests are performed for the following hardware to ensure that there is no hardware
defect. Defects of hardware circuits other than the following can be detected by
self-monitoring when the DC power is supplied.
Function tests
These tests are performed for the following functions that are fully software-based.
Timers test
Conjunctive tests
The tests are performed after the device is connected with the primary equipment and other
external equipment.
On load test.
After unpacking the product, check for any damage to the device case. If there is any damage, the
internal module might also have been affected, contact the vendor. The following items listed are
necessary.
Device panel
Date: 2017-08-17
12 Commissioning
Carefully examine the device panel, device inside and other parts inside to see that no
physical damage has occurred since installation.
Panel wiring
Check the conducting wire which is used in the panel to assure that their cross section
meeting the requirement.
Carefully examine the wiring to see that they are no connection failure exists.
Check each plug-in module of the equipment on the panel to make sure that they are well
installed into the equipment without any screw loosened.
Earthing cable
Check whether the earthing cable from the panel terminal block is safely screwed to the panel
steel sheet.
Check whether all the switches, equipment keypad, isolator binary inputs and push buttons
work normally and smoothly.
Insulation resistance tests are only necessary during commissioning if it is required for them to be
done and they have not been performed during installation.
Isolate all wiring from the earth and test the isolation with an electronic or brushless insulation
tester at a DC voltage not exceeding 500V, The circuits need to be tested should include:
DC power supply
Output contacts
Communication ports
Test method:
To unplug all the terminals sockets of this device, and do the Insulation resistance test for each
circuit above with an electronic or brushless insulation tester.
On completion of the insulation resistance tests, ensure all external wiring is correctly
reconnected to the device.
Date: 2017-08-17
12 Commissioning
Check that the external wiring is correct to the relevant device diagram and scheme diagram.
Ensure as far as practical that phasing/phase rotation appears to be as expected.
Check the wiring against the schematic diagram for the installation to ensure compliance with the
customer’s normal practice.
WARNING!
Energize this device ONLY if the power supply is within the specified operating range in
the chapter 2.
The device only can be operated under the auxiliary power supply depending on the device’s
nominal power supply rating.
The incoming voltage must be within the operating range specified in Chapter “Technical Data”,
before energizing the device, measure the auxiliary supply to ensure it within the operating range.
Other requirements to the auxiliary power supply are specified in Chapter “Technical Data”. See
this section for further details about the parameters of the power supply.
The current and voltage transformer connections must remain isolated from the device for these
checks. The trip circuit should also remain isolated to prevent accidental operation of the
associated circuit breaker.
Connect the device to DC power supply correctly and turn the device on. Check program version
and forming time displayed in command menu to ensure that are corresponding to what ordered.
If the time and date is not being maintained by substation automation system, the date and time
should be set manually.
Set the date and time to the correct local time and date using menu item “Clock”.
In the event of the auxiliary supply failing, with a battery fitted on CPU board, the time and date
will be maintained. Therefore when the auxiliary supply is restored the time and date will be
correct and not need to set again.
To test this, remove the auxiliary supply from the device for approximately 30s. After being
re-energized, the time and date should be correct.
Date: 2017-08-17
12 Commissioning
On power up, the green LED “HEALTHY” should have illuminated and stayed on indicating that
the device is healthy.
The device has latched signal devices which remember the state of the trip, auto-reclose when
the device was last energized from an auxiliary supply. Therefore these indicators may also
illuminate when the auxiliary supply is applied. If any of these LEDs are on then they should be
reset before proceeding with further testing. If the LED successfully reset, the LED goes out.
There is no testing required for that that LED because it is known to be operational.
It is likely that alarms related to voltage transformer supervision will not reset at this stage.
Apply the rated DC power supply and check that the “HEALTHY” LED is lighting in green. We
need to emphasize that the “HEALTHY” LED is always lighting in operation course except that the
equipment find serious errors in it.
Produce one of the abnormal conditions listed in Chapter “Supervision”, the “ALARM” LED will
light in yellow. When abnormal condition reset, the “ALARM” LED extinguishes.
NOTICE!
The closing circuit should remain isolated during these checks to prevent accidental
operation of the associated circuit breaker.
This test verified that the accuracy of current measurement is within the acceptable tolerances.
Apply rated current to each current transformer input in turn; checking its magnitude using a
multimeter/test set readout. The corresponding reading can then be checked in the devices menu.
NOTICE!
The closing circuit should remain isolated during these checks to prevent accidental
operation of the associated circuit breaker.
This test verified that the accuracy of voltage measurement is within the acceptable tolerances.
Apply rated voltage to each voltage transformer input in turn; checking its magnitude using a
multimeter/test set readout. The corresponding reading can then be checked in the devices menu.
This test checks that all the binary inputs on the equipment are functioning correctly.
The binary inputs should be energized one at a time, see external connection diagrams for
terminal numbers.
Ensure that the voltage applied on the binary input must be within the operating range.
Date: 2017-08-17
12 Commissioning
The status of each binary input can be viewed using device menu. Sign “1” denotes an energized
input and sign “0” denotes a de-energized input.
1. Confirm the external wiring to the current and voltage inputs is correct.
However, these checks can only be carried out if there are no restrictions preventing the
tenderization of the plant being protected.
Remove all test leads, temporary shorting leads, etc. and replace any external wiring that has
been removed to allow testing.
If it has been necessary to disconnect any of the external wiring from the device in order to
perform any of the foregoing tests, it should be ensured that all connections are replaced in
accordance with the relevant external connection or scheme diagram. Confirm current and
voltage transformer wiring.
If the device is in a new installation or the circuit breaker has just been maintained, the circuit
breaker maintenance and current counters should be zero. If a test block is installed, remove the
test plug and replace the cover so that the device is put into service.
Ensure that all event records, fault records and alarms have been cleared and LED’s has been
reset before leaving the device.
Date: 2017-08-17
12 Commissioning
Date: 2017-08-17
13 Maintenance
13 Maintenance
Table of Contents
13 Maintenance .................................................................................. 13-1
13.1 Appearance Check ...................................................................................... 13-1
13.2 Failure Tracing and Repair ......................................................................... 13-1
13.3 Replacing Failed Modules .......................................................................... 13-2
13.4 Cleaning ....................................................................................................... 13-3
13.5 Storage ......................................................................................................... 13-3
Date: 2017-08-17
13 Maintenance
This device is designed to require no special maintenance. All measurement and signal
processing circuit are fully solid state. All input modules are also fully solid state. The output relays
are hermetically sealed.
Since the device is almost completely self-monitored, from the measuring inputs to the output
relays, hardware and software defects are automatically detected and reported. The
self-monitoring ensures the high availability of the device and generally allows for a corrective
rather than preventive maintenance strategy. Therefore, maintenance checks in short intervals
are not required.
Operation of the device is automatically blocked when a hardware failure is detected. If a problem
is detected in the external measuring circuits, the device normally only provides alarm messages.
It is only allowed to plug or withdraw device board when the supply is reliably switched off.
Never allow the CT secondary circuit connected to this equipment to be opened while the
primary system is live when withdrawing an AC module. Never try to insert or withdraw the
device board when it is unnecessary.
Check weld spots on PCB whether they are well soldered without any rosin joint. All dual
inline components must be well plugged.
When a failure is detected by supervision, a remote alarm is issued and the failure is indicated on
the front panel with LED indicators and LCD display. It is also recorded in the event record.
Failures detected by supervision are traced by checking the “Superv State” screen on the LCD.
WARNING!
Module can ONLY be replaced while the device power supply is switched off.
ONLY appropriately trained and qualified personnel can perform the replacement by
strictly observing the precautions against electrostatic discharge.
WARNING!
Five seconds is NECESSARY for discharging the voltage. Hazardous voltage can be
present in the DC circuit just after switching off the DC power supply.
CAUTION!
Take anti-static measures such as wearing an earthed wristband and placing modules
on an earthed conductive mat when handling a module. Otherwise, electronic
components could be damaged.
CAUTION!
If the failure is identified to be in the device module and the user has spare modules, the user can
recover the device by replacing the failed modules.
Repair at the site should be limited to module replacement. Maintenance at the component level
is not recommended.
Check that the replacement module has an identical module name (AI, PWR, MON, BI, BO, etc.)
and hardware type-form as the removed module. Furthermore, the MON module replaced should
have the same software version. In addition, the AI and PWR module replaced should have the
same ratings.
The module name is indicated on the top front of the module. The software version is indicated in
LCD menu “Information”->“Version Info”.
Replacing a module
3. Short circuit all AC current inputs and disconnect all AC voltage inputs
Date: 2017-08-17
13 Maintenance
9. After replacing the MON module, input the application-specific setting values again.
2. Unplug the ribbon cable on the front panel by pushing the catch outside.
13.4 Cleaning
Before cleaning the device, ensure that all AC/DC supplies, current transformer connections are
isolated to prevent any chance of an electric shock whilst cleaning. Use a smooth cloth to clean
the front panel. Do not use abrasive material or detergent chemicals.
13.5 Storage
The spare device or module should be stored in a dry and clean room. Based on IEC standard
60255-1 the storage temperature should be from -40°C to +70°C, but the temperature of from 0°C
to +40°C is recommended for long-term storage.
Date: 2017-08-17
14 Decommissioning and Disposal
Table of Contents
14 Decommissioning and Disposal ................................................. 14-a
14.1 Decommissioning ....................................................................................... 14-1
14.2 Disposal ....................................................................................................... 14-1
Date: 2017-08-17
14 Decommissioning and Disposal
Date: 2017-08-17
14 Decommissioning and Disposal
14.1 Decommissioning
DANGER!
Switch OFF the circuit breaker for primary CTs and VTs BEFORE disconnecting the
cables of AI module.
WARNING!
Switch OFF the external miniature circuit breaker of device power supply BEFORE
disconnecting the power supply cable connected to the PWR module.
WARNING!
1. Switching off
To switch off this device, switch off the external miniature circuit breaker of the power supply.
2. Disconnecting Cables
Disconnect the cables in accordance with the rules and recommendations made by relational
department.
3. Dismantling
The device rack may now be removed from the system cubicle, after which the cubicles may
also be removed.
14.2 Disposal
NOTICE!
Strictly observe all local and national laws and regulations when disposing the device.
Date: 2017-08-17
14 Decommissioning and Disposal
Date: 2017-08-17
15 Manual Version History
Date: 2017-08-17
15 Manual Version History