Professional Documents
Culture Documents
Preface
Introduction
This guide and the relevant operating or service manual documentation for the equipment provide
full information on safe handling, commissioning and testing of this equipment.
Documentation for equipment ordered from NR is dispatched separately from manufactured goods
and may not be received at the same time. Therefore, this guide is provided to ensure that printed
information normally present on equipment is fully understood by the recipient.
Before carrying out any work on the equipment, the user should be familiar with the contents of
this manual, and read relevant chapter carefully.
This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
When electrical equipment is in operation, dangerous voltages will be present in certain parts of
the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.
Before working in the terminal strip area, the equipment must be isolated.
Proper and safe operation of the equipment depends on appropriate shipping and handling,
proper storage, installation and commissioning, and on careful operation, maintenance and
servicing. For this reason, only qualified personnel may work on or operate the equipment.
Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected;
Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;
Are trained in the care and use of safety apparatus in accordance with safety engineering
practices;
DANGER! means that death, severe personal injury and considerable equipment damage
will occur if safety precautions are disregarded.
WARNING! means that death, severe personal and considerable equipment damage
could occur if safety precautions are disregarded.
CAUTION! means that light personal injury or equipment damage may occur if safety
precautions are disregarded.
NOTICE! is particularly applies to damage to device and to resulting damage of the protected
equipment.
DANGER!
NEVER allow a open current transformer (CT) secondary circuit connected to this
device while the primary system is live. Open CT circuit will produce a dangerously high
voltage that cause death.
WARNING!
ONLY qualified personnel should work on or in the vicinity of this device. This personnel
MUST be familiar with all safety regulations and service procedures described in this
manual. During operating of electrical device, certain part of the device is under high
voltage. Severe personal injury and significant device damage could result from
improper behavior.
WARNING!
Do NOT touch the exposed terminals of this device while the power supply is on. The
generated high voltage causes death, injury, and device damage.
WARNING!
Thirty seconds is NECESSARY for discharging the voltage. Hazardous voltage can be
present in the DC circuit just after switching off the DC power supply.
CAUTION!
Earthing
Operating environment
ONLY use the device within the range of ambient environment and in an
environment free of abnormal vibration.
Ratings
Check the input ratings BEFORE applying AC voltage/current and power supply to
the device.
Do NOT attach or remove printed circuit board if the device is powered on.
External circuit
Check the supply voltage used when connecting the device output contacts to
external circuits, in order to prevent overheating.
Connection cable
NOTICE!
We reserve all rights to this document and to the information contained herein. Improper use in particular reproduction and dissemination
to third parties is strictly forbidden except where expressly authorized.
The information in this manual is carefully checked periodically, and necessary corrections will be included in future editions. If
nevertheless any errors are detected, suggestions for correction or improvement are greatly appreciated.
Documentation Structure
The manual provides a functional and technical description of this relay and a comprehensive set
of instructions for the relay’s use and application.
1 Introduction
Briefly introduce the application, functions and features about this relay.
2 Technical Data
Introduce the technical data about this relay, such as electrical specifications, mechanical
specifications, ambient temperature and humidity range, communication port parameters, type
tests, setting ranges and accuracy limits and the certifications that our products have passed.
3 Operation Theory
Introduce a comprehensive and detailed functional description of all protective elements.
4 Supervision
Introduce the automatic self-supervision function of this relay.
6 Hardware
Introduce the main function carried out by each plug-in module of this relay and providing the
definition of pins of each plug-in module, typical wiring is provided.
7 Settings
List settings including system settings, communication settings and etc.
9 Configurable Function
Brief introduction of configurable functions of the device and all configurable signals are listed.
10 Communication
Introduce the communication port and protocol which this relay can support, IEC60970-5-103,
IEC61850 and DNP3.0 protocols are introduced in details.
11 Installation
Introduce the recommendations on unpacking, handling, inspection and storage of this relay. A
guide to the mechanical and electrical installation of this relay is also provided, incorporating
earthing recommendations.
12 Commissioning
Introduce how to commission this relay, comprising checks on the calibration and functionality of
this relay.
13 Maintenance
A general maintenance policy for this relay is outlined.
Deviations may be permitted in drawings and tables when the type of designator can be obviously
derived from the illustration.
&
AND gate
≥1
OR gate
Comparator
Timer
t
Time (optional definite-time or inverse-time characteristic)
t
10ms 2ms
Timer [delay pickup (10ms), delay dropoff (2ms), non-settable]
[XXX] 0ms
Timer (delay pickup, settable)
0ms [XXX]
Timer (delay drop off, settable)
[XXX] [XXX]
Timer (delay pickup, delay drop off, settable)
Example
Ia, Ib, Ic, I0 IL1, IL2, IL3, IN IR, IY, IB, IN
Ua, Ub, Uc VL1, VL2, VL3 UR, UY, UB
Uab, Ubc, Uca VL12, VL23, VL31 URY, UYB, UBR
U0, U1, U2 VN, V1, V2 UN, U1, U2
1 Introduction
Table of Contents
List of Figures
1.1 Application
The PCS-921 is a digital breaker protection device and can be applied for all kinds of busbar
arrangement. By default, breaker failure protection, voltage protection, frequency protection,
overcurrent protection, dead zone protection, pole discrepancy protection and automatic reclosing
function is taken as the standard function of PCS-921.
PCS-921 supports configurable binary inputs, binary outputs, LEDs and IEC 61850 protocol.
Bus 1
PCS-921
52
Line 1 50BF 62PD 50/51G 50/51P 59 27 59G
52
Line 2
52
Bus 2
1.2 Function
1. Protection Function
Energy metering (active and reactive energy are calculated in import respectively export
direction)
3. Logic
4. Additional function
Self diagnostic
Auto-reclosing (79)
Synchro-checking (25)
Event recorder including 1024 disturbance records, 1024 binary events, 1024 supervision
events, 256 control logs and 1024 device logs.
Disturbance recorder including 32 disturbance records with waveforms (The file format of
disturbance recorder is compatible with international COMTRADE file.)
Conventional
PPS (RS-485): Pulse per second (PPS) via RS-485 differential level
PPM (DIN): Pulse per minute (PPM) via the optical coupler
PPS (DIN): Pulse per second (PPS) via the optical coupler
SAS
Advanced
PPS (Fiber) PPS: Pulse per second (PPS) via optical-fibre interface
NoTimeSyn
5. Monitoring
Frequency
6. Communication
Optional 2 or 4 Ethernet ports (depend on the chosen type of MON plug-in module) conform
to IEC 61850 protocol, DNP3.0 protocol or IEC 60870-5-103 protocol over TCP/IP
Optional 2 Ethernet ports via optic fiber (ST interface) conform to IEC 61850 protocol, DNP3.0
protocol or IEC 60870-5-103 protocol over TCP/IP
7. User Interface
Friendly HMI interface with LCD and 9-button keypad on the front panel.
Auxiliary software—PCS-Explorer
1.3 Features
The intelligent device integrated with protection, control and monitor provides powerful
protection function, flexible protection configuration, user programmable logic and
configurable binary input and binary output, which can meet with various application
requirements.
Flexible automatic reclosure supports various initiation modes and check modes.
Multiple setting groups with password protection and setting value saved permanently before
modification.
Powerful PC tool software can fulfill protection function configuration, modify setting and
waveform analysis.
2 Technical Data
Table of Contents
“System phase sequence”, which can be set by PCS-Explorer, this setting informs the
device of the actual system phase sequence, either ABC or ACB. CT and VT inputs on
the device, labeled as A, B and C, must be connected to system phase A, B and C for
correct operation.
2.6 Certifications
ISO9001:2008
ISO14001:2004
OHSAS18001:2007
ISO10012:2003
CMMI L5
2.7 Terminals
Connection Type Wire Size
Crimp terminals, 1.5mm ~4.0mm2 lead
2
2
AC current If using 4.0mm lead, only dedicated terminal cable lug provided by NR
can be adopted.
AC voltage Crimp terminals, 1.0mm2~2.5mm2 lead
Power supply Crimp terminals, 1.0mm2~2.5mm2 lead
2 2
Contact I/O Crimp terminals, 1.0mm ~2.5mm lead
Grounding (Earthing) Connection BVR type, 2.5mm²~6.0mm2 lead
Maximum duration 10000 sampled points (24 sampled points per cycle)
Recording position 10 cycles before pickup of trigger element
2.10.14 Auto-reclosing
Phase difference setting range 0~89 (Deg)
Accuracy 2.0Deg
0.02Un~0.8Un (V)
Voltage difference setting range
(Un:Secondary rated phase-to-ground voltage)
Accuracy Max(0.01Un, 2.5%)
Frequency difference setting range 0.02~1 (Hz)
Accuracy 0.01Hz
Operating time of synchronism check ≤1%Setting+20ms
Operating time of energizing check ≤1%Setting+20ms
Operating time of auto-reclosing ≤1%Setting+20ms
3 Operation Theory
Table of Contents
List of Figures
Figure 3.7-1 Logic diagram of earth fault protection (stage 1) ............................................. 3-38
Figure 3.7-2 Logic diagram of earth fault protection (stage x) ............................................. 3-39
Figure 3.9-2 Logic diagram of negative sequence overvoltage protection ........................ 3-55
Figure 3.9-3 Logic diagram of stage 1 of residual overvoltage protection ......................... 3-58
Figure 3.9-4 Logic diagram of stage 2 of residual overvoltage protection ......................... 3-58
Figure 3.9-5 Logic diagram of stage 3 of residual overvoltage protection ......................... 3-59
Figure 3.10-2 Logic diagram of stage 4 of negative-sequence overcurrent protection .... 3-74
Figure 3.15-1 Relationship between reference voltage and synchronism voltage ............ 3-97
Figure 3.15-4 Voltage connection for double busbars arrangement ................................. 3-100
Figure 3.15-5 Voltage selection for double busbars arrangement ..................................... 3-101
Figure 3.15-6 Voltage connection for one and a half breakers arrangement ................... 3-102
Figure 3.15-7 Voltage selection for bus CB of one and a half breakers arrangement ..... 3-103
Figure 3.15-8 Voltage selection for tie CB of one and a half breakers arrangement ....... 3-104
Figure 3.15-9 Reference voltage circuit failure supervision logic ..................................... 3-105
Figure 3.15-10 Synchronism voltage circuit failure supervision logic .............................. 3-105
Figure 3.16-9 Extra time delay and blocking logic of AR .................................................... 3-123
Figure 3.20-6 Configuration page of control output 01 (default configration) ................. 3-144
Figure 3.20-7 Configuration page of control output 02 (default configration) ................. 3-145
List of Tables
Table 3.9-6 Inverse-time curve parameters of residual overvoltage protection ................. 3-57
Table 3.9-9 Inverse-time curve parameters of phase undervoltage protection .................. 3-63
The device performs various protection functions by respective algorithms with the information
(currents and voltages) acquired from primary system through current transformer and voltage
transformer, so it is important to configure analog input channels correctly.
Further to correct configuration of analog input channels, other protected system information, such
as the parameters of voltage transformer and current transformer are also required.
The device generally considers transmission line as its protected object, current flows from busbar
to line is considered as the forward direction.
3.1.3 Settings
The status of circuit breaker (CB) position is applied for protection and control functions in this
device, such as, auto-reclose and VT circuit supervision, etc. The status of CB position can be
applied as input signals for other features configured by user.
The signal reflecting CB position is acquired via opto-coupler with settable delay pickup and
dropoff, and forms digital signal used by protection functions. CB position can reflect the status of
each phase by means of phase-segregated inputs.
In order to prevent that wrong status of CB position is input into the device via binary input,
appropriate monitor method is used to check the rationality of the binary input. When the binary
input of CB open position is detected but there is current detected in the line, the status of CB
position will be thought as incorrect and an alarm [Alm_52b] will be issued.
Together with the status of circuit breaker and the information of external circuit, this function can
be used to supervise control circuit of circuit breaker.
External manual closing binary input (ManCls) is only used for SOTF logic application, the control
of circuit breaker (CB) closing or opening should refer to section 3.29 (Control and Synchrocheck
for Manual Closing).
CB Position Supervision
52b_PhA Alm_52b
52b_PhB
52b_PhC
ManCls
CB Position Supervision
52b Alm_52b
ManCls
TCCS
52a TCCS.Alm
52b
TCCS.Input
ManCls
TCCS will be disabled automatically when it is used for phase-segregated circuit breaker.
NOTICE!
The signal [52a] only take effect in the tripping/closing circuit supervision and not affect
any protection function. ONLY IF tripping/closing circuit supervision is configured, this
signal needs to be connected to the device.
3.2.5 Logic
BI [52b_PhA] >=1
&
&
BI [52b_PhB] >=1
& &
&
SIG Ia>I_Line
>=1
& >=1 10s 10s Alm_52b
SIG Ib>I_Line
&
SIG Ic>I_Line
BI [52a] >=1
>=1
BI [52b] [TCCS.t_DPU] [TCCS.t_DDO] TCCS.Alm
BI [TCCS.Input]
I_Line is threshold value used to determine whether line is on-load or no-load. Default value
0.06In.
3.2.6 Settings
The device has one DSP module with fault detector DSP and protection DSP for fault detector and
protection calculation respectively. Protection DSP with protection fault detector element is
responsible for calculation of protection elements, and fault detector DSP is responsible to
determine fault appearance on the protected power system. Fault detector in fault detector DSP
picks up to provide positive supply to output relays. The output relays can only operate when both
the fault detector in fault detector DSP and a protection element operate simultaneously.
Otherwise, the output relays would not operate. An alarm message will be issued with blocking
outputs if a protection element operates while the fault detector does not operate.
Main part of FD is DPFC current detector element that detects the change of phase-to-phase
power frequency current, and residual current fault detector element that calculates the vector
sum of 3 phase currents as supplementary. They are continuously calculating the analog input
signals.
1. Fault detector based on DPFC current: DPFC current is greater than the setting value
2. Fault detector based on residual current: Residual current is greater than the setting value
4. Fault detector based on phase current: Phase current is greater than the setting value
5. Fault detector based on voltage: Phase voltage or phase-to-phase voltage is greater than the
setting value
6. Fault detector based on circuit breaker position: Circuit breaker position discrepancy
If any of the above conditions is complied, FD will operate to activate the output circuit providing
DC power supply to the output relays, then all protection functions are permitted to operate when
FD operate. The fault detector based on DPFC current and the fault detector based on residual
current are always enabled.
DPFC phase-to-phase current is obtained by subtracting the phase-to-phase current from that of a
cycle before.
ΔI = I(k)-I(k-24)
Where:
I(k-24) is the value of a sampling point before a cycle, 24 is the sampling points in one cycle.
200
100
-100
-200
0 20 40 60 80 100 120
Original Current
100
50
-50
-100
0 20 40 60 80 100 120
DPFC current
From above figures, it is concluded that DPFC can reflect the sudden change of current at the
initial stage of a fault and has a perfect performance of fault detection.
It is used to determine whether this pickup condition is met according to Equation 3.3-1.
For multi-phase short-circuit fault, the DPFC phase-to-phase current has high sensitivity to ensure
the pickup of protection device. For usual single phase to earth fault, it also has sufficient
sensitivity to pick up except the earth fault with very large fault resistance. Under this condition the
DPFC current is relative small, however, residual current is also used to judge pickup condition
(pickup condition 2).
This element adopts adaptive floating threshold varied with the change of load current
continuously. The change of load current is small and steadily under normal or power swing
condition, the adaptive floating threshold with the ΔISet is higher than the change of current under
these conditions and hence maintains the element stability.
Where:
ΔIΦΦMAX: The maximum half-wave integration value of phase-to-phase current (ΦΦ=AB, BC, CA)
The coefficient “1.25” is an empirical value which ensures the threshold always higher than the
unbalance output value of the system.
If operating condition is met, the fault detector based on DPFC current will operate to provide DC
power supply for output relays, the pickup signal will maintain 7s after the fault detector based on
The operation condition will be met when 3I0 is greater than the setting [FD.ROC.3I0_Set]. The
fault detector based on residual current is always in service.
Where:
3I0: residual current calculates from the vector sum of Ia, Ib and Ic
When the fault detector based on residual current operates and lasts for longer than 10 seconds,
an alarm [Alm_Pkp_I0] will be issued.
If operation condition is met, the fault detector based on residual current will operate to provide DC
power supply for output relay, and the pickup signal will maintain 7s after the fault detector based
on residual current drops off.
The operation condition will be met when negative-sequence current (I2) is greater than the
setting [FD.NOC.I2_Set]. It can be enabled or disabled by the logic setting [FD.NOC.En].
If operation condition is met, the fault detector based on negative-sequence current will operate to
provide DC power supply for output relay, and the pickup signal will maintain 7s after the fault
detector based on negative-sequence current drops off.
The fault detector based on phase current will operate to provide DC power supply for output relay
when phase overcurrent protection is enabled and meets the operation condition, and the pickup
signal will maintain 500ms after the fault detector based on phase current drops off.
This fault detector based on voltage includes the fault detectors of overvoltage protection,
undervoltage protection and frequency protection. The fault detector based on voltage will operate
to provide DC power supply for output relay when corresponding voltage element is enabled and
meets the operation condition, and the pickup signal will maintain 500ms after the fault detector
based on voltage drops off.
When pole discrepancy protection is enabled, i.e. the logic setting [62PD.En] is set as “1”, and if
three phases of circuit breaker are not in the same status, the fault detector based on circuit
breaker position will operate to provide DC power supply for output relays, and the pickup signal
will maintain 500ms after the the fault detector based on circuit breaker position drops off.
The fault detector based on auxiliary element will operate to provide DC power supply for output
relay when auxiliary element is enabled and meets the operation condition, and the pickup signal
will maintain 500ms after the fault detector based on auxiliary element drops off.
The protection device is running either of the two programs: one is “Regular program” for normal
state, and the other is “Fault calculation program” after protection fault detector picks up.
Under the normal state, the protection device will perform the following tasks:
3. Hardware self-check
Once the protection fault detector element in protection calculation DSP picks up, the protection
device will switch to fault calculation program, for example the calculation of phase overcurrent
protection, and to determine logic. If the fault is within the protected zone, the protection device will
send tripping command.
Main program
Sampling program
No Yes
Pickup?
The protection FD pickup conditions are the same as the FD in fault detector DSP as shown below.
The operation criteria for the conditions are also the same as that in fault detector DSP. Please
refer to section 3.3.2 for details.
FD
FD.Pkp
FD.DPFC.Pkp
FD.ROC.Pkp
FD.NOC.Pkp
3.3.6 Logic
Calculate negative-
I2>[FD.NOC.I2_Set] &
sequence current: I2
FD.NOC.Pkp
EN FD.NOC.En
3.3.7 Settings
Auxiliary element (AuxE) is mainly used to program logics to meet users’ applications or further
improve operating reliability of protection elements. Reliability of protective elements is assured,
auxiliary element is usually not required to configure. Auxiliary elements including current change
auxiliary element (AuxE.OCD), residual current auxiliary element (AuxE.ROC), phase current
auxiliary element (AuxE.OC), voltage change auxiliary element (AuxE.UVD), phase under voltage
auxiliary element (AuxE.UVG), phase-to-phase under voltage auxiliary element (AuxE.UVS) and
residual voltage auxiliary element (AuxE.ROV), and they can be enabled or disabled by
corresponding logic setting or binary inputs. Users can configure them according to applications
via PCS-Explorer software.
It shares DPFC current element of DPFC fault detector. If DPFC fault detector operates
(FD.DPFC.Pkp=1) and current change auxiliary element is enabled, current change auxiliary
element operates.
There are 3 stages for residual current auxiliary element (AuxE.ROC1, AuxE.ROC2 and
AuxE.ROC3). Each residual current auxiliary element will operate instantly if calculated residual
current amplitude is larger than corresponding current setting
AuxE.ROC1: 3I0>[AuxE.ROC1.3I0_Set]
AuxE.ROC2: 3I0>[AuxE.ROC2.3I0_Set]
AuxE.ROC3: 3I0>[AuxE.ROC3.3I0_Set]
Where:
There are 3 stages for phase current auxiliary element (AuxE.OC1, AuxE.OC2 and AuxE.OC3).
Each phase current auxiliary element will operate instantly if phase current amplitude is larger than
AuxE.OC1: IΦMAX>[AuxE.OC1.I_Set]
AuxE.OC2: IΦMAX>[AuxE.OC2.I_Set]
AuxE.OC3: IΦMAX>[AuxE.OC3.I_Set]
Where:
ΔUΦMAX>[AuxE.UVD.U_Set]
Where:
AuxE.UVG will operate instantly if any phase-to-ground voltage is lower than corresponding
voltage setting.
UΦMIN<[ AuxE.UVG.U_Set]
Where:
AuxE.UVS will operate instantly if any phase-to-phase voltage is lower than corresponding voltage
setting.
UΦΦMIN<[ AuxE.UVS.U_Set]
Where:
AuxE.ROV will operate instantly if calculated residual voltage is larger than corresponding voltage
setting.
3U0>[ AuxE.ROV.3U0_Set]
Where:
AuxE
AuxE.OCD.En AuxE.St
AuxE.OCD.Blk AuxE.OCD.St_DDO
AuxE.ROCx.En AuxE.OCD.On
AuxE.ROCx.Blk AuxE.ROCx.St
AuxE.OCx.En AuxE.ROCx.On
AuxE.OCx.Blk AuxE.OCx.St
AuxE.UVD.En AuxE.OCx.StA
AuxE.UVD.Blk AuxE.OCx.StB
AuxE.UVG.En AuxE.OCx.StC
AuxE.UVG.Blk AuxE.OCx.On
AuxE.UVS.En AuxE.UVD.St
AuxE.UVS.Blk AuxE.UVD.St_DDO
AuxE.ROV.En AuxE.UVD.On
AuxE.ROV.Blk AuxE.UVG.St
AuxE.UVG.StA
AuxE.UVG.StB
AuxE.UVG.StC
AuxE.UVG.On
AuxE.UVS.St
AuxE.UVS.StAB
AuxE.UVS.StBC
AuxE.UVS.StCA
AuxE.UVS.On
AuxE.ROV.St
AuxE.ROV.On
Where:
x can be 1, 2 or 3
3.4.5 Logic
SIG FD.DPFC.Pkp
SIG AuxE.OCD.En
&
& 0s [AuxE.OCD.t_DDO] AuxE.OCD.St_DDO
SIG AuxE.OCD.Blk
AuxE.OCD.On
En AuxE.OCD.En
SIG Ia
Calculate residual
SIG Ib current:
3I0=Ia+Ib+Ic
SIG Ic
3I0>[AuxE.ROC1.3I0_Set] &
SIG AuxE.ROC1.En
& AuxE.ROC1.St
SIG AuxE.ROC1.Blk
AuxE.ROC1.On
En AuxE.ROC1.En
3I0>[AuxE.ROC2.3I0_Set] &
SIG AuxE.ROC2.En
& AuxE.ROC2.St
SIG AuxE.ROC2.Blk
AuxE.ROC2.On
En AuxE.ROC2.En
3I0>[AuxE.ROC3.3I0_Set] &
SIG AuxE.ROC3.En
& AuxE.ROC3.St
SIG AuxE.ROC3.Blk
AuxE.ROC3.On
En AuxE.ROC3.En
>=1
SIG AuxE.OC1.En
&
& AuxE.OC1.St
SIG AuxE.OC1.Blk
En AuxE.OC1.En AuxE.OC1.On
>=1
SIG AuxE.OC2.En
&
& AuxE.OC2.St
SIG AuxE.OC2.Blk
En AuxE.OC2.En AuxE.OC2.On
>=1
SIG AuxE.OC3.En
&
& AuxE.OC3.St
SIG AuxE.OC3.Blk
En AuxE.OC4.En AuxE.OC3.On
0s [AuxE.UVD.t_DDO] AuxE.UVD.St_DDO
SIG AuxE.UVD.En
&
SIG AuxE.UVD.Blk AuxE.UVD.On
En AuxE.UVD.En
>=1
SIG AuxE.UVG.En
&
& AuxE.UVG.St
SIG AuxE.UVG.Blk
En AuxE.UVG.En
AuxE.UVG.On
>=1
SIG AuxE.UVS.En
&
& AuxE.UVS.St
SIG AuxE.UVS.Blk
En AuxE.UVS.En
AuxE.UVS.On
SIG AuxE.ROV.En
&
SIG AuxE.ROV.Blk AuxE.ROV.On
En AuxE.ROV.En
SIG AuxE.OCD.St_DDO
SIG AuxE.ROC1.St
>=1
SIG AuxE.ROC2.St
SIG AuxE.ROC3.St
>=1
SIG AuxE.OC1.St
>=1 AuxE.St
SIG AuxE.OC2.St
SIG AuxE.OC3.St
SIG AuxE.ROV.St
3.4.6 Settings
auxiliary element
Enabling/disabling stage 1 phase
current auxiliary element
10 AuxE.OC1.En 0 or 1
0: disable
1: enable
Current setting of stage 2 phase current
11 AuxE.OC2.I_Set (0.050~30.000)×In
auxiliary element
Enabling/disabling stage 2 phase
current auxiliary element
12 AuxE.OC2.En 0 or 1
0: disable
1: enable
Current setting of stage 3 phase current
13 AuxE.OC3.I_Set (0.050~30.000)×In
auxiliary element
Enabling/disabling stage 3 phase
current auxiliary element
14 AuxE.OC3.En 0 or 1
0: disable
1: enable
Voltage setting for voltage change
15 AuxE.UVD.U_Set 0~Un 0.001 V
auxiliary element
Extended time delay of voltage change
16 AuxE.UVD.t_DDO 0.000~10.000 0.001 s
auxiliary element
Enabling/disabling voltage change
auxiliary element
17 AuxE.UVD.En 0 or 1
0: disable
1: enable
Voltage setting for phase-to-ground
18 AuxE.UVG.U_Set 0~Un 0.001 V
under voltage auxiliary element
Enabling/disabling phase-to-ground
under voltage auxiliary element
19 AuxE.UVG.En 0 or 1
0: disable
1: enable
Voltage setting for phase-to-phase
20 AuxE.UVS.U_Set 0~Unn 0.001 V
under voltage auxiliary element
Enabling/disabling phase-to-phase
under voltage auxiliary element
21 AuxE.UVS.En 0 or 1
0: disable
1: enable
Voltage setting for residual voltage
22 AuxE.ROV.3U0_Set 0~Un 0.001 V
auxiliary element
Enabling/disabling residual voltage
auxiliary element
23 AuxE.ROV.En 0 or 1
0: disable
1: enable
Overcurrent protection is widely used in the power system as backup protection, but in some
cases, the direction of current is necessary to aid to complete the selective tripping. As shown
below:
L M N
EM C D A B EN
Fault
When line LM has an earth fault, the fault currents flowing through the relay A and the relay D are
of similar magnitude in most cases. It is desirable that the fault is isolated from the power system
by tripping the circuit breaker C and circuit breaker D. Hence, the overcurrent protection of relay A
and relay D require to associate with current direction to fulfill selective tripping.
Directional earth fault protection has a time delay due to coordinate with that of downstream so it
cannot clear the fault quickly.
The module computes direction of phase current and phase-to-phase current, zero-sequence
current and negative-sequence current.
The direction of phase current and phase-to-phase current equips with an under-voltage direction
function to ensure that phase or phase-to-phase overcurrent protection has explicit directionality
when the polarized voltage is too low for close up fault.
The direction of zero-sequence current and negative-sequence current direction equips with an
impedance compensation function to ensure that zero-sequence or negative-sequence
overcurrent protection has explicit directionality when the zero-sequence voltage or the
negative-sequence voltage is too low.
By setting the characteristic angle [RCA_OC] to determine the most sensitive forward angle of
phase current and phase-to-phase current, power value is calculated using phase current with
phase polarized voltage or phase-to-phase current with phase-to-phase polarized voltage to
determine the direction of phase current or phase-to-phase current respectively in forward
direction or reverse direction. When the power value is zero, neither forward direction nor reverse
direction is considered. As shown below:
jX
U
φ
θ I
R
O
Forward direction
Reverse direction
Where:
P=U×[I×COS(θ-φ)]
From above diagram can be seen, when θ=φ, P reaches to the maximum value. It is considered
as the most sensitive forward direction. Hence, φ is called as sensitivity angle of phase
overcurrent protection.
In the event of asymmetrical fault, because phase or phase-to-phase voltage may decrease to
very low voltage whereas positive-sequence voltage does not, the polarized voltage of phase or
phase-to-phase current direction uses positive-sequence voltage to avoid wrong direction due to
too low polarized voltage. Therefore, using positive-sequence voltage as polarized voltage can
ensure that the direction determination has no dead zone for asymmetrical fault. For symmetric
fault, if positive-sequence voltage decreases to 15%Un, the device uses memorized
positive-sequence voltage as polarized voltage, the memorized positive-sequence voltage is 1.5
cycles pre-fault positive-sequence voltage.
When using normal polarized voltage to calculate phase and phase-to-phase current direction,
there are total twelve direction determination algorithm including forward direction and reverse
direction.
When the symmetrical fault occurs on a power system, positive-sequence voltage may reduce to
less than 0.15Un, the device will switch to phase or phase-to-phase current direction for
under-voltage condition. The 1.5 cycle pre-fault positive-sequence voltage is used as polarized
voltage with reverse threshold to ensure stable direction decision when three-phase voltage goes
to approximately zero due to close up fault.
At first, the threshold is forward offset before direction is determined, and the threshold will be
reversed offset after direction is determined.
By setting the characteristic angle [RCA_ROC] and [RCA_NegOC] to determine the most
sensitive forward angle of zero-sequence current and negative-sequence current, power value is
calculated using zero-sequence current with zero-sequence voltage or negative-sequence current
with negative-sequence voltage to determine the direction of zero-sequence current and
negative-sequence current respectively in forward direction or reverse direction.
When the power value is between 0 and -0.1In, neither forward direction nor reverse direction is
considered.
jX 3U0
θ-180°
-3I0
φ
R
O
3I0
θ Reverse direction
Forward direction
Where:
P=U×[I×COS(θ-φ)]
Calculating the power value using zero-sequence current (3I0) and zero-sequence voltage (3U0)
to determine the direction of zero-sequence current
The zero-sequence current and the zero-sequence voltage can be gained by calculation
Calculating the power value using negative-sequence current (3I2) and negative-sequence
voltage (3U2) to determine the direction of negative-sequence current
The negative-sequence current and the negative-sequence voltage can be gained by calculation
is the setting [Z0_Comp], which cannot exceed the total zero-sequence impedance of
is the setting [Z2_Comp], which cannot exceed the total negative-sequence impedance
DIR
FwdDir_ROC
RevDir_ROC
FwdDir_NegOC
RevDir_NegOC
FwdDir_A
FwdDir_B
FwdDir_C
RevDir_A
RevDir_B
RevDir_C
FwdDir_AB
FwdDir_BC
FwdDir_CA
RevDir_AB
RevDir_BC
RevDir_CA
3.5.5 Settings
When a fault occurs in power system, usually the fault current would be very large and phase
overcurrent protection operates monitoring fault current is then adopted to avoid further damage to
protected equipment. Directional element can be selected to improve the sensitivity and selectivity
of the protection. For application on feeder-transformer circuits, second harmonic can also be
selected to block phase overcurrent protection to avoid the effect of inrush current on the
protection.
1. Four-stage phase overcurrent protection with independent logic, current and time delay
settings.
3. Direction control element can be selected to control each stage phase overcurrent protection
with three options: no direction, forward direction and reverse direction.
4. Second harmonic can be selected to block each stage of phase overcurrent protection.
3.6.2.1 Overview
2. Direction control element: one direction control element shared by all overcurrent elements,
and each overcurrent element can individually select protection direction.
3. Harmonic blocking element: one harmonic blocking element shared by all overcurrent
elements and each phase overcurrent element can individually enable the output signal from
harmonic element as a blocking input.
Where:
When phase overcurrent protection is used to protect feeder transformer circuits harmonic
blocking function can be selected for each stage of phase overcurrent element by configuring logic
setting [50/51Px.En_Hm2_Blk] (x=1, 2, 3 or 4) to prevent maloperation due to inrush current.
When the percentage of second harmonic component to fundamental component of any phase
current is greater than the setting [50/51P.K_Hm2], harmonic blocking element operates to block
stage x overcurrent element if corresponding logic setting [50/51Px.En_Hm2_Blk] enabled.
Operation criterion:
Equation 3.6-2
Where:
If fundamental component of any phase current is lower than the minimum operating current
(0.1In), then harmonic calculation is not carried out and harmonic blocking element does not
operate.
Where:
α is a constant.
K is a constant.
C is a constant.
The user can select the operating characteristic from various inverse-time characteristic curves by
setting [50/51Px.Opt_Curve], and parameters of available characteristics for selection are shown
in the following table.
If all available curves do not comply with user application, user may set [50/51Px.Opt_Curve] as
“UserDefine” to customize the inverse-time curve characteristic with constants α, K and C. (only
stage 1)
When inverse-time characteristic is selected, if calculated operating time is less than setting
[50/51Px.tmin], then the operating time of the protection changes to the value of setting
[50/51Px.tmin] automatically.
Define-time or inverse-time phase overcurrent protection drops off instantaneously after fault
current disappears.
50/51Px
50/51Px.En1 50/51Px.On
50/51Px.En2 50/51Px.StA
50/51Px.Blk 50/51Px.StB
50/51Px.StC
50/51Px.St
50/51Px.Op
3.6.5 Logic
SET Ic>[50/51Px.I_Set]
&
SET [50/51Px.Opt_Dir]=Foward & 50/51Px.StB
Timer
EN [50/51P1.En_VTS_Blk] t
50/51Px.Op
t
SIG I3P 2nd Hm Detect & &
SET [50/51Px.En_Hm2_Blk]
EN [50/51Px.En]
&
SIG 50/51Px.En1 &
50/51Px.On
SIG 50/51Px.En2
&
SIG 50/51Px.Blk
SIG FD.Pkp
x=1, 2, 3, 4
3.6.6 Settings
overcurrent protection
Enabling/disabling stage 2 of phase
overcurrent protection
17 50/51P2.En 0 or 1
0: disable
1: enable
Enabling/Disabling auto-reclosing
blocked when stage 2 of phase
18 50/51P2.En_BlkAR 0 or 1 overcurrent protection operates
0: disable
1: enable
Enabling/Disabling stage 2 of phase
overcurrent protection been blocked
19 50/51P2.En_VTS_Blk 0 or 1 by VT circuit failure
0: disable
1: enable
Non_Directional
Direction option for stage 2 of phase
20 50/51P2.Opt_Dir Forward
overcurrent protection
Reverse
Enabling/disabling second harmonic
blocking for stage 2 of phase
21 50/51P2.En_Hm2_Blk 0 or 1 overcurrent protection
0: disable
1: enable
DefTime, IECN,
IECV, IECE, IECST,
Option of characteristic curve for
IECLT, ANSIE,
22 50/51P2.Opt_Curve stage 2 of phase overcurrent
ANSIV, ANSI,
protection
ANSIM, ANSILTE,
ANSILTV, ANSILT
Time multiplier setting for stage 2 of
23 50/51P2.TMS 0.010~20000.000 0.001 inverse-time phase overcurrent
protection.
Minimum operating time for stage 2
24 50/51P2.tmin 0.010~20.000 0.001 s of inverse-time phase overcurrent
protection
Current setting for stage 3 of phase
25 50/51P3.I_Set (0.050~30.000)×In 0.001 A
overcurrent protection
Time delay for stage 3 of phase
26 50/51P3.t_Op 0.000~20.000 0.001 s
overcurrent protection
Enabling/disabling stage 3 of phase
overcurrent protection
27 50/51P3.En 0 or 1
0: disable
1: enable
28 50/51P3.En_BlkAR 0 or 1 Enabling/Disabling auto-reclosing
by VT circuit failure
0: disable
1: enable
Non_Directional
Direction option for stage 4 of phase
40 50/51P4.Opt_Dir Forward
overcurrent protection
Reverse
Enabling/disabling second harmonic
blocking for stage 4 of phase
41 50/51P4.En_Hm2_Blk 0 or 1 overcurrent protection
0: disable
1: enable
DefTime, IECN,
IECV, IECE, IECST,
Option of characteristic curve for
IECLT, ANSIE,
42 50/51P4.Opt_Curve stage 4 of phase overcurrent
ANSIV, ANSI,
protection
ANSIM, ANSILTE,
ANSILTV, ANSILT
Time multiplier setting for stage 4 of
43 50/51P4.TMS 0.010~20000.000 0.001 inverse-time phase overcurrent
protection.
Minimum operating time for stage 4
44 50/51P4.tmin 0.010~20.000 0.001 s of inverse-time phase overcurrent
protection
During normal operation of power system, there is trace residual current, whereas a fault current
flows to earth will result in greater residual current. Therefore, residual current is adopted for the
calculation of earth fault protection.
In order to improve the selectivity of earth fault protection in power grid with multiple power
sources, directional element can be selected to control earth fault protection. For application on
line-transformer unit, second harmonic also can be selected to block earth fault protection to avoid
the effect of sympathetic current on the protection.
1. Four-stage earth fault protection with independent logic, current and time delay settings.
3. Directional element can be selected to control each stage of earth fault protection with three
4. Second harmonic can be selected to block each stage of earth fault protection.
5. Stage 2, 3 or 4 of earth fatul protection can select short time delay to accelerate to trip.
3.7.2.1 Overview
1. Overcurrent element: each stage equipped with one independent overcurrent element.
2. Directional control element: one direction control element shared by all overcurrent elements,
and each overcurrent element can individually select protection direction.
3. Harmonic blocking element: one harmonic blocking element shared by all overcurrent
elements and each overcurrent element can individually enable the output signal of harmonic
blocking element as a blocking input.
The operation criterion for each stage of earth fault protection is:
Where:
In order to prevent effects of inrush current on earth fault protection, harmonic blocking function
can be selected for each stage of earth fault element by configuring logic setting
[50/51Gx.En_Hm2_Blk] (x=1, 2, 3 or 4).
Operation criterion:
Equation 3.7-2
Where:
If fundamental component of residual current is lower than the minimum operating current (0.1In)
then harmonic calculation is not carried out and harmonic blocking element does not operate.
All 4 stages earth fault protection can be selected as definite-time or inverse-time characteristic,
and inverse-time operating time curve is as follows.
Equation 3.7-3
Where:
K is a constant
C is a constant.
α is a constant.
The user can select the operating characteristic from various inverse-time characteristic curves by
setting [50/51Gx.Opt_Curve], and parameters of available characteristics for selection are shown
in the following table.
If all available curves do not comply with user application, user may set [50/51Gx.Opt_Curve] as
“UserDefine” to customize the inverse-time curve characteristic, and constants K, α and C with
configuration tool software. (only stage 1)
When inverse-time characteristic is selected, if calculated operating time is less than setting
[50/51Gx.tmin], then the operating time of the protection changes to the value of setting
[50/51Gx.tmin] automatically.
Define-time or inverse-time directional earth-fault protection drops off instantaneously after fault
current disappears.
50/51Gx
50/51Gx.En1 50/51Gx.On
50/51Gx.En2 50/51Gx.On_ShortDly
50/51Gx.Blk 50/51Gx.St
50/51Gx.En_ShortDly 50/51Gx.Op
50/51Gx.Blk_ShortDly
3.7.5 Logic
EN [50/51G1.En]
&
SIG 50/51G1.En1 &
50/51G1.On
SIG 50/51G1.En2
SIG 50/51G1.Blk
SET 3I0>[50/51G1.3I0_Set]
EN [50/51G1.En_Abnor_Blk] >=1
&
SET [50/51G1.Opt_Dir]=Non_Directional
EN [50/51G1.En_CTS_Blk]
>=1 >=1
SIG I3P 2nd Hm Detect & & 50/51G1.Op
[50/51G1.t_Op] 0
SET [50/51G1.En_Hm2_Blk]
SET [50/51G1.Opt_Curve]=DefTime
EN [50/51Gx.En]
&
SIG 50/51Gx.En1 &
50/51Gx.On
SIG 50/51Gx.En2
SIG 50/51Gx.Blk
SET 3I0>[50/51Gx.3I0_Set]
EN [50/51Gx.En_Abnor_Blk] >=1
&
SET [50/51Gx.Opt_Dir]=Non_Directional
EN [50/51Gx.En_CTS_Blk]
>=1
SIG I3P 2nd Hm Detect & &
[50/51Gx.t_Op] 0
SET [50/51Gx.En_Hm2_Blk]
>=1
SET [50/51Gx.Opt_Curve]=DefTime & 50/51Gx.Op
[50/51Gx.t_ShortDly] 0
EN [50/51Gx.En_ShortDly]
&
SIG [50/51Gx.En_ShortDly] 50/51Gx.On_ShortDly
SIG [50/51Gx.Blk_ShortDly]
Where:
x=2, 3, 4
Abnormal condition 1: when the system is under pole disagreement condition, for 1-pole AR, earth
fault protection will operate. If the logic setting [50/51Gx.En_Abnor_Blk] is set as “1”, the stage x of
earth fault protection will be blocked. If the logic setting [50/51Gx.En_Abnor_Blk] is set as “0”,
earth fault protection is not controlled by direction element.
Abnormal condition 2: When manually closing circuit breaker, three phases of the circuit breaker
maybe not operate simultaneously, and SOTF protection should operate. If the logic setting
[50/51Gx.En_Abnor_Blk] is set as “1”, the stage x of earth fault protection will be blocked. If the
logic setting [50/51Gx.En_Abnor_Blk] is set as “0”, earth fault protection is not controlled by
direction element.
Abnormal condition 3: VT circuit failure. If the logic setting [50/51Gx.En_Abnor_Blk] is set as “1”,
the stage x of earth fault protection will be blocked. If the logic setting [50/51Gx.En_Abnor_Blk] is
set as “0”, earth fault protection is not controlled by direction element.
3.7.6 Settings
ANSILTV, ANSILT,
UserDefine
Time multiplier setting for stage 1
11 50/51G1.TMS 0.010~200.000 0.001 of inverse-time earth fault
protection
Minimum operating time for stage
12 50/51G1.tmin 0.050~20.000 0.001 s 1 of inverse-time earth fault
protection
Constant “α” for stage 1 of
customized inverse-time
13 50/51G1.Alpha 0.010~5.000 0.001
characteristic earth fault
protection
Constant “C” for stage 1 of
customized inverse-time
14 50/51G1.C 0.000~20.000 0.001
characteristic earth fault
protection
Constant “K” for stage 1 of
customized inverse-time
15 50/51G1.K 0.050~20.000 0.001
characteristic earth fault
protection
Current setting for stage 2 of
16 50/51G2.3I0_Set (0.050~30.000)×In 0.001 A
earth fault protection
Time delay for stage 2 of earth
17 50/51G2.t_Op 0.000~20.000 0.001 s
fault protection
Short time delay for stage 2 of
18 50/51G2.t_ShortDly 0.000~20.000 0.001 s
earth fault protection
Enabling/disabling stage 2 of
earth fault protection
19 50/51G2.En 0 or 1
0: disable
1: enable
Enabling/disabling accelerate
stage 2 of earth fault protection
20 50/51G2.En_ShortDly 0 or 1
0: disable
1: enable
Enabling/Disabling auto-reclosing
blocked when stage 2 of earth
21 50/51G2.En_BlkAR 0 or 1 fault protection operates
0: disable
1: enable
Non_Directional
Direction option for stage 2 of
22 50/51G2.Opt_Dir Forward
earth fault protection
Reverse
Enabling/disabling second
23 50/51G2.En_Hm2_Blk 0 or 1
harmonic blocking for stage 2 of
0: disable
1: enable
Enabling/Disabling auto-reclosing
blocked when stage 4 of earth
47 50/51G4.En_BlkAR 0 or 1 fault protection operates
0: disable
1: enable
Direction option for stage 4 of
earth fault protection
48 50/51G4.Opt_Dir 0 or 1 0: no direction
1: forward direction
2: reverse direction
Enabling/disabling second
harmonic blocking for stage 4 of
49 50/51G4.En_Hm2_Blk 0 or 1 earth fault protection
0: disable
1: enable
Enabling/disabling blocking for
stage 4 of earth fault protection
50 50/51G4.En_Abnor_Blk 0 or 1 under abnormal conditions
0: disable
1: enable
Enabling/disabling blocking for
stage 4 of earth fault protection
51 50/51G4.En_CTS_Blk 0 or 1 under CT failure conditions
0: disable
1: enable
DefTime, IECN,
IECV, IECE,
IECST, IECLT,
Option of characteristic curve for
52 50/51G4.Opt_Curve ANSIE, ANSIV,
stage 4 of earth fault protection
ANSI, ANSIM,
ANSILTE,
ANSILTV, ANSILT
Time multiplier setting for stage 4
53 50/51G4.TMS 0.010~200.000 0.001 of inverse-time earth fault
protection
Minimum operating time for stage
54 50/51G4.tmin 0.050~20.000 0.001 s 4 of inverse-time earth fault
protection
Generally, fault current is very large when multi-phase fault occurs between CT and circuit breaker
(i.e. dead zone) and it will have a greater impact on the system. Breaker failure protection can
operate after a longer time delay, in order to clear the dead zone fault quickly and improve the
system stability, dead zone protection with shorter time delay (compared with breaker failure
protection) is adopted.
For some wiring arrangement (for example, circuit breaker is located between CT and the line), if
fault occurs between CT and circuit breaker, line protection can operate to trip circuit breaker
quickly, but the fault have not been cleared since local circuit breaker is tripped. Here dead zone
protection is needed in order to trip relevant circuit breaker.
The criterion for dead zone protection is: when dead zone protection is enabled, binary input of
initiating dead zone protection is energized (by default, three-phase tripping signal is used to
initiate dead zone protection), if overcurrent element for dead zone protection operates, then
corresponding circuit breaker is tripped and three phases normally closed contact of the circuit
breaker are energized, dead zone protection will operate to trip adjacent circuit breaker after a
time delay.
50DZ
50DZ.En1 50DZ.On
50DZ.En2
50DZ.St
50DZ.Blk
50DZ.Op
50DZ.Init
3.8.6 Logic
EN [50DZ.En]
&
SIG 50DZ.En1 &
50DZ.On
SIG 50DZ.En2
SIG 50DZ.Blk
BI [52b_PhA]
&
BI [52b_PhB]
BI [52b_PhC]
50DZ.St
SET Ia > [50DZ.I_Set]
&
>=1 & [50DZ.t_Op] 0ms 50DZ.Op
SET Ib > [50DZ.I_Set]
SIG 50DZ.Init
3.8.7 Settings
undervoltage may cause stability problem. Each voltage protection function has three individual
stages with respective time delay. These voltage protection functions can be enabled or disabled
separately. Selectable definite-time characteristic and multiple inverse-time characteristics are
available.
Abnormal high voltages often occur e.g. in low loaded, long distance transmission lines, in
islanded systems when generator voltage regulation fails, or load rejection of a generator. Even if
compensation reactors are provided to avoid line overvoltage by compensation of the line
capacitance and thus reduction of the overvoltage, the overvoltage will endanger the insulation if
the reactors fail. The line must be de-energized within a very short time.
The overvoltage protection in this device detects the phase voltages Ua, Ub and Uc or the
phase-to-phase voltages Uab, Ubc and Uca with an option of any phase or all phases operation
for output. The overvoltage protection can be used for tripping purpose as well as to initiate
transfer trip, which selectable controlled by local circuit breaker.
1. Three-stage phase overvoltage protection with independent logic, voltage and time delay
settings.
inverse-time characteristics.
4. “1-out-of-3” or “3-out-of-3” logic can be selected for protection criterion. (1-out-of-3 means any
1. Operation Criterion
Users can select phase voltage or phase-to-phase voltage for the protection calculation. If setting
[59Px.Opt_Up/Upp] is set to “0”, phase voltage criterion is selected and if [59Px.Opt_Up/Upp] is
set to “1”, phase-to-phase voltage criterion is selected.
When phase voltage or phase-to-phase voltage is greater than any enabled stage voltage setting,
the stage protection picks up and operates after delay, which will drop off instantaneously when
fault voltage disappears.
Two operation criteria of definite-time overvoltage protection are shown as follows, which of them
is applied depending on the logic setting [59Px.Opt_1P/3P].
or
Where:
When [59Px.Opt_1P/3P] is set as “1”, “1-out-of-3” logic (Equation 3.9-1) is selected as operation
criterion, and when set as “0”, “3-out-of-3” logic (Equation 3.9-2) is selected.
Two operation criteria of definite-time overvoltage protection are shown as follows, which of them
is applied depending on the logic setting [59Px.Opt_1P/3P].
or
When [59Px.Opt_1P/3P] is set as “1”, “1-out-of-3” logic (Equation 3.9-3) is selected as operation
criterion, and when set as “0”, “3-out-of-3” logic (Equation 3.9-4) is selected.
2. Characteristic Curve
Where:
K is a constant.
C is a constant.
α is a constant.
For stage x (x =1, 2 or 3) of overvoltage protection, operating characteristic can be chosen from
definite-time characteristic and 12 inverse-time characteristics by setting the logic setting
[59Px.Opt_Curve]. The parameters of each characteristic are listed in the following table.
When inverse-time characteristic is selected, if calculated operating time is less than setting
[59Px.tmin], then the operating time changes to the value of setting [59Px.tmin] automatically.
59Px
59Px.En1 59Px.On
59Px.En2 59Px.St
59Px.Blk 59Px.St1
59Px.St2
59Px.St3
59Px.Op
59Px.Alm
59Px.Op_InitTT
3.9.1.5 Logic
EN [59Px.En]
&
SIG 59Px.En1 &
59Px.On
SIG 59Px.En2
SIG 59Px.Blk
BI [52b_PhA]
&
BI [52b_PhB] &
BI [52b_PhC]
EN [59Px.En_52b_TT]
&
>=1
EN [59Px.En_TT] 59Px.Op_InitTT
EN [59Px.En_Alm] &
SIG FD.Pkp &
SIG 59Px.On
[59Px.Opt_Up/Upp] Timer
EN & & t
>=1 t
&
SET UA>[59Px.U_Set] &
&
SET UAB>[59Px.U_Set]
Timer
& & t
>=1
SET UB>[59Px.U_Set]
t &
59Px.Op
&
SET UBC>[59Px.U_Set]
&
>=1 >=1 59Px.Alm
Timer
& & t
&
>=1 t
SET UC>[59Px.U_Set]
&
>=1
59Px.St
SET UCA>[59Px.U_Set]
59Px.St1
59Px.St2
EN [59Px.Opt_1P/3P] 59Px.St3
x=1, 2 or 3
3.9.1.6 Settings
0: 3-out-of-3 mode
1: 1-out-of-3 mode
Option of phase-to-phase voltage or phase
voltage
16 59P2.Opt_Up/Upp 0 or 1
0: phase voltage
1: phase-to-phase voltage
Enabling/disabling stage 2 of overvoltage
protection for alarm purpose
17 59P2.En_Alm 0 or 1
0: disable
1: enable
Enabling/disabling transfer trip controlled
by CB open position for stage 2 of
18 59P2.En_52b_TT 0 or 1 overvoltage protection
0: disable
1: enable
Enabling/disabling stage 2 of overvoltage
protection operate to initiate transfer trip
19 59P2.En_TT 0 or 1
0: disable
1: enable
DefTime,
IECN, IECV,
IECE, IECST,
IECLT, ANSIE,
Option of characteristic curve for stage 2 of
20 59P2.Opt_Curve ANSIV, ANSI,
overvoltage protection
ANSIM,
ANSILTE,
ANSILTV,
ANSILT
Time multiplier setting for stage 2 of
21 59P2.TMS 0.010~200.000 0.001
inverse-time overvoltage protection
Minimum delay for stage 2 of inverse-time
22 59P2.tmin 0.050~20.000 0.001 s
overvoltage protection
Voltage setting for stage 3 of overvoltage
23 59P3.U_Set Un~2Unn 0.001 V
protection
Time delay for stage 3 of overvoltage
24 59P3.t_Op 0.000~30.000 0.001 s
protection
Enabling/disabling stage 3 of overvoltage
protection
25 59P3.En 0 or 1
0: disable
1: enable
Option of 1-out-of-3 mode or 3-out-of-3
mode
26 59P3.Opt_1P/3P 0 or 1
0: 3-out-of-3 mode
1: 1-out-of-3 mode
One stage negative sequence overvoltage protection is available for the device, it can be applied
according to the actual requirement.
59Q
59Q.En1 59Q.On
59Q.En2 59Q.Op
59Q.Blk 59Q.St
3.9.2.3 Logic
SIG 59Q.Blk
[59Q.t_Op] 59Q.Op
&
59Q.StA
SET U2>[59Q.U_Set]
3.9.2.4 Settings
A single phase earth fault occurrence in ungrounded system or Peterson coil grounded system will
result in residual overvoltage, so residual overvoltage protection is equipped to prevent protected
equipment being damaged by residual overvoltage in this condition.
1. Three-stage residual overvoltage protection with independent logic, voltage and time delay
settings.
Operation Criterion
Where:
If residual voltage is greater than the setting of any stage enabled residual overvoltage protection,
the stage residual overvoltage protection will operate after time delay and the stage protection will
drop off instantaneously after fault voltage disappears.
Time Curve
Equation 3.9-6
Where:
α is a constant.
The user can select the operating characteristic from various inverse-time characteristic curves by
setting [59Gx.Opt_Curve], and parameters of available characteristics for selection are shown in
the following table.
If all available curves do not comply with user application, user may configure setting
[59Gx.Opt_Curve] to “UserDefine” to customize the inverse-time curve characteristic, and
constants K, α and C.
59G
59Gx.En1 59Gx.On
59Gx.En2 59Gx.St
59Gx.Blk 59Gx.Op
59G3.Alm
3.9.3.5 Logic
EN [59G1.En]
&
SIG 59G1.En1 &
59G1.On
SIG 59G1.En2
SIG 59G1.Blk
&
59G1.St
SET 3U0>[59G1.3U0_Set]
[59G1.t_Op] 0 59G1.Op
EN [59G2.En]
&
SIG 59G2.En1 &
59G2.On
SIG 59G2.En2
SIG 59G2.Blk
&
59G2.St
SET 3U0>[59G2.3U0_Set]
& Timer
t
t
>=1
& 59G2.Op
[59G2.t_Op] 0
SET [59G2.Opt_Curve]=DefTime
EN [59G3.En]
&
SIG 59G3.En1 &
59G3.On
SIG 59G3.En2
SIG 59G3.Blk
&
59G3.St
SET 3U0>[59G3.3U0_Set]
& Timer
t
t
>=1
&
[59G3.t_Op] 0
SET [59G3.Opt_Curve]=DefTime
&
59G3.Op
EN [59G3.En_Trp]
&
59G3.Alm
3.9.3.6 Settings
The undervoltage protection can be applied to trip when fault occurs in a system. Three stages of
undervoltage protection are available measuring phase voltages UA, UB and UC or phase-to-phase
voltages UAB, UBC and UCA. The protection output can be selected for either any phase or all
phases operation. The undervoltage protection is normally used as decoupling system rather than
load shedding.
1. Three-stage phase undervoltage protection with independent logic, voltage and time delay
settings.
4. “1-out-of-3” or “3-out-of-3” logic can be selected for protection criterion. (1-out-of-3 means any
of three phase voltages, 3-out-of-3 means all three phase voltages)
1. Operation Criterion
Users can select phase voltage or phase-to-phase voltage for the protection calculation. If setting
[27Px.Opt_Up/Upp] is set to “0”, phase voltage criterion is selected and if [27Px.Opt_Up/Upp] is
When phase voltage or phase-to-phase voltage is less than any enabled stage voltage setting, the
stage protection picks up and operates after delay, which will drop off instantaneously when fault
voltage disappears.
Two operation criteria of definite-time undervoltage protection are shown as follows, which of them
is applied depending on the logic setting [27Px.Opt_1P/3P].
or
Where:
When [27Px.Opt_1P/3P] is set as “0”, “1-out-of-3” logic (Equation 3.9-7) is selected as operation
criterion, and when set as “1”, “3-out-of-3” logic (Equation 3.9-8) is selected.
Two operation criteria of definite-time undervoltage protection are shown as follows, which of them
is applied depending on the logic setting [27Px.Opt_Up/Upp].
or
Where:
When the setting [27Px.Opt_1P/3P] is set as “0”, “1-out-of-3” logic (Equation 3.9-9) is selected as
operation criterion, and when it is set as “1”, “3-out-of-3” logic (Equation 3.9-10) is selected.
2. Characteristic Curve
Where:
K is a constant.
C is a constant.
α is a constant.
For stage x (x =1, 2 or 3) of undervoltage protection, operating characteristic can be chosen from
definite-time characteristic and twelve inverse-time characteristics by setting the logic setting
[27Px.Opt_Curve]. The parameters of each characteristic are listed in the following table.
When inverse-time characteristic is selected, if calculated operating time is less than setting
[27Px.tmin], then the operating time changes to the value of setting [27Px.tmin] automatically.
27Px
27Px.En1 27Px.On
27Px.En2 27Px.Alm
27Px.Blk 27Px.Op
27Px.St
27Px.St1
27Px.St2
27Px.St3
27Px.U_Absent
3.9.4.5 Logic
1. Current FD element: including DPFC current element, residual current element and other FD
element that related to current (the blocking condition can enabled or disabled by the logic
setting [27Px.En_FD_Ctrl])
2. Having current condition (>0.06In) (the blocking condition can enabled or disabled by the
logic setting [27Px.En_Curr_Ctrl])
3. VT circuit failure signal (the blocking condition can enabled or disabled by the logic setting
[27Px.En_VTS_Blk])
4. If any phase of circuit breaker is open (binary input of normal close contact of breaker is
energized and the corresponding phase current is smaller than 0.06In), the undervoltage
protection will be blocked.
After the device is powered, if any phase current is larger than 0.06In or the circuit breaker is
closed, the undervoltage protection is enabled with a time delay of 100ms only when any phase
voltage is larger than 0.1Un, otherwise the alarm signal [27Px.U_Absent] will be issued after the
device is powered.
EN [27Px.En_FD_Ctrl] &
SIG FD.Pkp
SIG CB Open
SIG 27Px.U_Absent
&
>=1
UV_PhAB_Curr_Rls
&
>=1
UV_PhBC_Curr_Rls
&
>=1
UV_PhCA_Curr_Rls
En 27Px.En_Curr_Ctrl
EN [27Px.En]
&
SIG 27Px.En1 &
27Px.On
SIG 27Px.En2
SIG 27Px.Blk
EN [27Px.En_Alm]
SET [27P1.Opt_1P/3P]
SIG 27Px.On
SIG Block UV
&
SIG UV_PhB_Curr_Rls
SET UAB<[27Px.U_Set]
Timer &
& &
t 27Px.Op
SIG UV_PhC_Curr_Rls >=1
t
SET UB<[27Px.U_Set]
&
&
>=1 27Px.Alm
SIG UV_PhAB_Curr_Rls
&
SET UBC<[27Px.U_Set]
>=1
& & Timer
t
SIG UV_PhBC_Curr_Rls >=1
t
SET UC<[27Px.U_Set]
& >=1
SIG UV_PhCA_Curr_Rls 27Px.St
SET UCA<[27Px.U_Set]
27Px.St1
27Px.St2
27Px.St3
x=1, 2 or 3
3.9.4.6 Settings
0: 3-out-of-3 mode
1: 1-out-of-3 mode
Option of voltage criterion adopting
phase-to-phase voltage or phase voltage
5 27P1.Opt_Up/Upp 0 or 1
0: phase voltage
1: phase-to-phase voltage
Enabling/disabling stage 1 of
undervoltage protection operate to alarm
6 27P1.En_Alm 0 or 1
0: disable
1: enable
DefTime,
IECN, IECV,
IECE, IECST,
IECLT, ANSIE,
Option of characteristic curve for stage 1
7 27P1.Opt_Curve ANSIV, ANSI, 1
of undervoltage protection
ANSIM,
ANSILTE,
ANSILTV,
ANSILT
Time multiplier setting for stage 1 of
8 27P1.TMS 0.010~200.000 0.001
inverse-time undervoltage protection
Minimum delay for stage 1 of inverse-time
9 27P1.tmin 0.050~20.000 0.001 s
undervoltage protection
Enabling/disabling stage 1 of
undervoltage protection been controlled
10 27P1.En_FD_Ctrl 0 or 1 by current related fault detector element
0: disable
1: enable
Enabling/disabling stage 1 of
undervoltage protection been controlled
11 27P1.En_Curr_Ctrl 0 or 1 by having current condition
0: disable
1: enable
Enabling/disabling stage 1 of
undervoltage protection been blocked by
12 27P1.En_VTS_Blk 0 or 1 VT circuit failure
0: disable
1: enable
Voltage setting for stage 2 of undervoltage
13 27P2.U_Set 0~Unn 0.001 V
protection
Time delay for stage 2 of undervoltage
14 27P2.t_Op 0.000~30.000 0.001 s
protection
Enabling/disabling stage 2 of
15 27P2.En 0 or 1
undervoltage protection
0: disable
1: enable
Option of 1-out-of-3 mode or 3-out-of-3
mode
16 27P2.Opt_1P/3P 0 or 1
0: 3-out-of-3 mode
1: 1-out-of-3 mode
Option of voltage criterion adopting
phase-to-phase voltage or phase voltage
17 27P2.Opt_Up/Upp 0 or 1
0: phase voltage
1: phase-to-phase voltage
Enabling/disabling stage 2 of
undervoltage protection operate to alarm
18 27P2.En_Alm 0 or 1
0: disable
1: enable
DefTime,
IECN, IECV,
IECE, IECST,
IECLT, ANSIE,
Option of characteristic curve for stage 2
19 27P2.Opt_Curve ANSIV, ANSI, 1
of undervoltage protection
ANSIM,
ANSILTE,
ANSILTV,
ANSILT
Time multiplier setting for stage 2 of
20 27P2.TMS 0.010~200.000 0.001
inverse-time undervoltage protection
Minimum delay for stage 2 of inverse-time
21 27P2.tmin 0.050~20.000 0.001 s
undervoltage protection
Enabling/disabling stage 2 of
undervoltage protection been controlled
22 27P2.En_FD_Ctrl 0 or 1 by current related fault detector element
0: disable
1: enable
Enabling/disabling stage 2 of
undervoltage protection been controlled
23 27P2.En_Curr_Ctrl 0 or 1 by having current condition
0: disable
1: enable
Enabling/disabling stage 2 of
undervoltage protection been blocked by
24 27P2.En_VTS_Blk 0 or 1 VT circuit failure
0: disable
1: enable
Voltage setting for stage 3 of undervoltage
25 27P3.U_Set 0~Unn 0.001 V
protection
0: disable
1: enable
When an asymmetric short-circuit fault happens to the power system or the power system is under
asymmetrical three-phase operation, the power system will generate negative-sequence current.
Negative-sequence current will cause serious damage to generator, motor and other equipments,
so negative-sequence overcurrent protection is used to prevent the damage. In order to make
sure the selectivity of negative-sequence overcurrent protection in multiplex power supply system,
negative-sequence overcurrent protection can be controlled by direction control element.
2. Each stage can be selected to block AR by the setting and stage 4 of negative-sequence
overcurrent protection can be selected to operate to trip or alarm.
6. Each stage can select independent releasing threshold based on the ratio of
negative-sequence current to positive-sequence current to prevent negative-sequence
overcurrent protection from undesired operation for three-phase fault with asymmetrical
position exchange of three-phase.
3.10.2.1 Overview
1. Fault detector: each stage is controlled by the fault detector based on negative-sequence
current. Negative-sequence overcurrent protection can operate when the fault detector based
on negative-sequence current operate and it is enabled.
2. Overcurrent element: each stage equipped with one independent overcurrent element.
3. Directional control element: one direction control element shared by all overcurrent elements,
4. Ratio element: each stage is equipped with one independent ratio element (I2/I1), usually the
same setting is applied for all stages.
The operation criterion for each stage of negative-sequence overcurrent protection is:
Where:
Equation 3.10-2
Where:
K is a constant
C is a constant.
α is a constant.
The user can select the operating characteristic from various inverse-time characteristic curves by
setting [50/51Qx.Opt_Curve], and parameters of available characteristics for selection are shown
in the following table.
If all available curves do not comply with user application, user may set [50/51Qx.Opt_Curve] as
“UserDefine” to customize the inverse-time curve characteristic, and constants K, α and C with
configuration tool software. (only stage 1)
When inverse-time characteristic is selected, if calculated operating time is less than setting
[50/51Qx.tmin], then the operating time of the protection changes to the value of setting
[50/51Qx.tmin] automatically.
50/51Qx
50/51Gx.En1 50/51Qx.On
50/51Gx.En2 50/51Qx.St
50/51Qx.Blk 50/51Qx.Op
50/51Q4.Alm
3.10.5 Logic
EN [50/51Qx.En]
&
SIG 50/51Qx.En1 &
50/51Qx.On
SIG 50/51Qx.En2
SIG 50/51Qx.Blk
SET I2>[50/51Qx.I2_Set]
EN [50/51Qx.En_Abnor_Blk] >=1
& & &
SIG No abnormal conditions 50/51Qx.St
& Timer
t
50/51Qx.Op
t
SET [50/51Qx.Opt_Dir]=Non_Directional
EN [50/51Qx.En_CTS_Blk]
SIG FD.NOC.Pkp
x=1, 2 or 3
Abnormal condition 1: when the system is under pole disagreement condition, for 1-pole AR,
negative-sequence overcurrent protection will operate. If the logic setting [50/51Qx.En_Abnor_Blk]
is set as “1”, the stage x of negative-sequence overcurrent protection will be blocked. If the logic
setting [50/51Qx.En_Abnor_Blk] is set as “0”, negative-sequence overcurrent protection is not
controlled by direction element.
Abnormal condition 2: When manually closing circuit breaker, three phases of the circuit breaker
maybe not operate simultaneously, and SOTF protection should operate. If the logic setting
Abnormal condition 3: VT circuit failure. If the logic setting [50/51Qx.En_Abnor_Blk] is set as “1”,
the stage x of negative-sequence overcurrent protection will be blocked. If the logic setting
[50/51Qx.En_Abnor_Blk] is set as “0”, negative-sequence overcurrent protection is not controlled
by direction element.
EN [50/51Q4.En]
&
SIG 50/51Q4.En1 &
50/51Q4.On
SIG 50/51Q4.En2
SIG 50/51Q4.Blk
SET I2>[50/51Q4.I2_Set]
EN [50/51Q4.En_Abnor_Blk] >=1
& & &
SIG No abnormal conditions 50/51Q4.St
&
& Timer
SET [50/51Q4.Opt_Dir]=Non_Directional t
50/51Q4.Alm
t
SIG CTS.Alm &
EN [50/51Q4.En_CTS_Blk]
& Timer
SIG FD.NOC.Pkp t
50/51Q4.Op
t
EN [50/51Q4.En_Trp]
3.10.6 Settings
The frequency is an important parameter to characterize power system, and the measurement and
calculation of frequency are the basis of many protection functions. The frequency calculation
module can accurately calculate the frequency of voltage component.
Protection device can be applied to the power system within frequency range of 40Hz~63Hz, the
reference frequency can be set as 50Hz or 60Hz via the system setting [Opt_SysFreq].
Protection device provide frequency tracing function, which can improve the accuracy of protection
algorithm and the performance of protection devices. For the power system using 50Hz or 60Hz
as reference frequency, the frequency tracing function can be disabled if the fluctuation of the
frequency range is not great. For the power system that the fluctuation of the frequency range is
great, the frequency tracing function can be enabled to improve protection performance.
Frequency tracing module adopts the positive-sequence voltage which derived from protection
used voltage as the calculation reference, the positive-sequence voltage can be calculated as
following:
When no VT is connected to the protection device, the frequency tracing function is disabled
automatically, then the protection device calculates protection algorithm using the system
reference frequency. When the protection device detects a fault happening to the power system or
the voltage is smaller than 0.15Un, the frequency tracing function is disabled.
This module, which combines all aboving cases, outputs system frequency to the various
protection functions.
FreqCal
FreqTrack f
fn Alm_Freq
3.11.5 Logic
SIG U3P
fn Freqence
SIG f
calulation
SIG FreqTrace
3.11.6 Settings
If the power frequency of regional rises due to the active power excess demand, overfrequency
protection operates to perform generator rejection to shed part of the generators automatically
according to the rising frequency so that power supply and the load are re-balanced.
Overfrequency protection consists of the four stages (stage 1 to stage 4). When system frequency
is greater than the setting [81O.f_Pkp], overfrequency protection will put into service.
If the positive voltage U1<0.15Un, the calculation of protection is not carried out and the output
relay will be blocked.
Where:
f is system frequency.
81O.OFx
81O.En1 81O.OFx.On
81O.En2 81O.St
81O.Blk 81O.OFx.Op
3.12.1.5 Logic
SIG 81O.En1
&
SIG 81O.En2 &
81O.OF1.On
EN [81O.OF1.En]
SIG 81O.Blk
&
SIG FD.Pkp
OTH U1<0.15Un ≥1
EN [81O.OF1.En]
SIG 81O.En1
&
SIG 81O.En2 &
81O.OF2.On
EN [81O.OF2.En]
SIG 81O.Blk
&
SIG FD.Pkp
OTH U1<0.15Un ≥1
EN [81O.OF2.En]
SIG 81O.En1
&
SIG 81O.En2 &
EN [81O.OF3.En]
81O.OF3.On
SIG 81O.Blk
&
SIG FD.Pkp
OTH U1<0.15Un ≥1
EN [81O.OF3.En]
SIG 81O.En1
&
SIG 81O.En2 &
81O.OF4.On
EN [81O.OF4.En]
SIG 81O.Blk
&
SIG FD.Pkp
OTH U1<0.15Un ≥1
EN [81O.OF4.En]
SIG 81O.St1 ≥1
SIG 81O.St2
≥1
SIG 81O.St3 ≥1 81O.St
SIG 81O.St4
3.12.1.6 Settings
overfrequency protection
Frequency setting for stage 1 of
2 81O.OF1.f_Set 50.000~65.000 (Hz) 0.001 Hz
overfrequency protection
Time delay for stage 1 of
3 81O.OF1.t_Op 0.000~20.000 (s) 0.001 s
overfrequency protection
Enabling/disabling stage 1 of
overfrequency protection
4 81O.OF1.En 0 or 1
0: disable
1: enable
Frequency setting for stage 2 of
5 81O.OF2.f_Set 50.000~65.000 (Hz) 0.001 Hz
overfrequency protection
Time delay for stage 2 of
6 81O.OF2.t_Op 0.000~20.000 (s) 0.001 s
overfrequency protection
Enabling/disabling stage 2 of
overfrequency protection
7 81O.OF2.En 0 or 1
0: disable
1: enable
Frequency setting for stage 3 of
8 81O.OF3.f_Set 50.000~65.000 (Hz) 0.001 Hz
overfrequency protection
Time delay for stage 3 of
9 81O.OF3.t_Op 0.000~20.000 (s) 0.001 s
overfrequency protection
Enabling/disabling stage 3 of
overfrequency protection
10 81O.OF3.En 0 or 1
0: disable
1: enable
Frequency setting for stage 4 of
11 81O.OF4.f_Set 50.000~65.000 (Hz) 0.001 Hz
overfrequency protection
Time delay for stage 4 of
12 81O.OF4.t_Op 0.000~20.000 (s) 0.001 s
overfrequency protection
Enabling/disabling stage 4 of
overfrequency protection
13 81O.OF4.En 0 or 1
0: disable
1: enable
In case of frequency decline due to lack of active power in the power system, underfrequency
protection operates to shed part of the load according to the declined value of frequency to
re-balance the power supply and the load.
Underfrequency protection consists of the four stages (stage 1 to stage 4). When system
frequency is smaller than the setting [81U.f_Pkp], underfrequency protection will put into service.
If the positive voltage U1<0.15Un, the calculation of protection is not carried out and the output
relay will be blocked.
If -df/dt≥[81U.df/dt_Blk], the calculation of protection is not carried out and the output relay will
be blocked. The blocking element will not be released automatically until the system frequency
recovers to be less than the setting [81U.f_Pkp].
Where:
f is system frequency.
Where:
df/dt is the frequency slip speed and the time step (i.e. dt) for the calucation is equal to 5 cycle.
Underfrequency protection can be blocked by the frequency slip speed (df/dt). If the logic setting
[81U.UFx.En_df/dt_Blk] (x=1, 2, 3 or 4) is set as “1”, when Equation 3.12-2 and Equation 3.12-3
are met, it is decided that a fault occurred and the corresponding stage underfrequency protection
is blocked at the same time for the purpose of waiting for operation of other related protection. The
blocking signal will not reset until the system frequency recovers, i.e. the system frequency is
greater than the setting [81U.f_Pkp]. If the logic setting is set as “0”, when Equation 3.12-2 and
Equation 3.12-3 are met, the stage underfrequency protection will be released to operate.
81U.UFx
81U.En1 81U.UFx.On
81U.En2 81U.St
81U.Blk 81U.UFx.Op
3.12.2.5 Logic
SIG 81U.En1
&
SIG 81U.En2
EN [81U.UF1.En]
&
81U.UF1.On
SIG 81U.Blk
&
SIG FD.Pkp &
OTH U1<0.15Un ≥1
EN [81U.UF1.En]
SIG 81U.En1
&
SIG 81U.En2
EN [81U.UF2.En]
&
81U.UF2.On
SIG 81U.Blk
&
SIG FD.Pkp &
OTH U1<0.15Un ≥1
EN [81U.UF2.En]
SIG 81U.En1
&
SIG 81U.En2
EN [81U.UF3.En]
&
81U.UF3.On
SIG 81U.Blk
&
SIG FD.Pkp &
OTH U1<0.15Un ≥1
EN [81U.UF3.En]
SIG 81U.En1
&
SIG 81U.En2
EN [81U.UF4.En]
&
81U.UF4.On
SIG 81U.Blk
&
SIG FD.Pkp &
OTH U1<0.15Un ≥1
EN [81U.UF4.En]
SIG 81U.St2
>=1
SIG 81U.St3 >=1 81U.St
SIG 81U.St4
3.12.2.6 Settings
Duplicated protection configurations are usually adopted for EHV power system, but the primary
equipment, circuit breaker, is not duplicated. Breaker failure protection is adopted to cater circuit
breaker tripping failure.
Breaker failure protection issues a back-up trip command to trip adjacent circuit breakers in case
of a tripping failure of the circuit breaker, and clears the fault as requested by the device. To utilize
the protection information of faulty equipment and the electrical information of failure circuit
breaker to constitute the criterion of breaker failure protection, it can ensure that the adjacent
circuit breakers of failure circuit breaker are tripped with a shorter time delay, so that the affected
area is minimized, and ensure stable operation of the entire power grid to prevent generators,
transformers and other components from seriously damaged.
The instantaneous re-tripping function, after receiving tripping signal from other device and the
corresponding phase overcurrent element operating, is available and provides phase-segregated
binary output contact, which can ensure the circuit breaker is still tripped in case the secondary
circuit between the device and the circuit breaker is abnormal, to avoid undesired tripping of
breaker failure protection and the expansion of the affected area. Instantaneous re-tripping
function does not block AR.
When both the phase-segregated tripping contact from line protection and the corresponding
phase overcurrent element operate, or both the three-phase tripping contact and any phase
overcurrent element operate, breaker failure protection will send three-phase tripping command to
trip local circuit breaker after time delay of [50BF.t1_Op] and trip all adjacent circuit breakers after
time delay of [50BF.t2_Op].
When the protection element except undervoltage element within this device operates and issues
tripping signal, breaker failure protection will also be initiated.
Taking into account that the faulty current is too small for generator or transformer fault, the
sensitivity of phase current element may not meet the requirements, residual current criterion and
negative-sequence current criterion are provided in addition to the phase overcurrent element for
breaker failure protection initiated by input signal [50BF.ExTrp3P_GT] from generator and
transformer protection. They can be enabled or disabled by logic settings [50BF.En_3I0_3P] and
[50BF.En_I2_3P] respectively.
For some special fault (for example, mechanical protection or overvoltage protection operating),
maybe faulty current is very small and current criterion of breaker failure protection is not met, in
order to make breaker failure protection can also operate under the above situation, an input
signal [50BF.ExTrp_WOI] is equipped to initiate breaker failure protection, once the input signal is
energized, normally closed auxiliary contact of circuit breaker is chosen in addition to breaker
failure current check to trigger breaker failure timer. The device takes current as priority with CB
auxiliary contact (52b) as an option criterion for breaker failure check.
50BF
50BF.ExTrp3P_L 50BF.On
50BF.ExTrp3P_GT 50BF.Op_ReTrpA
50BF.ExTrp_WOI 50BF.Op_ReTrpB
50BF.ExTrpA 50BF.Op_ReTrpC
50BF.ExTrpB 50BF.Op_ReTrp3P
50BF.ExTrpC 50BF.Op_t1
50BF.En 50BF.Op_t2
50BF.Blk
3.13.5 Logic
SIG 50BF.En
&
EN [50BF.En] 50BF.On
SIG 50BF.Blk
SIG 50BF.On
&
SIG FD.Pkp
EN [50BF.En_ReTrp]
EN [50BF.En_3I0_1P] >=1
SET 3I0>[50BF.3I0_Set]
&
SIG BFI_A >=1 & [50BF.t_ReTrp] 0ms 50BF.Op_ReTrpA
BI [50BF.ExTrpA]
SET IA>[50BF.I_Set]
&
SIG BFI_B >=1 & [50BF.t_ReTrp] 0ms 50BF.Op_ReTrpB
BI [50BF.ExTrpB]
SET IB>[50BF.I_Set]
&
SIG BFI_C >=1 & [50BF.t_ReTrp] 0ms 50BF.Op_ReTrpC
BI [50BF.ExTrpC] >=1
BI [50BF.ExTrp_WOI]
&
EN [50BF.En_3I0_3P] &
SET 3I0>[50BF.3I0_Set]
& >=1 >=1 [50BF.t1_Op] 0ms 50BF.Op_t1
EN [50BF.En_I2_3P] & &
[50BF.t2_Op] 0ms 50BF.Op_t2
SET I2>[50BF.I2_Set]
&
EN [50BF.En_CB_Ctrl]
BI [52b_PhA]
&
BI [52b_PhB]
BI [52b_PhC]
SIG FD.Pkp
Where:
BFI_A, BFI_B, BFI_C: A-phase, B-phase and C-phase breaker failure protection initiating signal,
please refer to Figure 3.17-1.
3.13.6 Settings
The pole discrepancy of circuit breaker may occur during operation of a breaker with segregated
operating gears for the three phases. The reason could be an interruption in the tripping/closing
circuits, or mechanical failure. A pole discrepancy can only be tolerated for a limited period. When
there is loading, zero-sequence or negative-sequence current will be generated in the power
system, which will result in overheat of the generator or the motor. With the load current increasing,
overcurrent elements based on residual current or negative-sequence current may operate. Pole
discrepancy protection is required to operate before the operation of these overcurrent elements.
Pole discrepancy protection determines three-phase breaker pole discrepancy condition by its
phase segregated CB auxiliary contacts. In order to improve the reliability of pole discrepancy
protection, the asymmetrical current component can be selected as addition criteria when needed.
62PD
62PD.En1 62PD.On
62PD.En2 62PD.St
62PD.Blk 62PD.Op
62PD.In_PD
3.14.5 Logic
Phase-segregated circuit breaker auxiliary contacts are connected to the device. When the state
of three phase-segregated circuit breaker auxiliary contacts are inconsistent, pole discrepancy
protection will be started and initiate output after a time delay [62PD.t_Op].
Pole discrepancy protection can be blocked by external input signal [62PD.Blk]. In general, this
input signal is usually from the output of 1-pole AR initiation, so as to prevent pole discrepancy
protection from operation during 1-pole AR initiation.
SIG 62PD.En1
&
SIG 62PD.En2 &
62PD.On
EN [62PD.En]
SIG 62PD.Blk
&
SIG FD.Pkp
62PD.St
EN [62PD.En_3I0/I2_Ctrl] >=1 &
[62PD.t_Op] 0ms 62PD.Op
SET 3I0>[62PD.3I0_Set] >=1
SET I2>[62PD.I2_Set]
BI [52b_PhA] &
&
SIG Ia<0.06In
SIG Ib<0.06In
>=1
BI [52b_PhC] &
SIG Ic<0.06In
Where:
3.14.6 Settings
1: enable
Enabling/disabling residual
current criterion and
negative-sequence current
5 62PD.En_3I0/I2_Ctrl 0 or 1 criterion for pole discrepancy
protection
0: disable
1: enable
3.15 Synchrocheck
3.15.1 General Application
The purpose of synchrocheck is to ensure two systems are synchronism before they are going to
be connected.
When two asynchronous systems are connected together, due to phase difference between the
two systems, larger impact will be led to the system during closing. Thus auto-reclosing and
manual closing are applied with the synchrocheck to avoid this situation and maintain the system
stability. The synchrocheck includes synchronism check and dead charge check.
The synchronism check function measures the conditions across the circuit breaker and compares
them with the corresponding settings. The output is only given if all measured quantities are
simultaneously within their set limits.
The dead charge check function measures the amplitude of reference voltage and synchronism
voltage, and then compare them with the live check setting [25.U_Lv] and the dead check setting
[25.U_Dd]. The output is only given when the measured quantities comply with the criteria.
Synchrocheck in this device can be used for auto-reclosing and manual closing for both
single-breaker and dual-breakers. Details are described in the following sections.
When used for the synchrocheck of single-breaker, comparative relationship between reference
voltage (Uref) and synchronism voltage (Usyn) for synchrocheck is as follows.
Uref Usyn
Figure 3.15-1 shows the characteristics of synchronism check element used for the auto-reclosing
if both reference voltage and synchronism voltage are live. The synchronism check element
operates if voltage difference, phase angle difference and frequency difference are all within their
setting values.
Usyn≥[25.U_Lv]
Uref≥[25.U_Lv]
|Usyn- Uref|≤[25.U_Diff]
Usyn×Uref×cosØ≥0
Usyn×Uref×sin([25.phi_Diff]) ≥Usyn×Uref×|sinØ|
Where,
|f(Usyn)-f(Uref)|≤[25.f_Diff]
If frequency check is disabled (i.e. [25.En_fDiffChk] is set as “0”), a detected maximum slip cycle
can also be determined by the following equation based on phase difference setting and the
synchronism check time setting:
f =[25.phi_Diff]/(180×[25.t_SynChk])
Where:
f is slip cycle
If frequency check is enabled (i.e. [25.En_fDiffChk] is set as “1”), then [25.t_SynChk] can be set to
be a very small value (default value is 50ms).
This function module supports voltage switching. In general, voltage switching is fulfilled by
external circuit (the setting [CBConfigMode]=NoVoltSel); if using this module to fulfill voltage
switching, the busbar arrangement should be determined (determined by the setting
[CBConfigMode]), including double busbars arrangement ([CBConfigMode]=DblBusOneCB) and
1½ breakers arrangement ([CBConfigMode]=3/2BusCB or [CBConfigMode]=3/2TieCB).
Analog input defines four voltage inputs, UL1, UB1, UL2, UB2, and their usage are as follow:
UL1: it connects with three-phase protection voltages (from line or busbar), which mainly are used
by distance protection, voltage protection and so on. According to the voltage switching result,
synchrocheck logic choose one voltage to be used for synchrocheck function, synchrocheck
function requires to judgment the phase identification information of the voltage, which is
determined by the setting [25.Opt_Source_UL1], please refer to the setting description of
[25.Opt_Source_UL1] for details. If voltage switching function is not used, the reference voltage
will be selected from UL1 fixedly.
UB1: according to the voltage switching result, synchrocheck logic determined whether the voltage
is used for synchrocheck function. Synchrocheck function requires to judgment the phase
identification information of the voltage, which is determined by the setting [25.Opt_Source_UB1],
please refer to the setting description of [25.Opt_Source_UB1] for details. If voltage switching
function is not used, UB1 will be taken as the synchronism voltage.
UL2: according to the voltage switching result, synchrocheck logic determined whether the voltage
is used for synchrocheck function. Synchrocheck function requires to judgment the phase
identification information of the voltage, which is determined by the setting [25.Opt_Source_UL2],
please refer to the setting description of [25.Opt_Source_UL2] for details. When voltage switching
is available, it is only used for 1½ breakers arrangement, it is fixedly connected to the voltage of
the other line of the same diameter in 1½ breakers arrangement.
UB2: according to the voltage switching result, synchrocheck logic determined whether the voltage
is used for synchrocheck function. Synchrocheck function requires to judgment the phase
identification information of the voltage, which is determined by the setting [25.Opt_Source_UB2],
please refer to the setting description of [25.Opt_Source_UB2] for details. When voltage switching
is available, it is connected to synchronism voltage for double busbars arrangement or 1½
breakers arrangement.
Voltage selection function is not required for this busbar arrangement, the connection of the
voltage signals and respective VT MCB auxiliary contacts to the device is shown in the Figure
3.15-2 and Figure 3.15-3.
Bus
} Ua
UL1 Ub CB
Uc
25.MCB_VT_UL1
UB1
25.MCB_VT_UB1
Line
Three-phase protection voltages are from busbar VT. As shown in above figure, the reference
voltage (Uref) is selected among three-phase protection voltages, and synchronism voltage (Usyn)
is from line VT.
Bus
UB1 CB
25.MCB_VT_UB1
} Ua
UL1 Ub
Uc
25.MCB_VT_UL1 Line
In the figures, the setting [VTS.En_LineVT] is used to determine protection voltage signals (Ua, Ub,
Uc) from line VT or bus VT according to the condition. This setting is only used for VT circuit failure
logic, and it does not affect the synchrocheck mode. Three-phase protection voltages are from line
VT, as shown in above figure, the reference voltage (Uref) is selected among UL1 three-phase
protection voltages, and synchronism voltage (Usyn) is from busbar VT.
Bus2
Bus1
B1D B2D
UB1
25.MCB_VT_UB1
UB2
25.MCB_VT_UB2
25.NC_UB1DS
25.NO_UB1DS } CB
25.NC_UB2DS
25.NO_UB2DS }
} Ua
UL1 Ub
Line
Uc
25.MCB_VT_UL1
For double busbars arrangement, selection of appropriate voltage signals from Bus 1 and Bus 2
for synchronizing are required. Line VT signal is taken as reference voltage (Uref) to check
synchronizing with the voltage after voltage selection function. Selection approach is as follows.
For the disconnector positions, the normally open (NO) and normally closed (NC) contacts of the
disconnector for bus 1 and bus 2 are required to determine the disconnector open and closed
positions. The voltage selection logic is as follows.
BI 25.NO_UB1DS &
UB1_Sel
BI 25.NC_UB1DS
Voltage
Selection Logic
BI 25.NO_UB2DS &
UB2_Sel
BI 25.NC_UB2DS
&
Alm_Invalid_Sel
UB1 UB(Usyn)
UB2
After acquiring the disconnector open and closed positions of double busbars, use the following
logic to acquire the feeder voltage of double busbars.
If voltage selection is invalid (Alm_Invalid_Sel=1), keep original selection and without switchover.
For one and a half breakers arrangement, selection of appropriate voltage signals among Line1
VT, Line2 VT and Bus 2 VT as reference voltage to check synchronizing with Bus 1 voltage signal
for closing breaker at Bus 1 side.
Bus1
UB1
25.MCB_VT_UB1
25.NC_UB1DS
25.NO_UB1DS } B1D
} Ua Line 1
UL1 Ub
Uc
25.MCB_VT_UL1
L1D
25.NC_UL1DS
25.NO_UL1DS } Line 2
UL2
25.MCB_VT_UL2
25.NC_UL2DS
25.NO_UL2DS }
}
L2D
25.NC_UB2DS
25.NO_UB2DS
UB2
25.MCB_VT_UB2
B2D
Bus2
Figure 3.15-6 Voltage connection for one and a half breakers arrangement
For the circuit breaker at bus side (take bus breaker of Bus 1 as an example), the device acquires
the disconnector open and closed positions of two feeders and Bus 2. The voltage selection logic
is as follows.
BI 25.NO_UL1DS &
UL1_Sel
BI 25.NC_UL1DS
&
BI 25.NO_UL2DS & UL2_Sel
BI 25.NC_UL2DS
&
BI 25.NO_UB2DS & UB2_Sel
BI 25.NC_UB2DS
&
Alm_Invalid_Sel
UL1 UL(Uref)
UL2
UB2
UB1 UB(Usyn)
Figure 3.15-7 Voltage selection for bus CB of one and a half breakers arrangement
For the tie breaker, the device acquires the disconnector open and closed positions of two feeders
and two busbars. Either Line 1 VT or Bus 1 VT signal is selected as reference voltage to check
synchronizing with the selected voltage between Line 2 VT and Bus 2 VT. The voltage selection
logic is as follows.
BI 25.NO_UL1DS &
UL1_Sel
BI 25.NC_UL1DS
&
BI 25.NO_UB1DS & UB1_Sel
BI 25.NC_UB1DS
&
UL1 UL(Uref)
UB1
BI 25.NO_UL2DS &
UL2_Sel
BI 25.NC_UL2DS
&
BI 25.NO_UB2DS & UB2_Sel
BI 25.NC_UB2DS
>=1
& Alm_Invalid_Sel
UL2 UB(Usyn)
UB2
Figure 3.15-8 Voltage selection for tie CB of one and a half breakers arrangement
When the voltage selection fails (including VT circuit failure and MCB failure), the device will issue
the corresponding failure signal. If the voltage selection is invalid (Alm_Invalid_Sel=1), keep
original selection and without switchover.
In order to simplify description, one of the two voltages used in the synchrocheck (synchronism check
and dead charge check) which obtained after voltage selection function is regarded as reference
voltage, and another is synchronism voltage.
If voltage from synchronism voltage VT or reference voltage VT is used for auto-reclosing with
synchronism or dead reference voltage or synchronism voltage check, the synchronism voltage
circuit and reference voltage circuit are monitored.
During normal operation, the circuit breaker is in closed state (52b of three phases are
de-energized), if automatic reclosing cycle is in progress and no fault detector operates, then the
synchronism voltage is lower than the setting [25.U_Lv], it means that synchronism voltage circuit
fails and the synchronism voltage alarm [25.Alm_VTS_Usyn] or reference voltage alarm
[25.Alm_VTS_Uref] will be issued with a time delay of 10s. If the MCB of synchronism voltage or
reference voltage is open, the corresponding alarm signal [25.Alm_VTS_Usyn] or
[25.Alm_VTS_Uref] will be issued instantaneously.
If no check mode is enabled (the signal [25.On_NoChk] is “1”), synchrocheck used voltage circuit
When synchronism voltage circuit failure is detected, function of dead check in auto-reclosing logic
will be disabled.
After synchronism voltage reverted to normal condition, the alarm will be reset automatically with a
time delay of 10s.
SIG 79.Inprog
&
10s 10s
SIG Uref<[25.U_Lv]
>=1
&
BI 25.MCB of Uref 25.Alm_VTS_Uref
SIG 25.On_LvL_DdB
SIG 25.Blk_VTS_UL
SIG 79.Inprog
&
10s 10s >=1
SIG Usyn<[25.U_Lv] &
25.Alm_VTS_Usyn
BI 25.MCB of Usyn
SIG 25.On_LvL_DdB
SIG 25.Blk_VTS_UB
Where:
“25.MCB of Uref” means binary input for VT MCB auxiliary contact of the reference voltage after
voltage switching.
“25.MCB of Usyn” means binary input for VT MCB auxiliary contact of the synchronism voltage
after voltage switching.
25
25.Blk_Chk UL1_Sel
UL2_Sel
25.Blk_SynChk
UB1_Sel
25.Blk_DdChk UB2_Sel
Alm_Invalid_Sel
25.Start_Chk
25.On_SynChk
25.Start_3PLvChk 25.On_DdL_DdB
25.Sel_SynChk 25.On_DdL_LvB
25.On_LvL_DdB
25.Sel_DdL_DdB
25.On_NoChk
25.Sel_DdL_LvB 25.Ok_fDiffChk
25.Ok_UDiffChk
25.Sel_LvL_DdB
25.Ok_phiDiffChk
25.Sel_NoChk
25.Ok_DdL_DdB
25.Blk_VTS_Uref 25.Ok_DdL_LvB
25.Ok_LvL_DdB
25.Blk_VTS_Usyn
25.Chk_LvL
25.MCB_VT_UL1 25.Chk_DdL
25.MCB_VT_UL2 25.Chk_LvB
25.Chk_DdB
25.MCB_VT_UB1
25.Ok_DdChk
25.MCB_VT_UB2 25.Ok_SynChk
25.NC_UL1DS 25.Ok_Chk
25.Ok_3PLvChk
25.NO_UL1DS
25.Alm_VTS_Uref
25.NC_UB1DS
25.Alm_VTS_Usyn
25.NO_UB1DS
25.f_Ref
25.NC_UL2DS 25.f_Syn
25.NO_UL2DS 25.U_Diff
25.f_Diff
25.NC_UB2DS
25.Phi_Diff
25.NO_UB2DS
dead check)
Dead reference voltage and live synchronism voltage condition is met
15 25.Ok_DdL_LvB (reference voltage is low than voltage threshold of dead check and
synchronism voltage is higher than voltage threshold of live check)
Live reference voltage and dead synchronism voltage condition is met
16 25.Ok_LvL_DdB (reference voltage is higher than voltage threshold of live check and
synchronism voltage is low than voltage threshold of dead check)
17 25.Chk_LvL Reference voltage is greater than the voltage threshold of live check [25.U_Lv]
Reference voltage is smaller than the voltage threshold of dead check
18 25.Chk_DdL
[25.U_Dd]
Synchronism voltage is greater than the voltage threshold of live check
19 25.Chk_LvB
[25.U_Lv]
Synchronism voltage is smaller than the voltage threshold of dead check
20 25.Chk_DdB
[25.U_Dd]
21 25.Ok_DdChk To indicate that dead charge check condition of AR is met
22 25.Ok_SynChk To indicate that synchronism check condition of AR is met
23 25.Ok_Chk To indicate that synchrocheck condition of AR is met
24 25.Ok_3PLvChk To indicate that live three-phase check condition is met
25 25.Alm_VTS_Uref Reference voltage circuit is abnormal
26 25.Alm_VTS_Usyn Synchronism voltage circuit is abnormal
27 25.f_Ref Frequency of the voltage used by protection calculation
28 25.f_Syn Frequency of the voltage used by synchrocheck
29 25.U_Diff Voltage difference for synchronism check
30 25.f_Diff Frequency difference for synchronism check
31 25.phi_Diff Phase difference for synchronism check
3.15.5 Logic
These logic diagrams give the introduction to the working principles of the synchronism check and
dead charge check.
The frequency difference, voltage difference, and phase difference of voltages from both sides of
the circuit breaker are calculated in the device, they are used as input conditions of the
synchronism check.
When the synchronism check function is enabled and the voltages of both ends meets the
requirements of the voltage difference, phase difference, and frequency difference, and there is no
synchronism check blocking signal, it is regarded that the synchronism check conditions are met.
Synchronism check logic is usually used for 3-pole AR, and 1-pole AR is usually adopts no check
logic. However, the circuit breaker at local end can not reclosed unless the circuit breaker at
remote end is reclosed successfully. In order to meet this requirement, live three-phase check can
be used for 1-pole AR, determined by the setting [25.En_3PLvChk], ensure that three-phase
voltages is restored to normal at local end after the circuit breaker at remote end is reclosed.
1
EN [25.En_SynChk]
25.On_SynChk
SIG 25.Sel_SynChk
0
EN [25.SetOpt]
EN [25.En_3PLvChk]
SIG Uref.a>[25.U_Lv]
>=1
&
SIG Uref.b>[25.U_Lv]
SIG Uref.c>[25.U_Lv]
&
SIG 25.Start_3PLvChk 200ms 0ms 25.Ok_3PLvChk
SIG 25.Blk_SynChk
&
SIG [25.On_SynChk]
&
SIG 25.Start_Chk
SIG Usyn>[25.U_Lv]
& &
SIG Uref>[25.U_Lv] 50ms 0ms & [25.t_SynChk] 0ms 25.Ok_SynChk
SIG 25.Ok_UdiffChk
SIG 25.Ok_phiDiffChk
SIG 25.Ok_fDiffChk
The dead charge check conditions have three types, namely, live-synchronism voltage and
dead-reference voltage check, dead-synchronism voltage and live-reference voltage check and
dead-synchronism voltage and dead-reference voltage check. The above three modes can be
enabled and disabled by the corresponding logic settings ([25.En_DdL_DdB], [25.En_LvL_DdB]
and [25.En_DdL_LvB]) or external signal, when the setting [25.SetOpt] is set as “1”, dead charge
check mode is determined by corresponding logic settings. Otherwise, dead charge check mode is
determined by external signal.
The device can calculate the measured synchronism voltage and reference voltage and compare
them with the settings [25.U_Lv] and [25.U_Dd]. When the voltage is higher than [25.U_Lv], the
synchronism voltage/reference voltage is regarded as live. When the voltage is lower than
[25.U_Dd], the synchronism voltage/reference voltage is regarded as dead.
1
EN [25.En_DdL_DdB]
25.On_DdL_DdB
SIG 25.Sel_SynChk
0
EN [25.SetOpt]
1
EN [25.En_LvL_DdB]
25.On_LvL_DdB
SIG 25.Sel_LvL_DdB
0
EN [25.SetOpt]
1
EN [25.En_DdL_LvB]
25.On_DdL_LvB
SIG 25.Sel_DdL_LvB
0
EN [25.SetOpt]
SIG Usyn>[25.U_Lv]
SIG Usyn>[25.U_Lv]
SIG Usyn<[25.U_Dd]
SIG 25.Alm_VTS_Uref
No check mode is provided for synchrocheck logic, no check mode can be determined by
corresponding logic setting [25.En_NoChk] or external signal. As shown in following figure, when
the setting [25.SetOpt] is set as “1”, no check mode is determined by the setting [25.En_NoChk].
Otherwise, synchronism check mode is determined by external signal.
1
EN [25.En_NoChk]
25.On_NoChk
SIG 25.Sel_NoChk
0
EN [25.SetOpt]
SIG 25.Ok_SynChk
>=1
EN 25.On_NoChk 25.Ok_Chk
SIG 25.Ok_DdChk
3.15.6 Settings
To maintain the integrity of the overall electrical transmission system, the device is installed on the
transmission system to isolate faulted segments during system disturbances. Faults caused by
lightning, wind, or tree branches could be transient in nature and may disappear once the circuit is
de-energized. According to statistics, for overhead transmission line, 80%~90% of the faults on
overhead lines are the transient faults. Auto-reclosing systems are installed to restore the faulted
section of the transmission system once the fault is extinguished (providing it is a transient fault).
For certain transmission systems, auto-reclosure is used to improve system stability by restoring
critical transmission paths as soon as possible.
Besides overhead lines, other equipment failure, such as cables, busbar, transformer fault and so
on, are generally permanent fault, and auto-reclosing is not initiated after faulty feeder is tripped.
For some mixed circuits, such as overhead line with a transformer unit, hybrid transmission lines,
etc., it is required to ensure that auto-reclosing is only initiated for faults overhead line section, or
make a choice according to the situation.
This auto-reclosing logic can be used with either integrated device or external device. When the
auto-reclosure is used with integrated device, the internal protection logic can initiate AR,
moreover, a tripping contact from external device can be connected to the device via opto-coupler
input to initiate integrated AR function.
When external auto-reclosure is used, the device can output some configurable output to initiate
external AR, such as, contact of initiating AR, phase-segregated tripping contact, single-phase
tripping contact, three-phase tripping contact and contact of blocking AR. According to
requirement, these contacts can be selectively connected to external auto-reclosure device to
initiate AR.
For phase-segregated circuit breaker, AR mode can be 1-pole AR for single-phase fault and
3-pole AR for multi-phase fault, or always 3-pole AR for any kinds of fault according to system
requirement. For persistent fault or multi-shot AR number preset value is reached, the device will
send final tripping command. The device will provide appropriate tripping command based on
faulty phase selection if adopting 1-pole AR.
AR can be enabled or disabled by logic setting or external signal via binary input. When AR is
enabled, the device will output contact [79.On], otherwise, output contact [79.Off]. After some
reclosing conditions, such as, CB position, CB pressure and so on, is satisfied, the device will
output contact [79.Ready].
According to requirement, the device can be set as one-shot or multi-shot AR. When adopting
multi-shot AR, the AR mode of first time reclosing can be set as 1-pole AR, 3-pole AR or 1/3-pole
AR. The rest AR mode is only 3-pole AR and its number is determined by the maximum 3-pole
reclosing number.
For one-shot AR or first reclosing of multi-shot AR, AR mode can be selected by logic setting
[79.En_1PAR], [79.En_3PAR] and [79.En_1P/3PAR] or external signal via binary inputs. When
3-pole or 1/3-pole AR mode is selected, the following three types of check modes can be selected:
dead charge check, synchronism check and no check.
79
79.En 79.On
79.Blk 79.Off
79.Sel_1PAR 79.Close
79.Sel_3PAR 79.Ready
79.Sel_1P/3PAR 79.AR_Blkd
79.Trp 79.Active
79.Trp3P 79.Inprog
79.TrpA 79.Inprog_1P
79.TrpB 79.Inprog_3P
79.TrpC 79.Inprog_3PS1
79.LockOut 79.Inprog_3PS2
79.PLC_Lost 79.Inprog_3PS3
79.WaitMaster 79.Inprog_3PS4
79.CB_Healthy 79.WaitToSlave
79.Clr_Counter 79.Perm_Trp1P
79.Ok_Chk 79.Perm_Trp3P
79.Ok_3PLvChk 79.Rcls_Status
79.Fail_Rcls
79.Succ_Rcls
79.Fail_Chk
79.Mode_1PAR
79.Mode_3PAR
79.Mode_1/3PAR
3.16.5 Logic
3.16.5.1 AR Ready
For the first reclosing of multi-shot AR, AR mode can be 1-pole AR or 3-pole AR, however, the
selection is valid only to the first reclosing, after that it can only be 3-pole AR.
When logic setting [79.SetOpt] is set as “1”, AR mode is determined by logic settings. When logic
setting [79.SetOpt] is set as “0”, AR mode is determined by external signal via binary inputs.
An auto-reclosure must be ready to operate before performing reclosing. The output signal
[79.Ready] means that the auto-reclosure can perform at least one time of reclosing function, i.e.,
breaker open-close-open.
When the device is energized or after the settings are modified, the following conditions must be
met before the reclaim time begins:
1. AR function is enabled.
2. The circuit breaker is ready, such as, normal storage energy and no low pressure signal.
3. The duration of the circuit breaker in closed position before fault occurrence is not less than
the setting [79.t_CBClsd].
After the auto-reclosure operates, the auto-reclosure must reset, i.e., [79.Active]=0, in addition to
the above conditions for reclosing again.
When there is a fault on an overhead line, the concerned circuit breakers will be tripped normally.
After fault is cleared, the tripping command will drop off immediately. In case the circuit breaker is
in failure, etc., and the tripping signal of the circuit breaker maintains and in excess of the time
delay [79.t_PersistTrp], AR will be blocked, as shown in the following figure.
En [79.En_PDF_Blk]
En [79.N_Rcls]=1
>=1
& 79.AR_Blkd
SIG Three phase trip
& >=1
&
The input signal [79.CB_Healthy] must be energized before auto-reclosure gets ready. Because
most circuit breakers can finish one complete process: open-closed-open, it is necessary that
circuit breaker has enough energy before reclosing. When the time delay of AR is exhausted, AR
will be blocked if the input signal [79.CB_Healthy] is still not energized within time delay
[79.t_CBReady]. If this function is not required, the input signal [79.CB_Healthy] can be not to
configure, and its state will be thought as “1” by default.
In order to block AR reliably even if the signal of manually open circuit breaker not connected to
the input of blocking AR, when the circuit breaker is open by manually and there is CB position
input under normal conditions, AR will be blocked with the time delay of 100ms if AR is not initiated
and no any trip signal.
When the input signal [79.LockOut] is energized, auto-reclosure will be blocked immediately. The
blocking flag of AR will be also controlled by the internal blocking condition of AR. When the
EN [79.En] &
EN [79.En_ExtCtrl]
>=1
79.On
&
SIG 79.En &
SIG 79.Blk
When a fault occurs under pole disagreement condition, blocking AR can be enabled or disabled.
The time delay [79.t_SecFault] is used to discriminate another fault which begins after 1-pole AR
initiated. AR will be blocked if another fault happens after this time delay if the logic setting
[79.En_PDF_Blk] is set as “1”, and 3-pole AR will be initiated if [79.En_PDF_Blk] is set as “1”.
AR will be blocked immediately once the blocking condition of AR appears, but the blocking
condition of AR will drop off with a time delay [79.t_DDO_BlkAR] after blocking signal disappears.
When one-shot and 1-pole AR is enabled, auto-reclosure will be blocked immediately if there are
binary inputs of multi-phase CB position is energized.
When any protection element operates to trip, the device will output a signal [79.Active] until AR
drop off (Reset Command). Any tripping signal can be from external protection device or internal
protection element.
AR function can be enabled by internal logic settings of AR mode or external signal via binary
inputs in addition to internal logic setting [79.En]. When logic setting [79.En_ExtCtrl] is set as “1”,
AR enable are determined by external signal via binary inputs and logic settings. When logic
setting [79.En_ExtCtrl] set as “0”, AR enable are determined only by logic settings.
For one-shot reclosing, if 1-pole AR mode is selected, auto-reclosure will reset when there is
three-phase tripping signal or input signal of multi-phase open position.
SIG 79.On
SIG 79.Mode_3PAR
SIG 79.Ready
SIG 79.Trp
SIG 79.Trp3P
SIG 79.TrpC
When AR is enabled, the device will output the signal [79.Perm_Trp3P] if AR is not ready, or AR
mode is set as 3-Pole AR, or another fault occurs after the circuit breaker is open.
3.16.5.2 AR Initiation
AR mode can be selected by external signal via binary inputs or internal logic settings. If the logic
setting [79.SetOpt] set as “1”, AR mode is determined by the internal logic settings. If the logic
settings [79.SetOpt] set as “0”, AR mode is determined by the external inputs.
AR can be initiated by tripping signal of line protection, and the tripping signal may be from internal
trip signal or external trip signal.
When selecting 1-pole AR or 1/3-pole AR, line single-phase fault will trigger 1-pole AR. When AR
is ready to reclosing (“79.Ready”=1) and the single-phase tripping command is received, this
single-phase tripping command will be kept in the device, and 1-pole AR will be initiated after the
single-phase tripping command drops off. The single-phase tripping command kept in the device
will be cleared after the completion of auto-reclosing sequence (Reset Command). Its logic is
shown in Figure 3.16-4.
&
SIG 79.Ready
&
1-pole AR Initiation
SIG 79.Sel_1PAR >=1
SIG 79.Sel_1P/3PAR
When selecting 3-pole AR or 1/3-pole AR, three-phase tripping will trigger 3-pole AR. When AR is
ready to reclosing (“79.Ready”=1) and the three-phase tripping command is received, this
three-phase tripping command will be kept in the device, and 3-pole AR will be initiated after the
three-phase tripping command drops off. The three-phase tripping command kept in the device will
be cleared after the completion of auto-reclosing sequence. (Reset Command) Its logic is shown
in Figure 3.16-5.
&
SIG 79.Ready
&
3-pole AR Initiation
SIG 79.Sel_3PAR >=1
SIG 79.Sel_1P/3PAR
2. AR initiated by CB state
A logic setting [79.En_CBInit] is available for selection that AR is initiated by CB state. Under
normal conditions, when AR is ready to reclosing (“79.Ready”=1), AR will be initiated if circuit
breaker is open and corresponding phase current is nil. AR initiated by CB state can be divided
into initiating 1-pole AR and 3-pole AR, their logics are shown in Figure 3.16-6 and Figure 3.16-7
respectively. Usually normally closed contact of circuit breaker is used to reflect CB state.
EN [79.En_CBInit]
SIG 79.Ready
SIG 79.Sel_1P/3PAR
EN [79.Sel_1PAR] >=1
EN [79.Sel_1P/3PAR]
3.16.5.3 AR Reclosing
After AR is initiated, the device will output the initiating contact of AR. For 1-pole AR, in order to
prevent pole discrepancy protection from maloperation under pole discrepancy conditions, the
contact of “1-pole AR initiation” can be used to block pole discrepancy protection.
When the dead time delay of AR expires after AR is initiated, as for 1-pole AR, when the setting
[25.En_3PLvChk] is set as “0”, the result of synchronism check will not be judged, and reclosing
command will be output directly. When the setting [25.En_3PLvChk] is set as “1”, the reclosing is
not permissible unless live three-phase check is met. As far as the 3-pole AR, if the synchronism
check is enabled, the release of reclosing command shall be subject to the result of synchronism
check. After the dead time delay of AR expires, if the synchronism check is still unsuccessful within
the time delay [79.t_wait_Chk], the signal of synchronism check failure (79.Fail_Syn) will be output
and the AR will be blocked. If 3-pole AR with no-check is enabled, the condition of synchronism
check success (25.Ok_Chk) will always be established. And the signal of synchronism check
success (25.Ok_Chk) from the synchronism check logic can be applied by auto-reclosing function
inside the device or external auto-reclosure device.
79.Inprog_1P
SIG 1-pole AR Initiation >=1
79.Inprog
SIG 3-pole AR Initiation
79.Inprog_3P
&
SIG 79.Ok_3PLvChk
>=1
& [79.t_Wait_Chk] 0ms 79.Fail_Chk
SIG 79.Ok_Chk
In case pilot protection adopting permissive scheme, when the communication channel is
abnormal, pilot protection will be disabled. In the process of channel abnormality, an internal fault
occurs on the transmission line, backup protection at both ends of line will operate to trip the circuit
breaker of each end. The operation time of backup protection at both ends of the line is possibly
non-accordant, whilst the time delay of AR needs to consider the arc-extinguishing and insulation
recovery ability for transient fault, so the time delay of AR shall be considered comprehensively
according to the operation time of the device at both ends. When the communication channel of
main protection is abnormal (input signal [79.PLC_Lost] is energized), and the logic setting
[79.En_AddDly] is set as “1”, then the dead time delay of AR shall be equal to the original dead
time delay of AR plus the extra time delay [79.t_AddDly], so as to ensure the recovery of insulation
intensity of fault point when reclosing after transient fault. This extra time delay [79.t_AddDly] is
only valid for the first shot AR.
>=1
BI [79.PLC_Lost]
&
SIG 79.Active
&
Extend AR time
EN [79.En_AddDly]
Reclosing pulse length may be set through the setting [79.t_PW_AR]. For the circuit breaker
without anti-pump interlock, a logic setting [79.En_CutPulse] is available to control the reclosing
pulse. When this function is enabled, if the device operates to trip during reclosing, the reclosing
pulse will drop off immediately, so as to prevent multi-shot reclosing onto fault. After the reclosing
command is issued, AR will drop off with time delay [79.t_Reclaim], and can carry out next
reclosing.
EN [79.En_CutPulse]
>=1
&
SIG 79.AR_Out [79.t_Reclaim] 0ms Reset Command
The reclaim timer defines a time from the issue of the reclosing command, after which the
reclosing function resets. Should a new trip occur during this time, it is treated as a continuation of
the first fault. The reclaim timer is started when the CB closing command is given.
SET [79.Opt_Priority] =1
The output signal “79.WaitToSlave” is usually configured to the signal “79.WaitMaster” of slave AR.
Slave AR is permissible to reclosing only if master AR is reclosed successfully.
For transient fault, the fault will be cleared after the device operates to trip. After the reclosing
command is issued, AR will drop off after time delay [79.t_Reclaim], and can carry out next
reclosing. When the reclosing is unsuccessful or the reclosing condition is not met after AR
initiated, the reclosing will be considered as unsuccessful, including the following cases.
1. If any protection element operates to trip when AR is enabled ([79.On]=1) and AR is not ready
([79.Ready]=0), the device will output the signal (79.Fail_Rcls).
2. For one-shot AR, if the tripping command is received again within reclaim time after the
reclosing pulse is issued, the reclosing shall be considered as unsuccessful.
3. For multi-shot AR, if the reclosing times are equal to the setting value of AR number and the
tripping command is received again after the last reclosing pulse is issued, the reclosing shall
be considered as unsuccessful.
4. The logic setting [79.En_FailCheck] is available to judge whether the reclosing is successful
by CB state, when it is set as “1”. If CB is still in open position with a time delay [79.t_Fail] after
the reclosing pulse is issued, the reclosing shall be considered as unsuccessful. For this case,
the device will issue a signal (79.Fail_Rcls) to indicate that the reclosing is unsuccessful, and
this signal will drop off after (Reset Command). AR will be blocked if the reclosing shall be
considered as unsuccessful.
SIG 79.On
&
SIG 79.Ready
SIG 79.AR_Blkd
>=1
SIG AR Pulse
&
[79.t_Fail] 0ms &
SIG CB closed
EN [79.En_FailCheck] &
& 79.Succ_Rcls
0 [79.t_Fail]
After unsuccessful AR is confirmed, AR will be blocked. AR will not enter into the ready state
unless the circuit breaker position drops off , and can only begin to enter into the ready state again
after the circuit breaker is closed.
The device may be set up into one-shot or multi-shot AR. Through the setting [79.N_Rcls], the
maximum number of reclosing attempts may be set up to 4 times. Generally, only one-shot AR is
selected. Some corresponding settings may be hidden if one-shot AR is selected.
1. 1-pole AR
[79.N_Rcls]=1 means one-shot reclosing. For one-shot 1-pole AR mode, 1-pole AR will be initiated
only for single-phase fault and respective faulty phase selected, otherwise, AR will be blocked. For
single-phase transient fault on the line, line protection device will operate to trip and 1-pole AR is
initiated. After the dead time delay for 1-pole AR is expired, the device will send reclosing pulse,
and then the auto-reclosure will drop off after the time delay [79.t_Reclaim] to ready for the next
reclosing. For permanent fault, the device will operate to trip again after the reclosing is performed,
and the device will output the signal of reclosing failure [79.Fail_Rcls].
[79.N_Rcls]>1 means multi-shot reclosing. For multi-shot reclosing in 1-pole AR mode, the first
reclosing is 1-pole AR, and the subsequent reclosing can only be 3-pole AR. For single-phase
transient fault on the line, line protection device will operate to trip and then 1-pole AR is initiated.
After the dead time delay of the first reclosing is expired, the device will send reclosing pulse, and
then the auto-reclosure will drop off after the time delay [79.t_Reclaim] to ready for the next
reclosing. For permanent fault, the device will operate to trip again after the reclosing is performed,
and then 3-pole AR is initiated. At this time, the time delay applies the setting [79.t_Dd_3PS2].
After the time delay is expired, if the reclosing condition is met, the device will send reclosing pulse.
The sequence is repeated until the reclosing is successful or the maximum permit reclosing
number [79.N_Rcls] is reached. If the first fault is multi-phase fault, the device operates to trip
three-phase and initiate 3-pole AR. At this time, the time delay applies the setting [79.t_Dd_3PS1].
For the possible reclosing times of 3-pole AR in 1-pole AR mode, please refer to Table 3.16-2.
2. 3-pole AR
[79.N_Rcls]=1 means one-shot reclosing. For one-shot 3-pole AR mode, line protection device will
operate to trip when a transient fault occurs on the line and 3-pole AR will be initiated. After the
dead time delay for 3-pole AR is expired, the device will send reclosing pulse, and then the
auto-reclosure will drop off after the time delay [79.t_Reclaim] to ready for the next reclosing. For
permanent fault, the device will operate to trip again after the reclosing is performed, and the
device will output the signal of reclosing failure [79.Fail_Rcls].
[79.N_Rcls]>1 means multi-shot reclosing. For multi-shot reclosing in 3-pole AR mode, line
protection device will operate to trip when a transient fault occurs on the line and 3-pole AR will be
initiated. After the dead time delay of the first reclosing is expired, the device will send reclosing
pulse, and then the auto-reclosure will drop off after the time delay [79.t_Reclaim] to ready for the
next reclosing. For permanent fault, the device will operate to trip again after the reclosing is
performed, and then 3-pole AR is initiated after the tripping contact drops off. After the time delay
for AR is expired, the device will send reclosing pulse. The sequence is repeated until the
reclosing is successful or the maximum permit reclosing number [79.N_Rcls] is reached.
3. 1/3-pole AR
[79.N_Rcls]=1 means one-shot reclosing. For one-shot 1/3-pole AR mode, line protection device
will operate to trip when a transient fault occurs on the line and 1-pole AR will be initiated for
single-phase fault and 3-pole AR will be initiated for multi-phase fault. After respective dead time
delay for AR is expired, the device will send reclosing pulse, and then the auto-reclosure will drop
off after the time delay [79.t_Reclaim] to ready for the next reclosing. For permanent fault, the
device will operate to trip again after the reclosing is performed, and the device will output the
signal of reclosing failure [79.Fail_Rcls].
[79.N_Rcls]>1 means multi-shot reclosing. For multi-shot reclosing in 1/3-pole AR mode, line
protection device will operate to trip when a transient fault occurs on the line and AR will be
initiated. After the dead time delay of the first reclosing is expired, the device will send reclosing
pulse, and then the auto-reclosure will drop off after the time delay [79.t_Reclaim] to ready for the
next reclosing. For permanent fault, the device will operate to trip again after the reclosing is
performed, and then 3-pole AR is initiated after the tripping contact drops off. After the time delay
for AR is expired, the device will send reclosing pulse. The sequence is repeated until the
reclosing is successful or the maximum permit reclosing number [79.N_Rcls] is reached. For the
possible reclosing times of 3-pole AR in 1/3-pole AR mode, please refer to Table 3.16-2 .
The table below shows the number of reclose attempts with respect to the settings and AR modes.
Duplicated protection configurations are normally applied for UHV lines. If reclosing function is
integrated within line protections, the auto-reclosing function can be enabled in any or both of the
line protections without coordination.
If both sets of reclosing functions are enabled, when one of them first recloses onto a permanent
fault, the other will block the reclosing pulse according to the latest condition of the faulty phase.
For one-shot AR mode, if the current is detected in the faulty phase, AR will be blocked
immediately to prevent the circuit breaker from repetitive reclosing. For multi-shot AR mode, if the
current is detected in the faulty phase, the current reclosing pulse will be blocked and go into the
next reclosing pulse logic automatically. If the maximum permitted reclosing number [79.N_Rcls] is
reached, the auto-reclosure will drop off after the time delay [79.t_Reclaim].
For one-shot or multi-shot AR, there is a corresponding reclosing counter at each stage. After
reclosing pulse is sent, the corresponding reclosing counter will plus 1 and the reclosing counter
may be cleared by the submenu “Clear Counter”. If the circuit breaker is reclosed by other
devices during AR initiation, the auto-reclosure will go into the next reclosing pulse logic.
The following two examples indicate typical time sequence of AR process for transient fault and
permanent fault respectively.
Signal
Fault
Trip
CB 52b
Open
79.t_Reclaim [79.t_Reclaim]
79.Active
79.Inprog [79.t_Dd_1PS1]
79.Inprog_1P [79.t_Dd_1PS1]
79.Ok_Chk
AR Out [79.t_PW_AR]
79.Perm_Trp3P
79.Fail_Rcls
Time
Signal
Fault
Trip
Open Open
52b
79.t_Reclaim [79.t_Reclaim]
79.Active
79.Inprog
79.Inprog_1P [79.t_Dd_1PS1]
79.Inprog_3PS2 [79.t_Dd_3PS2]
79.Ok_Chk
79.Perm_Trp3P
79.Fail_Rcls 200ms
Time
3.16.6 Settings
AR will be blocked.
Maximum wait time for synchronism
9 79.t_Wait_Chk 0.000~600.000 0.001 s
check
Time delay allow for CB status change
10 79.t_Fail 0.000~600.000 0.001 s
to conform reclosing successful
For any enabled protection tripping elements, their operation signal will convert to appropriate
tripping signals through trip logics and then trigger output contacts by configuration.
This module gathers signals from phase selection and protection tripping elements and then
converts the operation signal from protection tripping elements to appropriate tripping signals. The
device can implement phase-segregated tripping or three-phase tripping, and may output the
contact of blocking AR and the contact of initiating breaker failure protection.
2 TRP.Blk Trip blocking input, it is triggered from binary input or programmable logic etc.
Protection operation elements, includes phase overcurrent protection, earth fault
3 Op_CBProt protection, pole discrepancy protection, dead zone protection, breaker failure
protection and etc (internal signal).
Input signal of permitting three-phase tripping
4 PrepTrp3P When this signal is valid, three-phase tripping will be adopted for any kind of
faults.
No. Output Signal Description
1 TRP.On Trip output is enabled
2 TRP.BlkAR Blocking auto-reclosing
3 TrpA Tripping phase-A circuit breaker
4 TrpB Tripping phase-B circuit breaker
5 TrpC Tripping phase-C circuit breaker
6 Trp Tripping any phase of circuit breaker
7 Trp3P Tripping three-phase circuit breaker
A-phase breaker failure protection initiating (BFI) signal, BFI signal shall be reset
8 BFI_A
immediately after tripping signal drops off (internal signal).
B-phase breaker failure protection initiating (BFI) signal, BFI signal shall be reset
9 BFI_B
immediately after tripping signal drops off (internal signal).
C-phase breaker failure protection initiating (BFI) signal, BFI signal shall be reset
10 BFI_C
immediately after tripping signal drops off (internal signal).
Breaker failure protection initiating (BFI) signal, BFI signal shall be reset
11 BFI
immediately after tripping signal drops off (internal signal).
3.17.4 Logic
After tripping signal is issued, the tripping pulse will be kept as same as the setting [t_Dwell_Trp] at
least. When the time delay is expired, for phase-segregated tripping, the tripping signal will drop
off immediately if the faulty current of corresponding phase is less than 0.06In (In is secondary
rated current), otherwise the tripping signal will be always kept until the faulty current of
corresponding phase is less than 0.06In. For three-phase tripping, the tripping signal will drop off
immediately if three-phase currents are all less than 0.06In, otherwise the tripping signal will be
always kept until three-phase currents are all less than 0.06In.
SIG Ia>0.06In
0 t_Dwell_Trp
&
&
>=1 TrpB
50BF.Op_ReTrpB t_Dwell_Trp 0
SIG &
SIG Ib>0.06In
0 t_Dwell_Trp
&
&
>=1 TrpC
50BF.Op_ReTrpC t_Dwell_Trp 0
SIG &
SIG Ic>0.06In
>=1
>=1 Trp
0 t_Dwell_Trp
&
&
SIG 50/51Qx.Op
>=1
SIG 59Px.Op
SIG 59Q.Op
SIG 62PD.Op
All operation elements (except for re-tripping element) are 3 phase tripping elements.
EN [50/51Px.En_BlkAR]
EN [50/51Qx.En_BlkAR]
EN 50/51Gx.En_BlkAR
SIG 59Px.Op
SIG 27Px.Op
>=1 >=1 >=1
SIG 81U.UFx.Op TRP.BlkAR
SIG 81O.OFx.Op
SIG 50BF.Op_t2
3.17.5 Settings
The purpose of VT circuit supervision is to detect whether VT circuit is normal. Some protection
functions should be disabled when VT circuit fails.
VT circuit failure can be caused by many reasons, such as fuse blown due to short-circuit fault,
poor contact of VT circuit, VT maintenance and so on. The device can detect them and issue an
alarm signal to block relevant protection functions. However, the alarm of VT circuit failure should
2. Only current protection functions are enabled and VT is not connected to the device.
VT circuit supervision can detect failure of single-phase, two-phase and three-phase on protection
VT. Under normal condition, the device continuously supervises input voltage from VT, VT circuit
failure signal will be activated if residual voltage exceeds the threshold value or positive-sequence
voltage is lower than the threshold value. If the device is under pickup state due to system fault or
other abnormality, VT circuit supervision will be disabled.
Under normal conditions, the device detect residual voltage greater than 8% of Unn to determine
single-phase or two-phase VT circuit failure, and detect three times positive-sequence voltage less
than Unn to determine three-phase VT circuit failure. Upon detecting abnormality on VT circuit, an
alarm will comes up after a time delay of [VTS.t_DPU] and drop off with a time delay of
[VTS.t_DDO] after VT circuit restored to normal.
VT (secondary circuit) MCB auxiliary contact as a binary input can be connected to the binary
input circuit of the device. If MCB is open (i.e. [VTS.MCB_VT] is energized), the device will
consider the VT circuit is not in a good condition and issues an alarm without a time delay. If the
auxiliary contact is not connected to the device, VT circuit supervision will be issued with time
delay as mentioned in previous paragraph.
When VT is not connected into the device, the alarm will be not issued if the logic setting
[VTS.En_Out_VT] is set as “1”. However, the alarm is still issued if the binary input [VTS.MCB_VT]
is energized, no matter that the logic setting [VTS.En_Out_VT] is set as “1” or “0”.
When VT neutral point fails, third harmonic of residual voltage is comparatively large. If third
harmonic amplitude of residual voltage is larger than 0.2Unn and without operation of fault
detector element, VT neutral point failure alarm signal [VTNS.Alm] will be issued after a time delay
of [VTS.t_DPU] and drop off with a time delay of [VTS.t_DDO] after three phases voltage restored
to normal.
VTS VTNS
VTS.Blk VTNS.Blk
VTS.MCB_VT
3.18.5 Logic
SIG 3U0>0.08Unn
>=1
SIG 3U1<Unn &
>=1 If FD.Pkp OR 79.Inprog operate, then
EN [VTS.En_LineVT] & circuit of time delay will be interrupted.
BI [VTS.MCB_VT]
>=1
& VTS.Alm
EN [VTS.En]
&
SIG [VTS.En]
SIG [VTS.Blk]
&
SIG FD.Pkp >=1
SIG 79.Inprog
If FD.Pkp OR 79.Inprog operate, then
circuit of time delay will be interrupted.
OTH U03>0.2Unn & >=1
[VTS.t_DPU] [VTS.t_DDO] & VTNS.Alm
EN [VTS.En_Out_VT]
EN [VTS.En]
&
SIG [VTNS.En]
SIG [VTNS.Blk]
If fault detector element operates or automatic reclosing cycle is in progress, and VT circuit failure
signal have been detected, then the VT circuit failure signal will be maintained, only when the fault
detector element and automatic reclosing element are all drop-off, VT circuit supervision will return
to normal operation.
3.18.6 Settings
The purpose of the CT circuit supervision is to detect any abnormality on CT secondary circuit.
CTS
CTS.En CTS.Alm
CTS.Blk
3.19.5 Logic
SIG 3I0>0.1In
&
SIG 3U0<3V
SIG IA<0.06In
>=1
SIG IB<0.06In
SIG IC<0.06In
The purpose of control is to open or close primary equipment, including circuit breaker (CB),
disconnector (DS) and earth switch (ES), or to issue outputs for signaling purpose. Synchronism
check and dead check are also provided for the control processes as below:
3. Remote closing CB from SCADA (i.e., local HMI system) or control center (CC)
Programmable interlocking logics within a bay and amongst different bays are provided by using
PCS-Explorer.
1. Control
High reliability is ensured by adopting the principle of selection before operation (abbreviated
SBO). When the binary input [BI_Maintenance] is energized as “1”, remote control from
SCADA/CC will be disabled, but local control will not be influenced.
1) The control source (SCADA/CC, or local LCD control operation, or manual control operation)
sends control selection command to this device
2) This device sends back the control selection result (success or failure) to the control source
after logic judgment
3) The control source sends control operation command to this device if the control selection
result is “success”. The control source will send control cancellation command to this device if
the control selection result is “failure”.
4) This device sends back the control operation result (success or failure) to the control source
after logic judgment.
Logic calculation result of interlocking is input to the remote control module as a criterion of remote
operation. When the enabling parameter of remote open/close interlock is “1”, remote control
module determines whether it can be output according to the calculation result of interlocking. If
the current breaker position or programmable part can meet the interlocking condition, remote
control can be output normally, otherwise remote operation is blocked. When the enabling
parameter of remote open/close interlock is “0”, interlocking function is disabled and remote
control will be output directly without the judgment of interlocking.
Holding time of each binary output contact can be set by configuring corresponding settings and is
often configured as 250ms. However, for the control circuits without latched relays, the holding
time must be longer to ensure successful control operation.
1
EN [MCBrd.25.En_SynChk]
MCBrd.25.On_SynChk
SIG MCBrd.25.Sel_SynChk
0
EN [MCBrd.25.SetOpt]
1
EN [MCBrd.25.En_NoChk]
MCBrd.25.On_NoChk
SIG MCBrd.25.Sel_NoChk
0
EN [MCBrd.25.SetOpt]
SIG BIinput.CILO.Disable
>=1
EN [CSWI01.En_Cls_Blk]
SIG CSWI01.CILO.EnCls
&
SIG BIinput.LocCtrl
SIG CSWI01.Cmd_LocCtrl
SIG MCBrd.25.Ok_Chk
EN [MCBrd.25.En_VTS_Blk_SynChk]
EN [MCBrd.En_Alm_VTS] &
&
SIG MCBrd.Alm_VTS
EN [MCBrd.25.En_VTS_Blk_DdChk]
EN [MCBrd.25.En_LvL_DdB]
>=1 & >=1
EN [MCBrd.25.En_DdL_LvB] >=1
EN [MCBrd.25.En_DdL_DdB]
SIG MCBrd.25.Ok_Chk
SIG MCBrd.25.On_NoChk
Only the first closing command “CSWI01.Op_Cls” controlled by synchrocheck logic can be used
for CB closing.
After receiving a closing command, this device will continuously check whether the 2 voltages
(Incoming voltage and reference voltage) involved in synchronism check (or dead check) can meet
the criteria. Within the duration of [MCBrd.25.t_Wait_Chk], if the synchronism check (or dead
check) criteria are not met, the signal “MCBrd.25.Ok_Chk” will be set as “0”; if the synchronism
check (or dead check) criteria are met, the signal “MCBrd.25.Ok_Chk” will be set as “1”.
When any of the following criteria is fulfilled, an alarm signal [MCBrd.Alm_VTS] will be issued with
a time delay of 1.25s, and drop off with a time delay of 10s after three phases voltage restored to
normal. The alarm signal will block the closing command for circuit breaker.
2. The positive-sequence voltage is smaller than 30V, and any phase current is greater than
0.04In.
SIG BIinput.CILO.Disable
>=1
EN [CSWIxx.En_Cls_Blk] &
[CSWIxx.t_PW_Cls] 0ms [CSWIxx.Op_Cls]
SIG CSWIxx.CILO.EnCls
SIG CSWIxx.Cmd_RmtCtrl
SIG CSWIxx.Cmd_LocCtrl
Access the menu “Local Cmd→Control” to issue control command locally, and this signal
“CSWIxx.Cmd_LocCtrl” will be set as “1”.
Remote control commands from SCADA/CC can be transmitted via IEC 60870-5-103 protocol or
IEC 61850 protocol, and this signal “CSWIxx.Cmd_RmtCtrl” will be set as “1”.
SIG BIinput.CILO.Disable
>=1
EN [CSWI01.En_Opn_Blk] &
[CSWI01.t_PW_Opn] 0ms CSWI01.Op_Opn
SIG CSWI01.CILO.EnOpn
SIG CSWI01.Cmd_LocCtrl
SIG BIinput.CILO.Disable
>=1
EN [CSWIxx.En_Opn_Blk] &
[CSWIxx.t_PW_Opn] 0ms CSWIxx.Op_Opn
SIG CSWIxx.CILO.EnOpn
SIG CSWIxx.Cmd_LocCtrl
Where:
The control output fulfills signal output circuit, and opens or closes circuit breaker, disconnector
and earth switch according to the control command. Object manipulation strictly performs three
steps: selection, check and excute, and perform output relay check, to ensure that the remote
control can be excuted safely and reliably.
When logic interlock is enabled, the device can receive the programmable interlock logic. The
device can automatically initiate the interlock logic to determine whether to allow control
operations. The device provides corresponding settings ([CSWIxx.En_Opn_Blk] and
[CSWIxx.En_Cls_Blk]) for each control object. When they are set as “1”, the interlock function of
the corresponding control object is enabled. The interlock logic can be configured by using
PCS-Explorer, and downloaded to the device via the Ethernet port. If the interlock function is
enabled, but it is not configured the interlock logic, the result of the logic output is 0.
The control record is a file which is used to store remote control command records of this device
circularly. If the record number is to 256, the storage area of the control record will be full. If this
device has received a new remote command, this device will delete the oldest remote control
record, and then store the latest remote control record.
There are 15 configuration page corresponding to 15 control outputs in totall respectively. Each
configuration page can finish some signals configuration, including remote control, local control,
disable interlock blocking, and so on.
In order to conveniently configure control output, the same output signals, including
“BIinput.RmtCtrl”, “BIinput.LocCtrl” and “BIinput.CILO.Disable”, are available after processing
binary signals internally, as shown in figure below.
The configuration rule about remote control and local control to binary outputs is as bellow:
Remot Local
CSWIxx. BIinput. CSWIxx. BIinput. Control Mode
RmtCtrl RmtCtrl LocCtrl LocCtrl
X X X X Neither Local control nor remote control are permissible.
0 X X X
Only local control is permissible.
X 0 X X
1 X X X
Only remote control is permissible.
X 1 X X
X X 0 X
Only remote control is permissible.
X X X 0
X X 1 X
Only local control is permissible.
X X X 1
0 X 0 X
0 X X 0
Neither Local control nor remote control are permissible.
X 0 0 X
X 0 X 0
0 X 1 X
X 0 1 X
Only local control is permissible.
0 X X 1
X 0 X 1
1 X 0 X
1 X X 0
Only remote control is permissible.
X 1 0 X
X 1 X 0
1 X 1 X
1 X X 1
Both Local control and remote control are permissible.
X 1 1 X
X 1 X 1
For remote control or local control, they can be configured by either of “CSWIxx.RmtCtrl” and
“BIinput.RmtCtrl”, or either of “CSWIxx.LocCtrl” and “BIinput.LocCtrl”.
2. Synchrocheck
Three synchrocheck modes are designed for CB closing: no check mode, dead check mode and
synchronism check mode, if any one of the condition of three synchrocheck modes satisfied, then
synchrocheck signal “MCBrd.25.Ok_Chk” will be asserted.
The synchronism check function measures the conditions across the circuit breaker and compares
them with the corresponding settings. The output is only given if all measured quantities are
simultaneously within their set limits. Compared to the synchronism check for auto-reclosing, an
additional criterion is applied to check the rate of frequency change (df/dt) between both sides of
the CB.
When the following four conditions are all met, the synchronism check is successful.
1) Phase angle difference between incoming voltage and reference voltage is less than the
setting [MCBrd.25.phi_Diff]
2) Frequency difference between incoming voltage and reference voltage is less than
[MCBrd.25.f_Diff]
3) Voltage difference between between incoming voltage and reference voltage is less than
[MCBrd.25.U_Diff]
4) Rate of frequency change between incoming voltage and reference voltage is less than
[MCBrd.25.df/dt]
The dead check function measures the amplitude of line voltage and bus voltage at both sides of
the circuit breaker, and then compare them with the live check setting [MCBrd.25.U_Lv] and the
dead check setting [MCBrd.25.U_Dd]. The dead check is successful when the measured
quantities comply with the criteria.
When this device is set to work in no check mode and receives a closing command, CB will be
closed without synchronism check and dead check.
Synchrocheck for manual closing also supports voltage switching. In general, voltage switching is
fulfilled by external circuit (the setting [CBConfigMode]=NoVoltSel); using this module to fulfill
voltage switching, the busbar arrangement should be determined by the setting [CBConfigMode]),
including
Analog input defines four voltage inputs, UL1, UB1, UL2, UB2, and their usage are as follow:
UL1: it connects with three-phase protection voltages (from line or busbar), which mainly are used
by distance protection, voltage protection and so on. According to the voltage switching result,
synchrocheck logic choose one voltage to be used for synchrocheck function, synchrocheck
function requires to judgment the phase identification information of the voltage, which is
determined by the setting [MCBrd.25.Opt_Source_UL1]. If voltage switching function is not used,
the reference voltage will be selected from UL1 fixedly.
UB1: according to the voltage switching result, synchrocheck logic determined whether the voltage
is used for synchrocheck function. Synchrocheck function requires to judgment the phase
identification information of the voltage, which is determined by the setting
[MCBrd.25.Opt_Source_UB1]. If voltage switching function is not used, UB1 will be taken as the
synchronism voltage.
UL2: according to the voltage switching result, synchrocheck logic determined whether the voltage
is used for synchrocheck function. Synchrocheck function requires to judgment the phase
identification information of the voltage, which is determined by the setting
[MCBrd.25.Opt_Source_UL2]. When voltage switching is available, it is only available for 1½
breakers arrangement, it is fixedly connected to the voltage of the other line of the same diameter
in 1½ breakers arrangement.
UB2: according to the voltage switching result, synchrocheck logic determined whether the voltage
is used for synchrocheck function. Synchrocheck function requires to judgment the phase
identification information of the voltage, which is determined by the setting
[MCBrd.25.Opt_Source_UB2]. When voltage switching is available, it is connected to synchronism
voltage for double busbars arrangement or 1½ breakers arrangement.
Synchrocheck for manual closing supports voltage switching function, and the switching logic is as
same as that of synchrocheck for protection closing. The setting [CBConfigMode] should be set
according to the actual primary busbar arrangement, otherwise, the voltage switching of
synchrocheck for manual closing will fail, so as to block manual closing with synchrocheck.
During dead charge check, when only single-phase voltage is connected to UL1, live voltage is
valid if the setting [VTS.En] should be set as “0” and the connected single-phase voltage is higher
than the setting [MCBrd.25.U_Lv], otherwise, live voltage is regarded as live only when three
phases voltages are all higher than [MCBrd.25.U_Lv].
CSWI01
CSWI01.CILO.EnOpn CSWI01.Op_Opn
CSWI01.CILO.EnCls CSWI01.Op_Cls
CSWI01.RmtCtrl
CSWI01.LocCtrl
CSWI01.CILO.Disable
CSWIxx
CSWIxx.CILO.EnOpn CSWIxx.Op_Opn
CSWIxx.CILO.EnCls CSWIxx.Op_Cls
CSWIxx.RmtCtrl
CSWIxx.LocCtrl
CSWIxx.CILO.Disable
BIinput
BIinput.RmtCtrl BIinput.RmtCtrl
BIinput.LocCtrl BIinput.LocCtrl
BIinput.CILO.Disable BIinput.CILO.Disable
CSWI01.ManSynCls
CSWI01.ManOpn
CSWI02.ManSynCls
CSWI02.ManOpn
xx can be from 02 to 15
It is used to disable the interlock blocking function for control output. If the
9 BIinput.CILO.Disable signal “BIinput.CILO.Disable” is “1”, all binary outputs will not be blocked
by interlock conditions.
When the condition of local control is met and the signal
10 CSWI01.ManSynCls “CSWI01.ManSynCls” is “1”, the output contact [BO_CtrlCls01] is closed
to execute manually closing the circuit breaker with synschrochcek.
When the condition of local control is met and the signal
11 CSWI01.ManOpn “CSWI01.ManOpn” is “1”, the output contact [BO_CtrlOpn01] is closed to
execute manually open the circuit breaker.
12 MCBrd.25.Sel_SynChk Synchronism check for manual closing is selected.
13 MCBrd.25.Sel_NoChk No check for manual closing is selected.
No. Output Signal Description
1 CSWIxx.Op_Opn Open output of binary output No.xx. (xx=01~15)
2 CSWIxx.Op_Cls Closing output of binary output No.xx. (xx=01~15)
3 BIinput.RmtCtrl In order to be convenient to user configure control output, three same
output signals with input signals are available. The relationship with 15
4 BIinput.LocCtrl
binary output have been configured inside the device. The user only
assigns a specific binary input to input signal, the relevant function can be
5 BIinput.CILO.Disable gained. If some binary output need not be controlled by three signals,
please cancle the configuration by PCS-Explorer, and configure it
independently.
6 MCBrd.Alm_VTS VT circuit of circuit breaker No.x is abnormal.
3.20.5 Settings
4 Supervision
Table of Contents
List of Tables
4.1 Overview
Protection system is in quiescent state under normal conditions, and it is required to respond
promptly for faults which occurr on power system. When the device is in energizing process before
the LED “HEALTHY” is on, the device need to be checked to ensure no abnormality. Therefore,
the automatic supervision function, which checks the health of the protection system when startup
and during normal operation, plays an important role.
The numerical relay based on the microprocessor operations is suitable for implementing this
automatic supervision function of the protection system.
In case a defect is detected during initialization when DC power supply is provided to the device,
the device will be blocked with indication and alarm of relay out of service. It is suggested a trial
recovery of the device by re-energization. Please contact supplier if the device is still failure.
When a failure is detected by the automatic supervision, it is followed by a LCD message, LED
indication and alarm contact outputs. The failure alarm is also recorded in event recording report
and can be printed If required.
A minor abnormality may block a certain number of protections functions while the other functions
can still work. However, if severe hardware failure or abnormality, such as PWR module failure,
DC converter failure and so on, are detected, all protection functions will be blocked and the LED
“HEALTHY” will be extinguished and blocking output contacts BO_FAIL will be given. The
protective device then can not work normally and maintenance is required to eliminate the failure.
All the alarm signals and the corresponding handling suggestions are listed below.
NOTICE!
If the device is blocked or alarm signal is sent during operation, please do find out its
reason with the help of self-diagnostic record. If the reason can not be found at site,
please notify the factory NR. Please do not simply press button “TARGET RESET” on
the protection panel or re-energize on the device.
Blocking
No. Item Description
Device
Fail Signals
The device fails.
1 Fail_Device This signal will be pick up if any fail signal picks up Blocked
and it will drop off when all fail signals drop off.
2 Fail_Setting_OvRange Set value of any setting is out of scope. Blocked
disappear. Then users get the correct software version. It is not allowed that
the alarm signal is issued on the device already has been put into service. the
devices having being put into service so that the alarm signal disappears.
Please check the value of setting [Active_Grp] and binary input of indiating
active group, and make them matched. Then the “ALARM” LED will be
18 Alm_BI_SettingGrp
extinguished and the corresponding alarm message will disappear and the
device will restore to normal operation state.
19 Alm_DSP_Frame Please inform the manufacture or the agent for repair.
1. check whether the binary input module is connected to the power supply.
2. check whether the voltage of power supply is in the required range.
20 Bxx.Alm_OptoDC 3. After the voltage for binary input module restores to normal range, the
“ALARM” LED will be extinguished and the corresponding alarm message will
disappear and the device will restore to normal operation state.
Please check secondary values and protection settings. If settings are not set
reasonable to make fault detectors pick up, please reset settings, and then
21 Alm_Pkp_FD
the alarm message will disappear and the device will restore to normal
operation state.
Please check secondary values and protection settings. If settings are not set
reasonable to make fault detectors pick up, please reset settings, and then
22 Alm_Pkp_I0
the alarm message will disappear and the device will restore to normal
operation state.
Please check the corresponding VT secondary circuit. After the abnormality is
23 VTS.Alm
eliminated, the device returns to normal operation state.
Please check the corresponding VT secondary circuit of neutral point. After
24 VTNS.Alm
the abnormality is eliminated, the device returns to normal operation state.
Please check the corresponding CT secondary circuit. After the abnormality is
25 CTS.Alm
eliminated, the device returns to normal operation state.
Please check the auxiliary contact of CB. After the abnormality is eliminated,
26 Alm_52b
the device returns to normal operation state.
After maintenance is finished, please de-energized the binary input
27 BI_Maintenance [BI_Maintenance] and then the alarm will disappear and the device restore to
normal operation state.
2. check whether the wiring connection between the device and the clock
synchronization source is correct
28 Alm_TimeSyn 3. check whether the setting for selecting clock synchronization (i.e.
[Opt_TimeSyn]) is set correctly. If there is no clock synchronization, please
set the setting [Opt_TimeSync] as ”No TimeSync”.
When any fault detector picks up for longer than 50s, an alarm will be issued [Alm_Pkp_FD]
without the device blocked.
If 52b of three phases are energized that indicates circuit breaker is open but current is still
detected in the line (the measured current is greater than a settable threshold value) or
three-phase circuit breaker is in pole disagreement condition, an alarm signal [Alm_52b] will be
issued after 10s.
GOOSE alarm signal indicating that there is a network storm occurring on the
1 GAlm_AStorm_SL
network A.
GOOSE alarm signal indicating that there is a network storm occurring on the
2 GAlm_BStorm_SL
network B.
4 Namexx.GAlm_ADisc_SL_xx GOOSE alarm signal indicating that network A for Namexx is disconnected.
5 Namexx.GAlm_BDisc_SL_xx GOOSE alarm signal indicating that network B for Namexx is disconnected.
These are GOOSE alarm reports. When any alarm message is issued, the LED “ALARM” is lit without
the device being blocked. After the abnormality is removed, the device will return to normal with the
LED “ALARM” being distinguished automatically.
6 Namexx.GAlm_Cfg_SL_xx Please check the GOOSE configuration file and the network
Namexx is the name defined by the setting [Linkxx], xx=01, 02, 03, …, 64
5 Management
Table of Contents
5.1 Measurement
PCS-921 performs continuous measurement of the analogue input quantities. The current full
scale of relay is 40 times of rated current, and there is no effect to the performance of IED due to
overflowing of current full scale. The device samples 24 points per cycle and calculates the RMS
value in each interval and updated the LCD display in every 0.5 second. The measurement data
can be displayed on the LCD of the relay front panel or on the local/remote PC via software tool.
Navigate the menu to view the sampling value through LCD screen.
This device can be used for one or two circuit breaker configuration. If it is used for two circuit
breakers configuration, some corresponding metering will be suffixed by CBn (n is the number of
the CB and it can be 1 and 2).
“Measurement1” is use to display measured values from protection calculation DSP. The
measurement values can be displayed in primary value or secondary value by the setting
[Opt_Display_Status].
“Measurement2” is used to display measured values from fault detector DSP. The measurement
values can be displayed in primary value or secondary value by the setting [Opt_Display_Status].
“Measurement3” is used to display measured primary values and other calculated quantities
related to the measurement and control.
“Metering” is used to display metering values of active and reactive energy. The metering values
are always displayed in primary value.
5.2 Recording
5.2.1 Overview
PCS-921 provides the following recording functions:
1. Event recording
2. Disturbance recording
3. Present recording
All the recorded information except waveform can be viewed on local LCD or by printing.
Waveform could only be printed or extracted with PCS-Explorer software tool and a waveform
analysis software.
The device can store the latest 1024 disturbance records, 1024 binary events, 1024 supervision
events, 256 control logs and 1024 device logs. All the records are stored in non-volatile memory,
and when the available space is exhausted, the oldest record is automatically overwritten by the
latest one.
When any protection element operates or drops off, such as fault detector, distance protection etc.,
they will be logged in event records.
The device is under automatic supervision all the time. If there are any failure or abnormal
condition detected, such as, chip damaged, VT circuit failure and so on, it will be logged in event
records.
When there is a binary input is energized or de-energized, i.e., its state has changed from “0” to “1”
or from “1” to “0”, it will be logged in event records.
When the total number of control command records reaches 256, “Control_Logs” memory area
will be full. If the device receives a new control command now, the oldest control command record
will be deleted, and then the latest control command record will be stored and displayed.
If an operator implements some operations on the device, such as reboot protective device,
modify setting, etc., they will be logged in event records.
Disturbance records can be used to have a better understanding of the behavior of the power
network and related primary and secondary equipment during and after a disturbance. Analysis of
the recorded data provides valuable information that can be used to improve existing equipment.
This information can also be used when planning for and designing new installations.
5.2.3.2 Design
A disturbance record consists of fault record and fault waveform. A disturbance record can be
initiated by fault detector element, tripping element, reclosing element or configurable signal
[BI_TrigDFR].
The device can store up to 32 disturbance records with waveform in non-volatile memory. It is
based on first in first out queue that the oldest disturbance record will be overwritten by the latest
one.
1. Sequence number
Each operation will be recorded with a sequence number in the record and displayed on LCD
screen.
The time resolution is 1ms using the relay internal clock synchronized via clock synchronized
device if connected. The date and time is recorded when a system fault is detected.
An operating time (not including the operating time of output relays) is recorded in the record.
4. Faulty phase
5. Protection elements
MON module can store 32 pieces of fault waveform oscillogram in non-volatile memory. If a new
fault occurs when 32 fault waveform have been stored, the oldest will be overwritten by the latest
one.
Each fault record consists of all analog and digital quantities related to protection, such as original
current and voltage, differential current, alarm elements, and binary inputs and etc.
Each time recording includes several-cycle pre-disturbance waveform (the waveform cycle
number is configured via the communication setting [Num_Cyc_PreTrigDFR], the default value is
12-cycle), and 250 cycles at least and 500 cycles at most can be recorded. Each cycle waveform
is high-frequency recording at a rate of 1200Hz or 1440Hz (24 poingts per cycle).
Each time recording includes several-cycle waveform before triggering (the waveform cycle
number is configured via the communication setting [Num_Cyc_PreTrigDFR], the default value is
12-cycle), and 250 cycles at most can be recorded. Each cycle waveform is high-frequency
recording at a rate of 1200Hz or 1440Hz (24 poingts per cycle).
6 Hardware
Table of Contents
List of Figures
Figure 6.3-9 View of AI plug-in module (without synchronism voltage switchover) ......... 6-17
Figure 6.3-10 View of AI plug-in module (with synchronism voltage switchover) ............. 6-19
List of Tables
Table 6.3-1 Terminal definition and description of PWR plug-in module ............................ 6-11
Table 6.3-2 Terminal definition of NR1401 module (without synchronism voltage switchover)
.............................................................................................................................................. 6-18
Table 6.3-3 Terminal definition of NR1401 module (with synchronism voltage switchover)
.............................................................................................................................................. 6-19
Table 6.3-4 Terminal definition of NR1408 module (without synchronism voltage switchover)
.............................................................................................................................................. 6-21
PCS-921 is comprised of intelligent plug-in modules, except that few particular plug-in modules’
position cannot be changed in the whole device (gray plug-in modules as shown in Figure 6.1-1),
other plug-in modules like AI (analog input) and IO (binary input and binary output) can be flexibly
configured in the remaining slot positions.
MON module
PWR module
DSP module
DSP module
BO module
BO module
BO module
BO module
BO module
AI module
BI module
BI module
BI module
Slot No.
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1
PCS-921 has 16 slots, PWR plug-in module, MON plug-in module and DSP plug-in module are
assigned at fixed slots.
Besides 4 fixed modules are shown in above figure, there are 12 slots can be flexibly configured.
AI plug-in module can be configured at position between slot 02-03, BI plug-in module can be
configured at position between slot B08~B10, and BO plug-in module can be configured at
position between slot B11~B15.
This device is developed on the basis of our latest software and hardware platform, and the new
platform major characteristics are of high reliability, networking and great capability in
anti-interference. See Figure 6.1-2 for hardware diagram.
Output Relay
Binary Input
External
Protection
Conventional CT/VT A/D Calculation
DSP
ECVT
Fault
A/D Detector Pickup
DSP Relay
ECVT
ETHERNET
LCD +E
Clock SYN
Power
Uaux LED CPU
Supply
RJ45
Keypad
PRINT
The working process of the device is as shown in above figure: current and voltage from
conventional CT/VT are converted into small voltage signal and sent to DSP module after filtered
and A/D conversion for protection calculation and fault detector respectively (ECVT signal is sent
to the device without small signal and A/D convertion). When DSP module completes all the
protection calculation, the result will be recorded in 32-bit CPU on MON module. DSP module
carries out fault detector, protection logic calculation, tripping output, and MON module perfomes
SOE (sequence of event) record, waveform recording, printing, communication between the
device and SAS and communication between HMI and CPU. When fault detector detects a fault
and picks up, positive power supply for output relay is provided.
The items can be flexibly configured depending on the situations like sampling method of the
device (conventional CT/VT or ECT/EVT), and the mode of binary output (conventional binary
output or GOOSE binary output). The configurations for PCS-900 series based on microcomputer
are classified into standard and optional modules.
MON module provides functions like communication with SAS, event record, setting
management etc.
AI module converts AC current and voltage from current transformers and voltage
transformers respectively to small voltage signal.
DSP module performs filtering, sampling, protection calculation and fault detector calculation.
BI module provides binary inputs via opto-couplers with rating voltage among
24V/110V/125V/220V/250V (configurable).
BO module provides output contacts for tripping, and signal output contact for annunciation
signal, remote signal, fault and disturbance signal, operation abnormal signal etc.
PWR module converts DC 250/220/125/110V into various DC voltage levels for modules of
the device.
HMI module is comprised of LCD, keypad, LED indicators and multiplex RJ45 ports for user
as human-machine interface.
NET-DSP module receives and sends GOOSE messages, sampled values (SV) from
merging unit by IEC61850-9-2 protocol.
PCS-921 series is made of a 4U height 19” chassis for flush mounting. Components mounted on
its front include a 320×240 dot matrix LCD, a 9 button keypad, 20 LED indicators and a multiplex
RJ45 port. A monolithic micro controller is installed in the equipment for these functions.
1 11
HEALTHY PCS-9 21
2 12
ALARM BREAKER FAILURE RELAY
3 13
4 14
GRP
5 15
6 16 ENT
ESC
7 17
8 18
9 19
10 20
20 LED indicators are, from top to bottom, operation (HEALTHY), self-supervision (ALARM),
others are configurable.
For the 9-button keypad, “ENT” is “enter”, “GRP” is “group number” and “ESC” is “escape”.
BO_ALM BO_FAIL
ON
OFF
DANGER
1 BO_COM1
2 BO_FAIL
3 BO_ALM
4 BO_COM2
5 BO_FAIL
6 BO_ALM
7 OPTO+
8 OPTO-
9
10 PWR+
11 PWR-
12 GND
NR1102 NR1401 NR1161 NR1161 NR1504 NR1521A NR1521C NR1521C NR1521F NR1301
MON module
PWR module
DSP module
DSP module
BO module
BO module
BO module
BO module
AI module
BI module
Slot No.
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1
0203
Ib BI_01 + 0802
0204
…
0206 Ic
BI_06 + 0807
0213
BI_07 + 0809
Protection Voltage
0214 Ua
0215
…
0216 Ub
0218 Uc
Not used 0815
0220 UB1
0221
…
0222 UL2
BI_18 + 0821
0223
0224 UB2 0822
-
1101
Controlled by fault
BO_01
detector element
1102
P110 1103
PWR+
External DC power Power BO_02 1104
supply P111 Supply
PWR-
…
1121
OPTO+ P107 BO_11 1122
Power supply for
opto-coupler (24V) P108
OPTO-
1201
Signal Binary Output
BO_01 1202
1203
BO_02 1204
P102 BO_FAIL
…
P103 1221
BO_ALM
BO_11 1222
P101 COM
P105 BO_FAIL
P106 1301
Signal Binary Output
BO_ALM
BO_01 1302
P104 COM
(option)
1303
BO_02 1304
…
1321
BO_11 1322
A 0101
cable with single point earthing
To the screen of other coaxial
B 0102
COM
1503
SYN+ 0101 BO_CtrlCls1 1504
Clock SYN
SYN- 0102
…
BO_CtrlCls5
PRINT
P112
0225
Grounding
Bus
PCS-921 (conventional CT/VT and conventional binary input and binary output)
Slot No. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1
Module ID NR1102 NR1401 NR1161 NR1504 NR1504 NR1521 NR1521 NR1521 NR1521 NR1301
PCS-921 (conventional CT/VT and GOOSE binary input and binary output)
Slot No. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1
NET-DSP Module
MON module
PWR module
DSP module
DSP module
BO module
BO module
BI module
Slot No.
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1
BI_01 + 0801
MU
Phase B BI_02 + 0803
(LC Type)
Up to 8
Phase C TX - 0804
terminal
BI_03 + 0805
…
- 0806
…
BI_11 + 0821
- 0822
PWR+ P110
External DC power Power 1101
Controlled by fault
BO_01
detector element
supply P111 Supply 1102
PWR-
OPTO+ P107 1103
Power supply for BO_02 1104
opto-coupler (24V) P108
OPTO-
…
1121
BO_11 1122
1201
…
1221
P106 BO_ALM BO_11 1222
P104 COM
1501
BO_CtrlOpn1 1502
Signal Binary Output (option)
1503
A 0101 BO_CtrlCls1 1504
B 0102
COM
cable with single point earthing
To the screen of other coaxial
…
SGND 0103
1517
0104 BO_CtrlOpn5 1518
SYN+ 0101 1519
Clock SYN
RTS 0105
PRINTER
IRIG-B
PRINT
TXD 0106
Multiplex
SGND 0107 RJ45 (Front) P112
0225 Grounding
Bus
Slot No. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1
Slot No. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1
Module ID NR1102 NR1161 NR1136 NR1504 NR1504 NR1521 NR1521 NR1521 NR1521 NR1301
NET-
MON DSP BI BI BO BO BO BO PWR
DSP
In the protection system adopting electronic current and voltage transformer (ECT/EVT), the
merging unit will merge the sample data from ECT/EVT, and then send it to the device through
multi-mode optical fibre. DSP module receives the data from merging unit through the optical-fibre
interface to complete the protection calculation and fault detector.
The difference between the hardware platform based on ECT/EVT and the hardware platform
based on conventional CT/VT lies in the receiving module of sampled values only, and the device
receives the sampled value from merging unit through multi-mode optical fibre.
6.2.3 CT Requirement
-Rated primary current Ipn:
-Rated short-time thermal current Ith and rated dynamic current Idyn:
Performance verification
k stability factor = 2
Protective checking factor current (amps)
Ipcf
Same as the maximum prospective fault current
Isn Rated secondary current (amps)
Rct Current transformer secondary winding resistance (ohms)
Real resistance burden (ohms)
Rb
Rb=Rr+2×RL+Rc
For example:
= 30×5×(1+60/25)=510V
Esl′ = 2×Ipcf×Isn×(Rct+Rb)/Ipn
= 2×Ipcf ×Isn×(Rct+(Rr+2×RL+Rc))/Ipn
= 2×40000×5×(1+(0.1+2×0.5+0.1))/2000=440V
The +5V DC output provides power supply for all the electrical elements that need +5V DC power
supply in this device.
The use of an external miniature circuit breaker is recommended. The miniature circuit breaker
must be in the on position when the device is in operation and in the off position when the device is
in cold reserve.
A 12-pin connector is fixed on PWR module. The terminal definition of the connector is described
as below.
NR1301A
5V OK ALM
BO_ALM BO_FAIL
1 BO_COM1
2 BO_FAIL
3 BO_ALM
4 BO_COM2
5 BO_FAIL
6 BO_ALM
7 OPTO+
8 OPTO-
9
10 PWR+
11 PWR-
12 GND
The power switch in the dotted box of above figure maybe is not existed.
01
BO_FAIL
02
BO_ALM
03
04
BO_FAIL
05
BO_ALM
06
NOTICE!
The standard rated voltage of PWR module is self-adaptive to 88~300 Vdc. If input
voltage is out of range, an alarm signal (Fail_Device) will be issued. For non-standard
rated voltage power supply module please specify when place order, and check if the
rated voltage of power supply module is the same as the voltage of power source
before the device being put into service.
PWR module provides terminal 12 and grounding screw for device grounding. Terminal
12 shall be connected to grounding screw and then connected to the earth copper bar
of panel via dedicated grounding wire.
Effective grounding is the most important measure for a device to prevent EMI, so
effective grounding must be ensured before the device is put into service.
PCS-921, like almost all electronic relays, contains electrolytic capacitors. These
capacitors are well known to be subject to deterioration over time if voltage is not
applied periodically. Deterioration can be avoided by powering the relays up once a
year.
CAUTION!
Do NOT look into the end of an optical fiber connected to an optical port.
MON module consists of high-performance built-in processor, FLASH, SRAM, SDRAM, Ethernet
controller and other peripherals. Its functions include management of the complete device, human
machine interface, communication and waveform recording etc.
MON module uses the internal bus to receive the data from other modules of the device. It
communicates with the LCD module by RS-485 bus. This module comprises 100BaseT Ethernet
interfaces, RS-485 communication interfaces that exchange information with above system by
using IEC 61850, PPS/IRIG-B differential time synchronization interface and RS-232 printing
interface.
Modules with various combinations of memory and interface are available as shown in the table
below.
TX
ETHERNET ETHERNET
RX
TX
RX
ETHERNET
01 SYN+
02 SYN- To clock
RS-485 Twisted pair wire
03 SGND synchronization
04
05 RTS
RS-232 06 TXD To printer Cable
07 SGND
2 RJ45 Ethernet To SCADA
01 A
02 B
RS-485 To SCADA
03 SGND
04
05 A
06 B Twisted pair wire
RS-485 To SCADA
07 SGND
NR1101E 128M DDR 08
09 SYN+
10 SYN- To clock
RS-485
11 SGND synchronization
12
13 RTS
RS-232 14 TXD To printer Cable
15 SGND
16
The correct connection is shown in Figure 6.3-4. Generally, the shielded cable with two pairs of
twisted pairs inside shall be applied. One pair of the twisted pairs are respectively used to connect
the “+” and “–” terminals of difference signal. The other pair of twisted pairs are used to connect
the signal ground of the communication interface. The module reserves a free terminal for all the
communication ports. The free terminal has no connection with any signal of the device, and it is
used to connect the external shields of the cable when connecting multiple devices in series. The
external shield of the cable shall be grounded at one of the ends only.
B 02
COM
SGND 03
Clock SYN
SYN- 02
SGND 03
04
Cable
RTS 05
PRINT
TXD 06
SGND 07
Pin1
Pin2
Pin3
NOTICE!
As shown in Figure 6.3-5, the external receiving mode of IRIG-B differential time
synchronization interface can be set by the jumper J8&J9.
For AI module, if the plug is not put in the socket, external CT circuit is closed itself. Just shown as
below.
Plug
Socket
In
Out
In
Out
For the AI module NR1401, only one type of current channel (1A or 5A) is equipped. For the AI
module NR1408, the 1A and 5A current channels are all equipped. Please declare which kind of AI
module is needed before ordering. Maximum linear range of the current converter is 40In.
NR1401
Three phase currents (Ia, Ib and Ic) are input to AI module separately, terminal 01, 03 and 05 are
polarity marks. It is assumed that polarity mark of CT installed on line is at line side. Three phase
voltages (Ua, Ub, and Uc) are input to AI module, terminal 13, 15 and 17 are polarity marks.
P2 S2
P1 S1
02 01
04 03
06 05
13 14
15 16
17 18
19 20
13 14
15 16
17 18
19 20
The synchronism voltage can be connected to terminal 19 and 20 (terminal 19 is polarity mark).
The synchronism voltage could be any phase-to-ground voltage or phase-to-phase voltage.
Ia 01 Ian 02
NR1401
Ib 03 Ibn 04
Ic 05 Icn 06
07 08
09 10
11 12
Ua 13 Uan 14
Ub 15 Ubn 16
Uc 17 Ucn 18
Us 19 Usn 20
21 22
23 24
Table 6.3-2 Terminal definition of NR1401 module (without synchronism voltage switchover)
UB1, UB2 and UL2 are the synchronism voltage from bus VT and line VT used for synchrocheck, it
could be any phase-to-ground voltage or phase-to-phase voltage. The device can automatically
switch synchronism voltage according to auxiliary contact of CB position or DS position.
Ia 01 Ian 02
NR1401
Ib 03 Ibn 04
Ic 05 Icn 06
07 08
09 10
11 12
Ua 13 Uan 14
Ub 15 Ubn 16
Uc 17 Ucn 18
UB1 19 UB1n 20
UL2 21 UL2n 22
UB2 23 UB2n 24
Table 6.3-3 Terminal definition of NR1401 module (with synchronism voltage switchover)
If the auto-reclosing is enabled but synchronism check is not required, the synchronism voltage
should be disconnected.
NR1408
Terminal 0201, 0205 and 0209 are polarity marks of CT-1A, terminal 0203, 0207 and 0211 are
polarity marks of CT-5A. NR1408 module can support up to four voltage channels, so if NR1408
module is used, synchronism voltage switchover function is not available.
NR1408
Ia-1A 01 Ian-1A 02
Ia-5A 03 Ian-5A 04
Ib-1A 05 Ibn-1A 06
Ib-5A 07 Ibn-5A 08
Ic-1A 09 Icn-1A 10
Ic-5A 11 Icn-5A 12
Ir-1A 13 Irn-1A 14
Ir-5A 15 Irn-5A 16
Ua 17 Uan 18
Ub 19 Ubn 20
Uc 21 Ucn 22
Us 23 Usn 24
Table 6.3-4 Terminal definition of NR1408 module (without synchronism voltage switchover)
NR1161
This device can be equipped with 2 DSP plug-in modules at most and 1 DSP plug-in module at
least. The default DSP plug-in module is necessary, which mainly is responsible for protection
function including fault detector and protection calculation.
The module consists of high-performance double DSP (digital signal processor), 16-digit
high-accuracy ADC that can perform synchronous sampling and manage other peripherals. One
of double DSP is responsible for protection calculation, and can fulfill analog data acquisition,
protection logic calculation and tripping output. The other is responsible for fault detector, and can
fulfill analog data acquisition, fault detector and providing power supply to output relay.
When the module is connected with conventional CT/VT, it can perform the synchronous data
acquisition through AI plug-in module. When the module is connected with ECT/EVT, it can
receive the real-time synchronous sampled value from merging unit through NET-DSP plug-in
module.
The other module is optional and it is not required unless control and manual closing with
synchronism check are equppied with this device. The default DSP plug-in module is fixed at slot
04 and the option DSP plug-in module is fixed at slot 06.
CAUTION!
Do NOT look into the end of an optical fiber connected to an optical port.
NR1136A NR1136C
RX
This module consists of high-performance DSP (digital signal processor), 2~8 100Mbit/s
optical-fibre interface (LC type) and selectable IRIG-B interface (ST type). It supports GOOSE and
SV by IEC 61850-9-2 protocols. It can receive and send GOOSE messages to intelligent control
device, and receive SV from MU (merging unit).
This module supports IEEE1588 network time protocol, E2E and P2P defined in IEEE1588
protocol can be selected.This module supports Ethernet IEEE802.3 time adjustment message
format, UDP time adjustment message format and GMRP.
The device can output q data by GOOSE, and an output signal is provided “Output_q”. This signal
is used to indicate the quality of all output signals. According to the standard definition about the
quality by IEC 61850, the value of this signal is “0” under normal conditions, and it will be “2048”
(Bit1 is “1”, and other bits is “0”) when the device is under maintenance condtion.
The definition of each bit about quality signal by IEC 61850 is as below.
2. Step2: Taking “PTRC_out” module as an example, which can be found in “Symbol Library”
and instanced as bellow.
3. Step3: Double click the instanced module, the parameter list is displayed as bellow. Tr1~Tr8
are used for sending signals, q1~q8 are used for q data, the relationship between them is one
to one. Only one total q data can be added to all 8 sending signals by “batch_q”.
4. Step4: The output q data, named “Output_q” in variable library, is used for all sending signals.
The path is shown as bellow which is marked in red color.
5. Step5: Put the mouse on the “Output_q” signal, hold the left button of the mouse and drag it to
the corresponding position, and then release. The detail is as bellow.
After the above steps, save the modifications and compress driver file. Check the latest GOOSE
and CID file.
Voltage
264
176
154
140
110
87.5
77
62.5 Operation
55
Operation uncertain
No operation
The well-designed debounce technique is adopted in this device, and the state change of binary
input within “Debounce time” will be ignored. As shown in Figure 6.3-15.
All binary inputs should setup necessary debounce time to prevent the device from undesired
operation due to transient interference or mixed connection of AC system and DC system. When
the duration of binary input is less than the debounce time, the state of the binary input will be
ignored. When the duration of binary input is greater than the debounce time, the state of the
binary input will be validated and wrote into SOE.
In order to meet flexible configurable requirement for different project feild, all binary inputs
provided by the device are configurable. The device provide two parameters to setup debounce
time of delayed pickup and debounce time of delayed dropout based on specific binary signal.
1. Type 1
This type of binary inputs include enable/disable of protection functions, AR mode selection,
"BI_Print", "BI_RstTarg", "BI_Maintenance", disconnector position, settings group switch, open
and close command of circuit breaker and disconnector, enable/disable of auxiliary functions (for
example, manually trigger recording). They is on the premise of reliability, and the debounce time
of delayed pickup and delayed dropout is recommended to set as 100ms at least.
2. Type 2
This type of binary inputs include the time synchronization binary input "BI_TimeSyn", the
debounce time of delayed pickup and delayed dropout is usually set as 0ms.
3. Type 3
Debounce time
The debounce time of delayed pickup and delayed dropout is recommended to set as 15ms, in
order to prevent binary signals from misoperation due to mixed connection of AC system and DC
system.
The debounce time of delayed pickup and delayed dropout is recommended to set as (-t1+
t2+Time delay)≥15ms, in order to prevent binary signals from misoperation due to mixed
connection of AC system and DC system.
4. Type 4
This type of binary inputs are usually used as auxiliary input condition, and include the following
signals.
The debounce time of delayed pickup and delayed dropout is recommended to set as 5ms.
NR1503A/1503AR
Each BI module is with a 22-pin connector for 11 binary inputs, and its rated voltage can be
selected to be 110Vdc, 125Vdc, 220Vdc. Each binary input of NR1503A and NR1503AR has
independent negative power input of opto-coupler and can be configurable. NR1503A′s pickup
voltage and dropoff voltage are fixed value, and the range is from 55%Un to 70%Un. NR1503AR′s
pickup voltage and dropoff voltage are settable by the setting [xx.U_Pickup_BI] and
[xx.U_Dropoff_BI] from 55%Un to 80%Un.
BI_01 01
NR1503 Opto01- 02
BI_02 03
Opto02- 04
BI_03 05
Opto03- 06
BI_04 07
Opto04- 08
BI_05 09
Opto05- 10
BI_06 11
Opto06- 12
BI_07 13
Opto07- 14
BI_08 15
Opto08- 16
BI_09 17
Opto09- 18
BI_10 19
Opto10- 20
BI_11 21
Opto11- 22
[BI_n] can be configured as a specified binary input by PCS-Explorer software (n=01, 02, ……).
Terminal description for NR1503 is shown as follows.
NR1504A/NR1504AR
Each BI module is with a 22-pin connector for 18 binary inputs, and its rated voltage can be
selected to be 110Vdc, 125Vdc, 220Vdc. All binary inputs of NR1504A and NR1504AR share one
common negative power input and can be configurable. NR1504A′s pickup voltage and dropoff
voltage are fixed value, and the range is from 55%Un to 70%Un. NR1504AR′s pickup voltage and
dropoff voltage are settable by the setting [xx.U_Pickup_BI] and [xx.U_Dropoff_BI] from 55%Un to
80%Un.
Opto+ 01
NR1504 BI_01 02
BI_02 03
BI_03 04
BI_04 05
BI_05 06
BI_06 07
08
BI_07 09
BI_08 10
BI_09 11
BI_10 12
BI_11 13
BI_12 14
15
BI_13 16
BI_14 17
BI_15 18
BI_16 19
BI_17 20
BI_18 21
COM- 22
[BI_n] can be configured as a specified binary input by PCS-Explorer software (n=01, 02, ……).
Terminal description for NR1504 is shown as follows.
NR1508
NR1508A is with a 22-pin connector for 11 binary inputs, and its rated voltage is 220Vdc. Each
binary input of NR1508A has independent negative power input of opto-coupler and can be
configurable. NR1508A′s pickup voltage and dropoff voltage are fixed value, and the range is from
75%Un to 80%Un.
BI_01 01
NR1508A Opto01- 02
BI_02 03
Opto02- 04
BI_03 05
Opto03- 06
BI_04 07
Opto04- 08
BI_05 09
Opto05- 10
BI_06 11
Opto06- 12
BI_07 13
Opto07- 14
BI_08 15
Opto08- 16
BI_09 17
Opto09- 18
BI_10 19
Opto10- 20
BI_11 21
Opto11- 22
A default configuration is given for first four binary signals (BI_01, BI_02, BI_03, BI_04) in first BI
plug-in module, and they are [BI_TimeSyn], [BI_Print], [BI_Maintenance] and [BI_RstTarg]
respectively. They can alos be configured as other signals. Because the first binary signal [BI_01]
is set as [BI_TimeSyn] by default (the state change information of binary signal [BI_TimeSyn] does
not need be displayed), new binary signal should be added to state change message if it is set as
other signal.
It is used to receive clock synchronization signal from clock synchronization device, the binary
input [BI_TimeSyn] will change from “0” to “1” once pulse signal is received. When the device
adopts “Conventional” mode as clock synchronization mode (refer to section “Communication
Settings”), the device can receives PPM (pulse per minute) and PPS (pulse per second). If the
setting [Opt_TimeSyn] is set as other values, this binary input is invalid.
It is used to manually trigger printing latest report when the equipment is configured as manual
printing mode by logic setting [En_AutoPrint]=0. The printer button is located on the panel usually.
If the equipment is configured as automatic printing mode ([En_AutoPrint]=1), report will be printed
automatically as soon as it is formed.
It is used to block communication export when this binary input is energized. During device
maintenance or testing, this binary input is then energized not to send reports via communication
port, local display and printing still work as usual. This binary input should be de-energized when
the device is restored back to normal.
The application of the binary input [BI_Maintenance] for digital substation communication adopting
IEC61850 protocol is given as follows.
a) The protection device should send the state of this binary input to client.
b) When this binary input is energized, the bit “Test” of quality (Q) in the sent message changes
to “1”.
c) When this binary input is energized, the client cannot control the isolator link and circuit
breaker, modify settings and switch setting group remotely.
d) According to the value of the bit “Test” of quality (Q) in the message sent, the client
discriminate whether this message is maintenance message, and then deal with it correspondingly.
If the message is the maintenance message, the content of the message will not be displayed on
real-time message window, audio alarm not issued, but the picture is refreshed so as to ensure
that the state of the picture is in step with the actual state. The maintenance message will be
stored, and can be inquired, in independent window.
a) When this binary input is energized, the bit “Test” in the GOOSE message sent by the
protection device changes to “1”.
b) For the receiving end of GOOSE message, it will compare the value of the bit “Test” in the
GOOSE message received by it with the state of its own binary input (i..e [BI_Maintenance]), the
message will be thought as invalid unless they are conformable.
a) When this binary input of merging unit is energized, the bit “Test” of quality (Q) of sampling
data in the SV message sent change “1”.
b) For the receiving end of SV message, if the value of bit “Test” of quality (Q) of sampling data
in the SV message received is “1”, the relevant protection functions will be disabled, but under
maintenance state, the protection device should calculate and display the magnitude of sampling
data.
c) For duplicated protection function configurations, all merging units of control module
configured to receive sampling should be also duplicated. Both dual protection devices and dual
merging units should be fully independent each other, and one of them is in maintenance state will
not affect the normal operation of the other.
It is used to reset latching signal relay and LCD displaying. The reset is done by pressing a button
on the panel.
NOTICE!
The rated voltage of binary input is optional: 110V, 125V, 220V or 250V, which MUST
BE specified when placed order. It is necessary to CHECK whether the rated voltage of
BI module complies with site DC supply rating before put the relay in service.
There three binary signals are fixed for measurement functions, they are [BI_Rmt/Loc],
[BI_ManSynCls] and [BI_ManOpen] respectively.
“1”: the remote control, all the binary outputs can only be remotely controlled by SCADA or control
centers.
“0” the local control, each binary output can only be applied to open/close CB/DS/ES locally. Each
binary output can also be applied issue a signal locally.
When the device is under local control condition (i.e. [BI_Rmt/Loc] is de-energized), the manual
synchronism check for closing circuit breaker will be initiated if it is energized.
When the device is under local control condition (i.e. [BI_Rmt/Loc] is de-energized), the manual
control for open circuit breaker will be initiated if it is energized.
01
BO_01
NR1521A 02
03
BO_02
04
05
BO_03
06
07
BO_04
08
09
BO_05
10
11
BO_06
12
13
BO_07
14
15
BO_08
16
17
BO_09
18
19
BO_10
20
21
BO_11
22
01
BO_01
NR1521C 02
03
BO_02
04
05
BO_03
06
07
BO_04
08
09
BO_05
10
11
BO_06
12
13
BO_07
14
15
BO_08
16
17
BO_09
18
19
BO_10
20
21
BO_11
22
BO plug-in module (NR1521F) is dedicatedly for remote/manual open or closing to circuit breaker,
disconnector and earth switch. 5 pairs of binary outputs (one for open and the other for closing)
can be provided by this BO plug-in module configured in slot 15 if measurement and control
function is equipped with the device. Up to 10 pairs of binary outputs can be provided by two BO
plug-in modules that can be configured in slot 14 and 15 respectively. (BO plug-in module
configured in slot 14 is optional if open or closing contacts is not enough)
A normally open contact is presented via terminal 21-22 designated as ROS (i.e. remote operation
signal). Whenever any of binary output contacts for open or closing is closed, ROS contact will
close to issue a signal indicating that this device is undergoing a remote operation.
01
BO_CtrlOpn01
NR1521F 02
03
BO_CtrlCls01
04
05
BO_CtrlOpn02
06
07
BO_CtrlCls02
08
09
BO_CtrlOpn03
10
11
BO_CtrlCls03
12
13
BO_CtrlOpn04
14
15
BO_CtrlCls04
16
17
BO_CtrlOpn05
18
19
BO_CtrlCls05
20
21
BO_Ctrl
22
NR1580A can provide 6 output contacts with controlled by fault detector. It is a heavy-capacity
binary output plug-in module, which can be used to control the circuit breaker directly.
+ 01
NR1580A BO_01 02
- 03
04
+ 05
BO_02 06
- 07
08
+ 09
BO_03 10
- 11
12
+ 13
BO_04 14
- 15
16
+ 17
BO_05 18
- 19
20
+ 21
BO_06
- 22
7 Settings
Table of Contents
List of Tables
The device has some setting groups for protection to coordinate with the mode of power system
operation, one of which is assigned to be active. However, communication settings, system
settings, device settings, logic link settings and measurement and control settings are common for
all protection setting groups.
NOTICE!
All current settings in this chapter are secondary current converted from primary current
by CT ratio. Zero-sequence current or voltage setting is configured according to 3I0 or
3U0 and negative sequence current or voltage setting according to I2 or U2.
IED name of this device. If this setting is modified, the IED name in ".cid" file will be changed
simultaneously and vice versa.
IP address of Ethernet port 1, Ethernet port 2, Ethernet port 3 and Ethernet port 4
Subnet mask of Ethernet port 1, Ethernet port 2, Ethernet port 3 and Ethernet port 4
They are used for Ethernet communication based on the IEC 60870-5-103 protocol. When the IEC
61850 protocol is applied, the IP address of Ethernet A will be GOOSE source MAC address.
5. Gateway
6. En_Broadcast
This setting is only used only for IEC 60870-5-103 protocol. If NR network IEC 60870-5-103
protocol is used, the setting must be set as “1”.
7. Cfg_NetPorts_Bond
The setting is used to configure dual-networks switching, and it means that no dual-networks
switching is created when the setting is set as “0”. The device support a bond between any two
Ethernet ports, and the bond among three or above Ethernet ports is impermissible.
The devices communicate with SAS by station level network. In order to ensure reliable
communication, dual networks (i.e., network 1 and network 2) are adopted. Another special
communication mode based on dual networks is that Ethernet port 1 and Ethernet port 2 of the
device own the same IP address and MAC address, and network 1 and network 2 are used as hot
standby each other. When both network 1 and network 2 are normal, any of them is used to
communicate between the device and SAS. The device will automatically switch to the other
healthy network when one network is abnormal, which will not affect normal communication.
Taking NR1102D (with four Ethernet ports) as an example, each bit is corresponding with an
Ethernet port, i.e., Bit0, Bit1, Bit2 and Bit3 are corresponding with Ethernet port 1, Ethernet port 2,
Ethernet port 3 and Ethernet port 4 respectively. If a bond between Ethernet port 1 and Ethernet 2
is created, the setting [Cfg_NetPorts_Bond] is set as “3”. The specific setting is as below.
Ethernet port 1 Ethernet port 2 Ethernet port 1 Ethernet port 3 Ethernet port 1 Ethernet port 4
0 0 1 1 3 0 1 0 1 5 1 0 0 1 9
Ethernet port 2 Ethernet port 3 Ethernet port 2 Ethernet port 4 Ethernet port 3 Ethernet port 4
0 1 1 0 6 1 0 1 0 10 1 1 0 0 12
Ethernet port 1: Bit0, Ethernet port 2: Bit1, Ethernet port 3: Bit2, Ethernet port 4: Bit3
After the device is powered on, network 1 is selected when the link status of both network 1
and network 2 are normal.
When the link status of network 1 is abnormal, network 2 is selected if network 2 is normal.
When the link status of network 1 is abnormal, network 1 is kept to work if network 2 is also
abnormal.
When network 2 is working, network 2 is kept to work even if network 1 has been restored to
normal. The device will be switched to network 1 only if network 2 is abnormal.
8. Addr_RS485A, Addr_RS485B
They are the device′s communication address used to communicate with the SCADA or RTU via
serial ports (port A and port B).
9. Baud_RS485A, Baud_RS485B
1: Modbus Protocol
2: Reserved
NOTICE!
Above table listed all the communication settings, the device delivered to the user
maybe only show some settings of them according to the communication interface
configuration. If only the Ethernet ports are applied, the settings about the serial ports
(port A and port B) are not listed in this submenu. And the settings about the Ethernet
ports only listed in this submenu according to the actual number of Ethernet ports.
The standard arrangement of the Ethernet port is two, at most four (predetermined
when ordering). Set the IP address according to actual arrangement of Ethernet
numbers and the un-useful port/ports need not be configured. If PCS-Explorer
configuration tool auxiliary software is connected with this device through the Ethernet,
the IP address of PCS-Explorer must be set as one of the available IP address of this
device.
11. Threshold_Measmt_Net
12. Period_Measmt_Net
The time period for equipment sends measurement data to SCADA through IEC 60870-5-103
protocol.
13. Format_Measmt
The setting is used to select the format of measurement data sent to SCADA through IEC
60870-5-103 protocol.
1: GDD data type through IEC103 protocol is 7, i.e. 754 short real number of IEEE standard
14. Baud_Printer
15. En_AutoPrint
If automatic print is required for fault report after protection operating, it is set as “1”. Otherwise, it
should be set to “0”.
16. Opt_TimeSyn
There are four selections for clock synchronization of device, shown as follows.
Conventional
PPS (RS-485): Pulse per second (PPS) via RS-485 differential level
PPM (DIN): Pulse per minute (PPM) via the binary input [BI_TimeSyn]
PPS (DIN): Pulse per second (PPS) via the binary input [BI_TimeSyn]
SAS
Advanced
PPS (Fiber) PPS: Pulse per second (PPS) via optical-fibre interface
NoTimeSync
When no time synchronization signal is connected to the device, please select this option and the
alarm message [Alm_TimeSyn] will not be issued anymore.
“Conventional” mode and “SAS” mode are always be supported by the device, but “Advanced”
mode is only supported when NET-DSP module is equipped. The alarm signal [Alm_TimeSyn]
may be issued to remind user loss of time synchronization signals.
1) When “SAS” is selected, if there is no conventional clock synchronization signal, the device
will not send the alarm signal [Alm_TimeSyn]. When “Conventional” mode is selected, if there
is no conventional clock synchronization signal, “SAS” mode will be enabled automatically
with the alarm signal [Alm_TimeSyn] issued simultaneously.
3) When “NoTimeSyn” mode is selected, the device will not send alarm signals without time
synchronization signal. But the device can be still synchronized if receiving time
synchronization signal.
NOTICE!
The clock message via IEC 60870-5-103 protocol is invalid when the device receives
the IRIG-B signal through RCS-485 port.
17. IP_Server_SNTP
It is the address of the SNTP time synchronization server which sends SNTP timing messages to
the relay or BCU.
18. IP_StandbyServer_SNTP
synchronization is valid.
If the IEC61850 protocol is adopted in substations, the time tags of communication messages are
required according to UTC (Universal Time Coordinated) time.
The setting [OffsetHour_UTC] is used to set the hour offset of the current time zone to the GMT
(Greenwich Mean Time) zone; for example, if a relay is applied in China, the time zone of China is
east 8th time zone, so this setting is set as “8”. The setting [OffsetMinute_UTC] is used to set the
minute offset of the current time zone to the GMT zone.
Time zone GMT zone East 1st East 2nd East 3rd East 4th East 5th
Setting 0 1 2 3 4 5
th th th th th
Time zone East 6 East 7 East 8 East 9 East 10 East 11th
Setting 6 7 8 9 10 11
th st nd rd th
Time zone East/West 12 West 1 West 2 West 3 West 4 West 5th
Setting 12/-12 -1 -2 -3 -4 -5
th th th th th th
Time zone West 6 West 7 West 8 West 9 West 10 West 11
Setting -6 -7 -8 -9 -10 -11
20. Opt_Display_Status
This setting is used to set display mode of current in fault records, primary value or secondary
value. The sampled values of currents are displayed as secondary value by default. When it is set
as primary value, the secondary current are converted into primary current according to rated
secondary and primary value of CT respectively.
NOTICE!
After modifying this setting, the “HEALTHY” indicator of the protection device will GO
OUT, and the protection device will automatically restart and re-check the settings. The
device will be BLOCKED until the check process is finished.
21. Num_Cyc_PreTrigDFR
The setting is used to set the cycle number recorded by the device before the trigger element
operating.
22. t_Dly_Net_DNP
The setting is used to set transmission time delay for transmitting multi-frame messages during
DNP process (the setting is valid only if network DNP3.0 protocol is configured)
23. Format_Setting_DNP
The setting is used to set settings uploading format during DNP process (this setting is valid only if
network or serial port DNP3.0 protocol is configured).
24. En_TCPx_DNP
The logic setting is used to enable or disable network No.x DNP client. (x=1, 2, 3, 4)
1: enable
0: disable
When network No.x DNP client is not configured to be in service by PCS-Explorer, DNP client
settings corresponding to network No.x will be hidden.
25. Addr_Slave_TCPx_DNP
26. Addr_Master_TCPx_DNP
27. IP_Master_TCPx_DNP
28. Opt_Map_TCPx_DNP
29. Obj01DefltVar_TCPx_DNP
30. Obj02DefltVar_TCPx_DNP
31. Obj30DefltVar_TCPx_DNP
32. Obj32DefltVar_TCPx_DNP
33. Obj40DefltVar_TCPx_DNP
34. t_AppLayer_TCPx_DNP
35. t_KeepAlive_TCPx_DNP
36. En_UR_TCPx_DNP
The logic setting is used to enable or disable the unsolicited message function of network No.x
DNP client. (x=1, 2, 3, 4)
1: enable
0: disable
37. Num_URRetry_TCPx_DNP
It is the online retransmission number of the unsolicited message of network No.x DNP client. (x=1,
2, 3, 4)
38. t_UROfflRetry_TCPx_DNP
It is the offline timeout of the unsolicited message of network No.x DNP client. (x=1, 2, 3, 4)
39. Class_BI_TCPx_DNP
It is the class level of the “Binary Input” of network No.x DNP client. (x=1, 2, 3, 4)
40. Class_AI_TCPx_DNP
It is the class level of the “Analog Input” of network No.x DNP client. (x=1, 2, 3, 4)
41. t_Select_TCPx_DNP
42. t_TimeSynIntvl_TCPx_DNP
It is the time interval of the time synchronization function of network No.x DNP client. (x=1, 2, 3, 4)
6 Bxx.U_Pickup_BI 55%Un~80%Un
7 Bxx.U_Dropoff_BI 55%Un~80%Un
8 En_RevCT 0 or 1
9 En_Ctrl_SLD 0 or 1
10 En_PopupRecord_Blkd 0 or 1
2. Opt_Caption_103
0: Current language
1: Fixed Chinese
2: Fixed English
Default value of [Opt_Caption_103] is “0” (i.e. current language), and please set it as “1” (i.e. Fixed
Chinese) if the SAS is supplied by China Manufacturer.
3. En_Send_MMS_Qual_Chg
It is used to enable or disable that IEC 61850 communication program uploads tha variation of
data quality.
0: disable
1: enable
4. Opt_DualNetMode_MM
It is used to select network mode of MMS network for the communication with SCADA
0: Single network
5. Bxx.Un_BinaryInput
This setting is used to set voltage level of binary input module. If low-voltage BI module is
equipped, 24V, 30V or 48V can be set according to the actual requirement, and if high-voltage BI
module is equipped, 110V, 125V or 220V can be set according to the actual requirement.
6. Bxx.U_Pickup_BI
This setting is used to set pickup voltage of binary input module. Bxx: this plug-in module is
inserted in slot xx.
7. Bxx.U_Dropoff_BI
This setting is used to set dropoff voltage of binary input module. Bxx: this plug-in module is
inserted in slot xx.
8. En_RevCT
The default value is “0”, it can be set as “1” if the polarity of the CT on site is reverse.
9. En_Ctrl_SLD
This setting is used to enable or disable the switch control function from the single line diagram
displayed in the device LCD.
0: Disable
1: Enable
10. En_PopupRecord_Blkd
This setting is used to enable or disable the auto-popup function of event report in the device LCD.
0: Disable
1: Enable
5 U2n 80.00~220.00 V
6 I1n 100~30000 A
7 I2n 1 or 5 A
8 f_High_FreqAlm 50~65 Hz
9 f_Low_FreqAlm 40~60 Hz
The number of active setting group, 10 setting groups can be configured for protection settings,
and only one is active at a time.
2. PrimaryEquip_Name
It is recognized by the device automatically. Such setting is used for printing messages.
3. Opt_SysFreq
4. Un1
5. Un2
6. In1
7. In2
8. f_High_FreqAlm
Frequency upper limit setting. The device will issue an alarm [Alm_Freq], when system frequency
is higher than the setting.
9. f_Low_FreqAlm
Frequency lower limit setting. The device will issue an alarm [Alm_Freq], when system frequency
is lower than the setting.
Non_Directional
Direction option for stage 4 of phase overcurrent
40 50/51P4.Opt_Dir Forward
protection
Reverse
Enable second harmonic blocking for stage 4 of
41 50/51P4.En_Hm2_Blk 0 or 1
phase overcurrent protection
DefTime, IECN, IECV,
IECE, IECST, IECLT,
Option of characteristic curve for stage 4 of phase
42 50/51P4.Opt_Curve ANSIE, ANSIV, ANSI,
overcurrent protection
ANSIM, ANSILTE,
ANSILTV, ANSILT
Time multiplier setting for stage 4 of inverse-time
43 50/51P4.TMS 0.010~20000.000
phase overcurrent protection.
Minimum operating time for stage 4 of
44 50/51P4.tmin 0.010~20.000 (s)
inverse-time phase overcurrent protection
Non_Directional
Direction option for stage 1 of negative-sequence
6 50/51Q1.Opt_Dir Forward
overcurrent protection
Reverse
Enable blocking for stage 1 of negative-sequence
7 50/51Q1.En_Abnor_Blk 0 or 1
overcurrent protection under abnormal conditions
Enable blocking for stage 1 of negative-sequence
8 50/51Q1.En_CTS_Blk 0 or 1
overcurrent protection under CT failure conditions
DefTime
IECN
IECV
IECE
IECST
IECLT
Option of characteristic curve for stage 1 of ANSIE
9 50/51Q1.Opt_Curve
negative-sequence overcurrent protection ANSIV
ANSI
ANSIM
ANSILTE
ANSILTV
ANSILT
UserDefine
Time multiplier setting for stage 1 of inverse-time
10 50/51Q1.TMS 0.010~200.000
negative-sequence overcurrent protection
Minimum operating time for stage 1 of inverse-time
11 50/51Q1.tmin 0.050~20.000 (s)
negative-sequence overcurrent protection
Constant “α” for stage 1 of customized inverse-time
12 50/51Q1.Alpha characteristic negative-sequence overcurrent 0.010~5.000
protection
Constant “C” for stage 1 of customized inverse-time
13 50/51Q1.C characteristic negative-sequence overcurrent 0.000~20.000
protection
Constant “K” for stage 1 of customized inverse-time
14 50/51Q1.K characteristic negative-sequence overcurrent 0.050~20.000
protection
Current setting for stage 2 of negative-sequence
15 50/51Q2.I2_Set (0.050~30.000)×In (A)
overcurrent protection
Ratio coefficient (I2/I1) for stage 2 of
16 50/51Q2.I2/I1_Set 0.00~1.00
negative-sequence overcurrent protection
Time delay for stage 2 of negative-sequence
17 50/51Q2.t_Op 0.000~20.000 (s)
overcurrent protection
Enable stage 2 of negative-sequence overcurrent
18 50/51Q2.En 0 or 1
protection
Enable auto-reclosing blocked when stage 2 of
19 50/51Q2.En_BlkAR 0 or 1
negative-sequence overcurrent protection operates
Non_Directional
Direction option for stage 2 of negative-sequence
20 50/51Q2.Opt_Dir Forward
overcurrent protection
Reverse
Enable blocking for stage 2 of negative-sequence
21 50/51Q2.En_Abnor_Blk 0 or 1
overcurrent protection under abnormal conditions
Enable blocking for stage 2 of negative-sequence
22 50/51Q2.En_CTS_Blk 0 or 1
overcurrent protection under CT failure conditions
DefTime
IECN
IECV
IECE
IECST
IECLT
Option of characteristic curve for stage 2 of
23 50/51Q2.Opt_Curve ANSIE
negative-sequence overcurrent protection
ANSIV
ANSI
ANSIM
ANSILTE
ANSILTV
ANSILT
Time multiplier setting for stage 2 of inverse-time
24 50/51Q2.TMS 0.010~200.000
negative-sequence overcurrent protection
Minimum operating time for stage 2 of inverse-time
25 50/51Q2.tmin 0.050~20.000 (s)
negative-sequence overcurrent protection
Current setting for stage 3 of negative-sequence
26 50/51Q3.I2_Set (0.050~30.000)×In (A)
overcurrent protection
Ratio coefficient (I2/I1) for stage 3 of
27 50/51Q3.I2/I1_Set 0.00~1.00
negative-sequence overcurrent protection
Time delay for stage 3 of negative-sequence
28 50/51Q3.t_Op 0.000~20.000 (s)
overcurrent protection
Enable stage 3 of negative-sequence overcurrent
29 50/51Q3.En 0 or 1
protection
Enable auto-reclosing blocked when stage 3 of
30 50/51Q3.En_BlkAR 0 or 1
negative-sequence overcurrent protection operates
Non_Directional
Direction option for stage 3 of negative-sequence
31 50/51Q3.Opt_Dir Forward
overcurrent protection
Reverse
Enable blocking for stage 3 of negative-sequence
32 50/51Q3.En_Abnor_Blk 0 or 1
overcurrent protection under abnormal conditions
Enable blocking for stage 3 of negative-sequence
33 50/51Q3.En_CTS_Blk 0 or 1
overcurrent protection under CT failure conditions
DefTime
IECN
IECV
IECE
IECST
IECLT
Option of characteristic curve for stage 3 of
34 50/51Q3.Opt_Curve ANSIE
negative-sequence overcurrent protection
ANSIV
ANSI
ANSIM
ANSILTE
ANSILTV
ANSILT
Time multiplier setting for stage 3 of inverse-time
35 50/51Q3.TMS 0.010~200.000
negative-sequence overcurrent protection
Minimum operating time for stage 3 of inverse-time
36 50/51Q3.tmin 0.050~20.000 (s)
negative-sequence overcurrent protection
Current setting for stage 4 of negative-sequence
37 50/51Q4.I2_Set (0.050~30.000)×In (A)
overcurrent protection
Ratio coefficient (I2/I1) for stage 4 of
38 50/51Q4.I2/I1_Set 0.00~1.00
negative-sequence overcurrent protection
Time delay for stage 4 of negative-sequence
39 50/51Q4.t_Op 0.000~20.000 (s)
overcurrent protection
Enable stage 4 of negative-sequence overcurrent
40 50/51Q4.En 0 or 1
protection
Enable stage 4 of negative-sequence overcurrent
41 50/51Q4.En_Trp 0 or 1
protection operate to trip or alarm.
Enable auto-reclosing blocked when stage 4 of
42 50/51Q4.En_BlkAR 0 or 1
negative-sequence overcurrent protection operates
Non_Directional
Direction option for stage 4 of negative-sequence
43 50/51Q4.Opt_Dir Forward
overcurrent protection
Reverse
Enable blocking for stage 4 of negative-sequence
44 50/51Q4.En_Abnor_Blk 0 or 1
overcurrent protection under abnormal conditions
Enable blocking for stage 4 of negative-sequence
45 50/51Q4.En_CTS_Blk 0 or 1
overcurrent protection under CT failure conditions
DefTime
IECN
IECV
IECE
IECST
IECLT
Option of characteristic curve for stage 4 of
46 50/51Q4.Opt_Curve ANSIE
negative-sequence overcurrent protection
ANSIV
ANSI
ANSIM
ANSILTE
ANSILTV
ANSILT
Time multiplier setting for stage 4 of inverse-time
47 50/51Q4.TMS 0.010~200.000
negative-sequence overcurrent protection
Minimum operating time for stage 4 of inverse-time
48 50/51Q4.tmin 0.050~20.000 (s)
negative-sequence overcurrent protection
DefTime
IECN
IECV
IECE
IECST
IECLT
Option of characteristic curve for stage 2 of residual ANSIE
7 59G2.Opt_Curve
overvoltage protection ANSIV
ANSI
ANSIM
ANSILTE
ANSILTV
ANSILT
UserDefine
Time multiplier setting for stage 2 of residual
8 59G2.TMS 0.010~200.000
overvoltage protection
Minimum operating time for stage 2 of residual
9 59G2.tmin 0.050~20.000 (s)
overvoltage protection
Constant “α” for stage 2 of customized inverse-time
10 59G2.Alpha 0.010~5.000
characteristic residual overvoltage protection
Constant “C” for stage 2 of customized inverse-time
11 59G2.C 0.000~20.000
characteristic residual overvoltage protection
Constant “K” for stage 2 of customized inverse-time
12 59G2.K 0.050~20.000
characteristic residual overvoltage protection
Voltage setting of stage 3 of residual overvoltage
13 59G3.3U0_Set 0~Unn (V)
protection.
Time delay of stage 3 of residual overvoltage
14 59G3.t_Op 0.000~3600.000 (s)
protection.
15 59G3.En Enable stage 3 of residual overvoltage protection. 0 or 1
Enable stage 3 of residual overvoltage protection for
16 59G3.En_Trp 0 or 1
trip purpose.
DefTime
IECN
IECV
IECE
IECST
IECLT
Option of characteristic curve for stage 3 of residual ANSIE
17 59G3.Opt_Curve
overvoltage protection ANSIV
ANSI
ANSIM
ANSILTE
ANSILTV
ANSILT
UserDefine
Time multiplier setting for stage 3 of residual
18 59G3.TMS 0.010~200.00
overvoltage protection
Minimum operating time for stage 3 of residual
19 59G3.tmin 0.050~20.000 (s)
overvoltage protection
Constant “α” for stage 3 of customized inverse-time
20 59G3.Alpha 0.010~5.000
characteristic residual overvoltage protection
Constant “C” for stage 3 of customized inverse-time
21 59G3.C 0.000~20.000
characteristic residual overvoltage protection
Constant “K” for stage 3 of customized inverse-time
22 59G3.K 0.050~20.000
characteristic residual overvoltage protection
have a corresponding submenu in the submenu “Logic Links” for the logic link settings.
Each logic link settings is an “AND” condition of enabling the relevant function with the
corresponding binary input and logic setting. Through SAS or RTU, logic link settings can be set
as “1” or “0”; and it means that the relevant function can be in service or out of service through
remote command. It provides convenience for operation management.
The GOOSE link settings (in the submenu “GOOSE Links”) are used to determine whether the
relevant GOOSE elements are enabled or disabled. See the GOOSE related instruction manual
for the more information and details.
The spare link settings (in the submenu “Function Links”) are used for future application. It can
be defined according to project specification through the PCS-Explorer configuration tool.
Thses settings are applied to configure the status change confirmation time for No.xx double point
binary inputs. Up to 10 virtual double point binary inputs are provided in this device.
If a double point binary input changes from normal status to invalid status, i.e.: double point error
occurs, [CSWIxx.t_DPU_DPS] will be applied as the debouncing time for No.xx double point
binary input.
No. Name Remark Range
Table of Contents
List of Figures
Figure 8.1-4 Corresponding cable of the RJ45 port in the front panel .................................. 8-4
Figure 8.1-5 Rear view and terminal definition of NR1102C ................................................... 8-5
List of Tables
The operator can access the protective device from the front panel. Local communication with the
protective device is possible using a computer via a multiplex RJ45 port on the front panel.
Furthermore, remote communication is also possible using a PC with the substation automation
system via rear RS485 port or rear Ethernet port. The operator is able to check the protective
device status at any time.
This chapter describes human machine interface (HMI), and give operator an instruction about
how to display or print event report, setting and so on through HMI menu tree and display metering
value, including r.m.s. current, voltage and frequency etc. through LCD. Procedures to change
active setting group or a settable parameter value through keypad is also described in details.
NOTICE!
8.1 Overview
The human-machine interface consists of a human-machine interface (HMI) module which allows
a communication to be as simple as possible for the user. The HMI module helps to draw your
attention to something that has occurred which may activate a LED or a report displayed on the
LCD. Operator can locate the data of interest by navigating the keypad.
1 11
HEALTHY PCS-9 21
2 12
5 BREAKER FAILURE RELAY
ALARM
3 13
4 14
GRP
5 15
6 16 ENT
ESC
7 17
4
8 18
1
9 19
3
10 20
ENT
ESC
1. “ESC”:
2. “ENT”:
3. “GRP”
Page up/down
HEALTHY
ALARM
Steady Green Lit when the equipment is in service and ready for operation.
NOTICE!
“HEALTHY” LED can only be turned on by energizing the device and no abnormality
detected.
“ALARM” LED is turned on when abnormalities of device occurs like above mentioned
and can be turned off after abnormalities are removed except alarm report [CTS.Alm]
which can only be reset only when the failure is removed and the device is rebooted or
re-energized.
Other LED indicators with no labels are configurable and user can configure them to be
lit by signals of operation element, alarm element and binary output contact according
to requirement through PCS-Explorer software, but as drawn in figure, 2 LEDs are fixed
as the signals of “HEALTHY” (green) and “ALARM” (yellow), 18 LEDs are configurable
with selectable color among green, yellow and red.
P2
P1
P3
Figure 8.1-4 Corresponding cable of the RJ45 port in the front panel
P1: To connect the multiplex RJ45 port. An 8-core cable is applied here.
The definition of the 8-core cable in the above figure is introduced in the following table.
The Ethernet port can be used to communication with PC via auxiliary software (PCS-Explorer)
after connecting the protection device with PC, so as to fulfill on-line function (please refer to the
instruction manual of PCS-Explorer). At first, the connection between the protection device and PC
must be established. Through setting the IP address and subnet mask of corresponding Ethernet
interface in the menu “Settings→Device Setup→Comm Settings”, it should be ensured that the
protection device and PC are in the same network segment. For example, setting the IP address
and subnet mask of network A. (using network A to connect with PC)
The IP address and subnet mask of protection device should be [IP_LAN1]= 198.87.96.XXX,
[Mask_LAN1]=255.255.255.0, [En_LAN1]=1. (XXX can be any value from 0 to 255 except 102)
If the logic setting [En_LAN1] is non-available, it means that network A is always enabled. If using
other Ethernet port, for example, Ethernet B, the logic setting [En_LAN2] must be set as “1”.
NR1102C
ETHERNET
Network A
Network B
SYN+
SYN-
SGND
GND
RTS
TXD
SGND
Press “▲” to enter the main menu with the interface as shown in the following diagram:
MainMenu
Language
Clock
Quick Menu
For the first powered protective device, there is no record in quick menu. Press “▲” to enter the
main menu with the interface as shown in the following diagram:
Measurements
Status
Records
Settings
Local Cmd
Information
Test
Clock
Language
The descriptions about menu are based on the maximized configuration, for a specific project, if
some function is not available, the corresponding submenu will hidden.
Main Menu
Measurements
Status
Records
Settings
Local Cmd
Information
Test
Clock
Language
Under the main interface, press “▲” to enter the main menu, and select submenu by pressing “▲”,
“▼” and “ENT”. The command menu adopts a tree shaped content structure. The above diagram
provides the integral structure and all main menus (first level menus) under menu tree of the
protection device.
Main Menu
Measurements
Measurements1
Measurements2
Measurements3
Metering
This menu is used to display real-time measured values, including AC voltage, AC current, phase
angle and calculated quantities. These data can help users to acquaint the device’s status. This
menu comprises following submenus. Please refer to Section “Measurement” about the detailed
measured values.
8.2.3.2 Status
Main Menu
Status
Inputs
Contact Inputs
GOOSE Inputs
Outputs
Contact Outputs
GOOSE Outputs
Interlock Status
Superv State
Prot Superv
FD Superv
GOOSE Superv
SV Superv
BCU Superv
This menu is used to display real time input signals, output signals and alarm signals of the device.
These data can help users to acquaint the device′s status. This menu comprises following
submenus. Please refer to Section “Signal List” about the detailed input and output signals, and
Section “Supervision Alarms” about alarm signals.
1 Contact Inputs Display states of binary inputs derived from opto-isolated channels
1 Prot Superv Display states of self-supervision signals from protection calculation DSP
8.2.3.3 Records
Main Menu
Records
Disturb Records
Superv Events
IO Events
Device Logs
Control Logs
Clear Records
This menu is used to display all kinds of records, including the disturbance records, supervision
events, binary events and device logs, so that the operator can load to view and use as the
reference of analyzing accidents and repairing the device. All records are stored in non-volatile
memory, it can still record them even if it loses its power.
8.2.3.4 Settings
Main Menu
Settings
System Settings
Prot Settings
FD Settings
AuxE Settings
OC Settings
ROC Settings
NegOC Settings
BFP Settings
DeadZone Settings
OV Settings
UV Settings
NegOV Settings
ROV Settings
PD Settings
FreqProt Settings
VTS/CTS Settings
AR/Syn Settings
Copy Settings
BCU Settings
Syn Settings
BI Settings
Control Settings
Interlock Settings
Logic Links
Function Links
GOOSE Links
SV Links
Spare Links
Device Setup
Device Settings
Comm Settings
Label Settings
This menu is used to check the device setup, system parameters, protection settings and logic
links settings, as well as modifying any of the above setting items. Moreover, it can also execute
the setting copy between different setting groups.
Check or modify the logic links settings, including function links, SV links,
4 Logic Links
GOOSE links and spare links
4 Spare Links Check or modify spare links settings (used for programmable logic)
3 Label Settings Check or modify the label settings of each protection element.
8.2.3.5 Print
Main Menu
Device Info
Settings
System Settings
Prot Settings
BCU Settings
Logic Links
Device Setup
All Settings
Disturb Records
Superv Events
IO Events
Device Status
Waveforms
IEC103 Info
Cancel Print
This menu is used to print device description, settings, all kinds of records, waveforms, information
related with IEC60870-5-103 protocol, channel state and channel statistic.
Print the current state of the device, including the sampled value of
6 Device Status
voltage and current, the state of binary inputs, setting and so on
4 Spare Links Print spare links settings (used for programmable logic)
Main Menu
Local Cmd
Reset Target
Trig Oscillograph
Control
Download
Clear Counter
Clear AR Counter
This menu is used to reset the tripping relay with latch, indicator LED, LCD display, and as same
as the resetting function of binary inputs. This menu provides a method of manually recording the
current waveform data of the device under normal condition for printing and uploading SAS.
Besides, it can send out the request of program download, clear statistic information about
GOOSE SV AR and energy.
1 Reset Target Reset the local signal, indicator LED, LCD display and so on
8.2.3.7 Information
Main Menu
Information
Version Info
Board Info
MOT Info
In this menu, the LCD can display software information of all kinds of intelligent plug-in modules,
which consists of version, creating time of software, CRC codes and management sequence
number. Besides, plug-in module information and MOT information can also be viewed.
Display software information of DSP module, MON module and HMI module,
1 Version Info which consists of version, creating time of software, CRC codes and
management sequence number.
2 Board Info Monitor the current working state of each intelligent module.
8.2.3.8 Test
Main Menu
Test
SV Comm Counter
AR Counter
Device Test
Disturb Events
Superv Events
IO Events
Internal Signal
HMI Setup
Contrast
BacklitDur
LgtIntnsty
SupervLCD
SupervLED
NetPortBond Info
This menu is mainly used for developers to debug the program and for engineers to maintain the
protection device. It can be used to fulfill the communication test function. It is also used to
generate all kinds of reports or events to transmit to the SAS without any external input, so as to
debug the communication on site. Besides, it can also display statistic information about GOOSE
SV and AR.
6 HMI Setup Configure LCD display and check LCD display and LED indicators
7 NetPortBond Info Check link status of current working port and bonding ports
View the relevant information about disturbance records (only used for
1 Disturb Events
debugging persons)
View the relevant information about supervision events (only used for
2 Superv Events
debugging persons)
View the relevant information about binary events (only used for debugging
3 IO Events
persons)
Users can respectively execute the test automatically or manually by selecting commands “All
Test” or “Select Test”.
8.2.3.9 Clock
The current time of internal clock can be viewed here. The time is displayed in the form
YY-MM-DD and hh:mm:ss by default. All values are presented with digits and can be modified.
8.2.3.10 Language
According to different access authority, the corresponding operations to the device by LCD panel
can be allowed to perform. For the operation that requires authorization, the corresponding user
logs in and the correct password must be input after the operation can be performed.
Taking “User1” as an example, four kinds of authorities: View, Control, Setting, Project are shown
as below.
1. Press the “▲” to enter the main menu, the following interface will be shown when performing
an operation. (Multi-users have been configured in advance)
2. Press the “◄” or “►” to select username, and press the “ESC” to exit this menu
Username User1
Password
3. Press the “ENT” or “▼” to move, and the following interface will be shown after the username
is confirmed.
Username User1
Password ******
0 1 2 3 4 5 6 7 8 9 [OK]
4. Press the “◄” or “►” to select number or letter, and press “ENT” to ensure selected character.
5. Press the “▲” or “▼” to page up/down to select previous group or next group characters.
7. When the password reaches to 8 bits, the device will verify whether the username and
password are correctly. If the password is shorter than 8 bits, select and press “OK” to begin
to verify whether the username and password are correctly.
8. Press the “ESC” to cancel entered character during entering password, and the password will
be cleared if the password check fails. When the password is cleared, press the “ESC” to
select the username again.
9. The device provides the function of password memory, the following interface will be shown if
the valid time of the password is set and last entered password is no timeout.
Username User1
Password *******
10. Press the “ENT” to verify the password, press the “◄” or “►” to switch the username and the
password will be cleared, and press the “ESC” to exit the interface.
11. If the password is correct and the user owns the authority of the operation performed, the
operation will be performed.
If the password is incorrect, the device will issue an alarm signal “Password Error”. If the password
is correct but the user has no the authority of the operation performed, the device will issue an
alarm signal “Unauthorized”. If the password is incorrect or the user has no the authority of the
operation performed more than three times, the device will issue an alarm signal “PWD Error or
Unauthorized, Screen Locked” and the device will return to main interface after the screen is
locked for 1 minutes, which will be recorded in device log.
1. Right-click the menu “LCD Graph”, and select the menu item “Edit Shortcut Key” to display
the configuration interface of function key shortcuts as shown below.
2. In configuration interface, double-click the table item in the list of “Extend Command” to select
LCD extend command of dropdown list corresponding with keypads in front panel as shown
below. Select the first blank item in dropdown list to cancel the setup.
3. Double-click the table item in the list of “Attribute” to edit the attribute of keypad in front panel
as shown below. When the attribute is set as “1”, the corresponding operation can not excute
unless input correct password. When the attribute is set as “0” or blank, password is not
required. After finishing configuration, click the button “OK”.
4. The name description of extend command can be modified in signal setup interface, the
operation “Refresh” in the interface of “Source” must be excute at first before configuring
function shortcuts key or generating drive file package.
5. Right-click device node and execute the menu “Compress Driver File” to generate drive file
package of the device. The file “LCDConfig.txt” in drive file package of the device records
related contents about shortcuts key. If shortcuts keys are not required, set “Extend
Command” corresponding with function shortcuts key as blank, and generate drive file
package of the device again.
In general, the function of “GRP” is switch setting group, however, the original function of “GRP” is
blocked when configuring function shortcuts key. (the setting group can be switched by shortcuts
key, binary input or modifying the setting) Under main interface, press “GRP” to display the
interface of function shortcuts key and press “ESC” to return to main interface.
Shortcut keys
[ ] LCD.ExtCmd04
[ ] LCD.ExtCmd05
[ ] LCD.ExtCmd06
[ ] LCD.ExtCmd07
[ + ] LCD.ExtCmd08
[ - ] LCD.ExtCmd09
[ ENT ] LCD.ExtCmd10
Password:
000
Under the interface of function shortcuts key, press a shortcuts key to excute corresponding
operation. If the attribute of the extend command is set as “1”, the corresponding operation can not
excute unless input correct password. The extend command excuted by shortcuts key outputs a
pulse signal with 500ms, and for the operation requiring latching signal, the device provides
“T_FF” and “RS_FF” to fulfill the application, which can be configured by PCS-Explorer.
complete the initialization of the device. During the initialization of the device, the “HEALTHY”
indicator lamp of the device goes out.
The device can display single line diagram (SLD) and primary operation information, it can support
wiring configuration function. LCD configuration file can be downloaded via the network. Remote
control operation through single line diagram is also supported.
Under normal condition, LCD will display the following interface. LCD adopts white color as its
backlight that is activated if once there is any keyboard operation, moreover, the backlight will be
extinguished automatically if no keyboard operation is detected for a duration.
S 2010-06-08 10:10:00
Ia 0.00A
Ib 0.00A
Ic 0.00A
3I0 0.00A
Ua 0.02V
Ub 0.00V
Uc 0.00V
3U0 0.02V
U_Syn 0.00V
f 50.00Hz
The content displayed on the screen contains: the current date and time of the device (with a
format of yyyy-mm-dd hh:mm:ss:), the active setting group number, three-phase current sampling
value, residual current sampling value, three-phase voltage sampling value, residual voltage
sampling value, the synchronism voltage sampling value, line frequency and the address relevant
to IP address of Ethernet A. If all the sampling values of the voltage and the current can’t be fully
displayed within one screen, they will be scrolling-displayed automatically from the top to the
bottom.
If the device has detected any abnormal state, it′ll display the self-check alarm information.
“S” indicates that device clock is synchronized. If “S” disappears, it means that device clock is not
synchronized.
Up to 1024 disturbance records can be stored in this device. If there is protection element
operation, LCD will automatically display the latest group of disturbance records, and two kinds of
LCD display interfaces will be available depending on whether there are supervision events or not.
For the situation that the disturbance records and the supervision events coexist, the upper half
part is the disturbance record, and the lower half part is the supervision event. The following items
are listed in the upper half part: record No., record name, generation time of the disturbance
record. If there is protection element operation, faulty phase and relative operation time (with
reference to the corresponding fault detector element) will be displayed. If the disturbance records
can not be displayed in one page, they will be displayed in several pages alternately.
If there is no supervision event, disturbance records will be displayed as shown in the following
figure.
0000ms FD.DPFC.Pkp
0024ms A 50/51P.Op
If the device has the supervision event, the display interface will show the disturbance record and
the supervision event at the same time.
0000ms FD.DPFC.Pkp
0024ms A 50/51P.Op
Superv Events
Alm_Device
2013-01-15 13:22:23:669 shows the time of the disturbance record, the format is
“yyyy-mm-dd hh:mm:ss:fff”.
0000ms FD.DPFC.Pkp shows fault detector element and its operation time (set as
“0000ms” fixedly).
0024ms A 50/51P.Op shows operation element and its relative operation time (with
reference to the corresponding fault detector element).
All the protection elements have been listed in Chapter “Operation Theory”, and please refer to
each protection element for details. The reports related to oscillography function are showed in the
following table.
S Superv Events
Alm_Device
Alm_Version
Alm_Version
BI_Maintenance 0 1
2013-01-15 13:31:23:669 shows date and time when the report occurred, the format is
“yyyy-mm-dd hh:mm:ss:fff”.
BI_Maintenance 0→1 shows the state change of binary input, including binary input
name, original state and final state.
Device Logs NO. 4 shows the title and the number of the device log
2008-11-28 10:18:47:569 shows date and time when the report occurred, the format is
year–month-date and hour:minute:second:millisecond
It will be displayed on LCD before disturbance records and supervision events are confirmed. Only
pressing both “ENT” and “ESC” at the same time can switch among disturbance records,
supervision events and the normal running state of the device to display it. IO events will be
displayed for 5s and then it will return to the previous display interface automatically.
2. Press the “▲” or “▼” to move the cursor to the “Measurements” menu, and then press the
“ENT” or “►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the “ENT” to
enter the menu;
4. Press the “▲” or “▼” to page up/down (if all information cannot be displayed in one display
screen, one screen can display 14 lines of information at most);
6. Press the “ENT” or “ESC” to exit this menu (returning to the “Measurements” menu);
2. Press the key “▲” or “▼” to move the cursor to the “Status” menu, and then press the “ENT”
or “►” to enter the menu.
3. Press the key “▲” or “▼” to move the cursor to any command menu item, and then press the
key “ENT” to enter the submenu.
4. Press the “▲” or “▼” to page up/down (if all information cannot be displayed in one display
screen, one screen can display 14 lines of information at most).
5. Press the key “◄” or “►” to select pervious or next command menu.
6. Press the key “ENT” or “ESC” to exit this menu (returning to the “Status” menu).
2. Press the “▲” or “▼” to move the cursor to the “Records” menu, and then press the “ENT” or
“►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the “ENT” to
enter the menu;
7. Press the “ENT” or “ESC” to exit this menu (returning to the “Records” menu);
2. Press the “▲” or “▼” to move the cursor to the “Print” menu, and then press the “ENT” or “►”
to enter the menu;
3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the “ENT” to
enter the menu;
Selecting the “Disturb Records”, and then press the “+” or “-” to select pervious or next
record. After pressing the key “ENT”, the LCD will display “Start Printing... ”, and then
automatically exit this menu (returning to the menu “Print”). If the printer doesn’t complete its
current print task and re-start it for printing, and the LCD will display “Printer Busy…”. Press
the key “ESC” to exit this menu (returning to the menu “Print”).
Selecting the command menu “Superv Events” or “IO Events”, and then press the key “▲” or
“▼” to move the cursor. Press the “+” or “-” to select the starting and ending numbers of
printing message. After pressing the key “ENT”, the LCD will display “Start Printing…”, and
then automatically exit this menu (returning to the menu “Print”). Press the key “ESC” to exit
this menu (returning to the menu “Print”).
4. If selecting the command menu “Device Info”, “Device Status“ or “IEC103_Info”, press the
key “ENT”, the LCD will display “Start printing..”, and then automatically exit this menu
(returning to the menu “Print”).
5. If selecting the “Settings”, press the key “ENT” or “►” to enter the next level of menu.
6. After entering the submenu “Settings”, press the key “▲” or “▼” to move the cursor, and then
press the key “ENT” to print the corresponding default value. If selecting any item to printing:
Press the key “+” or “-” to select the setting group to be printed. After pressing the key
“ENT”, the LCD will display “Start Printing…”, and then automatically exit this menu (returning
to the menu “Settings”). Press the key “ESC” to exit this menu (returning to the menu
“Settings”).
7. After entering the submenu “Waveforms”, press the “+” or “-” to select the waveform item
to be printed and press ”ENT” to enter. If there is no any waveform data, the LCD will display
“No Waveform Data!” (Before executing the command menu “Waveforms”, it is necessary to
execute the command menu “Trig Oscillograph” in the menu “Local Cmd”, otherwise the
LCD will display “No Waveform Data!”). With waveform data existing:
Press the key “+” or “-” to select pervious or next record. After pressing the key “ENT”, the LCD
will display “Start Printing…”, and then automatically exit this menu (returning to the menu
“Waveforms”). If the printer does not complete its current print task and re-start it for printing, and
the LCD will display “Printer Busy…”. Press the key “ESC” to exit this menu (returning to the menu
“Waveforms”).
2. Press the “▲” or “▼” to move the cursor to the “Settings” menu, and then press the “ENT” or
“►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the “ENT” to
enter the menu;
7. Press the “ESC” to exit this menu (returning to the menu “Settings”).
NOTICE!
If the displayed information exceeds 14 lines, the scroll bar will appear on the right side
of the LCD to indicate the quantity of all displayed information of the command menu
and the relative location of information where the current cursor points at.
2. Press the “▲” or “▼” to move the cursor to the “Settings” menu, and then press the “ENT” or
“►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the “ENT” to
enter the menu;
7. Press the “ESC” to exit this menu (returning to the menu “Settings” );
8. If selecting the command menu “System Settings”, move the cursor to the setting item to be
modified, and then press the “ENT”;
Press the “+” or “-” to modify the value (if the modified value is of multi-bit, press the “◄” or “►”
to move the cursor to the digit bit, and then press the “+” or “-” to modify the value), press the
“ESC” to cancel the modification and return to the displayed interface of the command menu
“System Settings”. Press the “ENT” to automatically exit this menu (returning to the displayed
interface of the command menu “System Settings”).
Move the cursor to continue modifying other setting items. After all setting values are modified,
press the “◄”, “►” or “ESC”, and the LCD will display “Save or Not?”. Directly press the “ESC” or
press the “◄” or “►” to move the cursor. Select the “Cancel”, and then press the “ENT” to
automatically exit this menu (returning to the displayed interface of the command menu “System
Settings”).
Press the “◄” or “►” to move the cursor. Select “No” and press the “ENT”, all modified setting item
will restore to its original value, exit this menu (returning to the menu “Settings”).
Press the “◄” or “►” to move the cursor to select “Yes”, and then press the “ENT”, the LCD will
display password input interface.
____
Input a 4-bit password (“+”, “◄”, “▲” and “-”). If the password is incorrect, continue inputting it,
and then press the “ESC” to exit the password input interface and return to the displayed interface
of the command menu “System Settings”. If the password is correct, LCD will display “Save
Setting Now…”, and then exit this menu (returning to the displayed interface of the command
menu “System Settings”), with all modified setting items as modified values.
NOTICE!
For different setting items, their displayed interfaces are different but their modification
methods are the same. The following is ditto.
9. If selecting the submenu “Prot Settings”, and press “ENT” to enter. After selecting different
command menu, the LCD will display the following interface: (take “FD Settings” as an
example)
FD Settings
Active Group : 01
Selected Group : 02
Press the “+” or “-” to modify the value, and then press the “ENT” to enter it. Move the cursor to
the setting item to be modified, press the “ENT” to enter.
Take the setting [FD.DPFC.I_Set] as an example is selected to modify, then press the “ENT” to
enter and the LCD will display the following interface. is shown the “+” or “-” to modify the value
and then press the “ENT” to confirm.
FD.DPFC.I_Set
NOTICE!
After modifying protection settings in current active setting group or system parameters
of the device, the “HEALTHY” LED indicator the device will be lit off, and the MON
module will check the new settings. If the abnormality is detected during the setting
check, corresponding alarm signals will be issued. Moreover, if the critical error is
detected, the device will be blocked.
2. Press the “▲” or “▼” to move the cursor to the “Settings” menu, and then press the “ENT” or
“►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to the command menu “Copy Settings”, and then
press the “ENT” to enter the menu.
Copy Settings
Active Group: 01
Copy To Group: 02
Press the “+” or “-” to modify the value. Press the “ESC”, and return to the menu “Settings”.
Press the “ENT”, the LCD will display the interface for password input, if the password is incorrect,
continue inputting it, press the “ESC” to exit the password input interface and return to the menu
“Settings”. If the password is correct, the LCD will display “Settings Copied!”, and exit this menu
(returning to the menu “Settings”).
Active Group: 01
Change To Group: 02
Press the “+” or “-” to modify the value, and then press the “ESC” to exit this menu (returning to
the main menu). After pressing the “ENT”, the LCD will display the password input interface. If the
password is incorrect, continue inputting it, and then press the “ESC” to exit the password input
interface and return to its original state. If the password is correct, the “HEALTHY” indicator lamp
of the protection device will go out, and the protection device will re-check the protection setting. If
the check doesn’t pass, the protection device will be blocked. If the check is successful, the LCD
will return to its original state.
2. Press the “+”, “-”, “+”, “-” and “ENT”; Press the “ESC” to exit this menu (returning to the
original state). Press the “ENT” to carry out the deletion.
NOTICE!
The operation of deleting device message will delete all messages saved by the
protection device, including disturbance records, supervision events, binary events, but
not including device logs. Furthermore, the message is IRRECOVERABLE after
deletion, so the application of the function shall be cautious.
2. Press the key “▲” or “▼” to move the cursor to the command menu “Local Cmd”, and
then press the key “ENT” to enter submenus. Press the key “▲” or “▼” to move the
cursor to the command menu “Control”, and then press the key “ENT” to enter and the
following display will be shown on LCD.
Password:
___
Input a 3-bit password (“111”). If the password is incorrect, continue inputting it, and then press the
“ESC” to exit the password input interface and return to the displayed interface of the command
menu “Control”. If the password is correct, it will go to the following step.
3. Press the key “▲” or “▼” to move the cursor to the control object and press the key
“ENT” to select control object.
Control
Step1: select Control Object
1. CSWI01
2. CSWI02
3. CSWI03
4. CSWI04
5. CSWI05
6. CSWI06
7. CSWI07
8. CSWI08
9. CSWI09
10. CSWI10
4. Press the key “◄” or “►” to select control command press the key “ENT” to the next step.
3) (Stop): Reserved
CSWI01
Step2: select Control Command
InterlockChk InterlockNotChk
Result
5. Press the key “◄” or “►” to select synchronism check mode and press the key “ENT” to
the next step.
4) LoopCheck: Reserved
CSWI01
Step3: select Execution Condition
InterlockChk InterlockNotChk
Result
6. Press the key “◄” or “►” to select interlock mode and press the key “ENT” to next step.
CSWI01
Step4: select Interlock Condition
InterlockChk InterLockNotChk
Result
7. Press the key “◄” or “►” to select control type and press the key “ENT”.
As shown in the following figure, operation results will be shown after “Result” at the bottom of the
LCD.
CSWI01
Step5: select Control Type
InterlockChk InterLockNotChk
Result
NOTICE!
An example of normal display with SLD is shown in the following figure. The single line diagram of
the default display on the LCD is shown as below when the device is in normal situation, if this
device adopts the single line diagram as default display.
Bus1
Bus2
M011 M0112
M0131
M01
M0151
M0171
Feeder M01
Press key “▼” continuously to select a circuit breaker or a switch which will be opened or closed.
Then press key “ENT” to start to control the selected circuit breaker or switch. If it is the first time to
do control operation after a long time, it needs to input a correct password. The control operation
window will be valid for 150s after inputting correct password. The password for control operation
is fixed, and it is “111”.
Bus1
Bus2
M011 M0112
M0131
M01
M0151
M0171 Password:
Feeder M01 000
After inputting correct password, press key “ENT” to control the selected circuit breaker or switch.
Press key “▼” continuously to select the expected circuit breaker or switch with closed position,
and then press key “ENT” to start to open the selected circuit breaker or switch.
Bus1
Bus2
M011 M0112
M0131
M01
M0151
M0171
Feeder M01 Open Close?
Bus1
Bus2
M011 M0112
M0131
M01
M0151
M0171
Feeder M01 Op Success
2. Press the “▲” or “▼” to move the cursor to the “Clock” menu, and then press the “ENT” to
enter clock display
3. Press the “▲” or “▼” to move the cursor to the date or time to be modified;
4. Press the “+” or “-” to modify value, and then press the “ENT” to save the modification and
return to the main menu;
5. Press the “ESC” to cancel the modification and return to the main menu.
NOTICE!
Move the cursor to select the item “Format” to setup time display format. Press the “+”
or “-” to modify from the following options.
2. YYYY/MM/dd
3. DD-MM-YYYY
4. DD/MM/YYYY
5. MM-DD-YYYY
6. MM/DD/YYYY
Clock
Year: 2008
Month: 11
Day: 28
Hour: 20
Minute: 59
Format: YYYY/MM/DD
2. Press the “▲” or “▼” to move the cursor to the “Information” menu, and then press the “ENT”
or “►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to the command menu “Board Info”, and then press
the “ENT” to enter the menu;
5. Press the “ENT” or “ESC” to exit this menu (returning to the “Information” menu).
2. Press the “▲” or “▼” to move the cursor to the “Information” menu, and then press the “ENT”
3. Press the key “▲” or “▼” to move the cursor to the command menu “Version Info”, and then
press the key “ENT” to display the software version.
2. Press the key “▲” or “▼” to move the cursor to the “Test” menu, and then press the key
“ENT” or “►” to enter the menu.
3. Press the key “▲” or “▼” to move the cursor to the submenu “Device Test”, and then press
the key “ENT” to enter the submenu, to select test item. If “Disturb Events” “Superv Events”
or “IO Events” is selected, two options “All Test” and “Select Test” are provided.
Prot Element
All Test
Select Test
4. Press the key “▲” or “▼” to move the cursor to select the corresponding command menu “All
Test” or “Select Test”. If selecting the “All Test”, press the “ENT”, and the device will
successively carry out all operation element message test one by one.
5. If “Select Test” is selected, press the key “ENT”. Press the “+” or “-” to page up/down, and
then press the key “▲” or “▼” to move the scroll bar. Move the cursor to select the
corresponding protection element. Press the key “ENT” to execute the communication test of
this protection element, the substation automatic system (SAS) will receive the corresponding
message.
NOTICE!
If no input operation is carried out within 60s, exit the communication transmission and
return to the “Test” menu, at this moment, the LCD will display “Communication Test
Timeout and Exiting...”.
Press the key “ESC” to exit this menu (returning to the menu “Test”, at this moment, the LCD will
display “Communication Test Exiting…”.
2. Press the key “▲” or “▼” to move the cursor to the command menu “Language”, and then
press the key “ENT” to enter the menu and the following display will be shown on LCD.
1 中文
2 English
3 XXXX
3. Press the key “▲” or “▼” to move the cursor to the language user preferred and press the key
“ENT” to execute language switching. After language switching is finished, LCD will return
to the menu “Language”, and the display language is changed. Otherwise, press the key
“ESC” to cancel language switching and return to the menu “Language”.
NOTICE!
LCD interface provided in this chapter is only a reference and available for explaining
specific definition of LCD. The displayed interface of the actual device may be some
different from it, so you shall be subject to the actual protection device.
9 Configurable Function
Table of Contents
List of Figures
List of Tables
After function configuration is finished, disabled protection function will be hidden in the device and
in setting configuration list of PCS-Explorer Software. The user can select to show or hide some
setting by this way, and modify the setting value.
Please refer to the instruction manual “PCS-Explorer Auxiliary Software” for details.
Overall functions:
9.3.1 Overview
Generic Object Oriented Substation Event (GOOSE) is the mechanism in IEC61850 standard
used to satisfy fast message demand of substation automation system, and provides means of
fast information transmission and exchange under network communication conditions. In case of
any status change, intelligent electronic device (IED) will use change report to transmit binary
objects in high speed, i.e. GOOSE report. Information exchange among IEDs is realized by
GOOSE.
PCS-900 series features GOOSE network message interface independent of MMS message
interface and of high real-time property. Therefore, PCS-900 series can receive binary inputs via
opto-coupler and send output commands via binary output contact, as well as GOOSE input
signals, and can configure GOOSE output commands and GOOSE output signals. Configuration
of GOOSE signals is obtained by GOOSE file based on SCD file.
PCS-900 series supports single network mode and dual network mode, P2P mode and networking
mode, as well as mode based on station level network MMS or process level network. Networking
mode can be selected by parameters setup or configuration tool PCS-Explorer. For important
occasions, in order to ensure no loss of data during transmission, it is recommended to configure
dual GOOSE network in which process level is independent of station level for the protection
device. Refer to the figure as below.
Control Center
……
Protocol Converter
Third-Party IEDs
Switch Process Bus: Sampled Value, GOOSE (Tripping/Binary Input), IEEE 1588, GMRP Clock Synchronization
PCS-221 PCS-222
Process Level Merging Unit Circuit Breaker Controller
Optical Fiber ……
Electronic/Optical CT & VT
Circuit Breaker: GIS/AIS
The above figure shows a typical dual network mode, in which process level network is separate
from station level network, to ensure that important information (e.g. tripping signal) is not affected
Ring network is not recommended for GOOSE network configuration, to avoid the problem of
network storm. Duplicated protection configuration and their GOOSE networks shall be totally
independent of each other, to ensure that in case of any network fault in one set of duplicated
protection configuration, the other set will not be affected.
Normally, manufacturers provide ICD file, system integrator prepare SCD file of the whole
substation according to design blueprints, and each IED manufacturer exports its CID file after
receiving SCD configuration model.
GOOSE service is directly mapped to network data link layer. To ensure important information
transmission priority, broadcast address is used for multi-channle transmission of information.
GOOSE message allows high-speed transmission of tripping signals, which has high transmission
success rate.
GOOSE message is not sent at fixed interval. When there is no GOOSE event, interval of GOOSE
message transmission is fixed and relatively long. However, after an event occurs, data
transmission will change, and the interval set for this occasion is the shortest. GOOSE adopts
continual repeated transmission to realize reliable transmission, and during this period,
transmission interval will gradually increase, till the event status becomes stable. Later, GOOSE
message transmission will be back to fixed interval. The whole process is shown as below:
Transmission Time
Event
Where:
T0 is retransmission in stable conditions (no event for a long time), and it can be configured
(typical value is 5000ms)
T1 is the shortest retransmission time after the event, and it can be configured (typical value is
2ms)
T2 is retransmission times until achieving the stable conditions time, and it is fixed at 2T1.
T3 is retransmission times until achieving the stable conditions time, and it is fixed at 4T1.
GOOSE transmission adopts retransmission mechanism and has 4 transmission times: T0, T1, T2,
and T3. After the event occurs, a frame message will be transmitted, transmitting again after
interval T1, and still transmitting after another interval T1. And then, transmitting again after
interval T2 and yet transmitting after interval T3. At this time, if no new event occurs, transmission
will continue at interval T0 again.
Data transmitted are defined by definition of GOOSE transmission dataset and GOOSE control
blocks. PCS-900 series supports transmission of 8 GOOSE control blocks at maximum. GOOSE
can transmit both binary quantities and analog quantities of not large change, e.g. temperature
and humidity.
At maximum, PCS-900 series can receive 128 control block data, subject to control by GOOSE
Links. GOOSE reception control block is controlled by GOOSE links of corresponding serial
number, and provides corresponding alarm signal of the same serial number.
After the receiver receives GOOSE data, if GOOSE data is invalid (refer to section 9.3.2.3), the
GOOSE data shall be processed accordingly, i.e. clear (zero), force to 1, or keep.
1. The next frame of GOOSE message is not received within 1.1 times of maximum message
survival time
NOTICE!
Each frame of transmitted GOOSE data includes maximum message survival time,
normally 2 times of GOOSE heartbeat time (t0).
“Test” state of GOOSE message is set to 1 if the reception control block receives
message with “Test” bit, otherwise it is set to 0 if message without “Test” bit is received.
If GOOSE message is not received within 2 times of maximum message survival time, GOOSE
link disconnection will be reported. For example, receiver sets GOOSE heartbeat time (t0) to 5s,
so that specified message survival time in transmitted message is 10s. After GOOSE receives one
frame of message, if the next frame is not received within 11s, , GOOSE data is invalid. If not
received in 20s (2 times of message survival time), GOOSE link disconnection will be reported.
If invalid data or data link disconnection is tested by unplugging network wire, note that since
network line disconnection occurs at any time between two groups of heartbeat messages, invalid
GOOSE data is normally reported in 6~11s after actual disconnection, and GOOSE network link
disconnection is normally reported in 15~20s after actual disconnection.
NOTICE!
Invalid GOOSE data is not synchronized with GOOSE link disconnection in time. The
former is reported when message is not received within 1.1 times maximum message
survival time, while the latter is only reported when message is not received within 2
times maximum message survival time.
This device features fast detection of network storm and fast handling of network messages. In
case of network storm in single network, this device can ensure no loss of normal network
messages, and protection functions will not be affected.
In case of network storm in dual network, this device can maintain reception and handling of
messages in one of the networks, and actual test has shown that protection functions are basically
not affected.
GOOSE reception and transmission message provide a “Test” bit. The receiver will compare this
“Test” bit in received message with its own “Test” bit. If they are consistent, operation will occur,
otherwise, invalid GOOSE data will be reported (refer to section 9.3.2.3). This eliminates mutual
effect between device in operation and device in maintainence.
Different from traditional contact signals, which can can be set to enable/disable corresponding
signals, PCS-900 series adopts the following modes to enable and disable corresponding signals
including “Test” state.
1. When the “Test” bit in GOOSE message is consistent with the “Test” of the receiver, GOOSE
data is valid, otherwise it is invalid (refer to section 9.3.2.3). In this way, the device in service
and device in maintainence do not affect each other.
2. In “Test” state, the receiver still has event recording and state display functions, to facilitate
check of circuit.
3. GOOSE logic link is provided to solve the problem of selective transmission of signals.
Transmitter can be isolated from receiver by disabling relevant GOOSE logic link. The setup
of transmission and reception logic links can be consistent with traditional logic links.
4. For transmitter, GOOSE element will perform AND of data value and transmission logic link
state, and then detect change of data, so as to decide activation of a new round of
transmission flow.
All input signals for this device are listed in the following table.
If an input signal is gray in PCS-Explorer, it means the input signal is not configurable. If a input
signal is dark in PCS-Explorer, it means the input signal is configurable.
If a output signal is gray in PCS-Explorer, it means the output signal is not configurable. If a output
signal is dark in PCS-Explorer, it means the output signal is configurable.
[25.U_Dd]
Synchronism voltage is greater than the voltage threshold of live check
19 25.Chk_LvB
[25.U_Lv]
Synchronism voltage is smaller than the voltage threshold of dead check
20 25.Chk_DdB
[25.U_Dd]
21 25.Ok_DdChk To indicate that dead charge check condition of AR is met
22 25.Ok_SynChk To indicate that synchronism check condition of AR is met
23 25.Ok_Chk To indicate that synchrocheck condition of AR is met
24 25.Ok_3PLvChk To indicate that live three-phase check condition is met
25 25.Alm_VTS_Uref Reference voltage circuit is abnormal
26 25.Alm_VTS_Usyn Synchronism voltage circuit is abnormal
Auto-reclosure
1 79.On Automatic reclosure is enabled
2 79.Off Automatic reclosure is disabled
3 79.Close Output of auto-reclosing signal
4 79.Ready Automatic reclosure have been ready for reclosing cycle
5 79.AR_Blkd Automatic reclosure is blocked
6 79.Active Automatic reclosing logic is actived
7 79.Inprog Automatic reclosing cycle is in progress
8 79.Inprog_1P The first 1-pole AR cycle is in progress
9 79.Inprog_3P 3-pole AR cycle is in progress
10 79.Inprog_3PS1 First 3-pole AR cycle is in progress
11 79.Inprog_3PS2 Second 3-pole AR cycle is in progress
12 79.Inprog_3PS3 Third 3-pole AR cycle is in progress
13 79.Inprog_3PS4 Fourth 3-pole AR cycle is in progress
Waiting signal of automatic reclosing which will be sent to slave (when
14 79.WaitToSlave
reclosing multiple circuit breakers)
15 79.Perm_Trp1P Single-phase circuit breaker will be tripped once protection device operates
16 79.Perm_Trp3P Three-phase circuit breaker will be tripped once protection device operates
10 Communication
Table of Contents
10 Communication ............................................................................. 10-a
10.1 Overview ...................................................................................................... 10-1
10.2 Rear Communication Port Information ..................................................... 10-1
10.2.1 RS-485 Interface.............................................................................................................. 10-1
List of Figures
Figure 10.2-1 EIA RS-485 bus connection arrangements ..................................................... 10-2
Figure 10.4-1 Dual-net full duplex mode sharing the RCB block instance ......................... 10-9
Figure 10.4-2 Dual-net hot-standby mode sharing the same RCB instance ..................... 10-10
Figure 10.4-3 Dual-net full duplex mode with 2 independent RCB instances .................. 10-11
10.1 Overview
This section outlines the remote communications interfaces of NR Relays. The protective device
supports a choice of three protocols via the rear communication interface (RS-485 or Ethernet),
selected via the model number by setting. The protocol provided by the protective device is
indicated in the menu “Settings→Device Setup→Comm Settings”.
The rear EIA RS-485 interface is isolated and is suitable for permanent connection of whichever
protocol is selected. The advantage of this type of connection is that up to 32 protective devices
can be “daisy chained” together using a simple twisted pair electrical connection.
It should be noted that the descriptions contained within this section do not aim to fully detail the
protocol itself. The relevant documentation for the protocol should be referred to for this
information. This section serves to describe the specific implementation of the protocol in the relay.
The EIA RS-485 two-wire connection provides a half-duplex fully isolated serial connection to the
product. The connection is polarized and whilst the product’s connection diagrams indicate the
polarization of the connection terminals it should be borne in mind that there is no agreed
definition of which terminal is which. If the master is unable to communicate with the product, and
the communication parameters match, then it is possible that the two-wire connection is reversed.
The EIA RS-485 bus must have 120Ω (Ohm) ½ Watt terminating resistors fitted at either end
across the signal wires (refer to Figure 10.2-1). Some devices may be able to provide the bus
terminating resistors by different connection or configuration arrangements, in which case
separate external components will not be required. However, this product does not provide such a
facility, so if it is located at the bus terminus then an external termination resistor will be required.
EIA RS-485
Master 120 Ohm
120 Ohm
The EIA RS-485 standard requires that each device is directly connected to the physical cable that
is the communications bus. Stubs and tees are expressly forbidden, such as star topologies. Loop
bus topologies are not part of the EIA RS-485 standard and are forbidden by it also.
Two-core screened cable is recommended. The specification of the cable will be dependent on the
application, although a multi-strand 0.5mm 2 per core is normally adequate. Total cable length must
not exceed 500m. The screen must be continuous and connected to ground at one end, normally
at the master connection point; it is important to avoid circulating currents, especially when the
cable runs between buildings, for both safety and noise reasons.
This product does not provide a signal ground connection. If a signal ground connection is present
in the bus cable then it must be ignored, although it must have continuity for the benefit of other
devices connected to the bus. At no stage must the signal ground be connected to the cables
screen or to the product’s chassis. This is for both safety and noise reasons.
10.2.1.4 Biasing
It may also be necessary to bias the signal wires to prevent jabber. Jabber occurs when the signal
level has an indeterminate state because the bus is not being actively driven. This can occur when
all the slaves are in receive mode and the master is slow to turn from receive mode to transmit
mode. This may be because the master purposefully waits in receive mode, or even in a high
impedance state, until it has something to transmit. Jabber causes the receiving device(s) to miss
the first bits of the first character in the packet, which results in the slave rejecting the message
and consequentially not responding. Symptoms of these are poor response times (due to retries),
increasing message error counters, erratic communications, and even a complete failure to
communicate.
Biasing requires that the signal lines be weakly pulled to a defined voltage level of about 1V. There
should only be one bias point on the bus, which is best situated at the master connection point.
The DC source used for the bias must be clean; otherwise noise will be injected. Note that some
devices may (optionally) be able to provide the bus bias, in which case external components will
not be required.
NOTICE!
It is extremely important that the 120Ω termination resistors are fitted. Failure to do so
will result in an excessive bias voltage that may damage the devices connected to the
bus.
As the field voltage is much higher than that required, NR cannot assume responsibility
for any damage that may occur to a device connected to the network as a result of
incorrect application of this voltage.
Ensure that the field voltage is not being used for other purposes (i.e. powering logic
inputs) as this may cause noise to be passed to the communication network.
It is recommended to use twisted screened eight-core cable as the communication cable. A picture
is shown bellow.
Each equipment is connected with an exchanger via communication cable, and thereby it forms a
star structure network. Dual-network is recommended in order to increase reliability. SCADA is
also connected to the exchanger and will play a role of master station, so the every equipment
which has been connected to the exchanger will play a role of slave unit.
SCADA
Switch: Net A
Switch: Net B
……
To use the rear port with IEC60870-5-103 communication, the relevant settings to the protective
device must be configured.
The IEC60870-5-103 interface over serial port (RS-485) is a master/slave interface with the
protective device as the slave device. It is properly developed by NR.
Initialization (reset)
Time synchronization
General interrogation
General commands
Disturbance records
The link layer strictly abides by the rules defined in the IEC60870-5-103.
10.3.2 Initialization
Whenever the protective device has been powered up, or if the communication parameters have
been changed, a reset command is required to initialize the communications. The protective
device will respond to either of the two reset commands (Reset CU or Reset FCB), the difference
is that the Reset CU will clear any unsent messages in the transmit buffer.
The protective device will respond to the reset command with an identification message ASDU 5,
the COT (Cause Of Transmission) of this response will be either Reset CU or Reset FCB
depending on the nature of the reset command.
If the protective device clock is synchronized using the IRIG-B input then it will not be possible to
set the protective device time using the IEC60870-5-103 interface. An attempt to set the time via
the interface will cause the protective device to create an event with the current date and time
taken from the IRIG-B synchronized internal clock.
status of binary signal and alarm element are sent by ASDU1 (time-tagged message). The cause
of transmission (COT) of these responses is 1.
All spontaneous events can be gained by printing, implementing submenu “IEC103 Info” in the
menu “Print”.
Refer the IEC60870-5-103 standard can get the enough details about general interrogation.
All general classification service group numbers can be gained by printing, implementing submenu
“IEC103 Info” in the menu “Print”.
The disturbance records are stored in uncompressed format and can be extracted using the
standard mechanisms described in IEC60870-5-103.
All channel numbers (ACC) of disturbance data can be gained by printing, implementing submenu
“IEC103 Info” in the menu “Print”.
10.4.1 Overview
The IEC 61850 standard is the result of years of work by electric utilities and vendors of electronic
equipment to produce standardized communications systems. IEC 61850 is a series of standards
describing client/server and peer-to-peer communications, substation design and configuration,
testing, environmental and project standards. The complete set includes:
IEC 61850-5: Communications and requirements for functions and device models
IEC 61850-7-1: Basic communication structure for substation and feeder equipment–
Principles and models
IEC 61850-7-2: Basic communication structure for substation and feeder equipment - Abstract
communication service interface (ACSI)
IEC 61850-7-3: Basic communication structure for substation and feeder equipment–
Common data classes
IEC 61850-7-4: Basic communication structure for substation and feeder equipment–
Compatible logical node classes and data classes
IEC 61850-8-1: Specific Communication Service Mapping (SCSM) – Mappings to MMS (ISO
9506-1 and ISO 9506-2) and to ISO/IEC 8802-3
IEC 61850-9-1: Specific Communication Service Mapping (SCSM) – Sampled values over
serial unidirectional multidrop point to point link
IEC 61850-9-2: Specific Communication Service Mapping (SCSM) – Sampled values over
ISO/IEC 8802-3
These documents can be obtained from the IEC (http://www.iec.ch). It is strongly recommended
that all those involved with any IEC 61850 implementation obtain this document set.
1. MMS protocol
IEC 61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper
(application) layer for transfer of real-time data. This protocol has been in existence for a number
of years and provides a set of services suitable for the transfer of data within a substation LAN
environment. IEC 61850-7-2 abstract services and objects are mapped to actual MMS protocol
services in IEC61850-8-1.
2. Client/server
This is a connection-oriented type of communication. The connection is initiated by the client, and
communication activity is controlled by the client. IEC61850 clients are often substation computers
running HMI programs or SOE logging software. Servers are usually substation equipment such
as protection relays, meters, RTUs, transformer, tap changers, or bay controllers.
3. Peer-to-peer
A substation configuration language is a number of files used to describe IED configurations and
communication systems according to IEC 61850-5 and IEC 61850-7. Each configured device has
an IED Capability Description (ICD) file and a Configured IED Description (CID) file. The
substation single line information is stored in a System Specification Description (SSD) file. The
entire substation configuration is stored in a Substation Configuration Description (SCD) file. The
SCD file is the combination of the individual ICD files and the SSD file, moreover, add
communication system parameters (MMS, GOOSE, control block, SV control block) and the
connection relationship of GOOSE and SV to SCD file.
Client-server mode is adopted: clients (SCADA, control center and etc.) communicate with the
IEDs via MMS communication network, and the IEDs operate as the servers. IEDs are connected
to clients passively, and they can interact with the clients according to the configuration and the
issued command of the clients.
Three modes for dual-MMS Ethernet (abbreviated as dual-net) are provided as below.
NOTICE!
Hereinafter, the normal operation status of net means the physical link and TCP link are
both ok. The abnormal operation status of net means physical link or TCP link is
broken.
10.4.3.1 Dual-net Full Duplex Mode Sharing the Same RCB Instance
Client Client
Figure 10.4-1 Dual-net full duplex mode sharing the RCB block instance
Net A and Net B share the same report control block (abbreviated as RCB) enabled by the client.
IED sends undifferentiated date through dual-net to the clients. If one net is physically
disconnected, the flag of RCB instance (i.e.: “RptEna” in above figure) is still “true”. Only when
both Net A and Net B are disconnected, the flag of the RCB instance will automatically change to
“false”.
In normal operation status of this mode, IED provides the same MMS service for Net A and Net B.
If one net is physically disconnected (i.e.: “Abnormal operation status” in above figure), the
working mode will switch to single-net mode seamlessly and immediately. Network communication
supervision is unnecessary here, and Buffered Report Control Block (abbreviated as BRCB) need
not to be used. On the other net, date alternation works normally. Therefore, MMS service can
interact normally without interruption. This mode ensures no data loss during one net is in
abnormal operation status.
In this mode, one report will be transmitted twice via dual nets for the same report instance, so the
client needs to distinguish whether two reports are same according to corresponding EntryIDs.
Client Client
Figure 10.4-2 Dual-net hot-standby mode sharing the same RCB instance
In this mode, the MMS service is provided on main MMS link, no MMS service interacts on the
standby MMS link. The definitions of two links are as follows:
Main MMS Link: Physically connected, TCP level connected, MMS report service available.
Standby MMS Link: Physically connected, TCP level connected, MMS report service not
available.
If the main net fails to operate (i.e.: “Abnormal operation status” in the above figure), the IED will
set “RptEna” to “false”. Meanwhile the client will detect the failure by heartbeat message or
“keep-alive”, it will automatically enable the RCB instance by setting “RptEna” back to “true”
through standby MMS link. By the buffer function of BRCB, the IED can provide uninterrupted
MMS service on the standby net. However, the differences of BRCB standards among different
manufacturers may cause data loss. Moreover, if duration of net switch is too long, the data loss is
positively as the capacity of BRCB’s buffer function is limited.
NOTICE!
The first mode and second mode, Net A IED host address and Net B IED host address
must be the same.
Client Client
Figure 10.4-3 Dual-net full duplex mode with 2 independent RCB instances
In this mode, IED provides 2 report instances for each RCB, Net A and Net B work independently
from each other, failures of any net will not affect the other net at all. Tow report instances are
required for each client. Therefore, the IED may be unable to provide enough report instances if
there are too many clients.
Net A and Net B send the same report separately when they operates normally, To ensure no
repeated data is saved into database, massive calculation is required for the client.
Moreover, accurate clock synchronization of the IED is required to distinguish whether 2 reports
are the same report according to the timestamps. Clock synchronization error of the IED may lead
to report loss/redundancy.
As a conclusion, for the second mode, it’s difficult to realize seamless switchover between dual
nets, however, for the third mode, the IED may be unable to provide enough report instances if too
many clients are applied on site. Considering client treatment and IED implementation, the first
mode (Dual-net full duplex mode sharing the same report instance) is recommended for MMS
communication network deployment.
Each IED represents one IEC61850 physical device. The physical device contains one or more
logical device(s), and the logical device contains many logical nodes. The logical node LPHD
contains information about the IED physical device. The logical node LLN0 contains common
The GGIO logical node is available in the PCS-900 series relays to provide access to digital status
points (including general I/O inputs and warnings) and associated timestamps and quality flags.
The data content must be configured before the data can be used. GGIO provides digital status
points for access by clients. It is intended that clients use GGIO in order to access digital status
values from the PCS-900 series relays. Clients can utilize the IEC61850 buffered reporting
features available from GGIO in order to build sequence of events (SOE) logs and HMI display
screens. Buffered reporting should generally be used for SOE logs since the buffering capability
reduces the chances of missing data state changes. All needed status data objects are transmitted
to HMI clients via buffered reporting, and the corresponding buffered reporting control block
(BRCB) is defined in LLN0.
Most of analog measured values are available through the MMXU logical nodes, and metering
values in MMTR, the else in MMXN, MSQI and so on. Each MMXU logical node provides data
from a IED current/voltage “source”. There is one MMXU available for each configurable source.
MMXU1 provides data from CT/VT source 1(usually for protection purpose), and MMXU2 provides
data from CT/VT source 2 (usually for monitor and display purpose). All these analog data objects
are transmitted to HMI clients via unbuffered reporting periodically, and the corresponding
unbuffered reporting control block (URCB) is defined in LLN0. MMXUx logical nodes provide the
following data for each source:
MMXU.MX.Hz: frequency
The following list describes the protection elements for PCS-921 series relays. The specified relay
will contain a subset of protection elements from this list.
PTUV: Undervoltage
PTOV: Overvoltage
PTOF: Overfrequency
PTUF: Underfrequency
RBRF:Breaker failure
RSYN: Synchronism-check
The protection elements listed above contain start (pickup) and operate flags, instead of any
element has its own start (pickup) flag separately, all the elements share a common start (pickup)
flags “PTRC.ST.Str.general”. The operate flag for PTOC1 is “PTOC1.ST.Op.general”. For
PCS-921 series relays protection elements, these flags take their values from related module for
the corresponding element. Similar to digital status values, the protection trip information is
reported via BRCB, and BRCB also locates in LLN0.
Logical node LLN0 is essential for an IEC61850 based IED. This LN shall be used to address
common issues for Logical Devices. Most of the public services, the common settings, control
values and some device oriented data objects are available here. The public services may be
BRCB, URCB and GSE control blocks and similar global defines for the whole device; the
common settings include all the setting items of communication settings, system settings and
some of the protection setting items, which can be configured to two or more protection elements
(logical nodes). In LLN0, the item Loc is a device control object, this Do item indicates the local
operation for complete logical device, when it is true, all the remote control commands to the IED
will be blocked and those commands make effective until the item Loc is changed to false. In
PCS-900 series relays, besides the logical nodes we describe above, there are some other logical
nodes below in the IEDs:
MMXU: This LN shall be used to acquire values from CTs and VTs and calculate measurands
such as r.m.s. values for current and voltage or power flows out of the acquired voltage and
current samples. These values are normally used for operational purposes such as power
flow supervision and management, screen displays, state estimation, etc. The requested
accuracy for these functions has to be provided.
LPHD: Physical device information, the logical node to model common issues for physical
device.
PTRC: Protection trip conditioning, it shall be used to connect the “operate” outputs of one or
more protection functions to a common “trip” to be transmitted to XCBR. In addition or
alternatively, any combination of “operate” outputs of protection functions may be combined to
RDRE: Disturbance recorder function. It triggers the fault wave recorder and its output refers
to the “IEEE Standard Format for Transient Data Exchange (COMTRADE) for Power System”
(IEC 60255-24). All enabled channels are included in the recording, independently of the
trigger mode.
IEC61850 buffered and unbuffered reporting control blocks locate in LLN0, they can be configured
to transmit information of protection trip information (in the Protection logical nodes), binary status
values (in GGIO) and analog measured/calculated values (in MMXU, MMTR and MSQI). The
reporting control blocks can be configured in CID files, and then be sent to the IED via an
IEC61850 client. The following items can be configured.
- Bit 1: Data-change
- Bit 4: Integrity
- Bit 1: Sequence-number
- Bit 2: Report-time-stamp
- Bit 3: Reason-for-inclusion
- Bit 4: Data-set-name
- Bit 5: Data-reference
- Bit 8: Conf-revision
- Bit 9: Segmentation
MMS file services are supported to allow transfer of oscillography, event record or other files from
a PCS-900 series relay.
10.4.5.3 Timestamps
The Universal Time Coordinated(UTC for short) timestamp associated with all IEC61850 data
items represents the latest change time of either the value or quality flags of the data item.
IEC61850 specifies that each logical node can have a name with a total length of 11 characters.
The name is composed of:
Complete names are of the form xxxxxxPTOC1, where the xxxxxx character string is configurable.
Details regarding the logical node naming rules are given in IEC61850 parts 6 and 7-2. It is
recommended that a consistent naming convention be used for an entire substation project.
IEC61850 specifies the type of broadcast data transfer services: Generic Object Oriented
Substation Events (GOOSE). IEC61850 GOOSE services provide virtual LAN (VLAN) support,
Ethernet priority tagging, and Ether-type Application ID configuration. The support for VLANs and
priority tagging allows for the optimization of Ethernet network traffic. GOOSE messages can be
given a higher priority than standard Ethernet traffic, and they can be separated onto specific
VLANs. Devices that transmit GOOSE messages also function as servers. Each GOOSE
publisher contains a “GOOSE control block” to configure and control the transmission.
The GOOSE transmission (including subscribing and publishing) is controlled by GOOSE logic link
settings in device.
The PCS-900 series relays support IEC61850 Generic Object Oriented Substation Event (GOOSE)
communication. All GOOSE messages contain IEC61850 data collected into a dataset. It is this
dataset that is transferred using GOOSE message services. The GOOSE related dataset is
configured in the CID file and it is recommended that the fixed GOOSE be used for
implementations that require GOOSE data transfer between PCS-900 series relays.
IEC61850 GOOSE messaging contains a number of configurable parameters, all of which must be
correct to achieve the successful transfer of data. It is critical that the configured datasets at the
transmission and reception devices are an exact match in terms of data structure, and that the
GOOSE addresses and name strings match exactly.
Client-Server roles
SCSMs supported
M1 Logical device N Y
M2 Logical node N Y
M3 Data N Y
M4 Data set N Y
M5 Substitution N Y
Reporting
M7-1 sequence-number N Y
M7-2 report-time-stamp N Y
M7-3 reason-for-inclusion N Y
M7-4 data-set-name N Y
M7-5 data-reference N Y
M7-6 buffer-overflow N Y
M7-7 entryID N Y
M7-8 BufTm N Y
M7-9 IntgPd N Y
M7-10 GI N Y
M7-11 conf-revision N Y
M8-1 sequence-number N Y
M8-2 report-time-stamp N Y
M8-3 reason-for-inclusion N Y
M8-4 data-set-name N Y
M8-5 data-reference N Y
M8-6 BufTm N Y
M8-7 IntgPd N Y
M8-8 GI N Y
M8-9 conf-revision N Y
Logging N N
M9 Log control N N
M9-1 IntgPd N N
M10 Log N N
M11 Control N Y
M12 GOOSE Y Y
M13 GSSE N N
Y = service is supported
Server
S1 GetServerDirectory TP N Y
Application association
S2 Associate N Y
S3 Abort N Y
S4 Release N Y
Logical device
S5 GetLogicalDeviceDirectory TP N Y
Logical node
S6 GetLogicalNodeDirectory TP N Y
S7 GetAllDataValues TP N Y
Data
S8 GetDataValues TP N Y
S9 SetDataValues TP N Y
S10 GetDataDirectory TP N Y
S11 GetDataDefinition TP N Y
Data set
S12 GetDataSetValues TP N Y
S13 SetDataSetValues TP N N
S14 CreateDataSet TP N N
S15 DeleteDataSet TP N N
S16 GetDataSetDirectory TP N Y
Substitution
S17 SetDataValues TP N Y
S18 SelectActiveSG TP N Y
S19 SelectEditSG TP N Y
S20 SetSGValues TP N Y
S21 ConfirmEditSGValues TP N Y
S22 GetSGValues TP N Y
S23 GetSGCBValues TP N Y
Reporting
S24 Report TP N Y
S25 GetBRCBValues TP N Y
S26 SetBRCBValues TP N Y
S27 Report TP N Y
S28 GetURCBValues TP N Y
S29 SetURCBValues TP N Y
Logging
S30 GetLCBValues TP N N
S31 SetLCBValues TP N N
Log
S32 QueryLogByTime TP N N
S33 QueryLogAfter TP N N
S34 GetLogStatusValues TP N N
GOOSE-CONTROL-BLOCK
S35 SendGOOSEMessage MC N Y
S36 GetGoReference TP N Y
S37 GetGOOSEElementNumber TP N N
S38 GetGoCBValues TP N Y
S39 SetGoCBValues TP N N
GSSE-CONTROL-BLOCK
S40 SendGSSEMessage MC N N
S41 GetReference TP N N
S42 GetGSSEElementNumber TP N N
S43 GetGsCBValues TP N N
S44 SetGsCBValues TP N N
Multicast SVC
S45 SendMSVMessage MC N N
S46 GetMSVCBValues TP N N
S47 SetMSVCBValues TP N N
Unicast SVC
S48 SendUSVMessage TP N N
S49 GetUSVCBValues TP N N
S50 SetUSVCBValues TP N N
Control
S51 Select N N
S52 SelectWithValue TP N Y
S53 Cancel TP N Y
S54 Operate TP N Y
S55 CommandTermination TP N Y
S56 TimeActivatedOperate TP N N
File transfer
S57 GetFile TP N Y
S58 SetFile TP N N
S59 DeleteFile TP N N
S60 GetFileAttributeValues TP N Y
Time
IARC: Archiving -
IHMI: Human machine interface -
ITCI: Telecontrol interface -
ITMI: Telemonitoring interface -
A: Logical Nodes For Automatic Control
ANCR: Neutral current regulator -
ARCO: Reactive power control -
ATCC: Automatic tap changer controller -
AVCO: Voltage control -
M: Logical Nodes For Metering And Measurement
MDIF: Differential measurements -
MHAI: Harmonics or interharmonics -
MHAN: Non phase related harmonics or interharmonic -
MMTR: Metering -
MMXN: Non phase related measurement YES
MMXU: Measurement YES
MSQI: Sequence and imbalance YES
MSTA: Metering statistics -
S: Logical Nodes For Sensors And Monitoring
SARC: Monitoring and diagnostics for arcs -
SIMG: Insulation medium supervision (gas) -
SIML: Insulation medium supervision (liquid) -
SPDC: Monitoring and diagnostics for partial discharges -
X: Logical Nodes For Switchgear
XCBR: Circuit breaker YES
XSWI: Circuit switch -
T: Logical Nodes For instrument transformers
TCTR: Current transformer YES
TVTR: Voltage transformer YES
Y: Logical Nodes For Power Transformers
YEFN: Earth fault neutralizer (Peterson coil) -
YLTC: Tap changer -
YPSH: Power shunt -
YPTR: Power transformer -
Z: Logical Nodes For Further Power System Equipment
ZAXN: Auxiliary network -
ZBAT: Battery -
ZBSH: Bushing -
ZCAB: Power cable -
ZCAP: Capacitor bank -
ZCON: Converter -
ZGEN: Generator -
10.5.1 Overview
The descriptions given here are intended to accompany this relay. The DNP3.0 protocol is not
described here; please refer to the DNP3.0 protocol standard for the details about the DNP3.0
implementation. This manual only specifies which objects, variations and qualifiers are supported
in this relay, and also specifies what data is available from this relay via DNP3.0.
The relay operates as a DNP3.0 slave and supports subset level 3 of the protocol, plus some of
the features from level 4. The DNP3.0 communication uses the Ethernet ports (electrical or optical)
at the rear side of this relay.
The supported object groups and object variations are show in the following table.
REQUEST RESPONSE
OBJECT GROUP & VARIATION Master may issue Master shall parse
Outstation shall parse Outstation may issue
Group Variation Function Qualifier Function Qualifier
Description
Number Number Code (DEC) Code (HEX) Code (DEC) Code (HEX)
1
00, 01
(read)
Binary Input: (start, stop)
1 0 22
Any Variation 06
(assign
(no range, or all)
class)
00, 01
Binary Input: 1 (start, stop) 129 00, 01
1 1
Packed format (read) 06 (response) (start, stop)
(no range, or all)
00, 01
Binary Input: 1 (start, stop) 129 00, 01
1 2
With flags (read) 06 (response) (start, stop)
(no range, or all)
06
Binary Input Event: 1 (no range, or all)
2 0
Any Variation (read) 07, 08
(limited qty)
06 129
Binary Input Event: 1 (no range, or all) (response) 17, 28
2 1
Without time (read) 07, 08 130 (index)
(limited qty) (unsol. resp)
06 129
Binary Input Event: 1 (no range, or all) (response) 17, 28
2 2
With absolute time (read) 07, 08 130 (index)
(limited qty) (unsol. resp)
06 129
Binary Input Event: 1 (no range, or all) (response) 17, 28
2 3
With relative time (read) 07, 08 130 (index)
(limited qty) (unsol. resp)
00, 01
Binary output: 1 (start, stop)
10 0
Any Variation (read) 06
(no range, or all)
REQUEST RESPONSE
OBJECT GROUP & VARIATION Master may issue Master shall parse
Outstation shall parse Outstation may issue
Group Variation Function Qualifier Function Qualifier
Description
Number Number Code (DEC) Code (HEX) Code (DEC) Code (HEX)
00, 01
Binary output: 1 (start, stop)
10 0
Any Variation (read) 06
(no range, or all)
Binary output: 2 00, 01
10 1
Packed format (write) (start, stop)
3
(select)
4 17, 28 129 echo of
Binary Command:
(operate) (index) (response) request
Control relay output
12 1 5
block
(direct op)
(CROB)
6
17, 28
(dir. op, no
(index)
ack)
1
00, 01
(read)
Analog Input: (start, stop)
30 0 22
Any Variation 06
(assign
(no range, or all)
class)
00, 01
Analog Input: 1 (start, stop) 129 00, 01
30 1
32-bit with flag (read) 06 (response) (start, stop)
(no range, or all)
00, 01
Analog Input: 1 (start, stop) 129 00, 01
30 2
16-bit with flag (read) 06 (response) (start, stop)
(no range, or all)
00, 01
Analog Input: 1 (start, stop) 129 00, 01
30 3
32-bit without flag (read) 06 (response) (start, stop)
(no range, or all)
00, 01
Analog Input: 1 (start, stop) 129 00, 01
30 4
16-bit without flag (read) 06 (response) (start, stop)
(no range, or all)
REQUEST RESPONSE
OBJECT GROUP & VARIATION Master may issue Master shall parse
Outstation shall parse Outstation may issue
Group Variation Function Qualifier Function Qualifier
Description
Number Number Code (DEC) Code (HEX) Code (DEC) Code (HEX)
00, 01
Analog Input:
1 (start, stop) 129 00, 01
30 5 Single-prec flt-pt
(read) 06 (response) (start, stop)
with flag
(no range, or all)
06
Analog Input Event: 1 (no range, or all)
32 0
Any Variation (read) 07, 08
(limited qty)
06 129
Analog Input Event: 1 (no range, or all) (response) 17,28
32 1
32-bit without time (read) 07, 08 130 (index)
(limited qty) (unsol. resp)
06 129
Analog Input Event: 1 (no range, or all) (response) 17,28
32 2
16-bit without time (read) 07, 08 130 (index)
(limited qty) (unsol. resp)
06 129
Analog Input Event:
1 (no range, or all) (response) 17,28
32 5 Single-prec flt-pt
(read) 07, 08 130 (index)
without time
(limited qty) (unsol. resp)
00, 01
Analog Input
1 (start, stop)
34 0 Deadband:
(read) 06
Any Variation
(no range, or all)
00, 01
1 (start, stop) 129 00, 01
(read) 06 (response) (start, stop)
Analog Input
(no range, or all)
34 1 Deadband:
00, 01
16-bit
2 (start, stop)
(write) 17,28
(index)
00, 01
Analog Input
1 (start, stop) 129 00, 01
34 2 Deadband:
(read) 06 (response) (start, stop)
32-bit
(no range, or all)
REQUEST RESPONSE
OBJECT GROUP & VARIATION Master may issue Master shall parse
Outstation shall parse Outstation may issue
Group Variation Function Qualifier Function Qualifier
Description
Number Number Code (DEC) Code (HEX) Code (DEC) Code (HEX)
00, 01
2 (start, stop)
(write) 17, 28
(index)
00, 01
1 (start, stop) 129 00, 01
(read) 06 (response) (start, stop)
Analog Input
(no range, or all)
34 3 Deadband:
00, 01
Single-prec flt-pt
2 (start, stop)
(write) 17, 28
(index)
00, 01
Analog Output
1 (start, stop)
40 0 Status:
(read) 06
Any Variation
(no range, or all)
00, 01
Analog Output
1 (start, stop) 129 00, 01
40 1 Status:
(read) 06 (response) (start, stop)
32-bit with flag
(no range, or all)
00, 01
Analog Output
1 (start, stop) 129 00, 01
40 2 Status:
(read) 06 (response) (start, stop)
16-bit with flag
(no range, or all)
Analog Output 00, 01
Status: 1 (start, stop) 129 00, 01
40 3
single-prec flt-pt with (read) 06 (response) (start, stop)
flag (no range, or all)
3
(select)
4 17, 28 129 echo of
(operate) (index) (response) request
Analog Output:
41 1 5
32-bit
(direct op)
6
17, 28
(dir. Op, no
(index)
ack)
REQUEST RESPONSE
OBJECT GROUP & VARIATION Master may issue Master shall parse
Outstation shall parse Outstation may issue
Group Variation Function Qualifier Function Qualifier
Description
Number Number Code (DEC) Code (HEX) Code (DEC) Code (HEX)
3
(select)
4 17,28 129 echo of
(operate) (index) (response) request
Analog Output:
41 2 5
16-bit
(direct op)
6
17, 28
(dir. Op, no
(index)
ack)
3
(select)
4 17,28 129 echo of
(operate) (index) (response) request
Analog Output:
41 3 5
Single-prec ft-pt
(direct op)
6
17, 28
(dir. Op, no
(index)
ack)
07
1 07 129
(limited
Time and Data: (read) (limited qty = 1) (response)
50 1 qty = 1)
Absolute time
2 07
(write) (limited qty = 1)
Time and Data:
2 07
50 3 Absolute time at last
(write) (limited qty = 1)
recorded time
129
Time and Data CTO: 07
(response)
51 1 Absolute time, (limited
130
synchronized qty = 1)
(unsol. resp)
129
Time and Data CTO: 07
(response)
51 2 Absolute time, (limited
130
unsynchronized qty = 1)
(unsol. resp)
1
(read)
Class Objects: 06
60 1 22
Class 0 data (no range, or all)
(assign
class)
REQUEST RESPONSE
OBJECT GROUP & VARIATION Master may issue Master shall parse
Outstation shall parse Outstation may issue
Group Variation Function Qualifier Function Qualifier
Description
Number Number Code (DEC) Code (HEX) Code (DEC) Code (HEX)
06
1 (no range, or all)
(read) 07, 08
(limited qty)
20
(enable
Class Objects:
60 2 unsol.)
Class 1 data
21
06
(disable
(no range, or all)
unsol.)
22
(assign
class)
06
1 (no range, or all)
(read) 07, 08
(limited qty)
20
(enable
Class Objects:
60 3 unsol.)
Class 2 data
21
06
(disable
(no range, or all)
unsol.)
22
(assign
class)
06
1 (no range, or all)
(read) 07, 08
(limited qty)
20
(enable
Class Objects :
60 4 unsol.)
Class 3 data
21
06
(disable
(no range, or all)
unsol.)
22
(assign
class)
This relay now supports 4 Ethernet clients and 2 serial port clients. Each client can be set the DNP
related communication parameters respectively and be selected the user-defined communication
table. This relay supports a default communication table and 4 user-defined communication tables,
and the default communication table is fixed by the manufacturer and not permitted to configure by
the user.
The user can configure the user-defined communication table through the PCS-Explorer
configuration tool auxiliary software. The object groups “Binary Input”, “Binary Output”, “Analog
Input” and “Analog Output” can be configured according to the practical engineering demand.
To the analog inputs, the attributes “deadband” and “factor” of each analog input can be configured
independently. To the analog outputs, only the attribute “factor” of each analog output needs to be
configured. If the integer mode is adopted for the data formats of analog values (to “Analog Input”,
“Object Variation” is 1, 2 and 3; to “Analog Output”, “Object Variation” is 1 and 2.), the analog
values will be multiplied by the “factor” respectively to ensure their accuracy. And if the float mode
is adopted for the data formats of analog values, the actual float analog values will be sent directly.
The judgment method of the analog input change is as below: Calculate the difference between
the current new value and the stored history value and make the difference value multiply by the
“factor”, then compare the result with the “deadband” value. If the result is greater than the
“deadband” value, then an event message of corresponding analog input change will be created.
In normal communication process, the master can online read or modify a “deadband” value by
reading or modifying the variation in “Group34”.
The remote control signals, logic links and external extended output commands can be configured
into the “Binary Output” group. The supported control functions are listed as below.
Information Point Pulse On/Null Pulse On/Close Pulse On/Trip Latch On/Null Latch Off/Null
Remote Control Not supported Close Trip Close Trip
Logic Link Not supported Set Clear Set Clear
Extended Output See following description
This relay does not transmit the unsolicited messages if the related logic setting is set as “0”. If the
unsolicited messages are transmitted, the related logic setting should be set as “1” firstly and then
the DNP3.0 master will transmit “Enable Unsolicited” command to this relay through “Function
Code 20” (Enable Unsolicited Messages). If the “Binary Input” state changes or the difference
value of the “Analog Input” is greater than the “deadband” value, this device will transmit
unsolicited messages. If the DNP3.0 master needs not to receive the unsolicited messages, it
should forbid this relay to transmit the unsolicited messages through “Function Code 21” (Disable
Unsolicited Messages).
If the DNP3.0 master calls the Class0 data, this relay will transmit all actual values of the “Analog
Input”, “Binary Input” and “Analog Output”. The classes of the “Analog Input” and “Binary Input”
can be defined by modifying relevant settings. In communication process, the DNP3.0 master can
online modify the class of an “Analog Input” or a “Binary Input” through “Function Code 22” (Assign
Class).
11 Installation
Table of Contents
11 Installation...................................................................................... 11-a
11.1 Overview ....................................................................................................... 11-1
11.2 Safety Information ........................................................................................ 11-1
11.3 Check the Shipment ..................................................................................... 11-2
11.4 Material and Tools Required........................................................................ 11-2
11.5 Device Location and Ambient Conditions .................................................. 11-2
11.6 Mechanical Installation ................................................................................ 11-3
11.7 Electrical Installation and Wiring ................................................................ 11-4
11.7.1 Grounding Guidelines .......................................................................................................11-4
List of Figures
Figure 11.6-1 Dimensions and panel cut-out of PCS-921 ..................................................... 11-3
Figure 11.6-2 Demonstration of plugging a board into its corresponding slot .................. 11-4
Figure 11.7-4 Glancing demo about the wiring for electrical cables ................................... 11-7
11.1 Overview
The device must be shipped, stored and installed with the greatest care.
Choose the place of installation such that the communication interface and the controls on the
front of the device are easily accessible.
Air must circulate freely around the device. Observe all the requirements regarding place of
installation and ambient conditions given in this instruction manual.
Take care that the external wiring is properly brought into the device and terminated correctly and
pay special attention to grounding. Strictly observe the corresponding guidelines contained in this
section.
In certain cases, the settings have to be configured according to the demands of the engineering
configuration after replacement. It is therefore assumed that the personnel who replace modules
and units are familiar with the use of the operator program on the service PC.
WARNING!
ONLY insert or withdraw a module while the device power supply is switched off. To this
end, disconnect the power supply cable that connects with the PWR module.
NOTICE!
Industry packs and ribbon cables may ONLY be replaced on a workbench for electronic
equipment. Electronic components are sensitive to electrostatic discharge when not in
the unit's housing.
NOTICE!
NOTICE!
A module can ONLY be inserted in the slot designated in the chapter 6. Components
can be damaged or destroyed by inserting module in a wrong slot.
Should boards have to be removed from this device installed in a grounded cubicle in an HV
switchgear installation, please discharge yourself by touching station ground (the cubicle)
beforehand.
Only hold electronic boards at the edges, taking care not to touch the components.
Only works on the board which has been removed from the cubicle on a workbench designed
for electronic equipment and wear a grounded wristband. Do not wear a grounded wristband,
however, while inserting or withdrawing units.
Always store and ship the electronic boards in their original packing. Place electronic parts in
electrostatic screened packing materials.
Visually inspect all the material when unpacking it. When there is evidence of transport damage,
lodge a claim immediately in writing with the last carrier and notify the nearest NR Company or
agent.
If the equipment is not going to be installed immediately, store all the parts in their original packing
in a clean dry place at a moderate temperature. The humidity at a maximum temperature and the
permissible storage temperature range in dry air are listed in Chapter “Technical Data”.
A suitable drill and spanners are required to secure the cubicles to the floor using the plugs
provided (if this device is mounted in cubicles).
Excessively high temperature can appreciably reduce the operating life of this device.
The place of installation should permit easy access especially to front of the device, i.e. to the
human machine interface of the equipment.
There should also be free access at the rear of the equipment for additions and replacement of
electronic boards.
Since every piece of technical equipment can be damaged or destroyed by inadmissible ambient
conditions, such as:
1. The location should not be exposed to excessive air pollution (dust, aggressive substances).
2. Surge voltages of high amplitude and short rise time, extreme changes of temperature, high
levels of humidity, severe vibration and strong induced magnetic fields should be avoided as
far as possible.
The equipment can in principle be mounted in any attitude, but it is normally mounted vertically
(visibility of markings).
It is necessary to leave enough space top and bottom of the cut-out in the cubicle for
heat emission of this device.
The device adopts IEC standard chassis and is rack with modular structure. It uses an integral
faceplate and plug terminal block on backboard for external connections. PCS-921 series is IEC
4U high. Figure 11.6-1 shows its dimensions and panel cut-out.
F ron t S id e
C u t-O u t
Following figure shows the installation way of a module being plugged into a corresponding slot.
In the case of equipment supplied in cubicles, place the cubicles on the foundations that have
been prepared. Take care while doing so not to jam or otherwise damage any of the cables that
have already been installed. Secure the cubicles to the foundations.
All these precautions can only be effective if the station ground is of good quality.
Switching operations in HV installations generate transient over voltages on control signal cables.
There is also a background of electromagnetic RF fields in electrical installations that can induce
spurious currents in the devices themselves or the leads connected to them.
On the other hand, electronic apparatus can transmit interference that can disrupt the operation of
other apparatus.
In order to minimize these influences as far as possible, certain standards have to be observed
with respect to grounding, wiring and screening.
Metal accessories such as side plates, blanking plates etc., must be effectively connected
surface-to-surface to the grounded frame to ensure a low-impedance path to ground for RF
interference. The contact surfaces must not only conduct well, they must also be non-corroding.
NOTICE!
If the above conditions are not fulfilled, there is a possibility of the cubicle or parts of it
forming a resonant circuit at certain frequencies that would amplify the transmission of
interference by the devices installed and also reduce their immunity to induced
interference.
Movable parts of the cubicle such as doors (front and back) or hinged equipment frames must be
effectively grounded to the frame by three braided copper strips (see Figure 11.7-1).
The metal parts of the cubicle housing and the ground rail are interconnected electrically
conducting and corrosion proof. The contact surfaces shall be as large as possible.
NOTICE!
For metallic connections please observe the voltage difference of both materials
according to the electrochemical code.
The cubicle ground rail must be effectively connected to the station ground rail by a
grounding strip (braided copper).
There are some ground terminals on some connectors of this device, and the sign is “GND”. All the
ground terminals are connected in the cabinet of this device. Therefore, the ground terminal on the
rear panel (see Figure 11.7-2) is the only ground terminal of this device.
The grounding strips must therefore be of (preferably tinned) braided copper and not round copper
conductors, as the cross-section of round copper would have to be too large.
Proper terminations must be fitted to both ends (press/pinch fit and tinned) with a hole for bolting
them firmly to the items to be connected.
The surfaces to which the grounding strips are bolted must be electrically conducting and
non-corroding.
Press/pinch fit
cable terminal
Braided
copper strip Terminal bolt
Contact surface
There are several types of cables that are used in the connection of this device: braided copper
cable, serial communication cable etc. Recommendation of each cable:
Power supply, binary input & output: stranded conductor, 1.0mm 2 ~ 2.5mm2
DANGER!
NEVER allow a open current transformer (CT) secondary circuit connected to this
device while the primary system is live. Open CT circuit will produce a dangerously high
A female connector is used for connecting the wires with it, and then a female connector plugs into
a corresponding male connector that is in the front of one board. See Chapter “Hardware” for
further details about the pin defines of these connectors.
The following figure shows the glancing demo about the wiring for the electrical cables.
Figure 11.7-4 Glancing demo about the wiring for electrical cables
12 Commissioning
Table of Contents
12 Commissioning ............................................................................ 12-a
12.1 Overview ...................................................................................................... 12-1
12.2 Safety Instructions ...................................................................................... 12-1
12.3 Commission Tools ...................................................................................... 12-1
12.4 Setting Familiarization ................................................................................ 12-2
12.5 Product Checks ........................................................................................... 12-2
12.5.1 With the Device De-energized ......................................................................................... 12-3
12.1 Overview
This device is numerical in their design, implementing all functions in software. The device
employs a high degree self-checking, so in the unlikely event of a failure, it will give an alarm.
Blank commissioning test and setting records are provided at the end of this manual for
completion as required.
Before carrying out any work on the device, the user should be familiar with the contents of the
safety and technical data sections and the ratings on the device’s rating label.
DANGER!
WARNING!
ONLY qualified personnel should work on or in the vicinity of this device. This
personnel MUST be familiar with all safety regulations and service procedures
described in this manual. During operating of electrical device, certain part of the
device is under high voltage. Severe personal injury and significant device damage
could result from improper behavior.
The earthing screw of the device must be connected solidly to the protective earth conductor
before any other electrical connection is made.
Hazardous voltages can be present on all circuits and components connected to the supply
voltage or to the measuring and test quantities.
Hazardous voltages can be present in the device even after disconnection of the supply
voltage (storage capacitors!)
The limit values stated in the Chapter “Technical Data” must not be exceeded at all, not even
during testing and commissioning.
When testing the device with secondary test equipment, make sure that no other
measurement quantities are connected. Take also into consideration that the trip circuits and
may be close commands to the circuit breakers and other primary switches are disconnected
from the device unless expressly stated.
NOTICE!
Modern test set may contain many of the above features in one unit.
Multifunctional dynamic current and voltage injection test set with interval timer.
Multimeter with suitable AC current range and AC/DC voltage ranges of 0~440V and 0~250V
respectively.
Optional equipment:
An electronic or brushless insulation tester with a DC output not exceeding 500V (for
insulation resistance test when required).
A portable PC, with appropriate software (this enables the rear communications port to be
tested, if this is to be used, and will also save considerable time during commissioning).
EIA RS-485 to EIA RS-232 converter (if EIA RS-485 IEC60870-5-103 port is being tested).
Tester: HELP-9000.
With the front cover in place all keys are accessible. All menu cells can be read. The LED
indicators and alarms can be reset. Protection or configuration settings can be changed, or fault
and event records cleared. However, menu cells will require the appropriate password to be
entered before changes can be made.
If the application-specific settings have been applied to the device prior to commissioning, it is
advisable to make a copy of the settings so as to allow them restoration later. This could be done
by extracting the settings from the device itself via printer or manually creating a setting record.
This device is fully numerical and the hardware is continuously monitored. Commissioning tests
can be kept to a minimum and need only include hardware tests and conjunctive tests. The
function tests are carried out according to user’s correlative regulations.
The following tests are necessary to ensure the normal operation of the equipment before it is first
put into service.
Hardware tests
These tests are performed for the following hardware to ensure that there is no hardware
defect. Defects of hardware circuits other than the following can be detected by
self-monitoring when the DC power is supplied.
Function tests
These tests are performed for the following functions that are fully software-based.
Timers test
Conjunctive tests
The tests are performed after the device is connected with the primary equipment and other
external equipment.
On load test.
After unpacking the product, check for any damage to the device case. If there is any damage, the
internal module might also have been affected, contact the vendor. The following items listed are
necessary.
Device panel
Carefully examine the device panel, device inside and other parts inside to see that no
physical damage has occurred since installation.
Panel wiring
Check the conducting wire which is used in the panel to assure that their cross section
Carefully examine the wiring to see that they are no connection failure exists.
Check each plug-in module of the equipment on the panel to make sure that they are well
installed into the equipment without any screw loosened.
Earthing cable
Check whether the earthing cable from the panel terminal block is safely screwed to the panel
steel sheet.
Check whether all the switches, equipment keypad, isolator binary inputs and push buttons
work normally and smoothly.
Insulation resistance tests are only necessary during commissioning if it is required for them to be
done and they have not been performed during installation.
Isolate all wiring from the earth and test the isolation with an electronic or brushless insulation
tester at a DC voltage not exceeding 500V, The circuits need to be tested should include:
DC power supply
Output contacts
Communication ports
Test method:
To unplug all the terminals sockets of this device, and do the Insulation resistance test for each
circuit above with an electronic or brushless insulation tester.
On completion of the insulation resistance tests, ensure all external wiring is correctly
reconnected to the device.
Check that the external wiring is correct to the relevant device diagram and scheme diagram.
Ensure as far as practical that phasing/phase rotation appears to be as expected.
Check the wiring against the schematic diagram for the installation to ensure compliance with the
customer’s normal practice.
WARNING!
Energize this device ONLY if the power supply is within the specified operating range in
the Chapter “Technical Data”.
The device only can be operated under the auxiliary power supply depending on the device’s
nominal power supply rating.
The incoming voltage must be within the operating range specified in Chapter “Technical Data”,
before energizing the device, measure the auxiliary supply to ensure it within the operating range.
Other requirements to the auxiliary power supply are specified in Chapter “Technical Data”. See
this section for further details about the parameters of the power supply.
The following groups of checks verify that the device hardware and software is functioning
correctly and should be carried out with the auxiliary supply applied to the device.
The current and voltage transformer connections must remain isolated from the device for these
checks. The trip circuit should also remain isolated to prevent accidental operation of the
associated circuit breaker.
Connect the device to DC power supply correctly and turn the device on. Check program version
and forming time displayed in command menu to ensure that are corresponding to what ordered.
If the time and date is not being maintained by substation automation system, the date and time
should be set manually.
Set the date and time to the correct local time and date using menu item “Clock”.
In the event of the auxiliary supply failing, with a battery fitted on CPU board, the time and date
will be maintained. Therefore when the auxiliary supply is restored the time and date will be
correct and not need to set again.
To test this, remove the auxiliary supply from the device for approximately 30s. After being
re-energized, the time and date should be correct.
On power up, the green LED “HEALTHY” should have illuminated and stayed on indicating that
the device is healthy.
The device has latched signal devices which remember the state of the trip, auto-reclose when
the device was last energized from an auxiliary supply. Therefore these indicators may also
illuminate when the auxiliary supply is applied. If any of these LEDs are on then they should be
reset before proceeding with further testing. If the LED successfully reset, the LED goes out.
There is no testing required for that that LED because it is known to be operational.
It is likely that alarms related to voltage transformer supervision will not reset at this stage.
Apply the rated DC power supply and check that the “HEALTHY” LED is lighting in green. We
need to emphasize that the “HEALTHY” LED is always lighting in operation course except that the
equipment find serious errors in it.
Produce one of the abnormal conditions listed in Chapter “Supervision”, the “ALARM” LED will
light in yellow. When abnormal condition reset, the “ALARM” LED extinguishes.
NOTICE!
The closing circuit should remain isolated during these checks to prevent accidental
operation of the associated circuit breaker.
This test verified that the accuracy of current measurement is within the acceptable tolerances.
Apply rated current to each current transformer input in turn; checking its magnitude using a
multimeter/test set readout. The corresponding reading can then be checked in the devices menu.
NOTICE!
The closing circuit should remain isolated during these checks to prevent accidental
operation of the associated circuit breaker.
This test verified that the accuracy of voltage measurement is within the acceptable tolerances.
Apply rated voltage to each voltage transformer input in turn; checking its magnitude using a
multimeter/test set readout. The corresponding reading can then be checked in the devices menu.
This test checks that all the binary inputs on the equipment are functioning correctly.
The binary inputs should be energized one at a time, see external connection diagrams for
terminal numbers.
Ensure that the voltage applied on the binary input must be within the operating range.
The status of each binary input can be viewed using device menu. Sign “1” denotes an energized
input and sign “0” denotes a de-energized input.
1. Confirm the external wiring to the current and voltage inputs is correct.
However, these checks can only be carried out if there are no restrictions preventing the
tenderization of the plant being protected.
Remove all test leads, temporary shorting leads, etc. and replace any external wiring that has
been removed to allow testing.
If it has been necessary to disconnect any of the external wiring from the device in order to
perform any of the foregoing tests, it should be ensured that all connections are replaced in
accordance with the relevant external connection or scheme diagram. Confirm current and
voltage transformer wiring.
If the device is in a new installation or the circuit breaker has just been maintained, the circuit
breaker maintenance and current counters should be zero. If a test block is installed, remove the
test plug and replace the cover so that the device is put into service.
Ensure that all event records, fault records and alarms have been cleared and LED’s has been
reset before leaving the device.
13 Maintenance
Table of Contents
13 Maintenance .................................................................................. 13-a
13.1 Appearance Check ...................................................................................... 13-1
13.2 Failure Tracing and Repair ......................................................................... 13-1
13.3 Replace Failed Modules ............................................................................. 13-2
13.4 Cleaning ....................................................................................................... 13-3
13.5 Storage ......................................................................................................... 13-3
This device is designed to require no special maintenance. All measurement and signal
processing circuit are fully solid state. All input modules are also fully solid state. The output relays
are hermetically sealed.
Since the device is almost completely self-monitored, from the measuring inputs to the output
relays, hardware and software defects are automatically detected and reported. The
self-monitoring ensures the high availability of the device and generally allows for a corrective
rather than preventive maintenance strategy. Therefore, maintenance checks in short intervals are
not required.
Operation of the device is automatically blocked when a hardware failure is detected. If a problem
is detected in the external measuring circuits, the device normally only provides alarm messages.
2. It is only allowed to plug or withdraw device board when the supply is reliably switched off.
Never allow the CT secondary circuit connected to this equipment to be opened while the
primary system is live when withdrawing an AC module. Never try to insert or withdraw the
device board when it is unnecessary.
3. Check weld spots on PCB whether they are well soldered without any rosin joint. All dual
inline components must be well plugged.
When a failure is detected by supervision, a remote alarm is issued and the failure is indicated on
the front panel with LED indicators and LCD display. It is also recorded in the event record.
Failures detected by supervision are traced by checking the “Superv State” screen on the LCD.
WARNING!
Module can ONLY be replaced while the device power supply is switched off.
ONLY appropriately trained and qualified personnel can perform the replacement by
strictly observing the precautions against electrostatic discharge.
WARNING!
Five seconds is NECESSARY for discharging the voltage. Hazardous voltage can be
present in the DC circuit just after switching off the DC power supply.
CAUTION!
Take anti-static measures such as wearing an earthed wristband and placing modules
on an earthed conductive mat when handling a module. Otherwise, electronic
components could be damaged.
CAUTION!
If the failure is identified to be in the device module and the user has spare modules, the user can
recover the device by replacing the failed modules.
Repair at the site should be limited to module replacement. Maintenance at the component level is
not recommended.
Check that the replacement module has an identical module name (AI, PWR, MON, BI, BO, etc.)
and hardware type-form as the removed module. Furthermore, the MON module replaced should
have the same software version. In addition, the AI and PWR module replaced should have the
same ratings.
The module name is indicated on the top front of the module. The software version is indicated in
LCD menu “Information”->“Version Info”.
1) Replacing a module
Short circuit all AC current inputs and disconnect all AC voltage inputs
After replacing the MON module, input the application-specific setting values again.
Unplug the ribbon cable on the front panel by pushing the catch outside.
13.4 Cleaning
Before cleaning the device, ensure that all AC/DC supplies, current transformer connections are
isolated to prevent any chance of an electric shock whilst cleaning. Use a smooth cloth to clean
the front panel. Do not use abrasive material or detergent chemicals.
13.5 Storage
The spare device or module should be stored in a dry and clean room. Based on IEC standard
60255-1 the storage temperature should be from -40°C to +70°C, but the temperature of from 0°C
to +40°C is recommended for long-term storage.
Table of Contents
14 Decommissioning and Disposal ................................................. 14-a
14.1 Decommissioning ....................................................................................... 14-1
14.2 Disposal ....................................................................................................... 14-1
14.1 Decommissioning
DANGER!
Switch OFF the circuit breaker for primary CTs and VTs BEFORE disconnecting the
cables of AI module.
WARNING!
Switch OFF the external miniature circuit breaker of device power supply BEFORE
disconnecting the power supply cable connected to the PWR module.
WARNING!
1. Switching off
To switch off this device, switch off the external miniature circuit breaker of the power supply.
2. Disconnecting cables
Disconnect the cables in accordance with the rules and recommendations made by relational
department.
3. Dismantling
The device rack may now be removed from the system cubicle, after which the cubicles may
also be removed.
14.2 Disposal
NOTICE!
Strictly observe all local and national laws and regulations when disposing the device.
6 is modified
Jumpers configuration of clock synchronization port of
MON module is added;
Add system phase sequence selection, ABC or ACB;
Add the settings [En_Send_MMS_Qual_Chg],
[Opt_DualNetMode_MMS], [En_Ctrl_SLD] and
[En_PopupRecord_Blkd] in “device settings”;
Add the settings [IEDNAME] and [En_BICheckBO] in
“communication settings”;
R2.01 R2.02 R3.30 2016-07-15 DNP protocol related communication settings are added;
Add the menu “HMI Setup”;
Add the keypad operation: modify the time display format
and remote control via SLD;
Add the setting [Cfg_NetPorts_Bond] and its related
description;
Add the monitoring about bonding network ports;
Modify the lower limit of the setting [81O.OFx.t_Op] and
[81U.UFx.t_Op].
Section 3.20 is modified
R2.02 R2.03 R3.30 2017-06-15
Section 8.4 and Section 8.5.3 are added
The normally closed and normally open auxiliary contact in
the voltage selection logic diagram of Section 3.15.2.2 and
R2.03 R2.04 R3.40 2017-10-15
Section 3.15.2.3 are exchanged;
The device setting [En_RevCT] is added