Reinforced Concrete Beam Detailing


According to ACI Code
Clearly, the detailing of the reinforced concrete members is the key to good design and
execution of work at the site. That is why poor detailing of reinforcement makes the
structure undergo cracking, excessive deflection, or even collapse.

Reinforcements resist tensile forces. They may also be required in the compression zones to
increase the compression capacity, enhance ductility, to reduce long-term deflections, or
increase the flexural capacity for beams.

Added to that, they prevent cracking of concrete due to shrinkage and temperature stresses.

Finally, different aspects of reinforced concrete beam detailing based on ACI Code is
explained in the following sections.

Types of reinforcement in a beam


• Main bars (bottom steels)- deal with tension force
• Top bars (anchor bars)-hold stirrups in their position
• Cut off bars- deal with tension forces
• Stirrups with different spacing-tackle vertical and diagonal shear.

Hooked anchors
The function of hooked anchors is the provision of additional anchorage when there is
inadequate straight length available to develop a bar.

Commonly, standard hooks described in ACI Code Section 7.1 utilized apart from the case
where it is specifically specified.

The ACI standard hooks are as follows:


ACI standard hooks for primary reinforcement

• 180-degree bend plus 4db extension, but not less than 65 mm at free end of bar.
• 90-degree bend plus 12db extension at free end of bar.

Fig.1: Standard hook, 180degree

Fig.2:Standard hook, 90degree

ACI standard hooks for stirrups

• 16 bar and smaller, 90-degree bend plus 6db extension at free end of bar.
• 19, No. 22, and No. 25 bar, 90-degree bend plus 12db extension at free end of bar
• 25 bar and smaller, 135-degree bend plus 6db extension at free end of bar.
Fig.3:Stirrup hooks

Fig.4:seismic stirrup, 135degree

Minimum bend diameters


Standard bends in reinforcing bars are described in terms of the inside diameter of bend
because this is easier to measure than the radius of bend.

The primary factors which control the minimum bend diameter are feasibility of bending
without breakage and avoidance of crushing the concrete inside the bend.

• Diameter of bend measured on the inside of the bar, other than for stirrups in sizes
No. 10 through No. 16, shall not be less than the values in Table 1.
• Inside diameter of bend for stirrups shall not be less than 4db for No. 16 bar and
smaller. For bars larger than No. 16, diameter of bend shall be in accordance with
Table 1.
• Inside diameter of bend in welded wire reinforcement for stirrups shall not be less
than 4db for deformed wire larger than MD40 and 2db for all other wires. Bends
with inside diameter of less than 8db shall not be less than 4db from nearest
welded intersection.

Table 1 minimum inside diameter of hooks based on the size of the bars

Bar size Minimum diameter

No.10 to No.25 6db

No.29, No.32, and No.36 8db

No.43 and No.57 10db

db is the diameter of the bar

Fig.5:Inside diameter of hooked bar

Stirrups
In beam detailing, the detailer or designer shall provide sizes, spacing, location, and types
of all stirrups which include open and closed stirrups. stirrups may be vertical or inclined.
Fig.5:Various stirrup
configurations
Moreover, where the design requires closed stirrup for shear, the closure may consist of
overlapped, standard 90o end hooks of one or two-piece stirrups, or properly spliced pairs of
U-stirrups.

Furthermore, when the design requires closed ties for torsion, the closure may consist of
overlapped, standard 135o hooks of one- or two-piece ties enclosing a longitudinal bar.

Lastly, there are different techniques for anchorage of stirrups, but the most common is to
use one of the standard hooks as shown in figure 3 and figure 4.

Development length (ld)


The development length (ld) is the shortest length of bar in which the bar stress can
increase from zero to the yield strength (fy). It is different in tension and compression, and
basic equation for each case are as follow:

Development length in tension

Use the following expression to calculate development length in tension, but no less than
30.48cm.
Where:

cb: factor that represents the smallest of the side cover. the cover over the bar or wire (in
both cases measured to the center of the bar or wire)

Ktr: factor which denotes the contribution of confining reinforcement across potential
splitting planes.

: the traditional reinforcement location factor to reflect the adverse effects of the top
reinforcement casting position.

: coating factor reflecting the effects of epoxy coating. The product of should not
exceed 1.7.

: reinforcement size factor that reflects the more favorable performance of smaller
diameter reinforcement.

: factor reflecting the lower tensile strength of lightweight concrete and the resulting
reduction of the splitting resistance, which increases the development length in lightweight
concrete.

(cb+ Ktr)/db equal to 2.5 if the result of (cb + Ktr)/db is less than 2.5.

db: bar diameter

Atr: total cross-sectional area of all transverse reinforcement within the spacing s.

n: number of bars or wires being developed along the plane of splitting

Factor in
development length Cases Values
equation
Horizontal reinforcement so placed that more than 30cm of fresh
1.3
concrete cast in the member below the development length or splice

Other reinforcement 1

Epoxy-coated bars or wires with cover less than 3db or clear spacing
1.5
less than 6db

All other epoxy-coated bars or wires 1.2

Uncoated and galvanized reinforcement 1

No. 19 and smaller bars and deformed wires 0.8

No. 22 and larger bars 1

For lightweight-aggregate concrete utilization 0.75

when the splitting tensile strength is specified, it is equal to


1
fc’^0.5/1.8fct but not more

for normal-weight concrete 1

Development length in compression

development length can be calculated using the greatest of the following formula, but it shall
not be smaller than 20.32cm.

ldc=(0.02fy / )db Equation 3

ldc=( (0.0003fy)db Equation 4

where

ldc: development length in compression bars

fy: yield strength of bars

db: bar diameter


Development of bundled bars

Individual bar development length within a bundle, in tension or compression, shall be that
for the individual bar, increased 20 percent for three-bar bundle, and 33 percent for four-bar
bundle.

Development Length ldh for standard hooks in tension

The development length, ldh, for standard hooks in tension is given as:

Where:

= 1.2 for epoxy-coated reinforcement

= 1.3 for lightweight aggregate concrete.

For other cases, and are equal to 1.0.

Fig.5:development length in end hooks


Bar cut off in beams and development length in flexural
reinforcement

Bar cut off in beams

Commonly, reinforcements are provided close to the bottom of beams so as to counter act
tensile forces on the beam.

Moreover, these reinforcements computed based on maximum moments at mid spans and
at face of supports. these moments reduce in beam regions other than mid span and
support faces.

Therefore, it is possible to cut off bars in zones where they are no longer required. hence,
cut off bars provide economic advantages.

However, bar cut off shall be kept as minimum as possible to decline design and
construction complexities.

Furthermore, it is important to extend the cut off bars beyond cut off point by development
length (ld) to ensure adequate bond between bar and concrete. Development length will be
discussed in the section below.

Lastly, the location of points where bars are no longer needed is a function of the flexural
tensions that results from the bending moments and the effects of shear on these tensile
forces.

Fig.6:Cut off bars


Development length in flexural reinforcement in beams

In beams, development length is provided at points of critical stress. The critical stress
points in beams are Points of maximum positive and negative moments are critical sections,
from which adequate anchorage ld must be provided.

Moreover, critical points are also at points within the span where adjacent reinforcement cut
off; continuing bars must have adequate anchorage ld from the theoretical cut-off points of
terminated bars.

Added to that, cut off bars shall extend beyond the theoretical cut-off points to resist flexure
for a distance equal to d or 12db.

Development of positive moment reinforcement

For simple members, minimum one-third of positive moment reinforcement and one-fourth
of positive moment reinforcement in continuous members must extend along the element
face into the support.

These reinforcements in beams shall extend into the support at least 152.3mm.

Development of negative moment reinforcement

Negative moment reinforcement in a continuous, restrained, or cantilever member, or in any


member of a rigid frame, shall be anchored in or through the supporting member by
embedment length, hooks, or mechanical anchorage.

Additionally, at least one-third the total tension reinforcement provided for negative moment
at a support shall have an embedment length beyond the point of inflection not less than d,
12db, or clear span /16, whichever is greater.
Fig.6:Anchorage of negative
moment reinforcement

Fig.7:Typical reinforcement details of non perimeter beams with open stirrups

Fig.8:Typical reinforcement details of non perimeter beams with closed stirrups


Fig.9:Typical reinforcement details of perimeter beams