You are on page 1of 4

SIMULASI SISTEM TENAGA LISTRIK

PERHITUNGAN SISTEM PU

Dosen Pengampu:
Dimas Okky Anggriawan, ST., MT

Oleh:
Fabria Alieftya Yusvianti
2320640023
D4 LJ Teknik Elektro Industri A

PROGRAM STUDI D4 TEKNIK ELEKTRO INDUSTRI


DEPARTEMEN TEKNIK ELEKTRO
POLITEKNIK ELEKTRONIKA NEGERI SURABAYA
2021
Diketahui:

Generator
SoldGenerator = 50 MVA
VoldGenerator = 23 kV
X =25%
Trafo 1:
SoldTrafo1 = 50 MVA
VoldTrafo1 = 23 kV
X =25%
Load 1:
SoldLoad1 = 10 MVA
VoldbaseLoad1 = 20 kV
X =20%
Trafo 2:
SoldTrafo2 = 20 MVA
VoldTrafo2 = 20 kV
X =10%
Motor 1:
SoldMotor1 = 10 MVA
VoldMotor1 = 0,38 kV
X = 10%
Motor 2:
SoldMotor2 = 5 MVA
VoldMotor2 = 0,38 kV
X = 15%
Base
Snew : 50 MVA
Vnew bus 4: 23 kV
Vnew bus 2 : 20 kV
Vnew bus 3 : 0,4 kV

Jawab:
S
Rumus : X new=X old × S ( )
new

old

50
( )
1. G= X new=0,25 × 50 =0,25 p . u
50
2. Motor 2=X new =0,25 ×( )=0,25 p .u
50
50
3. Load 1=X new =0,2× ( ) =1 p . u
10
50
4. Trafo2= X new =0,15 × ( )=0,375 p .u
20

2
S new V
Rumus : X new =X old × ( )( )
S old
× old
V new

50 0,38 2
5. Motor 1=X new =0,1× ( 10 ) ( 0,4 )
× =0,45 p .u
2
50 0,38
=0,15 ×( ) × (
0,4 )
6. Motor 2=X new =1,35 p . u
5