You are on page 1of 1

132KV/11.

5KV Grid Station


Customer: GEPCO
Head Marala

Contractor: Sino-Steel China


Page 1 of 1
Bay E-E02 Surge Arrestor
Date: 05-07-2017

Insulation Resistance Test of Bay E-02 Surge Arrestor

Applied Voltage Insulation Resistance

Phase KV TΩ

R 5 3.812

Y 5 2.918

B 5 3.410

Test Instrument Type Insulation Resistance Test Set


Make Chauvin Arnoux France
Model CA6550

Tested By Witnessed by Client

Ayk Pvt. Ltd. GEPCO


Name:
Signature:
Date: