You are on page 1of 1

132KV/11.

5KV Grid Station


Customer: GEPCO
Head Marala

Contractor: Sino-Steel China


Page 1 of 1
Bus-Bar DC Hi-Pot
Date: 13-07-2017

132 KV Bus-Bar DC Hi-pot

Sr.# Phase Applied Voltage Time Leakage Current

1 Red 80 KV 60 Sec 0.015mA

2 Yellow 80 KV 60 Sec 0.150mA

3 Blue 80 KV 60 Sec 0.095mA

Tested By Witnessed by Client

Ayk Pvt. Ltd. GEPCO


Name:
Signature: