600/lOOOV (Plain Annealed Copper Conductor. PVC Insulated and PVC-sheathed Cables) Three Core
No. and Ampacity of
Approxi Cross- Current Rating Approxoma Conductor for mat e Sectional 3S"C ambient ECC-size te Selecting Outer Area of temperature in Diameter CB/Fuse Sizes Dia met Conductor air of No./mm. ermm mm2 A A mm2 1/1.38 11.6 3 x 1.S re 16 16 4 1/1.78 12.9 3 x 2.5 re 23 23 4 7/0.85 15.0 3 x 4 rm 32 32 4 7/1.0S 16.3 3 x 6 rm 41 41 6 7/1.35 18.3 3 x 10 rm 56 56 10 7/1.71 21.4 3 x 16 rm 75 75 16 7/2.13 25.4 3 x 25 rm 98 98 16 20-wire 23.2 3 x 35 sm 120 120 16 20-wire 27.1 3 x SO sm 150 150 25 20-wire 30.0 3 x 70 sm 190 190 35 20-wire 34.S 3 x 95 sm 230 230 50 39-wire 37.2 3 x 120 sm 270 270 70 39-wire 41.l 3 x 150 sm 305 305 95 39-wire 45.3 3 x 185 sm 350 350 95 39-wire 50.9 3 x 240 sm 410 410 120 39-wire 57.3 3 x 300 sm 470 470 150 61-wire 62.0 3 x 400 sm 530 530 240 61-wire 72.1 3 x SOO sm 600 600 61-wire 80.2 3 x 630 sm 690 690