Work Instructions

Capstone C200/C1000 Series Microturbine


Standard Maintenance Schedule and Procedures

Failure to perform scheduled maintenance will void the microturbine warranty


and may void Factory Protection Plan (FPP) provisions.
Refer to New System Limited Warranty (460048).

440385 Rev B (November 2019) Page 1 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without
incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

Capstone Turbine Corporation


16640 Stagg Street  Van Nuys  CA 91406  USA
Telephone: +1 (818) 407-3600
Website: capstoneturbine.com
Document Library: documents.capstoneturbine.com

Capstone Technical Support


Telephone: +1 (866) 4-CAPSTONE or (866) 422-7786
E-mail: service@capstoneturbine.com

Copyright © 2019 Capstone Turbine Corporation. All Rights Reserved.

440386 Rev B (November 2019) Page 2 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without
incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

Table of Contents
1. Introduction ........................................................................................................................... 5
1.1. Purpose and Scope ..................................................................................................... 5
1.2. Capstone Document Links ........................................................................................... 5
1.3. Safety Procedures ....................................................................................................... 6
1.4. Safety Symbols ............................................................................................................ 7
2. Maintenance During Storage ................................................................................................. 8
2.1. Basic Storage Requirements (up to 6 Months) ............................................................. 8
2.2. Extended Storage Requirements (6 Months or longer)................................................. 8
2.3. Battery Maintenance (If Equipped) ............................................................................... 8
2.3.1. Sleep Mode ..................................................................................................... 9
2.3.2. Automatic Battery Charge ............................................................................. 10
2.3.3. Equalization Charge ...................................................................................... 10
3. General Maintenance Procedures ....................................................................................... 11
3.1. General Cleaning and Inspection ............................................................................... 11
3.2. Site Air Quality, Air Filter and Internal Component Maintenance ................................ 11
3.2.1. Site-Specific Air Filter Replacement Interval Evaluation ................................ 12
4. Fuel System Inspection and Maintenance ........................................................................... 13
4.1. Gaseous Fuel Fittings and Components .................................................................... 13
4.2. Liquid Fuel Fittings and Components ......................................................................... 14
5. Scheduled Maintenance Tables .......................................................................................... 14
5.1. Capstone System Scheduled Maintenance Tables .................................................... 14
5.2. Controllers and Accessories Scheduled Maintenance ................................................ 27
6. Responsibility ...................................................................................................................... 28
7. Capstone Technical Support ............................................................................................... 28
7.1. Capstone Document Library....................................................................................... 28

440386 Rev B (November 2019) Page 3 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without
incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

List of Tables
Table 1. C200/C1000 HPNG & Propane (Fuel Types H, P) Schedule – 4K to 80K Hours ........ 15
Table 2. C200/C1000 HPNG & Propane (Fuel Types H, P) Schedule – 84K to 160K Hours .... 16
Table 3. C200/C1000 LPNG (Fuel Type F) Schedule – 4K to 80K Hours ................................. 17
Table 4. C200/C1000 LPNG (Fuel Type F) Schedule – 84K to 160K Hours ............................. 18
Table 5. C200/C1000 Biogas (Fuel Types A, B) Schedule – 4K to 80K Hours ......................... 19
Table 6. C200/C1000 Biogas (Fuel Types A, B) Schedule – 84K to 160K Hours ..................... 20
Table 7. C200/C1000 HP Sour Gas (Fuel Type S) Schedule – 4K to 80K Hours ..................... 21
Table 8. C200/C1000 HP Sour Gas (Fuel Type S) Schedule – 84K to 160K Hours ................. 22
Table 9. C200/C1000 Liquid Fuel (Fuel Type D) Schedule – 4K to 80K Hours ......................... 23
Table 10. C200/C1000 Liquid Fuel (Fuel Type D) Schedule – 84K to 160K Hours ................... 24
Table 11. Additional C200/C1000 HazLoc Tasks Schedule – 4K to 80K Hours ......................... 25
Table 12. Additional C200/C1000 HazLoc Tasks Schedule – 84K to 160K Hours ..................... 26
Table 13. Capstone Controllers Scheduled .............................................................................. 27

440386 Rev B (November 2019) Page 4 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without
incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

1. Introduction
1.1. Purpose and Scope
This document lists standard maintenance intervals for Capstone C200 and C1000 Series
MicroTurbine® systems and major accessories.
All maintenance procedures must be performed by an Authorized Service Provider (ASP).

NOTE
Refer to specific Work Instructions to replace components or to complete the
maintenance listed. Many procedures are linked to Work Instructions or other
documents.

Scheduled maintenance intervals assume the microturbine is operating in controlled


environmental conditions. Systems operating in extreme or unusual conditions may require
different service and maintenance intervals. Actual service intervals are dependent on system
load demands, site conditions, fuel quality, and performance of routine preventive maintenance.
Maintenance intervals shown in hours are elapsed operating hours. Maintenance intervals shown
in months are elapsed calendar months.

1.2. Capstone Document Links


The following is a list of helpful Capstone documents linked in these Work Instructions. For your
convenience, a link to a Work Instruction or other document is placed with most maintenance
operations.
Click on the document number (in blue) to view the linked document.
 400003 Recommended Tools, Capstone MicroTurbine
 400008 C200 MicroTurbine User’s Manual
 400024 C1000 Series User’s Manual
 400025 CRMS-APS User’s Manual
 400026 APS User’s Manual
 410066 C200 Technical Reference
 440273 C200 Microturbine & C1000 Series Engine and System Inspection
 460006 Commissioning Checklist
 460048 New System Limited Warranty
 480010 Offshore Application Guide
 420006 Interactive Field Service Report
 Component replacement Work Instructions
 Other documents including Work Instructions for specific maintenance procedures

440386 Rev B (November 2019) Page 5 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without
incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

1.3. Safety Procedures


Become familiar with general safety precautions in the C200 and C1000 Series MicroTurbine
User’s Manual (400008/400024). Follow all warnings and cautions in this and referenced Work
Instructions to reduce the risk of death, injury or equipment damage.
Before performing most service and maintenance procedures:
 Close main fuel supply valve as required or instructed for procedure.

 Disconnect system from the utility. Isolate and lock out the utility (if applicable).

 Isolate and lock out any other sources of power to the microturbine. For example,
connections to the solid state relays in the microturbine Communications Bay.
 If battery pack is installed, set and lock battery pack circuit breaker OFF, and
disconnect/unplug battery cables.
 Ensure above power sources are OFF and the system has been disconnected for at least
10 minutes to reduce electric shock hazards.
 Maintain proper microturbine frame electrical ground.

 Verify with digital VOM that no voltage is present on the DC bus.

 Do not work on energized equipment unless specifically instructed to do so.

 Do not work on hot surfaces.

 For Hazardous Locations (HazLoc) Package applications (e.g., ATEX or CID2), the
pressurized enclosure shall not be opened unless:
● the system is not in operation;
● the surrounding/adjacent area is known to be free of flammable materials;
● the local atmosphere is not explosive;
● the microturbine indicated internal temperature is below 450°C (842°F);
● all devices have been isolated and de-energized for five minutes.
Warning labels similar to the following are attached to systems in these applications.

440386 Rev B (November 2019) Page 6 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without
incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

1.4. Safety Symbols


Capstone uses the following symbols with safety warning messages to alert you to potential
hazards to people or equipment, and to provide additional information for proper equipment
operation.

HIGH VOLTAGE WARNING: Identifies a high voltage hazard that can result in
personal injury or death.

ELECTRIC SHOCK WARNING: Identifies a hazardous voltage area that can


cause personal injury or death from electric shock if touched.

FLAMMABLE MATERIAL WARNING: Identifies a flammable or explosive material


hazard that can result in personal injury or death. No open flame or smoking
allowed.

SUFFOCATION WARNING: Identifies asphyxiation hazard that can result in


personal injury or death.

HOT SURFACE/AREA WARNING: Identifies a hot surface or area that can result
in personal injury.

CORROSIVE MATERIAL WARNING: Identifies corrosive material hazard that


can result in personal injury.

ACOUSTIC EMISSIONS WARNING: Identifies sound level hazard that can result
in personal injury. Hearing protection is required.

PACEMAKER WARNING: The turbine generator produces a magnetic field that


can be harmful to pacemaker wearers. Pacemaker wearers must stay more than
30 cm (12 in.) away from an operating turbine engine.

NOTE: Clarifies instructions or highlights important information.

440386 Rev B (November 2019) Page 7 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without
incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

2. Maintenance During Storage


2.1. Basic Storage Requirements (up to 6 Months)
1. For initial inspection purposes or maintenance tasks during storage, carefully remove
original packaging/crating. Do not destroy or discard packaging materials. Reinstall
packaging after initial inspection and before placing system into storage.
2. Keep system as dry as possible. Prevent moisture from entering protective packaging.
3. Maintain batteries. Refer to Battery Maintenance below.
4. Store system at temperature between -40°C (-40°F) and 65°C (149°F), and at relative
humidity of 40 percent or less, if possible.
5. For liquid fuel systems: Purge all fuel from system before storage.

2.2. Extended Storage Requirements (6 Months or longer)


1. Perform tasks listed under Basic Storage Requirements above.
2. For maintenance tasks during extended storage, carefully remove original
packaging/crating. Do not destroy or discard packaging materials. Reinstall packaging
between maintenance activities while system is in storage. Intake and exhaust sealing
caps for desiccant MUST remain installed during storage, except as necessary to
replace desiccant.
3. If storage time will extend beyond six months, replace desiccant and perform manual
engine rotation check at the beginning of extended storage time. Refer to Desiccant Kit
Replacement Work Instruction (440297) and Locked Rotor Identification Work Instruction
(440289).
4. Replace desiccant and perform manual engine rotation check every 12 months and
whenever intake and exhaust sealing caps are removed. Refer to Desiccant Kit
Replacement Work Instruction (440297) and Locked Rotor Identification Work Instruction
(440289). Note that rotation alone will not prevent sticking from occurring.
5. Keep system as dry as possible. Prevent moisture from entering protective packaging.
6. In high humidity conditions (greater than 60 percent relative humidity continuous long
term), consult with local commercial water damage prevention and remediation providers
to prepare/preserve system(s) for high humidity conditions.
7. Maintain batteries. Refer to Battery Maintenance below.
8. Repack system in original packaging/crating or equivalent before shipping system to
final installation site.

2.3. Battery Maintenance (If Equipped)


Microturbines equipped with the Dual Mode option are equipped with sealed lead acid (SLA)
batteries. During system operation, battery packs are charged automatically. During periods of

440386 Rev B (November 2019) Page 8 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without
incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

extended system down time or during storage, battery packs will self-discharge and require
periodic recharging (440073).
If possible, do not store battery-equipped systems or battery packs at temperatures above 40°C
(104°F). Battery life may be shortened during long-term storage above this temperature.
Fully charge the battery pack before placing system into storage, at recharge intervals shown in
the table and again when the system is put into or returned to service.
If battery-equipped systems will be stored for 6 months or longer, recharge the battery pack as
shown in the following table. Charging the battery pack during storage will reduce the possibility
of shortened battery life during storage up to one year. Battery life may be reduced during storage
times longer than one year even with proper battery maintenance.
Recharge intervals for battery packs in storage with the battery circuit breaker/isolation switch
OFF depend on ambient storage temperatures. Do not exceed the battery pack recharge intervals
shown in the following table. Recharge intervals also apply to UCB/JUCB batteries stored
unplugged from UCB/JUCB.

Storage Temperature Recharge Interval (Days)

< 20°C (68°F) 180

20°C (68°F) to 30°C (86°F) 90

30°C (86°F) to 40°C (104°F) 45

40°C (104°F) to 50°C (122°F) 20

50°C (122°F) to 60°C (140°F) 5

The battery circuit breaker acts as an isolation switch to allow battery disconnection for system
service or for long-term system storage. Set battery circuit breaker to OFF under any of the
following conditions:
● while performing microturbine maintenance/service tasks;
● when transporting the microturbine;
● if microturbine will not be operated for a period longer than 14 days.

2.3.1. Sleep Mode


Batteries start the microturbine and produce transient power immediately after start-up when
operating in Stand Alone mode.
They must be recharged more often and maintained at a higher state of charge (SoC) while the
system is in Sleep mode. Ambient storage temperatures determine recharge intervals during
Sleep Mode as specified in the following table.
If battery voltage is 180VDC or less, perform a Grid Connect Idle Recharge at the intervals shown
in the table. If the microturbine cannot be operated, use the Capstone External Battery Charger
(440073, 440276 HazLoc) to recharge the battery pack.

440386 Rev B (November 2019) Page 9 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without
incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

NOTE
Recharge intervals in the following table do not apply to UCB/JUCB batteries.

Ambient Temperature Recharge Interval (Days)

< 20°C (68°F) 35

20°C (68°F) to 30°C (86°F) 22


30°C (86°F) to 40°C (104°F) 15

40°C (104°F) to 50°C (122°F) 10

50°C (122°F) to 60°C (140°F) 7

NOTE
If the system will be in Stand Alone Sleep Mode for more than 5 to 7 days,
disconnect modem (if installed) to avoid UCB/JUCB battery discharge.

2.3.2. Automatic Battery Charge


The microturbine system will maintain the battery pack at approximately 80 percent SoC during
operation. This allows for sourcing and power transient sinking in Stand Alone Mode. After an
OFF command, the system will continue to run and will recharge the battery to at least 95 percent
SoC or for 45 minutes, whichever occurs first.

2.3.3. Equalization Charge


During normal use, battery cell capacity and charge becomes unequal. The microturbine can be
programmed to perform an equalization charge cycle to maintain a consistent charge across all
cells. The time to complete an equalization charge may be up to 4 hours.
Use Capstone Remote Monitoring Software (CRMS) to set charge intervals (see appropriate
CRMS Manual (Table 1).
If the system is not operating or is in storage, and is connected to the electric utility grid, command
a manual equalization charge as follows:

System Data Menu: Enter Password.


From Display Panel  Navigate to:
Stand Alone > Local Batt Chg > Enable: Press Accept

Select Settings: Battery Management


From CRMS/CRMS-APS  Set Equalization Charge slider to Enable

440386 Rev B (November 2019) Page 10 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without
incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

3. General Maintenance Procedures


3.1. General Cleaning and Inspection
During any site visit perform the following:
1. Inspect all enclosure panel/door seals and exhaust stack seal(s)/gasket(s). Ensure all
gaskets are present, intact and that there are no gaps between gaskets and doors.
Replace any damaged seal(s)/gasket(s).
2. Inspect all air intake paths – engine combustion air and electronics cooling air. Remove
dirt and debris, clean air paths as necessary.
3. Inspect all engine exhaust paths. Remove dirt and debris, clean exhaust paths as
necessary.
4. Inspect and remove debris from enclosure interior. Use vacuum cleaner and/or damp,
lint-free cloths as necessary to remove debris.
5. Inspect all fuel system fittings and components for leaks. Tighten fittings, repair leaks,
and/or replace damaged components, as required.
6. Inspect and secure any loose cables and harnesses.
7. Ensure that no cables or flexible conduits rest on either the brake resistors or High
Power Connection Module (HPCM).
8. Inspect surrounding area (3m/10ft radius where possible) for excessive dirt, dust or other
sources of air contamination. Clean surrounding area thoroughly to reduce dirt and dust
intake into microturbine. Refresh gravel at sites where gravel is used to reduce fine
ground-level dirt.
9. Inspect enclosure sides and roof for damage and chipped/peeling paint. Touch up paint
if necessary.

3.2. Site Air Quality, Air Filter and Internal Component


Maintenance
All air contains pollutants. While many of these pollutants are harmless to the microturbine
system, some air-borne substances will or can cause serious engine damage.
Pollutant particles range in size from small chemical and smoke particles (such as suspended
salts, minerals and corrosive compounds) to large substances (such as industrial dusts and
insects).
Environmental and seasonal variations affect air quality. Agricultural activity, natural vegetation
growth (sap, pollen, seeding, etc.), construction, and nearby industrial operations all contribute to
air-borne particulates. High concentrations of these particles is considered adverse air quality.
Capstone provides air filters for standard applications to trap harmful particles in the engine intake
air. Aluminum mesh filters trap particles larger than 15 microns in the enclosure and heatsink air

440386 Rev B (November 2019) Page 11 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without
incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

flow. Engine intake air and enclosure air filters require periodic cleaning or replacement as shown
in the maintenance tables.
Particles will cling to surfaces inside the system enclosure. When mixed with naturally occurring
moisture, this particle buildup may form restrictions to air flow over heatsinks and other
components that rely on cooling air flow. Overheating can occur, and lead to reduced performance
and/or system shutdown or failure. Other electronic and mechanical devices can be adversely
affected by poor air quality. Corrosion, caked-on dirt or discolored component surfaces may be
signs of adverse air quality.

3.2.1. Site-Specific Air Filter Replacement Interval Evaluation


At sites where adverse air quality exists, establish a site-specific air filter and heatsink cleaning
service interval as follows.
1. Establish a site air quality profile for new/newly commissioned systems.
a. Evaluate environmental air for obvious pollutants. Observe any active agricultural,
industrial, heavy construction activity, vehicle exhaust or natural pollution sources
such as bodies of water, large trees, dense insect populations, etc.
b. Create a short written description of obvious site pollutants and save with system
maintenance records.
c. Check engine air filter differential air pressure value (CRMS-Maintenance Edition,
Microturbine Data Window 3, parameter 219) via remote access every 30 days or
750 running hours for one year to establish a seasonal-cyclic baseline for long-term,
routine inspection. A value greater than .289 psia (8” WC) indicates a warning to
replace the filter. A value of .4335 (12” WC) indicates a clogged filter that must be
replaced immediately. When filters are replaced, examine filters carefully and note
filter condition (amount of clogging) and contaminants present. See Figure 1 (CRMS-
Maintenance Edition v5.6 shown; other versions similar).

Figure 1. Engine Air Filter Differential

2. Use site profile information to supplement air filter inspection and replacement intervals
listed in scheduled maintenance tables.
3. Also monitor system for “9043” fault declarations, which may indicate that IGBT heat
sinks are overheating due to contaminant buildup and require cleaning.

440386 Rev B (November 2019) Page 12 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without
incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

4. Fuel System Inspection and Maintenance


4.1. Gaseous Fuel Fittings and Components
Inspect the entire fuel system for leaks according to the maintenance schedule and whenever a
fuel system component is loosened, disconnected or replaced.
1. Inspect all fittings, connections, filters, valves, and gas compressors for leaks, from the
fuel supply inlet into the microturbine. Tighten fittings, repair leaks, and/or replace
damaged components, as required.
2. To leak check upstream of the microturbine internal fuel shutoff valve, check the fuel line
and all fittings for leaks using a leak detector such as Snoop®, soapy water, or a gas
sniffer. Capstone kit 610125-1XX contains Loctite® #567 and instructions for use with
NPT fittings (440147).
3. To check the fuel system downstream of the microturbine internal fuel shutoff valve,
proceed as follows:

ELECTRICAL WARNING
ELECTRICAL HAZARD! Use extreme caution and wear appropriate PPE
(Personal Protective Equipment) when working on energized equipment. Failure
to obey this warning may result in personal injury or death.
a. Start engine.
b. With engine running at idle, use leak detector to check fuel tubes and fittings, fuel
regulator (if installed), fuel filter and manifold connections for leaks. If using a liquid
leak solution, absorb excess liquid with shop towels to ensure no liquid drops onto
the electronic controllers.
c. If a gaseous fuel leak is found, stop the system immediately. Close the main fuel
supply valve. Repair the leak. Tighten fittings to specified torque (440072). Capstone
kit 610125-1XX contains Loctite® #567 and instructions for use with NPT fittings
(440147).
d. If a compression fitting cannot be sealed, do not tighten past specified torque
(440072). Order and install a replacement tube and fitting.
4. After tightening or replacing a fitting, open fuel supply inlet valve, start engine, and
confirm that leak has been repaired.

NOTE
When compressor is operating at 0 kW demanded load, compressor bottom sight
glass must be ½-full and top sight glass must be empty.

5. For LPNG microturbines: Check oil levels in primary oil separator, and add or remove
oil as needed. See note above regarding turbine operation and required oil levels.
6. If a gaseous fuel leak persists, contact Capstone Technical Support.

440386 Rev B (November 2019) Page 13 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without
incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

4.2. Liquid Fuel Fittings and Components

WARNING
FUEL EXPOSURE HAZARD! Wear appropriate personal protective equipment
including fuel-resistant gloves and eye protection when handling fuel system
components. Exposure to liquid fuel may cause skin and eye irritation or injury.
Inspect the entire fuel system for leaks according to the maintenance schedule and whenever a
fuel system component is loosened, disconnected or replaced. Leak check fuel filter housing after
fuel filter inspection.
1. Inspect all fittings, connections, filters, fuel pumps, and valves from the fuel supply inlet
into the microturbine for fuel build-up and/or leaks. Tighten fittings, repair leaks, and/or
replace leaking or damaged components.
2. Check for excessive fuel build-up on surfaces of components and assemblies where fuel
may drip and accumulate. Evidence of fuel leakage may include small liquid puddles or
oily dirt smudges. Tighten fittings and/or replace leaking or damaged components.
3. If a liquid fuel leak persists, contact Capstone Technical Support.
4. Check oil level in air assist compressor.
a. If system is operating, compressor sight-glass should be 1/2 covered by oil. If level is
lower, add oil.
b. If system is not operating, check oil as follows:
i. Make sure compressor vent cycle is complete.
ii. Open test valve to vent pressure from the aftercooler and pipework.
iii. Make sure that compressor pressure gauge indicates 0 psi.
iv. Oil should completely cover sight-glass. If level is lower, add oil.

5. Scheduled Maintenance Tables


Following are the Scheduled Maintenance Tables for Capstone Model C200/C1000 Series
systems. For each system type addressed, the first table covers the first 80,000 hours of
operation, and the following table covers 80,000 hours to 160,000 hours.

5.1. Capstone System Scheduled Maintenance Tables


Following are the Microturbine system maintenance tables. Maintenance tables for Microturbine
Accessories following Section 5.2.

440386 Rev B (November 2019) Page 14 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without
incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation • 16640 Stagg Street • Van Nuys • CA 91406 • USA
Maintenance Guide: Capstone C200/C1000 Series Microturbine

Table 1. C200/C1000 High Pressure Natural Gas and Propane (Fuel Types H, P) Maintenance Schedule – 4K to 80K Hours
Work

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00
Maintenance Component

0
Comments

00

00

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0
Instruction

12

16

20

24

28

32

36

40

44

48

52

56

60

64

68

72

76

80
4,

8,
Engi ne Ai r Fi l ter 440213
El ectroni cs Ai r Fi l ter 440213
Air Filtration
440342, Es ta bl i s h s i te-s peci fi c a i r fi l ter a nd hea ts i nk cl ea ni ng i nterva l See Site-Specific Air Filter Replacement Interval Evaluation. Cl ea n or
440185, repl a ce uni ts a s needed.
IGBT a nd El ectroni c Hea t Si nks
440250,
440186

Anti -Condens a ti on Hea ters Ins pect every 12 months 1 Hi gh humi di ty s ys tems onl y.

Fuel Sys tem (Li nes a nd Fi tti ngs ) S S S S S S S S S S S S S S S S S S S S See Gaseous Fuel Fittings and Components s ecti on i n thi s document.

• Perform Ba y MΩ i ns ul a ti on check a t hea ter el ement juncti on box.


Nomi na l Ω rea di ng s houl d be grea ter tha n 10 MΩ.
Fuel Supply, Combustion

Hea t Tra ce Wi ri ng (Propa ne Onl y) Perform MegOhm Check every 12 months • Perform Fuel Hea der Ω i ns ul a ti on check to ens ure proper opera ti on
of a l l ci rcui t l ea ds . Nomi na l Ω rea di ng s houl d be grea ter tha n 10 MΩ.
• If MΩ check fa i l s , conta ct Ca ps tone Techni ca l Support.

Inl i ne Fuel Fi l ter I R I R I R I R


More frequent repl a cement of fuel fi l ters a nd va l ves ma y i ndi ca te a n
Fuel Shutoff Va l ve 440217 R envi ronmenta l , i ns ta l l a ti on, or fuel qua l i ty i s s ue tha t needs to be
a ddres s ed.
Fuel Va l ve (Woodwa rd Va l ve) 440209 R

Injector As s embl i es 440193 I I R I I R I I R I I R Ins pect for i njector tube s cori ng or cutti ng, repl a ce i f cut through.
440192,
Igni ter R R R R R R R R R R
440279
440304,
Engi ne Combus tor Li ner I I R I I R Repl a ce i f cra cki ng, wa l l brea ches or other da ma ge obs erved.
440333
Batteries

UCB Ba ttery (Dua l Mode onl y) 440212 Repl a ce every 2 yea rs

Repl a ce every 3 yea rs or Refer to Battery Technical Reference (410044) for expected l i fe vs . duty
Ba ttery Pa ck (Dua l Mode onl y) 440216
20,000 hrs of mi croturbi ne opera ti on (whi chever occurs fi rs t) cycl e, a nd Battery Maintenance for recha rge i nterva l s .
Ba y El ectroni cs Fa n a nd EPDB Fa n R R
Powerhead and Other Electronics and Cables

More frequent repl a cement ma y i ndi ca te s i te ha rmoni c di s torti on


EMI Fi l ter R R R R
l evel s tha t exceed Ca ps tone s peci fi ca ti ons .
Ambi ent Cl i ma te Modul e More frequent repl a cement ma y be neces s a ry ba s ed on a mbi ent a i r
R R
a nd Vi nyl Tube condi ti ons (a i rborne pa rti cul a tes ) a t s i te.
Pers ona l i ty Modul es
440188 R R
(Fra me a nd Engi ne)
GCM, LCM, BCM Power Boa rds a nd
R
Ca pa ci tors (BCM i n Dua l Mode Onl y)
Externa l l y Acces s i bl e Ca bl es a nd Hi gh Humi di ty s ys tems : Ins pect every 12 months ; Repl a ce i f neces s a ry
Check conta cts a nd s ea ti ng.
Ha rnes s es Al l Others : Ins pect every 5 yea rs ; Repl a ce i f neces s a ry
Powerhea d 440316 R R
Dump Va l ve Hos e a nd Repl a ce when repl a ci ng powerhea d, a nd i f cra cki ng or bri ttl enes s i s
R R
Genera tor Bl ower Hos e obs erved.
Powerhea d Shroud Ora nge Sea l I R Repl a ce i f cra cked or bri ttl e.
Si l i cone/Fi bergl a s s Exha us t Sl eeves I R Repl a ce i f da ma ged.
Exha us t Ba ckfl ow Va l ve Sys tems wi th common exha us t onl y. Repl a ce i f da ma ge or
440334 I I I I I I I I I I
(If i ns ta l l ed) deteri ora ti on i s obs erved.
Encl os ure Pa nel Acous ti c Foa m I I I R Repl a ce i f cra cked or bri ttl e.
1
Power hea ters ON, wa i t 5 mi nutes . Veri fy a l l hea ters a re a t l ea s t 10ºC (18ºF) a bove a mbi ent tempera ture. Legend
Hea ters a re externa l l y powered. Refer to Ca ps tone Mi croturbi ne Hi gh Humi di ty Pa cka ge Appl i ca ti on Gui de
I = Inspect R = Replace
(480035).
C = Clean S = See instructions in this document

440386 Rev B (November 2019) Page 15 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without incurring any obligation either with respect to
equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

Table 2. C200/C1000 High Pressure Natural Gas and Propane (Fuel Types H, P) Maintenance Schedule – 84K to 160K Hours
Work

10 0

10 0

11 0

11 0

12 0

12 0

12 0

13 0

13 0

14 0

14 0

14 0

15 0

15 0

16 0
0
00

00

00

10 0
Maintenance Component

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00
Comments

0
,0

,0

,0

,0
Instruction

0,

4,

8,

2,

6,

0,

4,

8,

2,

6,

0,

4,

8,

2,

6,

0,
84

88

92

96
Engi ne Ai r Fi l ter 440213
El ectroni cs Ai r Fi l ter 440213
Air Filtration
440342, Es ta bl i s h s i te-s peci fi c a i r fi l ter a nd hea ts i nk cl ea ni ng i nterva l See Site-Specific Air Filter Replacement Interval Evaluation. Cl ea n or
440185, repl a ce uni ts a s needed.
IGBT a nd El ectroni c Hea t Si nks
440250,
440186
1
Anti -Condens a ti on Hea ters Ins pect every 12 months Hi gh humi di ty s ys tems onl y.

Fuel Sys tem (Li nes a nd Fi tti ngs ) S S S S S S S S S S S S S S S S S S S S See Gaseous Fuel Fittings and Components s ecti on i n thi s document.

• Perform Ba y MΩ i ns ul a ti on check a t hea ter el ement juncti on box.


Nomi na l Ω rea di ng s houl d be grea ter tha n 10 MΩ.
Fuel Supply, Combustion

Hea t Tra ce Wi ri ng (Propa ne Onl y) Perform MegOhm Check every 12 months • Perform Fuel Hea der Ω i ns ul a ti on check to ens ure proper opera ti on
of a l l ci rcui t l ea ds . Nomi na l Ω rea di ng s houl d be grea ter tha n 10 MΩ.
• If MΩ check fa i l s , conta ct Ca ps tone Techni ca l Support.

Inl i ne Fuel Fi l ter I R I R I R I R


More frequent repl a cement of fuel fi l ters a nd va l ves ma y i ndi ca te a n
Fuel Shutoff Va l ve 440217 R envi ronmenta l , i ns ta l l a ti on, or fuel qua l i ty i s s ue tha t needs to be
a ddres s ed.
Fuel Va l ve (Woodwa rd Va l ve) 440209 R

Injector As s embl i es 440193 I I R I I R I I R I I R Ins pect for i njector tube s cori ng or cutti ng, repl a ce i f cut through.
440192,
Igni ter R R R R R R R R R R
440279
440304,
Engi ne Combus tor Li ner I I R I I R Repl a ce i f cra cki ng, wa l l brea ches or other da ma ge obs erved.
440333
Batteries

UCB Ba ttery (Dua l Mode onl y) 440212 Repl a ce every 2 yea rs

Repl a ce every 3 yea rs or Refer to Battery Technical Reference (410044) for expected l i fe vs . duty
Ba ttery Pa ck (Dua l Mode onl y) 440216
20,000 hrs of mi croturbi ne opera ti on (whi chever occurs fi rs t) cycl e, a nd Battery Maintenance for recha rge i nterva l s .
Ba y El ectroni cs Fa n a nd EPDB Fa n R R
Powerhead and Other Electronics and Cables

More frequent repl a cement ma y i ndi ca te s i te ha rmoni c di s torti on


EMI Fi l ter R R R R
l evel s tha t exceed Ca ps tone s peci fi ca ti ons .
Ambi ent Cl i ma te Modul e More frequent repl a cement ma y be neces s a ry ba s ed on a mbi ent a i r
R R
a nd Vi nyl Tube condi ti ons (a i rborne pa rti cul a tes ) a t s i te.
Pers ona l i ty Modul es
440188 R R
(Fra me a nd Engi ne)
GCM, LCM, BCM Power Boa rds a nd
R
Ca pa ci tors (BCM i n Dua l Mode Onl y)
Externa l l y Acces s i bl e Ca bl es a nd Hi gh Humi di ty s ys tems : Ins pect every 12 months ; Repl a ce i f neces s a ry
Check conta cts a nd s ea ti ng.
Ha rnes s es Al l Others : Ins pect every 5 yea rs ; Repl a ce i f neces s a ry
Powerhea d 440316 R R
Dump Va l ve Hos e a nd Repl a ce when repl a ci ng powerhea d, a nd i f cra cki ng or bri ttl enes s i s
R R
Genera tor Bl ower Hos e obs erved.
Powerhea d Shroud Ora nge Sea l I R Repl a ce i f cra cked or bri ttl e.
Si l i cone/Fi bergl a s s Exha us t Sl eeves I R Repl a ce i f da ma ged.
Exha us t Ba ckfl ow Va l ve Sys tems wi th common exha us t onl y. Repl a ce i f da ma ge or
440334 I I I I I I I I I I
(If i ns ta l l ed) deteri ora ti on i s obs erved.
Encl os ure Pa nel Acous ti c Foa m I I I R Repl a ce i f cra cked or bri ttl e.
1
Power hea ters ON, wa i t 5 mi nutes . Veri fy a l l hea ters a re a t l ea s t 10ºC (18ºF) a bove a mbi ent tempera ture. Legend
Hea ters a re externa l l y powered. Refer to Ca ps tone Mi croturbi ne Hi gh Humi di ty Pa cka ge Appl i ca ti on Gui de
I = Inspect R = Replace
(480035).
C = Clean S = See instructions in this document

440386 Rev B (November 2019) Page 16 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without incurring any obligation either with respect to
equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

Table 3. C200/C1000 Low Pressure Natural Gas (Fuel Type F) Maintenance Schedule – 4K to 80K Hours
Work

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00
Maintenance Component

0
Comments

00

00

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0
Instruction

12

16

20

24

28

32

36

40

44

48

52

56

60

64

68

72

76

80
4,

8,
Engi ne Ai r Fi l ter 440213
El ectroni cs Ai r Fi l ter 440213

Air Filtration
440342, Es ta bl i s h s i te-s peci fi c a i r fi l ter a nd hea ts i nk cl ea ni ng i nterva l See Site-Specific Air Filter Replacement Interval Evaluation. Cl ea n or
440185, repl a ce uni ts a s needed.
IGBT a nd El ectroni c Hea t Si nks
440250,
440186

Anti -Condens a ti on Hea ters Ins pect every 12 months 1 Hi gh humi di ty s ys tems onl y.

Vi s ua l l y i ns pect hea t excha nger exteri or s urfa ces for pi nhol e or wel d
Hea t Excha nger I I I I C I I I I R
joi nt l ea ks .
Pul l tes t a l l power a nd control ca bl es to check for da ma ge, broken
Fuel Gas Booster (FGBR)

Wi ri ng a nd Ca bl i ng 440203 I I I I I I I I I I s tra nds or l oos e mounts . Ens ure a ny termi na l connecti ons a re
properl y s ecured.
Va ri a bl e Frequency Dri ve (VFD) Hea t
C C C C C C C C C C
Si nk
Va ri a bl e Frequency Dri ve (VFD) Fa n Repl a ce every 3 yea rs
Second Sta ge Oi l Sepa ra tor 440201 R R R R R R R R R R
FGBR Oi l 440359 R R R R R R R R R R Dra i n a nd repl eni s h oi l .
Oi l Fi l ter 440358 R R R R R R R R R R
PLC Ba ttery Repl a ce every 3 yea rs
Scrol l Compres s ors R R
Fuel Supply, Combustion

Fuel Sys tem (Li nes a nd Fi tti ngs ) S S S S S S S S S S S S S S S S S S S S See Gaseous Fuel Fittings and Components s ecti on i n thi s document.

Inl i ne Fuel Fi l ter I R I R I R I R


More frequent repl a cement of fuel fi l ters a nd va l ves ma y i ndi ca te a n
Fuel Shutoff Va l ve R envi ronmenta l , i ns ta l l a ti on, or fuel qua l i ty i s s ue tha t needs to be
a ddres s ed.
Fuel Va l ve (Woodwa rd Va l ve) 440209 R
Injector As s embl i es 440317 I I R I I R I I R I I R Ins pect for i njector tube s cori ng or cutti ng, repl a ce i f cut through.
440192,
Igni ter R R R R R R R R R R
440279
440304,
Engi ne Combus tor Li ner I I R I I R Repl a ce i f cra cki ng, wa l l brea ches or other da ma ge obs erved
440333
Batteries

UCB Ba ttery (Dua l Mode onl y) 440212 Repl a ce every 2 yea rs

440066, Repl a ce every 3 yea rs or Refer to Battery Technical Reference (410044) for expected l i fe vs . duty
Ba ttery Pa ck (Dua l Mode onl y)
410072 20,000 hrs of mi croturbi ne opera ti on (whi chever occurs fi rs t) cycl e, a nd Battery Maintenance for recha rge i nterva l s .
Ba y El ectroni cs Fa n a nd EPDB Fa n R R
More frequent repl a cement ma y i ndi ca te s i te ha rmoni c di s torti on
EMI Fi l ter R R R R
Elect and Cables

l evel s tha t exceed Ca ps tone s peci fi ca ti ons .


Ambi ent Cl i ma te Modul e More frequent repl a cement ma y be neces s a ry ba s ed on a mbi ent a i r
R R
a nd Vi nyl Tube condi ti ons (a i rborne pa rti cul a tes ) a t s i te.
Pers ona l i ty Modul es
440188 R R
(Fra me a nd Engi ne)
GCM, LCM, BCM Power Boa rds a nd
R
Ca pa ci tors (BCM i n Dua l Mode Onl y)
Externa l l y Acces s i bl e Ca bl es a nd Hi gh Humi di ty s ys tems : Ins pect every 12 months ; Repl a ce i f neces s a ry
Check conta cts a nd s ea ti ng.
Ha rnes s es Al l Others : Ins pect every 5 yea rs ; Repl a ce i f neces s a ry
Powerhea d 440316 R R
Dump Va l ve Hos e a nd Repl a ce when repl a ci ng powerhea d, a nd i f cra cki ng or bri ttl enes s i s
PH and Other

R R
Genera tor Bl ower Hos e obs erved.
Powerhea d Shroud Ora nge Sea l I R Repl a ce i f cra cked or bri ttl e.
Si l i cone/Fi bergl a s s Exha us t Sl eeves I R Repl a ce i f da ma ged.
Exha us t Ba ckfl ow Va l ve Sys tems wi th common exha us t onl y. Repl a ce i f da ma ge or
440334 I I I I I I I I I I
(If i ns ta l l ed) deteri ora ti on i s obs erved.
Encl os ure Pa nel Acous ti c Foa m I I I R Repl a ce i f cra cked or bri ttl e.
1
Power hea ters ON, wa i t 5 mi nutes . Veri fy a l l hea ters a re a t l ea s t 10ºC (18ºF) a bove a mbi ent tempera ture. Legend
Hea ters a re externa l l y powered. Refer to Ca ps tone Mi croturbi ne Hi gh Humi di ty Pa cka ge Appl i ca ti on Gui de
I = Inspect R = Replace
(480035).
C = Clean S = See instructions in this document

440386 Rev B (November 2019) Page 17 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without incurring any obligation either with respect to
equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

Table 4. C200/C1000 Low Pressure Natural Gas (Fuel Type F) Maintenance Schedule – 84K to 160K Hours
Work

10 0

10 0

11 0

11 0

12 0

12 0

12 0

13 0

13 0

14 0

14 0

14 0

15 0

15 0

16 0
0
00

00

00

10 0
Maintenance Component

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00
Comments

0
,0

,0

,0

,0
Instruction

0,

4,

8,

2,

6,

0,

4,

8,

2,

6,

0,

4,

8,

2,

6,

0,
84

88

92

96
Engi ne Ai r Fi l ter 440213
El ectroni cs Ai r Fi l ter 440213

Air Filtration
440342, Es ta bl i s h s i te-s peci fi c a i r fi l ter a nd hea ts i nk cl ea ni ng i nterva l See Site-Specific Air Filter Replacement Interval Evaluation. Cl ea n or
440185, repl a ce uni ts a s needed.
IGBT a nd El ectroni c Hea t Si nks
440250,
440186

Anti -Condens a ti on Hea ters Ins pect every 12 months 1 Hi gh humi di ty s ys tems onl y.

Vi s ua l l y i ns pect hea t excha nger exteri or s urfa ces for pi nhol e or wel d
Hea t Excha nger I I I I C I I I I R
joi nt l ea ks .
Fuel Gas Booster (FGBR)

Pul l tes t a l l power a nd control ca bl es to check for da ma ge, broken


Wi ri ng a nd Ca bl i ng 440203 I I I I I I I I I I s tra nds or l oos e mounts . Ens ure a ny termi na l connecti ons a re
properl y s ecured.
Va ri a bl e Frequency Dri ve (VFD) Hea t
C C C C C C C C C C
Si nk
Va ri a bl e Frequency Dri ve (VFD) Fa n Repl a ce every 3 yea rs
Ai r/Oi l Seconda ry Sepa ra tor 440201 R R R R R R R R R R
FGBR Oi l 440359 R R R R R R R R R R Dra i n a nd repl eni s h oi l .
Oi l Fi l ter 440358 R R R R R R R R R R
PLC Ba ttery Repl a ce every 3 yea rs
Scrol l Compres s ors R R
Fuel Supply, Combustion

Fuel Sys tem (Li nes a nd Fi tti ngs ) S S S S S S S S S S S S S S S S S S S S See Gaseous Fuel Fittings and Components s ecti on i n thi s document.

Inl i ne Fuel Fi l ter I R I R I R I R


More frequent repl a cement of fuel fi l ters a nd va l ves ma y i ndi ca te a n
Fuel Shutoff Va l ve R envi ronmenta l , i ns ta l l a ti on, or fuel qua l i ty i s s ue tha t needs to be
a ddres s ed.
Fuel Va l ve (Woodwa rd Va l ve) 440209 R
Injector As s embl i es 440317 I I R I I R I I R I I R Ins pect for i njector tube s cori ng or cutti ng, repl a ce i f cut through.
440192,
Igni ter R R R R R R R R R R
440279
440304,
Engi ne Combus tor Li ner I I R I I R Repl a ce i f cra cki ng, wa l l brea ches or other da ma ge obs erved
440333
Batteries

UCB Ba ttery (Dua l Mode onl y) 440212 Repl a ce every 2 yea rs

440066, Repl a ce every 3 yea rs or Refer to Battery Technical Reference (410044) for expected l i fe vs . duty
Ba ttery Pa ck (Dua l Mode onl y)
410072 20,000 hrs of mi croturbi ne opera ti on (whi chever occurs fi rs t) cycl e, a nd Battery Maintenance for recha rge i nterva l s .
Ba y El ectroni cs Fa n a nd EPDB Fa n R R
More frequent repl a cement ma y i ndi ca te s i te ha rmoni c di s torti on
EMI Fi l ter R R R R
Elect and Cables

l evel s tha t exceed Ca ps tone s peci fi ca ti ons .


Ambi ent Cl i ma te Modul e More frequent repl a cement ma y be neces s a ry ba s ed on a mbi ent a i r
R R
a nd Vi nyl Tube condi ti ons (a i rborne pa rti cul a tes ) a t s i te.
Pers ona l i ty Modul es
440188 R R
(Fra me a nd Engi ne)
GCM, LCM, BCM Power Boa rds a nd
R
Ca pa ci tors (BCM i n Dua l Mode Onl y)
Externa l l y Acces s i bl e Ca bl es a nd Hi gh Humi di ty s ys tems : Ins pect every 12 months ; Repl a ce i f neces s a ry
Check conta cts a nd s ea ti ng.
Ha rnes s es Al l Others : Ins pect every 5 yea rs ; Repl a ce i f neces s a ry
Powerhea d 440316 R R
Dump Va l ve Hos e a nd Repl a ce when repl a ci ng powerhea d, a nd i f cra cki ng or bri ttl enes s i s
PH and Other

R R
Genera tor Bl ower Hos e obs erved.
Powerhea d Shroud Ora nge Sea l I R Repl a ce i f cra cked or bri ttl e.
Si l i cone/Fi bergl a s s Exha us t Sl eeves I R Repl a ce i f da ma ged.
Exha us t Ba ckfl ow Va l ve Sys tems wi th common exha us t onl y. Repl a ce i f da ma ge or
440334 I I I I I I I I I I
(If i ns ta l l ed) deteri ora ti on i s obs erved.
Encl os ure Pa nel Acous ti c Foa m I I I R Repl a ce i f cra cked or bri ttl e.
1
Power hea ters ON, wa i t 5 mi nutes . Veri fy a l l hea ters a re a t l ea s t 10ºC (18ºF) a bove a mbi ent tempera ture. Legend
Hea ters a re externa l l y powered. Refer to Ca ps tone Mi croturbi ne Hi gh Humi di ty Pa cka ge Appl i ca ti on Gui de
I = Inspect R = Replace
(480035).
C = Clean S = See instructions in this document

440386 Rev B (November 2019) Page 18 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without incurring any obligation either with respect to
equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

Table 5. C200/C1000 Biogas (Fuel Types A, B) Maintenance Schedule – 4K to 80K Hours


Work

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00
Maintenance Component

0
Comments

00

00

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0
Instruction

12

16

20

24

28

32

36

40

44

48

52

56

60

64

68

72

76

80
4,

8,
Engi ne Ai r Fi l ter 440213
Air Filtration

El ectroni cs Ai r Fi l ter 440213


440342, See Site-Specific Air Filter Replacement Interval Evaluation. Cl ea n or
Es ta bl i s h s i te-s peci fi c a i r fi l ter a nd hea ts i nk cl ea ni ng i nterva l
440185, repl a ce uni ts a s needed.
IGBT a nd El ectroni c Hea t Si nks
440250,
440186
1
Anti -Condens a ti on Hea ters Ins pect every 12 months Hi gh humi di ty s ys tems onl y.
Fuel Sys tem (Li nes a nd Fi tti ngs ) S S S S S S S S S S S S S S S S S S S S See Gaseous Fuel Fittings and Components s ecti on i n thi s document.

Inl i ne Fuel Fi l ter I R I R I R I R I R


Fuel Supply, Combustion

More frequent repl a cement of fuel fi l ters a nd va l ves ma y i ndi ca te


Fuel Shutoff Va l ve 440213 R R R R R a n envi ronmenta l , i ns ta l l a ti on, or fuel qua l i ty i s s ue tha t needs to
be a ddres s ed.
Fuel Va l ve (Woodwa rd Va l ve) 440213 R R

440342,
440185,
Injector As s embl i es I R I R I R I R I R Ins pect for i njector tube s cori ng or cutti ng, repl a ce i f cut through.
440250,
440186
440192,
Igni ter R R R R R R R R R R
440279
440304,
Engi ne Combus tor Li ner I I R I I R Repl a ce i f da ma ge obs erved
440333
Batteries

UCB Ba ttery (Dua l Mode onl y) 440212 Repl a ce every 2 yea rs

Repl a ce every 3 yea rs or Refer to Battery Technical Reference (410044) for expected l i fe vs . duty
Ba ttery Pa ck (Dua l Mode onl y) 440216 cycl e, a nd Battery Maintenance for recha rge i nterva l s .
20,000 hrs of mi croturbi ne opera ti on (whi chever occurs fi rs t)
Ba y El ectroni cs Fa n a nd EPDB Fa n R R
Electronics and Cables

More frequent repl a cement ma y i ndi ca te s i te ha rmoni c di s torti on


EMI Fi l ter R R R R
l evel s tha t exceed Ca ps tone s peci fi ca ti ons .
Ambi ent Cl i ma te Modul e More frequent repl a cement ma y be neces s a ry ba s ed on a mbi ent a i r
R R
a nd Vi nyl Tube condi ti ons (a i rborne pa rti cul a tes ) a t s i te.
Pers ona l i ty Modul es
440188 R R
(Fra me a nd Engi ne)
GCM, LCM, BCM Power Boa rds a nd
R Incl ude a ny a s s oci a ted ca pa ci tor ba nks .
Ca pa ci tors (BCM i n Dua l Mode Onl y)
Externa l l y Acces s i bl e Ca bl es a nd Hi gh Humi di ty s ys tems : Ins pect every 12 months ; Repl a ce i f neces s a ry
Check conta cts a nd s ea ti ng.
Ha rnes s es Al l Others : Ins pect every 5 yea rs ; Repl a ce i f neces s a ry
Powerhead and Other

Powerhea d 440316 R R
Dump Va l ve Hos e a nd Repl a ce when repl a ci ng powerhea d, a nd i f cra cki ng or bri ttl enes s i s
R R
Genera tor Bl ower Hos e obs erved.
Powerhea d Shroud Ora nge Sea l I R I R Repl a ce i f cra cked or bri ttl e.
Si l i cone/Fi bergl a s s Exha us t Sl eeves I R Repl a ce i f da ma ged.
Exha us t Ba ckfl ow Va l ve Sys tems wi th common exha us t onl y. Repl a ce i f da ma ge or
440334 I I I I I I I I I I
(If i ns ta l l ed) deteri ora ti on i s obs erved.
Encl os ure Pa nel Acous ti c Foa m I I I R Repl a ce i f cra cked or bri ttl e.
1
Power hea ters ON, wa i t 5 mi nutes . Veri fy a l l hea ters a re a t l ea s t 10ºC (18ºF) a bove a mbi ent tempera ture. Legend
Hea ters a re externa l l y powered. Refer to Ca ps tone Mi croturbi ne Hi gh Humi di ty Pa cka ge Appl i ca ti on Gui de
I = Inspect R = Replace
(480035).
C = Clean S = See instructions in this document

440386 Rev B (November 2019) Page 19 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without incurring any obligation either with respect to
equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

Table 6. C200/C1000 Biogas (Fuel Types A, B) Maintenance Schedule – 84K to 160K Hours
Work

10 0

10 0

11 0

11 0

12 0

12 0

12 0

13 0

13 0

14 0

14 0

14 0

15 0

15 0

16 0
0
00

00

00

10 0
Maintenance Component

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00
Comments

0
,0

,0

,0

,0
Instruction

0,

4,

8,

2,

6,

0,

4,

8,

2,

6,

0,

4,

8,

2,

6,

0,
84

88

92

96
Engi ne Ai r Fi l ter 440213
Air Filtration

El ectroni cs Ai r Fi l ter 440213


440342, See Site-Specific Air Filter Replacement Interval Evaluation. Cl ea n or
Es ta bl i s h s i te-s peci fi c a i r fi l ter a nd hea ts i nk cl ea ni ng i nterva l
440185, repl a ce uni ts a s needed.
IGBT a nd El ectroni c Hea t Si nks
440250,
440186
1
Anti -Condens a ti on Hea ters Ins pect every 12 months Hi gh humi di ty s ys tems onl y.
Fuel Sys tem (Li nes a nd Fi tti ngs ) S S S S S S S S S S S S S S S S S S S S See Gaseous Fuel Fittings and Components s ecti on i n thi s document.

Inl i ne Fuel Fi l ter I R I R I R I R I R


Fuel Supply, Combustion

More frequent repl a cement of fuel fi l ters a nd va l ves ma y i ndi ca te


Fuel Shutoff Va l ve 440213 R R R R R a n envi ronmenta l , i ns ta l l a ti on, or fuel qua l i ty i s s ue tha t needs to
be a ddres s ed.
Fuel Va l ve (Woodwa rd Va l ve) 440213 R R

440342,
440185,
Injector As s embl i es I R I R I R I R I R Ins pect for i njector tube s cori ng or cutti ng, repl a ce i f cut through.
440250,
440186
440192,
Igni ter R R R R R R R R R R
440279
440304,
Engi ne Combus tor Li ner I I R I I R Repl a ce i f da ma ge obs erved
440333
Batteries

UCB Ba ttery (Dua l Mode onl y) 440212 Repl a ce every 2 yea rs

Repl a ce every 3 yea rs or Refer to Battery Technical Reference (410044) for expected l i fe vs . duty
Ba ttery Pa ck (Dua l Mode onl y) 440216 cycl e, a nd Battery Maintenance for recha rge i nterva l s .
20,000 hrs of mi croturbi ne opera ti on (whi chever occurs fi rs t)
Ba y El ectroni cs Fa n a nd EPDB Fa n R R
Electronics and Cables

More frequent repl a cement ma y i ndi ca te s i te ha rmoni c di s torti on


EMI Fi l ter R R R R
l evel s tha t exceed Ca ps tone s peci fi ca ti ons .
Ambi ent Cl i ma te Modul e More frequent repl a cement ma y be neces s a ry ba s ed on a mbi ent a i r
R R
a nd Vi nyl Tube condi ti ons (a i rborne pa rti cul a tes ) a t s i te.
Pers ona l i ty Modul es
440188 R R
(Fra me a nd Engi ne)
GCM, LCM, BCM Power Boa rds a nd
R
Ca pa ci tors (BCM i n Dua l Mode Onl y)
Externa l l y Acces s i bl e Ca bl es a nd Hi gh Humi di ty s ys tems : Ins pect every 12 months ; Repl a ce i f neces s a ry
Check conta cts a nd s ea ti ng.
Ha rnes s es Al l Others : Ins pect every 5 yea rs ; Repl a ce i f neces s a ry
Powerhead and Other

Powerhea d 440316 R R
Dump Va l ve Hos e a nd Repl a ce when repl a ci ng powerhea d, a nd i f cra cki ng or bri ttl enes s i s
R R
Genera tor Bl ower Hos e obs erved.
Powerhea d Shroud Ora nge Sea l I R I R Repl a ce i f cra cked or bri ttl e.
Si l i cone/Fi bergl a s s Exha us t Sl eeves I R Repl a ce i f da ma ged.
Exha us t Ba ckfl ow Va l ve Sys tems wi th common exha us t onl y. Repl a ce i f da ma ge or
440334 I I I I I I I I I I
(If i ns ta l l ed) deteri ora ti on i s obs erved.
Encl os ure Pa nel Acous ti c Foa m I I I R Repl a ce i f cra cked or bri ttl e.
1
Power hea ters ON, wa i t 5 mi nutes . Veri fy a l l hea ters a re a t l ea s t 10ºC (18ºF) a bove a mbi ent tempera ture. Legend
Hea ters a re externa l l y powered. Refer to Ca ps tone Mi croturbi ne Hi gh Humi di ty Pa cka ge Appl i ca ti on Gui de
I = Inspect R = Replace
(480035).
C = Clean S = See instructions in this document

440386 Rev B (November 2019) Page 20 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without incurring any obligation either with respect to
equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

Table 7. C200/C1000 High Pressure Sour Gas (Fuel Type S) Maintenance Schedule – 4K to 80K Hours
Work

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00
Maintenance Component

0
Comments

00

00

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0
Instruction

12

16

20

24

28

32

36

40

44

48

52

56

60

64

68

72

76

80
4,

8,
Engi ne Ai r Fi l ter 440213
Air Filtration

El ectroni cs Ai r Fi l ter 440213


440342, See Site-Specific Air Filter Replacement Interval Evaluation. Cl ea n or
Es ta bl i s h s i te-s peci fi c a i r fi l ter a nd hea ts i nk cl ea ni ng i nterva l
440185, repl a ce uni ts a s needed.
IGBT a nd El ectroni c Hea t Si nks
440250,
440186
Anti -Condens a ti on Hea ters Ins pect every 12 months 1 Hi gh humi di ty s ys tems onl y.
Fuel Sys tem (Li nes a nd Fi tti ngs ) S S S S S S S S S S S S S S S S S S S S See Gaseous Fuel Fittings and Components s ecti on i n thi s document.
Fuel Supply, Combustion

Inl i ne Fuel Fi l ter I R I R I R I R I R


More frequent repl a cement of fuel fi l ters a nd va l ves ma y i ndi ca te a n
Fuel Shutoff Va l ve 440217 R R R R R envi ronmenta l , i ns ta l l a ti on, or fuel qua l i ty i s s ue tha t needs to be
a ddres s ed.
Fuel Va l ve (Woodwa rd Va l ve) 440209 R R R R R

Injector As s embl i es 440193 I R I R I R I R I R Ins pect for i njector tube s cori ng or cutti ng, repl a ce i f cut through.
440192,
Igni ter R R R R R R R R R R
440279
440304,
Engi ne Combus tor Li ner I I R I I R Repl a ce i f cra cki ng, wa l l brea ches or other da ma ge obs erved.
440333
Batteries

UCB Ba ttery (Dua l Mode onl y) 440212 Repl a ce every 2 yea rs

Repl a ce every 3 yea rs or Refer to Battery Technical Reference (410044) for expected l i fe vs . duty
Ba ttery Pa ck (Dua l Mode onl y) 440216
20,000 hrs of mi croturbi ne opera ti on (whi chever occurs fi rs t) cycl e, a nd Battery Maintenance for recha rge i nterva l s .
Ba y El ectroni cs Fa n a nd EPDB Fa n R R
Powerhead and Other Electronics and Cables

More frequent repl a cement ma y i ndi ca te s i te ha rmoni c di s torti on


EMI Fi l ter R R R R
l evel s tha t exceed Ca ps tone s peci fi ca ti ons .
Ambi ent Cl i ma te Modul e More frequent repl a cement ma y be neces s a ry ba s ed on a mbi ent a i r
R R
a nd Vi nyl Tube condi ti ons (a i rborne pa rti cul a tes ) a t s i te.
Pers ona l i ty Modul es
440188 R R
(Fra me a nd Engi ne)
GCM, LCM, BCM Power Boa rds a nd
R Incl ude a ny a s s oci a ted ca pa ci tor ba nks .
Ca pa ci tors (BCM i n Dua l Mode Onl y)
Externa l l y Acces s i bl e Ca bl es a nd Hi gh Humi di ty s ys tems : Ins pect every 12 months ; Repl a ce i f neces s a ry
Check conta cts a nd s ea ti ng.
Ha rnes s es Al l Others : Ins pect every 5 yea rs ; Repl a ce i f neces s a ry
Powerhea d 440316 R R
Dump Va l ve Hos e a nd Repl a ce when repl a ci ng powerhea d, a nd i f cra cki ng or bri ttl enes s
R R
Genera tor Bl ower Hos e obs erved
Powerhea d Shroud Ora nge Sea l R R R R Repl a ce ea rl i er i f cra cked or bri ttl e
Si l i cone/Fi bergl a s s Exha us t Sl eeves R R
Exha us t Ba ckfl ow Va l ve
440334 I I I I I I I I I I Sys tems wi th common exha us t onl y
(If i ns ta l l ed)
Encl os ure Pa nel Acous ti c Foa m I R I R Repl a ce ea rl i er i f cra cked or bri ttl e
1
Fi l ters ma y requi re more frequent a ttenti on dependi ng on envi ronment, i ns ta l l a ti on, a nd/or a i r/fuel qua l i ty. Legend
Ins pect new i ns ta l l a ti ons frequentl y to determi ne bes t i ns pecti on/repl a cement peri ods for a i r a nd fuel
I = Inspect R = Replace
fi l ters .
C = Clean S = See instructions in this document

440386 Rev B (November 2019) Page 21 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without incurring any obligation either with respect to
equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

Table 8. C200/C1000 High Pressure Sour Gas (Fuel Type S) Maintenance Schedule – 84K to 160K Hours
Work

10 0

10 0

11 0

11 0

12 0

12 0

12 0

13 0

13 0

14 0

14 0

14 0

15 0

15 0

16 0
0
00

00

00

10 0
Maintenance Component

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00
Comments

0
,0

,0

,0

,0
Instruction

0,

4,

8,

2,

6,

0,

4,

8,

2,

6,

0,

4,

8,

2,

6,

0,
84

88

92

96
Engi ne Ai r Fi l ter 440213
Air Filtration

El ectroni cs Ai r Fi l ter 440213


440342, See Site-Specific Air Filter Replacement Interval Evaluation. Cl ea n or
Es ta bl i s h s i te-s peci fi c a i r fi l ter a nd hea ts i nk cl ea ni ng i nterva l
440185, repl a ce uni ts a s needed.
IGBT a nd El ectroni c Hea t Si nks
440250,
440186
1
Anti -Condens a ti on Hea ters Ins pect every 12 months Hi gh humi di ty s ys tems onl y.
Fuel Sys tem (Li nes a nd Fi tti ngs ) S S S S S S S S S S S S S S S S S S S S See Gaseous Fuel Fittings and Components s ecti on i n thi s document.
Fuel Supply, Combustion

Inl i ne Fuel Fi l ter I R I R I R I R I R


More frequent repl a cement of fuel fi l ters a nd va l ves ma y i ndi ca te a n
Fuel Shutoff Va l ve 440217 R R R R R envi ronmenta l , i ns ta l l a ti on, or fuel qua l i ty i s s ue tha t needs to be
a ddres s ed.
Fuel Va l ve (Woodwa rd Va l ve) 440209 R R R R R

Injector As s embl i es 440193 I R I R I R I R I R Ins pect for i njector tube s cori ng or cutti ng, repl a ce i f cut through.
440192,
Igni ter R R R R R R R R R R
440279
440304,
Engi ne Combus tor Li ner I I R I I R Repl a ce i f cra cki ng, wa l l brea ches or other da ma ge obs erved.
440333
Batteries

UCB Ba ttery (Dua l Mode onl y) 440212 Repl a ce every 2 yea rs

Repl a ce every 3 yea rs or Refer to Battery Technical Reference (410044) for expected l i fe vs . duty
Ba ttery Pa ck (Dua l Mode onl y) 440216
20,000 hrs of mi croturbi ne opera ti on (whi chever occurs fi rs t) cycl e, a nd Battery Maintenance for recha rge i nterva l s .
Ba y El ectroni cs Fa n a nd EPDB Fa n R R
Powerhead and Other Electronics and Cables

More frequent repl a cement ma y i ndi ca te s i te ha rmoni c di s torti on


EMI Fi l ter R R R R
l evel s tha t exceed Ca ps tone s peci fi ca ti ons .
Ambi ent Cl i ma te Modul e More frequent repl a cement ma y be neces s a ry ba s ed on a mbi ent a i r
R R
a nd Vi nyl Tube condi ti ons (a i rborne pa rti cul a tes ) a t s i te.
Pers ona l i ty Modul es
440188 R R
(Fra me a nd Engi ne)
GCM, LCM, BCM Power Boa rds a nd
R
Ca pa ci tors (BCM i n Dua l Mode Onl y)
Externa l l y Acces s i bl e Ca bl es a nd Hi gh Humi di ty s ys tems : Ins pect every 12 months ; Repl a ce i f neces s a ry
Check conta cts a nd s ea ti ng.
Ha rnes s es Al l Others : Ins pect every 5 yea rs ; Repl a ce i f neces s a ry
Powerhea d 440316 R R
Dump Va l ve Hos e a nd Repl a ce when repl a ci ng powerhea d, a nd i f cra cki ng or bri ttl enes s
R R
Genera tor Bl ower Hos e obs erved
Powerhea d Shroud Ora nge Sea l R R R R Repl a ce ea rl i er i f cra cked or bri ttl e
Si l i cone/Fi bergl a s s Exha us t Sl eeves R R
Exha us t Ba ckfl ow Va l ve
440334 I I I I I I I I I I Sys tems wi th common exha us t onl y
(If i ns ta l l ed)
Encl os ure Pa nel Acous ti c Foa m I R I R Repl a ce ea rl i er i f cra cked or bri ttl e
1
Fi l ters ma y requi re more frequent a ttenti on dependi ng on envi ronment, i ns ta l l a ti on, a nd/or a i r/fuel qua l i ty. Legend
Ins pect new i ns ta l l a ti ons frequentl y to determi ne bes t i ns pecti on/repl a cement peri ods for a i r a nd fuel
I = Inspect R = Replace
fi l ters .
C = Clean S = See instructions in this document

440386 Rev B (November 2019) Page 22 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without incurring any obligation either with respect to
equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

Table 9. C200/C1000 Liquid Fuel (Fuel Type D) Maintenance Schedule – 4K to 80K Hours
Work

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00
Maintenance Component

0
Comments

00

00

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0
Instruction

12

16

20

24

28

32

36

40

44

48

52

56

60

64

68

72

76

80
4,

8,
Engi ne Ai r Fi l ter 440213
El ectroni cs Ai r Fi l ter 440213
440342,
440185, See Site-Specific Air Filter Replacement Interval Evaluation. Cl ea n or
Air Filtration

IGBT a nd El ectroni c Hea t Si nks Es ta bl i s h s i te-s peci fi c a i r fi l ter a nd hea ts i nk cl ea ni ng i nterva l


440250, repl a ce uni ts a s needed.
440186
Ai r Compres s or Ma i n Fi l ter El ement
Ai r Compres s or Sa fety Fi l ter El ement
Ai r As s i s t Hea t Excha ngers I I I I I I I I I I I I I I I I I I I I Vi s ua l l y i ns pect hea t excha nger exteri or s urfa ces . Cl ea n i f neces s a ry.
Sta ge 1 a nd Sta ge 2 Ai r Dryers R R R R R R R R R R
1
Anti -Condens a ti on Hea ters Ins pect every 12 months Hi gh humi di ty s ys tems onl y.
Fuel Sys tem (Li nes a nd Fi tti ngs ) S S S S S S S S S S S S S S S S S S S S See Gaseous Fuel Fittings and Components s ecti on i n thi s document.
Fuel Boos t Pump 440368 R R R R R R R R R R
Fuel Supply, Combustion

Boos t Pump Fuel Fi l ter 440367 R R R R R R R R R R


Fuel Control Pump R R R R

Inl i ne Fuel Fi l ter I R I R I R I R I R More frequent repl a cement of fuel fi l ters a nd va l ves ma y i ndi ca te a n
envi ronmenta l , i ns ta l l a ti on, or fuel qua l i ty i s s ue tha t needs to be
Fuel Shutoff Va l ve R R a ddres s ed.

Injector As s embl i es 440317 R R R R Ins pect for i njector tube s cori ng or cutti ng, repl a ce i f cut through.
440192,
Igni ter R R R R R R R R R R
440279
440304,
Engi ne Combus tor Li ner I I R I I R Repl a ce i f cra cki ng, wa l l brea ches or other da ma ge obs erved.
440333
Batteries

UCB Ba ttery (Dua l Mode onl y) 440212 Repl a ce every 2 yea rs

Repl a ce every 3 yea rs or Refer to Battery Technical Reference (410044) for expected l i fe vs . duty
Ba ttery Pa ck (Dua l Mode onl y) 440216
20,000 hrs of mi croturbi ne opera ti on (whi chever occurs fi rs t) cycl e, a nd Battery Maintenance for recha rge i nterva l s .
Ba y El ectroni cs Fa n a nd EPDB Fa n R R
Powerhead and Other Electronics and Cables

More frequent repl a cement ma y i ndi ca te s i te ha rmoni c di s torti on


EMI Fi l ter R R R R
l evel s tha t exceed Ca ps tone s peci fi ca ti ons .
Ambi ent Cl i ma te Modul e More frequent repl a cement ma y be neces s a ry ba s ed on a mbi ent a i r
R R
a nd Vi nyl Tube condi ti ons (a i rborne pa rti cul a tes ) a t s i te.
Pers ona l i ty Modul es
440188 R R
(Fra me a nd Engi ne)
GCM, LCM, BCM Power Boa rds a nd
R Incl ude a ny a s s oci a ted ca pa ci tor ba nks .
Ca pa ci tors (BCM i n Dua l Mode Onl y)
Externa l l y Acces s i bl e Ca bl es a nd Hi gh Humi di ty s ys tems : Ins pect every 12 months ; Repl a ce i f neces s a ry
Check conta cts a nd s ea ti ng.
Ha rnes s es Al l Others : Ins pect every 5 yea rs ; Repl a ce i f neces s a ry
Powerhea d 440316 R R
Dump Va l ve Hos e a nd Repl a ce when repl a ci ng powerhea d, a nd i f cra cki ng or bri ttl enes s i s
R R
Genera tor Bl ower Hos e obs erved.
Powerhea d Shroud Ora nge Sea l I R Repl a ce i f cra cked or bri ttl e.
Si l i cone/Fi bergl a s s Exha us t Sl eeves I R Repl a ce i f da ma ged.
Exha us t Ba ckfl ow Va l ve Sys tems wi th common exha us t onl y. Repl a ce i f da ma ge or
440334 I I I I I I I I I I
(If i ns ta l l ed) deteri ora ti on i s obs erved.
Encl os ure Pa nel Acous ti c Foa m I I I R Repl a ce i f cra cked or bri ttl e.
1
Power hea ters ON, wa i t 5 mi nutes . Veri fy a l l hea ters a re a t l ea s t 10ºC (18ºF) a bove a mbi ent tempera ture. Legend
Hea ters a re externa l l y powered. Refer to Ca ps tone Mi croturbi ne Hi gh Humi di ty Pa cka ge Appl i ca ti on Gui de
I = Inspect R = Replace
(480035).
C = Clean S = See instructions in this document

440386 Rev B (November 2019) Page 23 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without incurring any obligation either with respect to
equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

Table 10. C200/C1000 Liquid Fuel (Fuel Type D) Maintenance Schedule – 84K to 160K Hours
Work

10 0

10 0

11 0

11 0

12 0

12 0

12 0

13 0

13 0

14 0

14 0

14 0

15 0

15 0

16 0
0
00

00

00

10 0
Maintenance Component

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00
Comments

0
,0

,0

,0

,0
Instruction

0,

4,

8,

2,

6,

0,

4,

8,

2,

6,

0,

4,

8,

2,

6,

0,
84

88

92

96
Engi ne Ai r Fi l ter 440213
El ectroni cs Ai r Fi l ter 440213
440342,
440185, See Site-Specific Air Filter Replacement Interval Evaluation. Cl ea n or
Air Filtration

IGBT a nd El ectroni c Hea t Si nks Es ta bl i s h s i te-s peci fi c a i r fi l ter a nd hea ts i nk cl ea ni ng i nterva l


440250, repl a ce uni ts a s needed.
440186
Ai r Compres s or Ma i n Fi l ter El ement
Ai r Compres s or Sa fety Fi l ter El ement
Ai r As s i s t Hea t Excha ngers I I I I I I I I I I I I I I I I I I I I Vi s ua l l y i ns pect hea t excha nger exteri or s urfa ces . Cl ea n i f neces s a ry.
Sta ge 1 a nd Sta ge 2 Ai r Dryers R R R R R R R R R R
Anti -Condens a ti on Hea ters Ins pect every 12 months 1 Hi gh humi di ty s ys tems onl y.
Fuel Sys tem (Li nes a nd Fi tti ngs ) S S S S S S S S S S S S S S S S S S S S See Gaseous Fuel Fittings and Components s ecti on i n thi s document.
Fuel Boos t Pump 440368 R R R R R R R R R R
Fuel Supply, Combustion

Boos t Pump Fuel Fi l ter 440367 R R R R R R R R R R


Fuel Control Pump R R R R

Inl i ne Fuel Fi l ter I R I R I R I R I R More frequent repl a cement of fuel fi l ters a nd va l ves ma y i ndi ca te a n
envi ronmenta l , i ns ta l l a ti on, or fuel qua l i ty i s s ue tha t needs to be
Fuel Shutoff Va l ve R R a ddres s ed.

Injector As s embl i es 440317 R R R R Ins pect for i njector tube s cori ng or cutti ng, repl a ce i f cut through.
440192,
Igni ter R R R R R R R R R R
440279
440304,
Engi ne Combus tor Li ner I I R I I R Repl a ce i f cra cki ng, wa l l brea ches or other da ma ge obs erved.
440333
Batteries

UCB Ba ttery (Dua l Mode onl y) 440212 Repl a ce every 2 yea rs

Repl a ce every 3 yea rs or Refer to Battery Technical Reference (410044) for expected l i fe vs . duty
Ba ttery Pa ck (Dua l Mode onl y) 440216
20,000 hrs of mi croturbi ne opera ti on (whi chever occurs fi rs t) cycl e, a nd Battery Maintenance for recha rge i nterva l s .
Ba y El ectroni cs Fa n a nd EPDB Fa n R R
Powerhead and Other Electronics and Cables

More frequent repl a cement ma y i ndi ca te s i te ha rmoni c di s torti on


EMI Fi l ter R R R R
l evel s tha t exceed Ca ps tone s peci fi ca ti ons .
Ambi ent Cl i ma te Modul e More frequent repl a cement ma y be neces s a ry ba s ed on a mbi ent a i r
R R
a nd Vi nyl Tube condi ti ons (a i rborne pa rti cul a tes ) a t s i te.
Pers ona l i ty Modul es
440188 R R
(Fra me a nd Engi ne)
GCM, LCM, BCM Power Boa rds a nd
R
Ca pa ci tors (BCM i n Dua l Mode Onl y)
Externa l l y Acces s i bl e Ca bl es a nd Hi gh Humi di ty s ys tems : Ins pect every 12 months ; Repl a ce i f neces s a ry
Check conta cts a nd s ea ti ng.
Ha rnes s es Al l Others : Ins pect every 5 yea rs ; Repl a ce i f neces s a ry
Powerhea d 440316 R R
Dump Va l ve Hos e a nd Repl a ce when repl a ci ng powerhea d, a nd i f cra cki ng or bri ttl enes s i s
R R
Genera tor Bl ower Hos e obs erved.
Powerhea d Shroud Ora nge Sea l I R Repl a ce i f cra cked or bri ttl e.
Si l i cone/Fi bergl a s s Exha us t Sl eeves I R Repl a ce i f da ma ged.
Exha us t Ba ckfl ow Va l ve Sys tems wi th common exha us t onl y. Repl a ce i f da ma ge or
440334 I I I I I I I I I I
(If i ns ta l l ed) deteri ora ti on i s obs erved.
Encl os ure Pa nel Acous ti c Foa m I I I R Repl a ce i f cra cked or bri ttl e.
1
Power hea ters ON, wa i t 5 mi nutes . Veri fy a l l hea ters a re a t l ea s t 10ºC (18ºF) a bove a mbi ent tempera ture. Legend
Hea ters a re externa l l y powered. Refer to Ca ps tone Mi croturbi ne Hi gh Humi di ty Pa cka ge Appl i ca ti on Gui de
I = Inspect R = Replace
(480035).
C = Clean S = See instructions in this document

440386 Rev B (November 2019) Page 24 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without incurring any obligation either with respect to
equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

Table 11. Additional C200/C1000 Hazardous Location (HazLoc) Maintenance Tasks Schedule – 4K to 80K Hours
Perform these additional or modified maintenance tasks in addition to those appropriate for the system fuel type.
Work

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00
Maintenance Component

0
Comments

00

00

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0

,0
Instruction

12

16

20

24

28

32

36

40

44

48

52

56

60

64

68

72

76

80
4,

8,
Engi ne Ai r Fi l ter 440213
El ectroni cs Ai r Fi l ter 440213
440342, See Site-Specific Air Filter Replacement Interval Evaluation. Cl ea n or
Es tabl i s h s i te-s peci fi c a i r fi l ter a nd hea ts i nk cl ea ni ng i nterva l
440185, repl a ce uni ts a s needed.
IGBT a nd El ectroni c Hea t Si nks
Air Filtration and Enclosure

440250,
440186
Power hea ters ON, wa i t 5 mi nutes . Veri fy a l l hea ters a re a t l ea s t 10ºC
Anti-Condens a tion Hea ters (18ºF) a bove a mbi ent tempera ture. Hea ters a re externa l l y powered.
Ins pect every 12 months
(Hi gh humi di ty s ys tems onl y) Refer to Capstone Microturbine High Humidity Package Application Guide
(480035).
Ins pect bl a des every 12 months ; s tart wi th both fa ns
Pres s uri za tion Bl ower Ai r Fi l ter I C Start wi th both fa ns a nd veri fy opera tiona l wi th no ra ttl i ng
a nd veri fy opera tiona l wi th no ra ttl i ng

Ga s Detector 480010 Ca l i bra te every 6 months

Ma gnehel i c Pres s ure Ga uge 480010 Ca l i bra te every 12 months

Record encl os ure pres s ure wi th mi croturbi ne off a nd compa re wi th


Encl os ure Lea k check every 12 months pres s ure a t time of commi s s i oni ng. If di fference exceeds 20% i ns pect
door ga s kets a nd i nl et/outlet ducting.

Legend
I = Inspect R = Replace
C = Clean S = See instructions in this document

440386 Rev B (November 2019) Page 25 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without incurring any obligation either with respect to
equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

Table 12. Additional C200/C1000 Hazardous Location (HazLoc) Maintenance Tasks Schedule – 84K to 160K Hours
Perform these additional or modified maintenance tasks in addition to those appropriate for the system fuel type.
Work

10 0

10 0

11 0

11 0

12 0

12 0

12 0

13 0

13 0

14 0

14 0

14 0

15 0

15 0

16 0
0
00

00

00

10 0
Maintenance Component

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00

00
Comments

0
,0

,0

,0

,0
Instruction

0,

4,

8,

2,

6,

0,

4,

8,

2,

6,

0,

4,

8,

2,

6,

0,
84

88

92

96
Engi ne Ai r Fi l ter 440213
El ectroni cs Ai r Fi l ter 440213
440342, See Site-Specific Air Filter Replacement Interval Evaluation. Cl ea n or
Es tabl i s h s i te-s peci fi c a i r fi l ter a nd hea ts i nk cl ea ni ng i nterva l
440185, repl a ce uni ts a s needed.
IGBT a nd El ectroni c Hea t Si nks
Air Filtration and Enclosure

440250,
440186
Power hea ters ON, wa i t 5 mi nutes . Veri fy a l l hea ters a re a t l ea s t 10ºC
Anti-Condens a tion Hea ters (18ºF) a bove a mbi ent tempera ture. Hea ters a re externa l l y powered.
Ins pect every 12 months
(Hi gh humi di ty s ys tems onl y) Refer to Capstone Microturbine High Humidity Package Application Guide
(480035).
Ins pect bl a des every 12 months ; s tart wi th both fa ns
Pres s uri za tion Bl ower Ai r Fi l ter I C Start wi th both fa ns a nd veri fy opera tiona l wi th no ra ttl i ng
a nd veri fy opera tiona l wi th no ra ttl i ng

Ga s Detector 480010 Ca l i bra te every 6 months

Ma gnehel i c Pres s ure Ga uge 480010 Ca l i bra te every 12 months

Record encl os ure pres s ure wi th mi croturbi ne off a nd compa re wi th


Encl os ure Lea k check every 12 months pres s ure a t time of commi s s i oni ng. If di fference exceeds 20% i ns pect
door ga s kets a nd i nl et/outlet ducting.

Legend
I = Inspect R = Replace
C = Clean S = See instructions in this document

440386 Rev B (November 2019) Page 26 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without incurring any obligation either with respect to
equipment previously sold or in the process of construction.
Capstone Turbine Corporation • 16640 Stagg Street • Van Nuys • CA 91406 • USA
Maintenance Guide: Capstone C200/C1000 Series Microturbine

5.2. Controllers and Accessories Scheduled Maintenance


Table 13. Capstone Controllers Scheduled Maintenance

s
ar

ar

ar
ye

ye

ye
Accessory Comments

5
y

y
er

er

er
Ev

Ev

Ev
UPS Battery R
Advanced Power
PLC Battery R
Server (APS)
Cooling Fans R
UPS Battery R
C1000 Controller PLC Battery
Cooling Fans R
UPS Battery R
Capstone Logic PLC Battery R
Controller (CLC) Cooling Fans R
Frame and Engine PMs R
UPS Battery R
PLC Battery R
HazLoc Controller
Cooling Fans R
Frame and Engine PMs R
Heat Trace UPS Battery R
Controller PLC Battery R
UPS Battery R
Hybrid UPS PLC Battery R
(HUPS) Controller Cooling Fans R
Frame and Engine PMs R

Legend
I = Inspect R = Replace
C = Clean S = See instructions in this document

440386 Rev B (November 2019) Page 27 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without
incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone Turbine Corporation
Maintenance Guide: Capstone C200/C1000 Series Microturbine

6. Responsibility
It is the responsibility of Capstone to:
 Make these procedures available to Authorized Service Providers so they can successfully
complete this task.
It is the responsibility of the Authorized Service Provider to:
 Read this document, understand its contents, and effectively complete procedures.
 Upon completion of service, submit a Field Service Report (420006) or Interactive Field
Service Report (420006) to service@capstoneturbine.com.

7. Capstone Technical Support


If you have questions or need assistance, please contact Capstone Customer Service:
 E-mail: service@capstoneturbine.com
 Toll Free Telephone: (866) 4-CAPSTONE or (866) 422-7786
 Direct Telephone: (818) 407-3600

7.1. Capstone Document Library


The latest revisions of all Capstone product documents are available on our website. Select this
link and login: http://documents.capstoneturbine.com/_login.
Capstone values your feedback. Please email comments or suggestions for improving
documentation to techpubs@capstoneturbine.com and enter "Documentation" in the subject line.

© 2019 Capstone Turbine Corporation. All rights reserved.

440386 Rev B (November 2019) Page 28 of 28


Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without
incurring any obligation either with respect to equipment previously sold or in the process of construction.

You might also like