N
FAN COIL UNIT WITH COOLING COIL AND ONE DRYER WITH CONSTANT SPEED MAKE UP
ELECTRIC HEATER SERVING GUEST ROOMS AND EXHAUST FANS
43
WHERE APPLICABLE
F_OFF: DI F_OFF: DI
F_MAN: DI F_MAN: DI
FS: DI FS: DI
FRS: DI FRS: DI
SEQUENCE OF OPERATIONS
F_OFF: DI
FSS: DO
THE SYSTEM CONSISTS OF CONSTANT SPEED GENERAL EXHAUST FANS AND MOTORIZED FIRE SMOKE DAMPERS
(MFSDs) APPLICABLE FOR FANS USING THE KATARA HALL SMOKE EXTRACTION DUCTWORK. DRYER
FNF: DI THE FANS SHALL BE DIRECTLY CONTROLLED AND MONITORED BY MEANS OF A DIRECT DIGITAL CONTROLLER
PROJECT
MOTORIZED FIRE SMOKE DAMPER
APPLICABLE FOR EXHAUST FANS (DDC).
FS: DI
USING THE KATARA HALL SMOKE
EXTRACTION DUCTWORK THE MOTORIZED FIRE SMOKE DAMPERS SHALL BE DIRECTLY CONTROLLED AND MONITORED BY MEANS OF A
SADS: DI EADS: DI
FRS: DI DIRECT DIGITAL CONTROLLER (DDC) IN CASE OF NORMAL OPERATION. THE DAMPERS WILL BE OPERATED
AUTOMATICALLY FROM THE FIRE ALARM PANEL, UPON DETECTION OF FIRE IN THE KATARA HALL. SADC: DO DS: DI EADC: DO KATARA TOWERS AT LUSAIL
THE DDC SHALL BE CONNECTED TO THE BUILDING MANAGEMENT SYSTEM (BMS). Lusail District, Doha
NORMAL OPERATION SEQUENCE CLIENT
SYSTEM START-UP
THE FAN SHALL BE OPERATED MANUALLY FROM THE FAN CONTROLLER OR REMOTELY AT THE BMS.
Katara Hospitality
MFSDS: DI THE MOTORIZED FIRE SMOKE DAMPERS SHALL BE NORMALLY OPEN IN CASE OF NORMAL OPERATION. Katara Hospitality Building, Marina District,
MFSDC: DO
FAN MONITORING
Lusail City, PO Box 2977 Doha, Qatar
DEDICATED DIFFERENTIAL PRESSURE SWITCH ACROSS THE FAN SHALL PROVE AIRFLOW. LEAD
CONSULTANT
DISHWASHER OPERATION:
THE EXHAUST FAN OF THE DISHWASHING MACHINE HOOD SHALL BE INTERLOCKED WITH THE DISHWASHING
MACHINE OPERATION, SO THAT IT ONLY RUNS IF THE DISHWASHING MACHINE IS ON.
IN CASE THE EXHAUST FAN FAILS, THE DDC SHALL CLOSE ITS CORRESPONDING MFSD.
DRYER
SUB -
SYSTEM SHUT DOWN SEQUENCE OF OPERATIONS CONSULTANTS
THE FAN SHALL BE SHUT DOWN MANUALLY FROM THE FAN CONTROLLER OR REMOTELY FROM THE BMS. SYSTEM DESCRIPTION SADS: DI EADS: DI
SADC: DO DS: DI EADC: DO
ALARMS THE SYSTEM CONSISTS OF THE FOLLOWING:
1. TWO DRYERS
AN ALARM SHALL BE INITIATED AT THE BMS FOR ANY OF THE FOLLOWING EVENTS: 2. MAKE-UP FAN WITH VFD
3. EXHAUST FAN WITH VFD
1. FAN FAILURE TO START. 4. MAKE-UP AND EXHAUST MOTORIZED DAMPERS
2. FAN FAILURE DURING NORMAL OPERATION.
3. HOA SWITCH IN HAND POSITION. THE FANS AND THE DAMPERS SHALL BE DIRECTLY CONTROLLED AND MONITORED BY MEANS OF A DIRECT
4. HOA SWITCH IN OFF POSITION. DIGITAL CONTROLLER (DDC). BMS SCHEDULE
5. MOTORIZED FIRE SMOKE DAMPER FAILURE. THE STATUS OF THE DRYER SHALL BE MONITORED BY THE DDC.
BMS SCHEDULE
THE DDC SHALL BE CONNECTED TO THE BUILDING MANAGEMENT SYSTEM (BMS).
FAN MONITORING
KATARA HOTEL
DEDICATED DIFFERENTIAL PRESSURE SWITCH ACROSS THE FAN SHALL PROVE AIRFLOW.
FSS FAN START/STOP X [ PK4b(i)-a & PK4b(ii)-a ]
FS FAN STATUS (ON/OFF) X X
FSS FAN START/STOP X DRYER OPERATION:
FNF FAN NORMAL/FAULT (TRIP) X X THROUGH DIFFERENTIAL PRESSURE SWITCH SUBMISSION
FS FAN STATUS (ON/OFF) X X
THROUGH DIFFERENTIAL PRESSURE SWITCH
WHEN A CERTAIN DRYER IS ON, ITS CORRESPONDING MAKE-UP AND EXHAUST DAMPERS SHALL OPEN. FRS FAN RUNNING STATUS X X STAMP TENDER
FNF FAN NORMAL/FAULT (TRIP) X X
IF ONE DRYER IS OPERATING, THE MAKE-UP AND EXHAUST FANS SHALL RUN AT LOW SPEED. F_MAN FAN IN "MANUAL" POSITION AT MCC X X FAN SWITCH POSITION TO BE SHOWN ON SCREEN (APPLICABLE ONLY OCTOBER 2019 PACKAGE PK4b(ii)-a-
FRS FAN RUNNING STATUS X X
IF BOTH DRYERS ARE OPERATING, THE MAKE-UP AND EXHAUST FANS SHALL RUN AT HIGH SPEED. F_OFF FAN IN "OFF" POSITION AT MCC X FOR FANS ABOVE ONE HP EQUIPPED WITH HOA SWITCHES)
F_MAN FAN IN "MANUAL" POSITION AT MCC X X FAN SWITCH POSITION TO BE SHOWN ON SCREEN (APPLICABLE ONLY PACKAGE TITLE
VFD
F_OFF FAN IN "OFF" POSITION AT MCC X FOR FANS ABOVE ONE HP EQUIPPED WITH HOA SWITCHES) SYSTEM SHUT DOWN BMS
FAN VFD SPEED DISPLAY X
MFSDS MOTORIZED FIRE SMOKE DAMPER STATUS
MFSDC MOTORIZED FIRE SMOKE DAMPER COMMAND
X X APPLICABLE FOR EXHAUST FANS USING THE KATARA HALL SMOKE
EXTRACTION DUCTWORK
THE FAN SHALL BE SHUT DOWN MANUALLY FROM THE FAN CONTROLLER OR REMOTELY FROM THE BMS WHEN
THE DRYER SWITCHES OFF
FAN VFD SPEED CONTROL X DRYERS VENTILATION
X
ALARMS
FAN VFD NORMAL/FAULT (TRIP)
FAN VFD STATUS
X
X
X
X
-a- CONTROL DIAGRAMS
FORMAT FIRST ISSUE DATE DESIGNED BY CHECKED BY SCALE PLOT NO. / AREA
AN ALARM SHALL BE INITIATED AT THE BMS FOR ANY OF THE FOLLOWING EVENTS: (ISSUE OF REV00)
DS DRYER STATUS X
1. FAN FAILURE TO START. Marina-hotel 001 /
2. FAN FAILURE DURING NORMAL OPERATION. MADS MAKE-UP AIR DAMPER STATUS X LUSAIL
3. HOA SWITCH IN HAND POSITION. MADC MAKE-UP AIR DAMPER CONTROL X PROJECT NO. PHASE BLDG. NO. DISCIPLINE SERIAL NO. PART REV. NO.
4. HOA SWITCH IN OFF POSITION.
EADS EXHAUST AIR DAMPER STATUS X
EADC EXHAUST AIR DAMPER CONTROL X Q17017-0100D TD GN MI 857 1 OF 1 00