KEY PLAN:

1 6 14 25 34
MECCA
U
N
FAN COIL UNIT WITH COOLING COIL AND ONE DRYER WITH CONSTANT SPEED MAKE UP
ELECTRIC HEATER SERVING GUEST ROOMS AND EXHAUST FANS
43

WHERE APPLICABLE

SEQUENCE OF OPERATIONS (FOR COOLING MODE:


INFORMATION) F_OFF: DI F_OFF: DI
THE 2-WAY MOTORIZED VALVE SHALL BE CONTROLLED BY THE FAN COIL A
UNIT CONTROLLER AND SHALL MODULATE THE CHILLED WATER FLOW TO BEDROOM THERMOSTAT F_MAN: DI F_MAN: DI
SYSTEM DESCRIPTION MAINTAIN THE SET TEMPERATURE INSIDE THE CONDITIONED SPACE. IN BY GUEST ROOM
CASE OF A GUESTROOM PROVIDED WITH TWO THERMOSTATS, THE MANAGEMENT SYSTEM FSS: DO FSS: DO
THE SYSTEM CONSISTS OF: LEGENDS & PARTICULAR NOTES:
2-WAY MOTORIZED VALVE SHALL MODULATE THE CHILLED WATER FLOW
TO MAINTAIN THE TEMPERATURE SETPOINT AS SENSED BY A DUCT FNF: DI FNF: DI
1. EC MOTOR FAN COIL UNIT WITH CONDENSATE PUMP (WHERE MOUNTED RETURN AIR TEMPERATURE SENSOR. HOWEVER, WHEN THE
APPLICABLE). BEDROOM THERMOSTAT MEASURES A TEMPERATURE DEVIATED FROM FS: DI FS: DI
2. ROOM MANAGEMENT SYSTEM CONTROLLER AND ACCESSORIES. THE SETPOINT BY MORE THAN A PREDEFINED ADJUSTABLE AMOUNT, THE
3. 2-WAY MODULATING PRESSURE INDEPENDENT CONTROL VALVE FCU CONTROLLER BY GUEST
BEDROOM'S THERMOSTAT SHALL OVERRIDE THE TEMPERATURE THERMOSTAT BY FRS: DI FRS: DI
ROOM MANAGEMENT SYSTEM
FOR CHILLED WATER COOLING. GUEST ROOM
CONTROL SUCH THAT THE MODULATING VALVE CONTROL WILL BE BASED
4. ELECTRIC HEATER MANAGEMENT
ON THE BEDROOM TEMPERATURE INSTEAD OF THE DUCT RETURN AIR SYSTEM
TEMPERATURE.
IN CASE THE SWITCHING CURRENT OF THE MOTOR EXCEEDS THE ASC
OUTPUT RATING, INTERFACE POWER RELAYS OR CONTACTORS SHALL BE HEATING MODE:
DRYER
INSTALLED. TREATED FRESH AIR
THE INTERFACING AND PROTECTION EQUIPMENT SHALL BE SELECTED THE ELECTRIC HEATER SHALL BE CONTROLLED BY THE FAN COIL UNIT
ACCORDING TO THE FCU MOTOR RATING. MAKE-UP FAN EXHAUST FAN
CONTROLLER AND SHALL MODULATE IN ORDER TO MAINTAIN THE SET
TEMPERATURE INSIDE THE CONDITIONED SPACE. IN CASE OF A RETURN AIR TEMPERATURE SENSOR FOR
THE FAN SPEED CONTROL SIGNAL SHALL BE 0-10VDC THE FCU'S OF THE GUESTROOMS
GUESTROOM PROVIDED WITH TWO THERMOSTATS, THE ELECTRIC
PROVIDED WITH 2 THERMOSTATS DS: DI
HEATER SHALL MODULATE IN ORDER TO MAINTAIN THE TEMPERATURE
NORMAL OPERATION SEQUENCE SETPOINT AS SENSED BY A DUCT MOUNTED RETURN AIR TEMPERATURE
SENSOR. HOWEVER, WHEN THE BEDROOM THERMOSTAT MEASURES A
OPERATING MODE TEMPERATURE DEVIATED FROM THE SETPOINT BY MORE THAN A
PREDEFINED ADJUSTABLE AMOUNT, THE BEDROOM'S THERMOSTAT RETURN AIR SUPPLY AIR
THE CONTROLLER SHALL OPERATE IN ONE OF THE FOLLOWING MODES: SHALL OVERRIDE THE TEMPERATURE CONTROL SUCH THAT THE
1. OCCUPIED SOLD MODE ELECTRIC HEATER CONTROL WILL BE BASED ON THE BEDROOM
2. UN-OCCUPIED SOLD MODE TEMPERATURE INSTEAD OF THE DUCT RETURN AIR TEMPERATURE.
3. OCCUPIED SOLD MODE
4. UN-OCCUPIED SOLD MODE SYSTEM SHUT DOWN
THE ACTIVE OPERATING MODE SHALL BE DETERMINED BASED ON ANY OF
THE FAN COIL UNIT SHALL BE SHUT DOWN MANUALLY FROM THE WALL
THE FOLLOWING MEANS:
MOUNTED MODULE OR REMOTELY FROM THE RMS.
SEQUENCE OF OPERATIONS
1. MANUALLY BY THE GUEST THROUGH THE RMS.
2. AUTOMATICALLY FROM THE RMS BASED ON ROOM STATUS. SHUT DOWN SEQUENCE SYSTEM DESCRIPTION
3. FROM THE RMS BY AN OPERATOR MANUALLY ENTERED
COMMAND. THE FAN SHALL FIRST SHUT DOWN THEN THE MODULATING VALVE SHALL THE SYSTEM CONSISTS OF A CONSTANT SPEED MAKE-UP AND EXHAUST FANS SERVING DRYER.
RETURN TO ITS NORMAL POSITION AND ELECTRIC HEATER SHALL TURN
SYSTEM OFF THE FANS SHALL BE DIRECTLY CONTROLLED AND MONITORED BY MEANS OF A DIRECT DIGITAL CONTROLLER
OFF. (DDC).
THE STATUS OF THE DRYER SHALL BE MONITORED BY THE DDC.
THE ROOM MANAGEMENT SYSTEM CONTROLLER SHALL BE SET TO THE WINDOW / BALCONY DOOR SWITCH CONTROL
AUTOMATIC POSITION. BMS SCHEDULE THE DDC SHALL BE CONNECTED TO THE BUILDING MANAGEMENT SYSTEM (BMS).
WHEN THE FAN COIL UNIT IS OFF, THE 2-WAY CHILLED WATER THE WINDOW / BALCONY DOOR SWITCH INSTALLED IN EVERY
MODULATING PRESSURE INDEPENDENT VALVE SHALL BE NORMALLY GUESTROOM SHALL BE CONNECTED DIRECTLY TO THE FCU NORMAL OPERATION SEQUENCE
CLOSED AND THE ELECTRIC HEATER SHALL BE OFF. CONTROLLER. WHEN A WINDOW OR A BALCONY DOOR IS OPENED, AND
SYSTEM START-UP LEVEL +9.40 M (QNHD) = +0.00 M (ARCHITECTURAL)
AFTER A PREDEFINED ADJUSTABLE TIME DELAY, THE FCU CONTROLLER
SYSTEM START-UP SHALL SHUT DOWN THE FCU FAN AND CLOSE THE CHILLED WATER SCHEMATIC
DESCRIPTION NOTES THE FAN SHALL BE OPERATED MANUALLY FROM THE FAN CONTROLLER OR REMOTELY AT THE BMS.
CONTROL VALVE. REFERENCE GENERAL NOTES:
THE FAN COIL UNIT SHALL BE OPERATED MANUALLY FROM THE WALL BMS SCHEDULE
FAN MONITORING
MOUNTED MODULE OR REMOTELY FROM THE RMS.
FAN SPEED MAY BE SELECTED BY THE GUEST OR BY THE GUEST ROOM
INTERLOCKS DEDICATED DIFFERENTIAL PRESSURE SWITCH ACROSS THE FAN SHALL PROVE AIRFLOW.
MANAGEMENT SYSTEM.
DRYER OPERATION:
THE COOLING COIL SHALL BE INTERLOCKED WITH THE ELECTRIC ROOM TEMPERATURE X X PROGRAMMABLE LOW & HIGH ALARM VALUES
TEMPERATURE CONTROL HEATING COIL IN ORDER TO AVOID SIMULTANEOUS OPERATION.
SETPOINT MONITORING BY BMS THE MAKE-UP AND EXHAUST FANS SHALL BE INTERLOCKED WITH THE DRYER MACHINE OPERATION, SO THAT SCHEMATIC
ROOM TEMPERATURE SETPOINT X DESCRIPTION NOTES
THE CHILLED WATER VALVE AND ELECTRIC HEATING COIL OPERATION THEY BOTH RUN WHEN THE DRYER MACHINE IS ON. REFERENCE
THE CONTROLLER SHALL MAINTAIN THE COMFORT LEVEL TO A SHALL BE INTERLOCKED WITH THE FAN IN ORDER TO PREVENT AIR UNIT STATUS (ON/ OFF) X X DIRTY FILTER ALARM BASED ON RUNNING HOURS
PRE-DEFINED SETPOINT DURING THE OCCUPIED AND UNOCCUPIED HEATING OR AIR COOLING IF THE FAN IS OFF. OPERATION MODE X SYSTEM SHUT DOWN
PERIODS BY CONTROLLING THE COOLING VALVE. IN THE UNSOLD THE CHILLED WATER VALVE AND ELECTRIC HEATER SHALL BE CONDENSATE PUMP FAULT (WHERE APPLICABLE) X X
UNOCCUPIED MODE, A PRESET SETBACK VALUE SHALL BE USED AS THE INTERLOCKED WITH THE WINDOW / BALCONY DOOR SWITCH THROUGH THE FAN SHALL BE SHUT DOWN MANUALLY FROM THE FAN CONTROLLER OR REMOTELY FROM THE BMS WHEN
WINDOW / DOOR SWITCH X IN GUESTROOMS THE DRYER SWITCHES OFF. FSS FAN START/STOP X
ROOM TEMPERATURE SETPOINT. THE FCU CONTROLLER IN ORDER TO DEACTIVATE THE COOLING /
HEATING IN CASE A WINDOW OR BALCONY DOOR REMAINS OPEN FOR A FIRE MODE X X SIGNAL RECEIVED FROM FIRE ALARM PANEL FS FAN STATUS (ON/OFF) X X
THE OCCUPANT SHALL ONLY BE ABLE TO RAISE OR LOWER THE ROOM PREDEFINED ADJUSTABLE TIME DELAY.
ALARMS
FNF FAN NORMAL/FAULT (TRIP) X X THROUGH DIFFERENTIAL PRESSURE SWITCH
TEMPERATURE SETPOINT BY A FEW DEGREES TO A PRE-DEFINED LIMIT IN CASE OF CONDENSATE PUMP FAULT (WHERE APPLICABLE), THE FCU
AN ALARM SHALL BE INITIATED AT THE BMS FOR ANY OF THE FOLLOWING EVENTS: FRS FAN RUNNING STATUS X X
AS SET BY THE RMS. WHERE MORE THAN ONE THERMOSTAT ARE SHALL STOP.
INSTALLED, THE TEMPERATURE SETPOINT CAN BE DEFINED BY ANY ONE 1. FAN FAILURE TO START. F_MAN FAN IN "MANUAL" POSITION AT MCC X X FAN SWITCH POSITION TO BE SHOWN ON SCREEN (APPLICABLE ONLY
OF THESE DEVICES AND SHALL BE REFLECTED ON THE DISPLAY OF ALL 2. FAN FAILURE DURING NORMAL OPERATION.
FIRE CONTROL 3. HOA SWITCH IN HAND POSITION.
F_OFF FAN IN "OFF" POSITION AT MCC X FOR FANS ABOVE ONE HP EQUIPPED WITH HOA SWITCHES)
INTERCONNECTED DEVICES.
4. HOA SWITCH IN OFF POSITION.
IN THE EVENT OF A FIRE, THE BMS SHALL SHUT DOWN ALL THE FAN COIL
DS DRYER STATUS X
UNITS.

F_OFF: DI F_OFF: DI

F_MAN: DI F_MAN: DI

GENERAL EXHAUST FANS VSD POINTS AS SHOWN IN


FSS: DO
TWO DRYERS WITH VARIABLE SPEED MAKE UP VSD POINTS AS SHOWN IN
FSS: DO
THE SCHEDULE OF THE SCHEDULE OF
POINTS FNF: DI
AND EXHAUST FANS POINTS FNF: DI

FS: DI FS: DI

FRS: DI FRS: DI

SEQUENCE OF OPERATIONS
F_OFF: DI

F_MAN: DI SYSTEM DESCRIPTION

FSS: DO
THE SYSTEM CONSISTS OF CONSTANT SPEED GENERAL EXHAUST FANS AND MOTORIZED FIRE SMOKE DAMPERS
(MFSDs) APPLICABLE FOR FANS USING THE KATARA HALL SMOKE EXTRACTION DUCTWORK. DRYER
FNF: DI THE FANS SHALL BE DIRECTLY CONTROLLED AND MONITORED BY MEANS OF A DIRECT DIGITAL CONTROLLER
PROJECT
MOTORIZED FIRE SMOKE DAMPER
APPLICABLE FOR EXHAUST FANS (DDC).
FS: DI
USING THE KATARA HALL SMOKE
EXTRACTION DUCTWORK THE MOTORIZED FIRE SMOKE DAMPERS SHALL BE DIRECTLY CONTROLLED AND MONITORED BY MEANS OF A
SADS: DI EADS: DI
FRS: DI DIRECT DIGITAL CONTROLLER (DDC) IN CASE OF NORMAL OPERATION. THE DAMPERS WILL BE OPERATED
AUTOMATICALLY FROM THE FIRE ALARM PANEL, UPON DETECTION OF FIRE IN THE KATARA HALL. SADC: DO DS: DI EADC: DO KATARA TOWERS AT LUSAIL
THE DDC SHALL BE CONNECTED TO THE BUILDING MANAGEMENT SYSTEM (BMS). Lusail District, Doha
NORMAL OPERATION SEQUENCE CLIENT

SYSTEM START-UP

THE FAN SHALL BE OPERATED MANUALLY FROM THE FAN CONTROLLER OR REMOTELY AT THE BMS.
Katara Hospitality
MFSDS: DI THE MOTORIZED FIRE SMOKE DAMPERS SHALL BE NORMALLY OPEN IN CASE OF NORMAL OPERATION. Katara Hospitality Building, Marina District,
MFSDC: DO
FAN MONITORING
Lusail City, PO Box 2977 Doha, Qatar
DEDICATED DIFFERENTIAL PRESSURE SWITCH ACROSS THE FAN SHALL PROVE AIRFLOW. LEAD
CONSULTANT
DISHWASHER OPERATION:

THE EXHAUST FAN OF THE DISHWASHING MACHINE HOOD SHALL BE INTERLOCKED WITH THE DISHWASHING
MACHINE OPERATION, SO THAT IT ONLY RUNS IF THE DISHWASHING MACHINE IS ON.

MOTORIZED FIRE SMOKE DAMPER OPERATION:

IN CASE THE EXHAUST FAN FAILS, THE DDC SHALL CLOSE ITS CORRESPONDING MFSD.
DRYER
SUB -
SYSTEM SHUT DOWN SEQUENCE OF OPERATIONS CONSULTANTS

THE FAN SHALL BE SHUT DOWN MANUALLY FROM THE FAN CONTROLLER OR REMOTELY FROM THE BMS. SYSTEM DESCRIPTION SADS: DI EADS: DI
SADC: DO DS: DI EADC: DO
ALARMS THE SYSTEM CONSISTS OF THE FOLLOWING:
1. TWO DRYERS
AN ALARM SHALL BE INITIATED AT THE BMS FOR ANY OF THE FOLLOWING EVENTS: 2. MAKE-UP FAN WITH VFD
3. EXHAUST FAN WITH VFD
1. FAN FAILURE TO START. 4. MAKE-UP AND EXHAUST MOTORIZED DAMPERS
2. FAN FAILURE DURING NORMAL OPERATION.
3. HOA SWITCH IN HAND POSITION. THE FANS AND THE DAMPERS SHALL BE DIRECTLY CONTROLLED AND MONITORED BY MEANS OF A DIRECT
4. HOA SWITCH IN OFF POSITION. DIGITAL CONTROLLER (DDC). BMS SCHEDULE
5. MOTORIZED FIRE SMOKE DAMPER FAILURE. THE STATUS OF THE DRYER SHALL BE MONITORED BY THE DDC.
BMS SCHEDULE
THE DDC SHALL BE CONNECTED TO THE BUILDING MANAGEMENT SYSTEM (BMS).

NORMAL OPERATION SEQUENCE


SCHEMATIC
DESCRIPTION NOTES
SYSTEM START-UP REFERENCE
SCHEMATIC
REFERENCE
DESCRIPTION NOTES THE FAN SHALL BE OPERATED MANUALLY FROM THE FAN CONTROLLER OR REMOTELY AT THE BMS.

FAN MONITORING
KATARA HOTEL
DEDICATED DIFFERENTIAL PRESSURE SWITCH ACROSS THE FAN SHALL PROVE AIRFLOW.
FSS FAN START/STOP X [ PK4b(i)-a & PK4b(ii)-a ]
FS FAN STATUS (ON/OFF) X X
FSS FAN START/STOP X DRYER OPERATION:
FNF FAN NORMAL/FAULT (TRIP) X X THROUGH DIFFERENTIAL PRESSURE SWITCH SUBMISSION
FS FAN STATUS (ON/OFF) X X
THROUGH DIFFERENTIAL PRESSURE SWITCH
WHEN A CERTAIN DRYER IS ON, ITS CORRESPONDING MAKE-UP AND EXHAUST DAMPERS SHALL OPEN. FRS FAN RUNNING STATUS X X STAMP TENDER
FNF FAN NORMAL/FAULT (TRIP) X X
IF ONE DRYER IS OPERATING, THE MAKE-UP AND EXHAUST FANS SHALL RUN AT LOW SPEED. F_MAN FAN IN "MANUAL" POSITION AT MCC X X FAN SWITCH POSITION TO BE SHOWN ON SCREEN (APPLICABLE ONLY OCTOBER 2019 PACKAGE PK4b(ii)-a-
FRS FAN RUNNING STATUS X X
IF BOTH DRYERS ARE OPERATING, THE MAKE-UP AND EXHAUST FANS SHALL RUN AT HIGH SPEED. F_OFF FAN IN "OFF" POSITION AT MCC X FOR FANS ABOVE ONE HP EQUIPPED WITH HOA SWITCHES)
F_MAN FAN IN "MANUAL" POSITION AT MCC X X FAN SWITCH POSITION TO BE SHOWN ON SCREEN (APPLICABLE ONLY PACKAGE TITLE
VFD
F_OFF FAN IN "OFF" POSITION AT MCC X FOR FANS ABOVE ONE HP EQUIPPED WITH HOA SWITCHES) SYSTEM SHUT DOWN BMS
FAN VFD SPEED DISPLAY X
MFSDS MOTORIZED FIRE SMOKE DAMPER STATUS
MFSDC MOTORIZED FIRE SMOKE DAMPER COMMAND
X X APPLICABLE FOR EXHAUST FANS USING THE KATARA HALL SMOKE
EXTRACTION DUCTWORK
THE FAN SHALL BE SHUT DOWN MANUALLY FROM THE FAN CONTROLLER OR REMOTELY FROM THE BMS WHEN
THE DRYER SWITCHES OFF
FAN VFD SPEED CONTROL X DRYERS VENTILATION
X

ALARMS
FAN VFD NORMAL/FAULT (TRIP)
FAN VFD STATUS
X
X
X
X
-a- CONTROL DIAGRAMS
FORMAT FIRST ISSUE DATE DESIGNED BY CHECKED BY SCALE PLOT NO. / AREA
AN ALARM SHALL BE INITIATED AT THE BMS FOR ANY OF THE FOLLOWING EVENTS: (ISSUE OF REV00)
DS DRYER STATUS X
1. FAN FAILURE TO START. Marina-hotel 001 /
2. FAN FAILURE DURING NORMAL OPERATION. MADS MAKE-UP AIR DAMPER STATUS X LUSAIL
3. HOA SWITCH IN HAND POSITION. MADC MAKE-UP AIR DAMPER CONTROL X PROJECT NO. PHASE BLDG. NO. DISCIPLINE SERIAL NO. PART REV. NO.
4. HOA SWITCH IN OFF POSITION.
EADS EXHAUST AIR DAMPER STATUS X
EADC EXHAUST AIR DAMPER CONTROL X Q17017-0100D TD GN MI 857 1 OF 1 00