LEGENDS & PARTICULAR NOTES:
TO SWIMMING POOL
ALARM
WLP: AI
LOW LEVEL LLA: DI
ALARM

LOW LEVEL
INTERLOCK
SAND SAND

BMS SCHEDULE
SWIMMING POOL HEATING
SEQUENCE OF OPERATIONS
THE SWIMMING POOL WATER HEATING IS INITIATED BY AN OPERATOR COMMAND OR

SCHEMATIC SYSTEM DESCRIPTION WHEN THE POOL WATER TEMPERATURE FALLS BELOW A PRESET LOW LIMIT
DESCRIPTION NOTES TEMPERATURE (TWO DEGREES BELOW THE POOL TEMPERATURE SETPOINT).
REFERENCE THE WATER HEATING CYCLE SHALL OPERATE IN THE FOLLOWING SEQUENCE:
THE SYSTEM CONSISTS OF THE FOLLOWING EQUIPMENT (FOR THE ACTUAL QUANTITIES
OF MECHANICAL EQUIPMENT REFER TO THE MECHANICAL SCHEDULES AND RISER 1. HOT WATER VALVES SHALL OPEN.
DIAGRAMS): 2. THE HOT WATER VALVES SHALL CLOSE WHEN THE WATER TEMPERATURE
ENTERING THE HEAT EXCHANGER REACHES THE PRESET POOL WATER
PWT POOL WATER TEMPERATURE X X 1. TWO CIRCULATION PUMPS TEMPERATURE SETPOINT.

CHWRT CHILLED WATER RETURN TEMPERATURE X X 2. SAND FILTERS


PROGRAMMABLE LOW AND HIGH ALARM VALUES 3. ONE SURGE TANK ALTERNATION
HWRT HOT WATER RETURN TEMPERATURE X X
4. PH DOSING UNIT
PSWT POOL SUPPLY WATER TEMPERATURE X X IN ORDER TO PROVIDE EQUAL OPERATING TIMES, CIRCULATION PUMPS SHALL BE
5. SALT CHLORINATION UNIT
6. HEAT EXCHANGER ALTERNATED AS DUTY/STANDBY AT EACH OPERATING CYCLE.

CHWVC CHILLED WATER VALVE COMMAND X 7. ALL NECESSARY COMPONENTS AND ACCESSORIES REQUIRED FOR THE
CHWVS CHILLED WATER VALVE STATUS X
PROPER OPERATION OF THE SYSTEM ALARMS & EQUIPMENT STATUS LEVEL +9.40 M (QNHD) = +0.00 M (ARCHITECTURAL)

HWVC HOT WATER VALVE COMMAND X


NORMAL OPERATION SEQUENCE AN ALARM SHALL BE INITIATED AT THE BMS FOR ANY OF THE FOLLOWING EVENTS: GENERAL NOTES:
HWVS HOT WATER VALVE STATUS X
BVC BYPASS VALVE COMMAND X SYSTEM OFF HOA SWITCH IN THE HAND POSITION
BVS BYPASS VALVE STATUS X HOA SWITCH IN THE OFF POSITION
WHEN THE SYSTEM IS OFF: DIRTY FILTER
1. ALL PUMPS ARE OFF. LOW WATER LEVEL ALARM IN SURGE TANK
POWER FAIL X X HIGH WATER LEVEL ALARM IN SURGE TANK
2. ALL MOTORIZED VALVES ARE CLOSED.
3. WATER TREATMENT UNITS ARE OFF. ALL ALARMS INDICATED IN THE SCHEDULE OF POINTS
SFS SAND FILTER STATUS X X THROUGH DIFFERENTIAL PRESSURE SWITCH
PHDS PH DOSING STATUS X X SYSTEM START-UP & OPERATING SEQUENCE INTERLOCKS
SCUS SALT CHLORINATION UNIT STATUS X X
SYSTEM SHALL BE STARTED MANUALLY FROM THE POOL TECHNICAL ROOM OR FROM THE INTERLOCK SHALL PREVENT THE START-UP OF THE CIRCULATION PUMPS IN CASE
WTHL WATER TANK HIGH LEVEL X X BMS AND SHALL BE MONITORED AND CONTROLLED BY THE BMS. IF THE DUTY PUMP OF LOW WATER LEVEL IN THE SURGE TANK.
WTML WATER TANK MEDIUM LEVEL X FAILS THE STANDBY PUMP SHALL AUTOMATICALLY CUT-IN. COOLING AND HEATING CYCLES SHALL BE INTERLOCKED IN ORDER TO PREVENT
LLA LOW LEVEL ALARM X X X SIMULTANEOUS OPERATION AND TO PREVENT COOLING OR HEATING WHEN THE PUMPS
SWIMMING POOL COOLING ARE OFF.
WLP WATER LINE PRESSURE X X

THE SWIMMING POOL WATER COOLING IS INITIATED BY AN OPERATOR COMMAND OR INTEGRATION WITH BUILDING BMS
PUMPS WHEN THE POOL WATER TEMPERATURE EXCEEDS A PRESET HIGH LIMIT TEMPERATURE
(TWO DEGREES ABOVE THE POOL TEMPERATURE SETPOINT).
PSS PUMP START/STOP X X A COMPLETE INTERFACE SOLUTION TO THE BMS SHALL BE PROVIDED.
THE WATER COOLING CYCLE SHALL OPERATE IN THE FOLLOWING SEQUENCE:
PS PUMP STATUS (ON/OFF) X
1. CHILLED WATER VALVES SHALL OPEN.
THE INTERFACE BETWEEN THE WATER TREATMENT CONTROLLERS AND BMS SHALL
PNF PUMP NORMAL/FAULT (TRIP) X X THROUGH DIFFERENTIAL PRESSURE SWITCH 2. THE CHILLED WATER VALVES SHALL CLOSE WHEN THE WATER TEMPERATURE
INCLUDE ALL NECESSARY CABLES AND REQUIRED CONTACTS FOR THE PROPER
P-HOA-MAN PUMP IN "MANUAL" POSITION AT MCC X X ENTERING THE HEAT EXCHANGER REACHES THE PRESET POOL WATER
HARDWIRED AND / OR SOFTWARE TRANSFER OF THE INFORMATION TO THE BMS.
PUMP SWITCH POSITION TO BE SHOWN ON SCREEN TEMPERATURE SETPOINT.
P-HOA-OFF PUMP IN "OFF" POSITION AT MCC X X

WATER FEATURE
HAMMAM MOTORIZED DAMPERS

SEQUENCE OF OPERATIONS

SYSTEM DESCRIPTION
FADS: DI EADS: DI
THE SYSTEM CONSISTS OF THE FOLLOWING EQUIPMENT:
FADC: DO EADC: DO
1. FILTRATION PUMPS SETS
2. FILTERS
3. CHEMICAL DOSING UNITS (WHERE APPLICABLE)
4. ALL NECESSARY COMPONENTS AND ACCESSORIES REQUIRED FOR THE PROPER OPERATION OF
THE SYSTEM FRESH AIR EXHAUST AIR PROJECT

THE SYSTEM SHALL BE DIRECTLY CONTROLLED AND MONITORED BY MEANS OF A DEDICATED CONTROL
PANEL.

THE CONTROL PANEL SHALL BE CONNECTED TO THE BUILDING MANAGEMENT SYSTEM (BMS). KATARA TOWERS AT LUSAIL
Lusail District, Doha
NORMAL OPERATION SEQUENCE
CLIENT
SYSTEM OFF
SGS: DI
WHEN THE SYSTEM IS DISABLED, ALL PUMPS ARE OFF. Katara Hospitality
SYSTEM START-UP & OPERATING SEQUENCE
Katara Hospitality Building, Marina District,
SYSTEM SHALL BE STARTED MANUALLY FROM THE PUMP ROOM, AUTOMATICALLY ACCORDING TO A Lusail City, PO Box 2977 Doha, Qatar
PREDEFINED SCHEDULE OR REMOTELY FROM THE BMS.
HAMMAM
IF THE DUTY PUMP FAILS TO START, THE STANDBY PUMP SHALL CUT IN AND AN ALARM SHALL BE SENT TO LEAD
THE BMS. CONSULTANT

ALTERNATION

IN ORDER TO PROVIDE EQUAL OPERATING TIMES, ALL PUMPS IN EACH SET SHALL BE AUTOMATICALLY
ALTERNATED AS DUTY/STANDBY.

ALARMS & EQUIPMENT STATUS SUB -


CONSULTANTS
AN ALARM SHALL BE INITIATED AT THE BMS FOR ANY OF THE FOLLOWING EVENTS:

1. PUMP FAILURE TO RUN


SEQUENCE OF OPERATION
2. DIRTY FILTER
3. DOSING UNIT ALARM SYSTEM DESCRIPTION
THE SYSTEM CONSISTS OF A FRESH AIR MOTORIZED DAMPER AND AN EXHAUST AIR MOTORIZED DAMPER.
INTERLOCK THESE DAMPERS SHALL BE INTERLOCKED WITH THE OPERATION OF THE HAMMAM STEAM GENERATOR IN
ORDER TO OPEN WHEN THE STEAM GENERATOR RUNS AND TO CLOSE WHEN IT STOPS.
LOW WATER LEVEL INTERLOCK

THE INTERLOCK SHALL PREVENT THE START-UP OF THE PUMPS IN CASE OF LOW WATER LEVEL IN THE
SURGE TANK (OR LOW FLOW AS APPLICABLE).

BMS SCHEDULE

BMS SCHEDULE KATARA HOTEL


SCHEMATIC
DESCRIPTION NOTES
[ PK4b(i)-a & PK4b(ii)-a ]
REFERENCE
SCHEMATIC SUBMISSION
DESCRIPTION NOTES
REFERENCE STAMP TENDER
OCTOBER 2019 PACKAGE PK4b(ii)-a-
FADS FRESH AIR DAMPER STATUS X
FADC FRESH AIR DAMPER COMMAND
PACKAGE TITLE
X
PUMPS
EADS EXHAUST AIR DAMPER STATUS X BMS
PUMP ENABLE/DISABLE X
PUMP STATUS (ON/OFF) X
EADC EXHAUST AIR DAMPER COMMAND X CONTROL DIAGRAMS 1
PUMP NORMAL/FAULT (TRIP) X X
SGS STEAM GENERATOR STATUS X
-a-
PUMP RUNNING STATUS X X THROUGH DIFFERENTIAL PRESSURE SWITCH
FORMAT FIRST ISSUE DATE DESIGNED BY CHECKED BY SCALE PLOT NO. / AREA
FILTER STATUS X X (ISSUE OF REV00)

DOSING UNIT STATUS X Marina-hotel 001 /


LUSAIL
DOSING UNIT NORMAL/FAULT X X
PROJECT NO. PHASE BLDG. NO. DISCIPLINE SERIAL NO. PART REV. NO.

Q17017-0100D TD GN MI 801 1 OF 1 00