SPECIFICATIONS OF HERMETIC SCROLL COMPRESSOR
MODEL C-SBR145H16A
△
△
△
△
△
NO. DATE PAGE REVISION DETAILS SANYO SIGNED CLIENT SIGNED
REVISION RECORD
USER: MANUFACTURER:
DALIAN SANYO COMPRESSOR CO., LTD.
PURCHASING TECHNICAL
LEADER APPROVED CHECKED SUBMITTED
MANAGER MANAGER
1
Section 1. General Specifications
Content Unit Specification
Phase — 1
Rated Frequency Hz 60
Refrigerant — R22
Number of Poles — 2
Notes
2 Motor specifications in the table are the average values for your reference.
Expiration of Specification
Expiration of this specification shall be effected until issuing a notice with indication of the expiration date from the
issued date . In case of improvement or elimination of this specification , it shall be handled by the revision record
2
Section 2. Performance Warranty
2.1 Performance
Hz 60 60 Remark
Power Source (1PH)
V 208 230
Hz 60
Power Source (1PH)
V 230
Notes
Conditions
Compressor Temp. °C (°F) 10~60(50~140)
2.4 Others
Content Unit Specification
L.P. S. MPa(G)/psig 1.6(232)
Design Pressure
H. P. S. MPa(G)/psig 3.0(435)
Insulation Resistance MΩ 100 (without refrigerant)
Dielectric Strength V 1800 (1 second)
Residual Moisture mg 300
Note:
1. The insulation resistance be measured with a DC500V megohm tester.
3
Section 3. Standard Accessories
4
Section 4. Compressor Protection
FOR LIQUID
REFRIGERANT
CHARGING
CAPILLARY
LIQUID LINE
SERVICE
OUTDOOR VALVE
INDOOR
HEAT HEAT
EXCHANGER EXCHANGER
GAS LINE
REVERSING SERVICE VALVE
VALVET
LOW
PRESSURE
SWITCH
COMPRESSOR CRANKCASE
HEATER
5
Section 5. Operating Envelope
70 Transient Operation
60
Condensing Temperature(℃)
50
Normal Operation
40
30
20
10
-30 -25 -20 -15 -10 -5 0 5 10 15 20
Evaporating Temperature(℃)
6
Section 6. Application Standard & Limit
Standard: Applicable to ordinary conditions in Japan JIS B8616 or standards relative to JIS B8616, such as standard rating
conditions, maximum operating conditions, low temperature conditions, etc.
Limit: Applicable to transitional brief period of time, such as start-up and beginning of defrost mode.
No. Item Standard Limit Note
1 Refrigerant R22(Meet the standard of Japan JIS K1517)
Voltage at compressor
9 Running Voltage Within ±10% of the rated voltage
terminals.
Three Phase Models: 85% of the rated voltage min. Voltage at compressor
10 Starting Voltage
Single Phase Models: 90% of the rated voltage min. terminals.
On Period: Until the oil level returns to the center of the lower bearing For at least 7 minutes -
11 On/Off Cycling on/3 minutes-off is
Off Period: Until balance of high and low pressure is obtained recommendable.
Abnormal Pressure Pressure Rise: 3.0MPa(G) (435psig) Max. By high pressure switch
15
Rise/Drop Pressure Drop: 0.03MPa(G) (4.35psig) Min. By low pressure switch
System Moisture
16 200ppm Max.
Level
System 1 Vol.% Max. 24 hrs. after vacuuming:
17 Uncondensable Gas
Residual Oxygen 0.1 Vol.% Max. 1.01kPa Max.
Level
。
18 Tilt 5 Deg.Max.
Operation beyond the above limits must be approved by Dalian SANYO Compressor Co., Ltd. (G): Gauge Pressure
7
Notes
1 Installation should be completed within 15 minutes after removing the rubber plugs.
4 Evacuation and Refrigerant charge : Evacuate internal section in the refrigeration system from high and low pressure
sides and charge liquid refrigerant from condenser outlet side. Additional charge shall be done with gas condition from
low side.
7 Crankcase heater is required when the oil sump temperature is too low to meet the requirement of item 6 on page7.
8 Voltage fluctuation between compressor terminals, during operation, shall be within 2% of the rated voltage.
8
Section 7. Selection of Electrical Wire
Voltage drop may occur due to the large current draw during compressor starting.
We recommend selecting the wire size from the table below.
③
terminal plate compressor
indoor
outdoor
power ① ② ③
terminal
source indoor compressor
plate
5m max. 10m max. 15m max. 20m max. 30m max. 50m max. 1m max.
20max. 2.0 2.0 2.0 3.5 5.5 8.0 2.0
30max. ↑ ↑ 3.5 5.5 ↑ 14.0 ↑
40max. ↑ 3.5 5.5 ↑ 8.0 ↑ ↑
50max. ↑ ↑ ↑ 8.0 14.0 22.0 ↑
60max. ↑ 5.5 ↑ ↑ ↑ ↑ ↑
70max. 3.5 ↑ 8.0 14.0 ↑ ↑ 3.5
80max. ↑ ↑ ↑ ↑ 22.0 30.0 ↑
90max. ↑ ↑ 14.0 ↑ ↑ ↑ ↑
100max. ↑ 8.0 ↑ ↑ ↑ 38.0 ↑
110max. ↑ ↑ ↑ ↑ ↑ ↑ ↑
120max. 5.5 ↑ ↑ 22.0 30.0 ↑ ↑
140max. ↑ 14.0 ↑ ↑ ↑ 50.0 5.5
160max. ↑ ↑ 22.0 ↑ ↑ ↑ ↑
180max. ↑ ↑ ↑ ↑ 38.0 60.0 8.0
200max. 8.0 ↑ ↑ 30.0 ↑ ↑ ↑
220max. ↑ ↑ ↑ ↑ 50.0 80.0 ↑
240max. ↑ ↑ ↑ ↑ ↑ ↑ 14.0
7.3 Caution of Ground
The internal motor protector does not protect the compressor against all possible conditions.
Please be sure that the system utilizes the ground connection when installed in the field.
9
No. Part Code Qty Name
238.2
[9.378]
1 C-SBR145H16A 1 Compressor
2 A-0101-DSB 1 Terminal Box Cover
190.5
[7.505]
3 A-0201-DSB 1 Terminal Box Clip
H
O
L
E
4 A-0301-DSB 1 Eyelet Rub Lead Wire
4-φ18 φ0.709
5 1 Nameplate
6 B-0101-DSB 1 Screw Special
[9.378]
[7.505]
. 5 .0
]
238.2
190.5
13
[5 140
12 740]
[4
0.
.
3
[4.889]
[5.169]
124.1
131.3
41. °
5° 31.0
0°
45.
77.2
77.2
1 DISCHARGE TUBE φ13.1 [3.039]
10
[φ0.516]
R S
2
68.2
SUCTION TUBE φ22.3
[2.685]
68.2
3 [φ0.878]
R C
[2.923]
74.2
S
BOLT 5
[17.785]
451.4
[16.567]
TERMINAL
420.8
φ176.4 TERMINAL
4 [φ6.9502]
[12.249]
310.9
[10.205]
259.0
[0.098]
2.5
5 Part Code
D-0109-DSB
85]
[0.985]
25.00
Name
6
Compressor Outline Drawing
No. Part QTY Name
1 M-0101-DSB 4 Mounting Grommet
2 M-0201-DSB 4 Mounting Sleeve
3 B-0101-DSB 1 Screw Special
1 40
[1.575]
M8 BOLT
[1.260]
2
WASHER
32
WASHER SPRING
8
[0.315] 3
COMPRESSOR BASE
6
R 1 630] 20
0.
[R [0.787]
24
[1.811]
[0.945]
[1.811]
46.0
M4[1.575]
[1.457]
37.0
46
19
11
[0.748]
1
11
[0.433]
[R R3
2 0. φ8.6
11 [φ0.339]
8 ]
φ10.6
[φ0.417]
[0.394]
[1.811]
10
[1.496]
46
38
19
[0.748]
Part Code
M-5101-DSB
Name
Mounting Parts Listing
`
12
Part Code
D-0202-DSB
Name
Packing Dimensions
13
Part Code
E-0916-DSB
Name
Wiring Diagram