1. Fire extinguishers are manufactured in accordance with EN3-7+A1:2007,all tests
should comply with the standard requirement . 2. Every parts should be verified before final assembly. No mechanical defect is admitted 3. Fire extinguisher will be charged with 2 0-0,1 kg of Carbon Dioxide, with water content less than 0,015% water. 4. Leakage test – fire extinguisher 10 min – use a soapy solution over the essembly area. No bubbles admitted. 5. After passing the final test the horn will be fit on the valve threaded connector. 6. The label should be positioned after the leaking test and clean – up of the fire extinguisher. The label should be positioned to permit reading when the fire extinguisher is pinned to its support. 5. The fire extinguisher will be packed in cardboard boxes or in PVC mash, according to the clients demand.
9 Plastic seal WS-T11-02 1 PVC 0,002
8 7 6 Label G2-21-06.0 1 Autocolant 0,001 5 Carbon Dioxide EN 25923 2.000 4 Horn Assembly 1 Ans. 0,116 3 Dip Tube G2-21-03.0 1 PVC 0.050 2 Control Valve ans FY 22200 1 Subans. Import 0,410 1 Cylinder MTZ2-01-2HA 1 34CrMo1 Import 3,800 Item Name Drawing Pcs Materiel Obs. Weigh . t
Design Ing.L.D. Istrate
Drawing Ing.L.D. Istrate ASSEMBLY G2-21-00.1 G2-21-00.0 Checked I Ing. A. Trandafir Checked II Ing. A.Trandafir Aproved Ing.E. Tohaneanu Mass Tehnosting 2kg. Carbon Dioxide Echipamente portable fire extinguisher type TS2/CO2/21 Date 10.01.2007