TECHNICAL DATASHEET MODEL: KCAFSHQ-10

COMPRESSED AIR FOAM SYSTEM (CAFS) 10 LTR FIRE EXTINGUISHER


Compressed Air Foam System (CAFS) 10 Ltr Fire Extinguishers applicable on Class A, B Which involves flammable solids
& liquids.

Brief description: CAFS Fire Extinguishers with nominal charge of 10 Ltr. Constructed of MS Sheet by MIG Welding
process and specially designed foam making cap. It is supplied with a carrying backpack and specially designed Nozzle
(gun) which can throw the agent effectively at 10-12 Mtr (Wet mode) and 8 Mtr (Dry mode).
Client : PO No.

1.00 GENERAL DATA


1.01 Manufacturer Kanadia Fyr Fyter Pvt Ltd
1.02 Trade Mark “KANEX”
1.04 Type Backpack type
1.05 Quantity
2.00 MATERIALS OF CONSTRUCTION
2.01 Extinguishing Medium Distilled Water + Standard AFFF Foam
2.02 Body Mild Steel Sheet of IS:513
2.03 Neck Ring M.S. Pipe of IS:1239
2.04 Drain Plug LTB2 of IS:318
2.05 Air cylinder with valve 2L x 300 bar (PESO Approved) (Composite)
2.06 Discharge hose PVC Braided (Burst pr. ≥50kg/cm2)
2.07 Discharge nozzle Specially designed to achieve desired performance
2.08 Siphon Tube S.S.
3.00 GUARANTEED PERFORMANCE
3.01 Performance Requirement Effective Discharge Time: 55 sec (Wet mode) & 115 sec (Dry mode)
Bulk Range of Discharge: 10-12 Mtr (Wet mode) & 8 Mtr (Dry mode)
Percentage of Discharge: Not Less than 90 %
3.02 Temperature Range +5 °C to +55 °C
3.03 Service Pressure 18 bar

4.00 FIRE RATING (With regular Mechanical CLASS A : 43A (As per DIN EN-3-7)
foam) CLASS B : 233B (As per DIN EN-3-7)
IIB As per DIN EN-1866
Electrical Fire : Tested on 36KV Min. distance 1Mtr
(Recommended 1KV as per DIN EN 3)
With Special AFFF Foam : 55A-233B-IIB Rating can be provided
5.00 DIMENSIONS Max. Diameter: 300±10 mm.
Height: 700 mm (Approx.)
Filler Opening: 75mm
5.01 Thickness of sheet 2.0 mm
5.02 Full weight of cylinder 23 kg (Approx)

6.00 ANTI - CORROSIVE TREATMENT Phosphate Treatment Followed by epoxy powder coating of body DFT Not less than 50
Micron and Internal Plastic Lining

7.00 ACCESSORIES Backpack: Optional

8.00 MISCELLANEOUS
8.01 Inspection & Testing As per approved GTP
8.02 Finish PO Red as per IS : 5 (Shade 538 )
8.03 Maintenance, Care and Refilling As per IS:2190

9.00 APPROVAL
9.01 Electrical Fire test Tested on 36KV Min. distance 1Mtr
(Recommended 1KV as per DIN EN 3)
9.02 Fire Extinguisher CE

9.00 Packing Corrugated box

KANADIA FYR FYTER PVT LTD


tech2@gmail.com
www.kanexfire.com