Technical requirements

1. Fire extinguishers are manufactured in accordance with EN3-7+A1:2007,all tests


should comply with the standard requirement .
2. Every parts should be verified before final assembly. No mechanical defect is
admitted
3. Fire extinguisher will be charged with 20-0,1 kg of Carbon Dioxide, with water
content less than 0,015% water.
4. Leakage test – fire extinguisher 10 min – use a soapy solution over the essembly
area. No bubbles admitted.
5. After passing the final test the horn will be fit on the valve threaded connector.
6. The label should be positioned after the leaking test and clean – up of the fire
extinguisher. The label should be positioned to permit reading when the fire
extinguisher is pinned to its support.
5. The fire extinguisher will be packed in cardboard boxes or in PVC mash, according
to the clients demand.

9 Plastic seal WS-T11-02 1 PVC 0,002


8
7
6 Label G3-34-06.0 1 Autocolant 0,001
5 Carbon Dioxide EN 25923 2.000
4 Horn Assembly 1 Ans. 0,116
3 Dip Tube G3-34-03.0 1 PVC 0.050
2 Control Valve ans FY 22200 1 Subans. Import 0,410
1 Cylinder MTZ2-01-2HA 1 34CrMo1 Import 3,800
Item Name Drawing Pcs. Materiel Obs. Weight

Design Ing.L.D. Istrate


Drawing Ing.L.D. Istrate ASSEMBLY G2-21-00.0
G3-34-00.1
Checked I Ing. A. Trandafir
Checked II Ing. A.Trandafir
Aproved Ing.E. Tohaneanu Mass
Tehnosting 3kg. Carbon Dioxide
Echipamente portable fire extinguisher
type TS3/CO2/34
Date 10.01.2007