Flexible Link

BUSDUCT SYSTEM

FLANGE END

TRANSFORMER LV BOX
(NOT THE SCOPE OF BUSDUCT MANUFACTURERS)

FLEXIBLE LINK

Dimension of Braided Type Copper Flexible Link


50 100 120 150
25 25 30 40 30 40 40 40 35 40 40 35 "T"
25

25

25

25
40

40

40

40
20

20

20

20
150

150

150

150

320
20

20

20

20
40

40

40

40
25

25

25

25

25 25 30 40 30 40 40 40 35 40 40 35

FIG. 1 4-Ø12 HOLE FIG. 2 8-Ø12 HOLE FIG. 3 8-Ø12 HOLE FIG. 4 12-Ø12 HOLE

Busduct Rating Conductor Size Dimension “T” Busduct Rating Conductor Size Dimension “T”
Fig Model Fig Model
per Phase (mm) (mm) per Phase (mm) (mm)

400A One - 6 x 20 2200A One - 6 x 175


4 F15016 x 1 16
600A One - 6 x 30 2500A One - 6 x 200
F5013 x 1 13
700A One - 6 x 40 1 3000A Two - 6 x 110
3 F12014 x 2 14
800A One - 6 x 45 3500A Two - 6 x 125
1000A One - 6 x 60 F5013 x 2 13 4000A Two - 6 x 150 4 F15014 x 2 14.5
1250A One - 6 x 75 2 F10013 x 1 13 4500A Two - 6 x 175
4 F15016 x 2 16
1600A One - 6 x 110 5000A Two - 6 x 200
3 F12014 x 1 14
1800A One - 6 x 125 6300A Three - 6 x 175 4 F15016 x 3 16
2000A One - 6 x 150 4 F15014 x 1 14.5