Installation & Power Connections

Refer to user guide chapter 3.


Typical Control Connection

Example 1: 2 - Wire Start/Stop, Speed Potentiometer Example 2: 3 - Wire Start/Stop, 4 - 20 mA Reference Example 3: 2 - Wire Start/Stop, Multispeed (4 Speeds)

OFF ON
START/STOP START OFF ON
1 DI 1 Digital input 1 1 DI 1 Digital input 1 START/STOP 1 DI 1 Digital input 1
OFF ON
STOP 3 DI 2 Digital input 2

connection
3 DI 2 Digital input 2 Digital input 2

connection
3 DI 2

connection
FWD/REV OFF ON

CFW500-IOS (standard)
CFW500-IOS (standard)
CFW500-IOS (standard)
SPEED

Top
5 DI 3 Digital input 3

Top
Top
5 DI 3 Digital input 3 5 DI 3 Digital input 3 OFF ON
SPEED 7 DI 4 Digital input 4
7 DI 4 Digital input 4 7 DI 4 Digital input 4
9 +24 V dc 24 V dc power supply (150 mA) 9 +24 V dc 24 V dc power supply (150 mA)
9 +24 V dc 24 V dc power supply (150 mA)
2 AO1 Analog output 1
AO1 Analog output 1 2 AO1 Analog output 1
2

connection
connection

Bottom
4 GND Reference 0 V

connection

Bottom
4 GND Reference 0 V

Bottom
4 GND Reference 0 V DIP SWITCHES 6 AI 1 Analog input 1
6 AI 1 Analog input 1 (Not applicable)
6 AI 1 Analog input 1 8 +10 V dc Reference + 10 V dc potentiometer
8 +10 V dc Reference + 10 V dc potentiometer
8 +10 V dc Reference + 10 V dc potentiometer
PROG DEF User Description
DIP SWITCH 1
DIP SWITCH 1 P0220 0 1 Local/Remote = always remote
4 - 20 mA V AI1 mA
Speed V AI1 mA Reference
potentiometer
P0222 2 8 Remote reference = multispeed
P0227 3 1 Start/Stop remote = DIx
PROG DEF User Description PROG DEF User Description P0263 1 1 DI1 = start/stop
P0220 2 1 Local/Remote = always remote P0220 2 1 Local/Remote = always remote P0265 0 13 DI3 = multispeed
P0222 1 1 Remote reference = Al1 P0266 0 13 DI4 = multispeed
P0222 1 1 Remote reference = Al1
P0226 4 4 FWD/REV = DIx
P0227 1 1 Run/Stop remote = DIx P0124 3 ▲ Speed = ▲ (DI3 = open and DI4 = open)
P0227 1 1 Start/Stop remote = DIx
P0231 0 0 AI1 = speed reference P0125 10 ▲ Speed = ▲ (DI3 = open and DI4 = closed)
P0231 0 0 AI1 = speed reference
P0233 0 1 AI1 = 4 - 20 mA P0126 20 ▲ Speed = ▲ (DI3 = closed and DI4 = open)
P0233 0 0 AI1 = 0 - 10 V
P0263 1 1 DI1 = run/stop P0263 1 6 DI1 = start P0127 30 ▲ Speed = ▲ (DI3 = closed and DI4 = closed)
P0264 8 8 DI2 = FWD/REV P0264 8 7 DI2 = stop Note: ▲ Speed setting depends on application.

Programming Oriented Start Up - STARTUP Group (Scalar - V/F Mode) Relay Output
PROG DEF User Description
CFW500 Keypad PROG DEF User Description

Top connection
11 DO1-RL-NO Normally open NO
P0202 0 0 Control type V/F 11 Run
13 DO1-RL-C Common
P0401 - ■ Motor FLC (A) 12 Ready
NC P0275 13
Menu/Enter button: P0402 1710 ■ Motor speed (RPM) 15 DO1-RL-NC Normally closed 13 No fault
- Enter programming mode P0403 60 ■ Motor frequency 26 With fault
- Use to Select/Save
Note: for more advance functions, please refer to the the programming manual.
Note: set P0202 = 5 during oriented start-up for improved speed control and
Run button:
higher torque capacity at low speed (especially < 5 Hz).
- Run in local mode
■ Set as per motor nameplate data.
Changing Monitor Display Parameter
Stop button:
- Stop in local mode PROG DEF User Description
- Reset Motor Overload Settings - MOTOR Group Secondary
1 Speed reference (RPM) display
PROG User Description P0206
Up/Down buttons: 2 Output speed (RPM)
- Adjust speed in local mode P0156 1.1xP0401 Overload current at 100% speed
P0205 P0205 = 2 3 Motor current (A) Main display
- Navigate through parameters P0157 1.0xP0401 Overload current at 50% speed
P0206 P0206 = 1 5 Output frequency (Hz) P0205
Back/ESC button: P0158 0.8xP0401 Overload current at 5% speed
7 Output voltage (V)
- Return to monitoring mode
- Return to previous programming level 9 Motor torque (%)
Basic Application - BASIC Group
Note: for more advance functions, please refer to the programming manual (chapter 5.3).
PROG DEF Description
P0100 10s Acceleration time (s) Loading Factory Default Setting
P0101 10s Deceleration time (s)
P0133 3 Hz Minimum speed (Hz) PROG DEF User Description
P0134 66 Hz Maximum speed (Hz) P0204 0 5 Load factory defaults (60 Hz)
Applications Motors | Automation | Energy | Transmission & Distribution | Coatings

JJ Centrifugal pumps JJ Conveyors

CFW500
JJ Process dosing pumps JJ Roller tables
JJ Fans/ventilators JJ Granulators
JJ Blenders/mixers JJ Commercial dryers
JJ Compressors JJ Rotary filters
Machinery Drives
Quick Setup Guide

The values shown are subject to change without prior notice.


Cod: xxxx | Rev: 00 | Date (m/y): 06/2014
WEG Electric Corp.
6655 Sugarloaf Parkway
Duluth, GA 30097
Phone: 1-800-ASK-4WEG
www.weg.net