VISAKH MARKETING INSTALLATION RESITEMENT

PROJECT - WHITE OIL TERMINAL


Doc No:254624-400-DS-INT-022 Rev: C Page 1 of 7

DATASHEET FOR
MOTOR OPERATED BALL VALVES

Hindustan Petroleum Corporation Ltd Mott MacDonald Consultants (India) Pvt. Ltd.
Visakha Dispatch Station Kothari House, CTS No. 185
VR-ATP Area, Naval Base Post Off Andheri - Kurla Road
Visakhapatnam - 530 014 Andheri (East)
Andhra Pradesh Mumbai - 400 059

P:\Andheri\IndiaProject\254624 HPCL- White Oil Terminal\05 Control &


Automation\Documents\Documents\Specs\Package -II MOV 05.11.09\4_254624-400-DS-INT-022 Ball valve DS
Rev B.xls
DOCUMENT No. 254624-400-DS-INT-022 PAGE 3 OF 7
PROJECT No. 254624 RFQ/RFP NO.
CLIENT HINDUSTAN PETROLEUM CORP. LTD. LOCATION
PROJECT VENDOR
VISAKH MARKETING TERMINAL WHITE OIL PROJECT As per approved vendor list
MODEL BTA

BALL VALVE DATASHEET (OPEN PROTOCOL)


1 Tag No. : Note 1 P&ID : Note 1 Service : Note 1
2 Qty : Note 1 Fluid State: : Note 1 Crit Press Pc : Line no : Note 1
3 Units Max Normal Min: Shut-Off
4 Overall Flow Rate kg/hr - - - -
5 Gas Flow Rate kg/hr - - - -
6 water Flow Rate kg/hr - - - -
7 Liquid Flow Rate kg/hr - - - -
8 Inlet Pressure kg/cm2 g - - - -
SERVICE CONDITIONS

9 Outlet Pressure kg/cm2 g - - - -


10 Inlet Temperature Deg C - Note 1 - -
As mentioned in Doc
11 Density/ Spec Grav(Liq.)/Mol Wt (Vap.) g/cc - Note 1 -
254624-400-SP-INT-004
12 Viscosity(Emuls.)/Spec Heats Ratio(Vap.) Cp - Note 1 - -
13 Compressibility factor - - - -
14 Vapor Pressure Pv kPag - - - -
15 Required Cv - - - -
16 Travel % - - - -
17 Allowable/*Predicted SPL dBA - - - -
18 Design temperature Deg C Note 1 - - -
19 Design pressure kg/cm2 g Note 1 - - Note-1
Electric Actuator with Integral Starter suitable for quarter turn valves, 2 wire
20 Pipe Line Size: Note 1 61 Type: remote control using communication through Field control unit / Master control
LINE

station
21 Schedule 40 62 MFR: BTA Model: BTA
22 63 Shut-Off Differntial/Design Pressure --- kg/cm2 g
Ball valve (Split Body, full bore, solid ball, blow-out proof stem, quarter turn,
23 Type: 64 Electric Supply 415 V AC, 50 Hz 3 Phase
anti static)
ACTUATOR

24 Size: Note 1 ANSI Class: 150# 65 Power Consumption BTA


25 Max Press/Temp: 66 Open / Closing time BTA / Not less than 12 Sec.
26 MFR & Model: BTA 67 Open/ Closing Torque BTA
27 Body/Bonnet Matl: ASTM A216 GR WCB 68 Hazardous Area Protection Zone 1 Gr. IIA / II B, T3
VALVE BODY/BONNET

28 Liner Material/ID: NA 69 Ingress Protection IP 65 as per IEC 529

Two wire communication - MODBUS RTU network


29 End Connection: In: Flanged 70 Control:
through Field Control Unit / Master Control Unit

30 Out: Flanged 71 ESD Command Hardwired Command for Emergency Operation


31 Flange: 150#, RF, 125 to 200 AARH 72 Motor Type: Squirrel Cage Induction type
32 End Ext/Matl: 73 Fault Level Supply System : Fuse Protected
33 Flow Direction: Bidirectional 74 Rating KW : BTA
MOTOR

34 Type of Bonnet: Standard 75 Speed (RPM) : BTA


35 Lub & Iso Valve: NA Lube: N.A 76 Direction of Rotation: Clockwise, Anti Clocwise (Facing Drive End)
36 Packing Material: RTFE (Reinforced PTFE) 77 Cooling Method : Air
37 Packing Type: BTA 78
38 Type: BALL (Float type) 79 Starter: Integral with Motor
39 Size: BTA Rated Travel: 90 DEG. 80 Reduction Gearing Integral with Actuator
TRIM

40 Plug/Ball/Disk Material: SS316 81 Anti Condensation Heater: NA NA


ANCILLARIES

41 Seat Material: Soft seated, Reinforced PTFE 82 Local / Remote Switch: Required Required
42 Cage/Guide Material: N.A. 83 Local On/Off Controls: Required Required
43 Stem Material: AISI 316 84 Handwheel for Manual Operation: Required
44 Valve Position Indicator Required 85 Open / Closing Limit Switches: Required
45 Volume Tanks N.A 86 Local Poistion Indicator / Indicating LED's: Required
46 Antistatic feature Required 87 M12/ M25 for Control - Minimum 2 nos.
GENERAL

Cable Entries & Sizes:


47 NACE MR0175 Compliance reqd. N.A 88 M25 / M40 for Power
48 FIRE SAFE : Required 89 Opening & Closing Required
SIGNALS REQUIRED THROUGH LINK

49 Design Specs - BS EN ISO17292 90 Open & Closed Required


STATUS / ALARM

50 Other 91 Stopped Required


51 92 Torque switch tripped Required
52 Hydro Pressure: Required 93 Local / Remote & Local Push button Pressed Required
TEST

53 Shut-Off Class: Zero leakage/ TSO 94 Main power loss, Phase loss, Control power loss Required
54 ANSI/FCI Leakage Class: Class VI 95 Actuator fault, Field unit fault, contactor energizing fault Required
55 96 Thermostat tripped Required
ACCESSORIES

56 Material Certificate: Required 97 Valve jammed Required


57 Electrical Certificate: Required 98 Open Required
COMMAND
SP.

58 99 Close Required
59 100
60 101
NOTE: I For NOTES refer Page 4 of 5.
II Max. Actuator Torque: 125% of valve torque of pressure rating ANSI 150# & less than valve stem shear torque.

REV DATE BY CK'D APP. DESCRIPTION REV DATE BY CK'D APP. DESCRIPTION
A 24.07.09 HVS AYM RM Issued for Approval
B 05.11.09 HVS AYM RM Re Issued for Appv
C 04.01.10 HVS AYM RM Issued for Tender
DOCUMENT No. 254624-400-DS-INT-022 PAGE 4 OF 7
PROJECT No. 254624 RFQ/RFP NO.
CLIENT HINDUSTAN PETROLEUM CORP. LTD. LOCATION
PROJECT VENDOR
VISAKH MARKETING TERMINAL WHITE OIL PROJECT As per approved vendor list
MODEL BTA

BALL VALVE DATASHEET

NOTES:
1 Refer the Ball valves tag list as on Page 6 to 7.
2 Ball Valves shall meet the requirements specified in Specification Doc. No. 254624-400-SP-INT-022 Rev C
3 Vendor shall refer Piping Specification Index, Doc no.254624-400-SP-PIP-002 Rev C
4 Valve, actuator+integral starter+gear pinion+clutch & handle for manual operation shall be supplied as one assembled unit, completely furnished and tested
furnished and tested. Max.Actuator Torque:125% of valve torque for pressure rating of ANSI 150# & less than valve stem shear torque.
5 All items as indicated shall be provided with a permanently attached stainless steel tag plate.
6 Valve shall be firesafe in accordance with API 607, spec 6FA.
7 Inspection & test shall be performed on all valves as per API 6D/API-598.
8 BTA- Bidder to advise.Bidder to check and confirm the same. Mandetory while submitting the Bid.
9 Abbreviations : MAOP : Maximum Allowable Operating Pressure; FS: Fire Safe; J: Jacketed Body; BTA :Vendor to advise;
TSO: Tight Shut Off; FB: Full bore, TAS - Terminal Automation System, ESDV - Emergency Shutdown System Valve
Neg - Negligible
10 Vendor shall select the seat material as per the maximum temperature of fluid & leakage class specified.
11 Valve shall have anti-blowout stem,anti-static design and suitable for bi-directional use.
12 Limit switch tag numbers will be ZSO & ZSC followed by the valve number. For example for HV-4521, For open position the tag number will be HZSO-4521
& for close position the tag number will be HZSC-4521.
13 8" and above size valves shall have lifting lugs.
14 Double Compression Glands with shrouds & Plug shall be provided. Cable Gland adapters as required shall be provided.
15 Make for Electric Actuators-a. Rotork / Rotork, India, b. Limitorque, India, c. Auma, India
16 Vendor shall submit valve torque for - starting, running, end, stem shear torque, long standing torque & maximum actuator torque.

REV DATE BY CK'D APP. DESCRIPTION REV DATE BY CK'D APP. DESCRIPTION
A 19.06.09 HVS RRS RM Issued for Approval
B 01.09.09 HVS AYM RM Issued for Approval
C 04.01.10 HVS AYM RM Issued for Tender
DOCUMENT No. 254624-400-DS-INT-022 PAGE 5 OF7
PROJECT No. 254624 RFQ/RFP NO.
CLIENT HINDUSTAN PETROLEUM CORP. LTD. LOCATION
PROJECT VENDOR
VISAKH MARKETING TERMINAL WHITE OIL PROJECT As per approved vendor list
MODEL BTA

BALL VALVE DATASHEET (CONVENTIONAL)


1 Tag No. : Note 1 P&ID : Note 1 Service : Note 1
2 Qty : Note 1 Fluid State: : Note 1 Crit Press Pc : Line no : Note 1
3 Units Max Normal Min: Shut-Off
4 Overall Flow Rate kg/hr - - - -
5 Gas Flow Rate kg/hr - - - -
6 water Flow Rate kg/hr - - - -
7 Liquid Flow Rate kg/hr - - - -
8 Inlet Pressure kg/cm2 g - - - -
SERVICE CONDITIONS

9 Outlet Pressure kg/cm2 g - - - -


10 Inlet Temperature Deg C - Note 1 - -
As mentioned in Doc
11 Density/ Spec Grav(Liq.)/Mol Wt (Vap.) g/cc - Note 1 -
254624-400-SP-INT-004
12 Viscosity(Emuls.)/Spec Heats Ratio(Vap.) Cp - Note 1 - -
13 Compressibility factor - - - -
14 Vapor Pressure Pv kPag - - - -
15 Required Cv - - - -
16 Travel % - - - -
17 Allowable/*Predicted SPL dBA - - - -
18 Design temperature Deg C Note 1 - - -
19 Design pressure kg/cm2 g Note 1 - - Note-1

Electric Actuator with Integral Starter, hardwired remote control, local & remote
20 Pipe Line Size: Note 1 61 Type:
indication, handwheel
LINE

21 Schedule 40 62 MFR: BTA Model: BTA


22 63 Shut-Off Differntial/Design Pressure --- kg/cm2 g
Ball valve (Split Body, full bore, solid ball, blow-out proof stem, quarter turn,
23 Type: 64 Electric Supply 415 V AC, 50 Hz 3 Phase/230 VAC single phase
anti static)
ACTUATOR

24 Size: Note 1 ANSI Class: 150# 65 Power Consumption BTA


25 Max Press/Temp: 66 Open / Closing time BTA / Not more than 30 Sec.
26 MFR & Model: BTA 67 Open/ Closing Torque BTA
27 Body/Bonnet Matl: ASTM A216 GR WCB 68 Hazardous Area Protection Zone 1 Gr. IIA / II B, T3
VALVE BODY/BONNET

28 Liner Material/ID: NA 69 Ingress Protection IP 65 as per IEC 529

29 End Connection: In: Flanged 70 Control: Hardwired for command & status

30 Out: Flanged 71 ESD Command Hardwired Command for Emergency Operation


31 Flange: 150#, RF, 125 to 200 AARH 72 Motor Type: Squirrel Cage Induction type
32 End Ext/Matl: 73 Fault Level Supply System : Fuse Protected
33 Flow Direction: Bidirectional 74 Rating KW : BTA
MOTOR

34 Type of Bonnet: Standard 75 Speed (RPM) : BTA


35 Lub & Iso Valve: NA Lube: N.A 76 Direction of Rotation: Clockwise, Anti Clocwise (Facing Drive End)
36 Packing Material: RTFE (Reinforced PTFE) 77 Cooling Method : Air
37 Packing Type: BTA 78
38 Type: BALL (Float type) 79 Starter: Integral with Motor
39 Size: BTA Rated Travel: 90 DEG. 80 Torque Switches: 2 nos. 2 nos. for open & close
TRIM

40 Plug/Ball/Disk Material: SS316 81 Anti Condensation Heater: NA NA


ANCILLARIES

41 Seat Material: Soft seated, Reinforced PTFE 82 Local / Remote Switch: Required Required
42 Cage/Guide Material: N.A. 83 Local On/Off Controls: Required Required
43 Stem Material: AISI 316 84 Handwheel for Manual Operation: Required
44 Valve Position Indicator Required 85 Open / Closing Limit Switches: Required
45 Volume Tanks N.A 86 Local Poistion Indicator / Indicating LED's: Required
46 Antistatic feature Required 87 M12 / M25 for Control & Status - BTA
GENERAL

Cable Entries & Sizes:


47 NACE MR0175 Compliance reqd. N.A 88 M25 / M40 for Power
48 FIRE SAFE : Required 89 Opening & Closing NA
49 Design Specs - BS EN ISO17292 90 2 nos. DPDT Required - One each for open & close
Open & Closed
STATUS / ALARM

50 Other 91 (two separate cable entries)


HARDWIRED SIGNALS

51 92 Torque switch tripped 2 nos.Required - one each for open & close
52 Hydro Pressure: Required 93 Local / Remote Switch Required
TEST

53 Shut-Off Class: Zero leakage/ TSO 94 Main power / Phase / Control power loss Required
54 ANSI/FCI Leakage Class: Class VI 95 Actuator fault, contactor energizing fault Required
55 96 Thermostat tripped Required
ACCESSORIES

56 Material Certificate: Required 97 Valve jammed NA


57 Electrical Certificate: Required 98 Open Required
COMMAND
SP.

58 99 Close Required
59 100
60 101
NOTE: I For NOTES refer Page 4 of 5.
II Max. Actuator Torque: 125% of valve torque of pressure rating ANSI 150# & less than valve stem shear torque.

REV DATE BY CK'D APP. DESCRIPTION REV DATE BY CK'D APP. DESCRIPTION
A 24.07.09 HVS AYM RM Issued for Approval
B 05.11.09 HVS AYM RM Re Issued for Appv
C 04.01.10 HVS AYM RM Issued for Tender
DOCUMENT No. 254624-400-DS-INT-022 RFQ/RFP NO.
PROJECT No. 254624 LOCATION VISHAKHAPATNAM
CLIENT HINDUSTAN PETROLEUM CORP. LTD. VENDOR As per approved vendor list
PROJECT VISAKH MARKETING TERMINAL PROJECT MODEL BTA
MODEL VTA
MOTOR OPERATED BALL VALVE TAG LIST - FIRE SAFE, FULL BORE
Design
Valve pressure / Design Inlet
Tag Line Size Valve Valve
Sr No Area no Tag Service Description P & ID Line No. Size Shutoff Temperature Temperature Valve Actuator Time in Seconds Remarks
number Inches Class Type Fail
Inches Pressure °C °C
Action
Kg/cm2 (g)
Model / Torque
Make Model Torque Type Make Open Close
Size / kW

254624-400-PID- 6"-MS I-4443 - Ball Electric Max 45


1 400 HV 4425 MS I to TT Homogenization 6 6 150 # 4.5 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
A0-1044 A09A2 (TYP) Valve

254624-400-PID- Ball Electric Max 45


2 400 HV 4621 SKO to Homogenization Line 6"-SKO-4657 6 6 150 # 4.5 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
A0-1046 Valve

254624-400-PID- Ball Electric Max 45


3 400 HV 4911 ATF to Homogenization header 6"-ATF-4912 6 6 150 # 4.5 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
A0-1049 Valve

254624-400-PID- Ball Electric Max 45


4 400 HV 4910 ATF from pump outlet header 6"-ATF-4914 6 6 150 # 5.5 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
A0-1049 Valve

254624-400-PID- Ball Electric Max 45


5 400 HV 4913 ATF from pump outlet header 6"-SKO-4929 6 6 150 # 5.5 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
A0-1049 Valve

254624-400-PID- Ball Electric Max 45


6 400 HV 5032 NAPHTHA from pump outlet header 6"-NAP-5042 6 6 150 # 5.1 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
A0-1050 Valve

254624-400-PID- Ball Electric Max 45


7 400 HV 5033 NAPHTHA Homogenization header 6"-NAP-5050 6 6 150 # 4.5 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
A0-1050 Valves

254624-400-PID- Ball Electric Max 45


8 400 HV 5034 MS from pump outlet header for TT filling 6"-MS I-5049 6 6 150 # 5.1 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
A0-1050 Valves

254624-400-PID- Ball Electric Max 45


9 400 HV 5106 HEX TT over spill Recycle Line 3"-HEX-5125 3 3 150 # 3.5 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
A0-1051 Valve

MTO from refinery pumps to MTO storage 254624-400-PID- Ball Electric Max 45
10 400 HV 6207 4"-MTO-6204 4 4 150 # 15.5 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
tank 400T-050A A0-1062 Valves

MTO from 400T-050A to suction header 254624-400-PID- Ball Electric Max 45


11 400 HV 6208 6"-MTO-6206 6 6 150 # 3.5 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
for TT loading A0-1062 Valves

MTO from refinery pumps to MTO storage 254624-400-PID- Ball Electric Max 45
12 400 HV 6209 4"-MTO-6207 4 4 150 # 15.5 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
tank 400T-050B A0-1062 Valves

MTO from 400T-050B to suction header 254624-400-PID- Ball Electric Max 45


13 400 HV 6210 6"-MTO-6209 6 6 150 # 3.5 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
for TT loading A0-1062 Valves

254624-400-PID- Ball Electric Max 45


14 400 HV 6211 Header Isolation 6"-MTO-6202 6 6 150 # 3.5 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
A0-1062 Valve

MTO TT filling pump 400P-050A/S 254624-400-PID- Ball Electric Max 45


15 400 HV 6218 4"-MTO-6247 4 4 150 # 3.6 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
discharge A0-1062 Valve

MTO Homogenization header to MTO 254624-400-PID- Ball Electric Max 45


16 400 HV 6219 4"-MTO-6205 4 4 150 # 3.6 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
storage tank 400T-050A A0-1062 Valve

MTO Homogenization header to MTO 254624-400-PID- Ball Electric Max 45


17 400 HV 6220 4"-MTO-6208 4 4 150 # 3.6 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
storage tank 400T-050B A0-1062 Valve

ETHANOL Tank filling/Homogenization 254624-400-PID- Ball Electric Max 45


18 400 HV 6405 4"-ETH-6414 4 4 150 # 3.5 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
header to 400T-061A A0-1064 Valve

ETHANOL from 400T-016A to Suction 254624-400-PID- Ball Electric Max 45


19 400 HV 6406 6"-ETH-6415 6 6 150 # 3.5 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
header for TT unloading A0-1064 Valve

ETHANOL Tank filling/Homogenization 254624-400-PID- Ball Electric Max 45


20 400 HV 6407 4"-ETH-6416 4 4 150 # 3.5 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
header to 400T-061B A0-1064 Valve
DOCUMENT No. 254624-400-DS-INT-022 RFQ/RFP NO.
PROJECT No. 254624 LOCATION VISHAKHAPATNAM
CLIENT HINDUSTAN PETROLEUM CORP. LTD. VENDOR As per approved vendor list
PROJECT VISAKH MARKETING TERMINAL PROJECT MODEL BTA
MODEL VTA
MOTOR OPERATED BALL VALVE TAG LIST - FIRE SAFE, FULL BORE
Design
Valve pressure / Design Inlet
Tag Line Size Valve Valve
Sr No Area no Tag Service Description P & ID Line No. Size Shutoff Temperature Temperature Valve Actuator Time in Seconds Remarks
number Inches Class Type Fail
Inches Pressure °C °C
Action
Kg/cm2 (g)
Model / Torque
Make Model Torque Type Make Open Close
Size / kW

ETHANOL from 400T-016A to Suction 254624-400-PID- Ball Electric Max 45


21 400 HV 6408 6"-ETH-6417 6 6 150 # 3.5 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
header for TT unloading A0-1064 Valve

254624-400-PID- Ball Electric Max 45


22 400 HV 6409 ETHANOL suction header isolation 6"-ETH-6401 6 6 150 # 3.5 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
A0-1064 Valve

ETHANOL from suction header for TT 254624-400-PID- Ball Electric Max 45


23 400 HV 6410 6"-ETH-6412 6 6 150 # 3.5 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
unloading A0-1064 Valve

254624-400-PID- Ball Electric Max 45


24 400 HV 6411 ETHANOL from Tanker Unloading 6"-ETH-6408 6 6 150 # 3.5 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
A0-1064 Valve

ETHANOL TT unloading & blending pump 254624-400-PID- Ball Electric Max 45


25 400 HV 6412 4"-ETH-6405 4 4 150 # 9.8 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
300P-061A discharge A0-1064 Valve

ETHANOL TT unloading & blending pump 254624-400-PID- Ball Electric Max 45


26 400 HV 6413 4"-ETH-6402 4 4 150 # 9.8 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
300P-061A discharge A0-1064 Valve

ETHANOL TT unloading & blending pump 254624-400-PID- Ball Electric Max 45


27 400 HV 6414 6"-ETH-6419 6 6 150 # 3.5 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
300P-061B Suction A0-1064 Valve

ETHANOL from Tanker to pump 300P- 254624-400-PID- Ball Electric Max 45


28 400 HV 6415 6"-ETH-6420 6 6 150 # 3.5 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
061B Suction A0-1064 Valve

ETHANOL TT unloading & blending pump 254624-400-PID- Ball Electric Max 45


29 400 HV 6416 4"-ETH-6441 4 4 150 # 9.8 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
300P-061B discharge A0-1064 Valve

ETHANOL TT unloading & blending pump 254624-400-PID- Ball Electric Max 45


30 400 HV 6417 4"-ETH-6432 4 4 150 # 9.8 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
300P-061B discharge A0-1064 Valve

ETHANOL TT unloading & blending pump 254624-400-PID- Ball Electric Max 45


31 400 HV 6418 6"-ETH-6442 6 6 150 # 3.5 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
300P-061S Suction A0-1064 Valve

ETHANOL from Tanker to pump 300P- 254624-400-PID- Ball Electric Max 45


32 400 HV 6419 6"-ETH-6443 6 6 150 # 3.5 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
061S Suction A0-1064 Valve

ETHANOL TT unloading/blending pump 254624-400-PID- Ball Electric Max 45


33 400 HV 6420 4"-ETH-6449 4 4 150 # 9.8 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
300P-061S discharge A0-1064 Valve

ETHANOL TT unloading/blending pump 254624-400-PID- Ball Electric Max 45


34 400 HV 6421 4"-ETH-6448 4 4 150 # 9.8 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
300P-061S discharge A0-1064 Valve

ETHANOL TT unloading/blending pumps 254624-400-PID- Ball Electric Max 45


35 400 HV 6423 4"-ETH-6418 4 4 150 # 9.8 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
discharge to MS-I TT loading A0-1064 Valve

254624-400-PID- Ball Electric Max 45


36 400 HV 6801 WOT end of Piggable line 24"-WO-6820 24 24 150 # 15.5 - - Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
A0-1064 Valve

254624-400-PID- Ball Electric Max 45


37 400 HV 6802 Refinery end of Piggable line 24"-WO-6820 24 24 150 # 15.5 - - Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA Conv Electric
A0-1064 Valve
Actuator

254624-400-PID- Ball Electric Max 45


38 400 HV 6803 Inlet of Pig Receiver 24"-WO-6820 24 24 150 # 15.5 - - Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
A0-1064 Valve

254624-400-PID- Ball Electric Max 45


39 400 HV 5104 HEXANE TT Gantry filling header 6"-HEX-6110 6 6 150# 4 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
A0-1051 Valves

254624-400-PID- Ball Electric Max 45


40 400 HV 5105 MTO TT Gantry filling header 6"-MTO-6246 6 6 150# 4.8 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
A0-1051 Valves
DOCUMENT No. 254624-400-DS-INT-022 RFQ/RFP NO.
PROJECT No. 254624 LOCATION VISHAKHAPATNAM
CLIENT HINDUSTAN PETROLEUM CORP. LTD. VENDOR As per approved vendor list
PROJECT VISAKH MARKETING TERMINAL PROJECT MODEL BTA
MODEL VTA
MOTOR OPERATED BALL VALVE TAG LIST - FIRE SAFE, FULL BORE
Design
Valve pressure / Design Inlet
Tag Line Size Valve Valve
Sr No Area no Tag Service Description P & ID Line No. Size Shutoff Temperature Temperature Valve Actuator Time in Seconds Remarks
number Inches Class Type Fail
Inches Pressure °C °C
Action
Kg/cm2 (g)
Model / Torque
Make Model Torque Type Make Open Close
Size / kW

254624-400-PID- 2"-HSD-I-4153- Ball Electric Max 45


41 400 HV 6701 From HSD Tank Truck filling Pump 2 2 150# 3.5 - 65 Stayput BTA BTA BTA Actuator
BTA BTA BTA BTA
Sec / BTA
A0-1067 109A2 Valves