Professional Documents
Culture Documents
CT-7000
Breaker Test Plan
Up to 99 circuit-breaker test plans can be stored in the CT-7000. Test plans comprise
all circuit-breaker performance specifications (stroke, velocity, contact time). By
recalling a test plan, the user can immediately test a breaker and view a pass/fail report
(made by comparing actual performance with the specifications listed in the stored
test plan). A user does not need to look-up the breaker specifications to compare with
the test results to determine if the breaker passed the performance tests. Test plans
can be downloaded to the CT-7000 via a USB or RS-232C port.
The Model CT-7000 Series 2 is a third generation, stand-alone, microcomputer- Breaker Initiate Features
driven EHV Circuit-Breaker Analyzer. It is inexpensive and easy to use. The CT- A built-in solid-state initiate device lets users operate the breaker from the CT-
7000 is available in models with 3 dry contacts (CT7000-3), 6 dry contacts (CT- 7000. The operational modes include: Open, Close, Open-Close, Close-Open,
7000-6), or 12 dry-contact inputs (CT-7000-12). The CT-7000 fully analyzes cir- and Open-Close-Open. Multiple operations (e.g., Open-Close, Open-Close-
cuit-breaker performance: contact time, stroke, velocity, over-travel, and contact Open) can be initiated by using programmable delay time or by sensing the
wipe. Contact-motion analysis includes: Open, Close, Open-Close, Close-Open, breaker’s contact condition.
and Open-Close-Open. The CT-7000 timing window is selectable: 1-second, 10-
Diagnostic Capabilities
second, or 20-second periods. The 10-second and 20-second timing windows
The CT-7000 can perform diagnostics on its internal electronics. Self testing of
allow timing of long duration events (Circuit-Switcher contacts).
transducer and contact-test cables lets users check out the Timer whenever verifi-
Contact Timing Inputs cation is required.
Breaker contact timing uses dry-contact input channels. Each contact-input Computer Interface
channel can detect main contact and insertion-resistor contact times (displays
The CT-7000 can be used in the stand-alone mode or computer controlled
milliseconds and cycles).
mode. USB and RS-232C Ports allow an IBM-PC compatible computer to con-
Voltage Monitoring Inputs trol the CT-7000. From the PC, circuit breakers can be timed and users can
One analog voltage input channel is dedicated to monitoring circuit-breaker dc retrieve timing shots saved in the CT-7000 flash EEPROM. A Windows® XP-based
power supply or coil voltages 0 to 300 volts, dc or peak ac. One digital voltage input Breaker-Analysis software lets users time circuit breakers, retrieve test-shot
channel allows users to monitor voltage on/off status of an A/B switch. data stored in the computer’s hard-drive, re-analyze the stored data, and gener-
ate reports in the office. Test reports can be exported to Excel, allowing the user
Trip/Close Current Monitoring to generate customized test-result reports. Users may also create a circuit-
A built-in Hall-effect current sensor records Trip/Close current level and duration. breaker database library. Additionally, users can create circuit-breaker test
The breaker’s operate-coil current waveform duration (effectively, a performance plans to be downloaded to the CT-7000.
"fingerprint" or "current profile") can be used as a diagnostic tool for analysis of
a breaker’s performance. User Interface
An alpha-numeric keypad lets users enter breaker ID and control functions. A 4-
Breaker Stroke and Velocity line by 20-character LCD readout displays user messages. The LCD is back lighted
Three travel transducer digital channels let the CT-7000 measure stroke, over-trav- so messages can be viewed in low light levels. A display contrast control is locat-
el, and bounce-back. Unlike other types of transducers, the digital transducer ed on the front panel.
requires neither calibration nor setup. A breaker contact-velocity calculation is
2
alyze OCB, Vacuum, and SF6 Circuit
Breakers with Vanguard’s CT-7000
Contact Timing Channel Voltage Input Channels
Linear
Transducer
RS-232C Port Trigger Input Connector
Resistor Type
Transducer Connector
CT-7000 S2
Digital Circuit Breaker Analyzer
PC Printer Output
▼
Ordering Information
CT-7000 Series 2 Digital Circuit Breaker Timer
CT-7000, 3 Contact Channels, Cables, PC Software Part No: CT-7000-3 S2 See
CT-7000, 6 Contact Channels, Cables, PC Software Part No: CT-7000-6 S2 Page 87
CT-7000,12 Contact Channels, Cables, PC Software Part No: CT-7000-12 S2 for Travel
SPECIFICATIONS
TYPE Special purpose test equipment, portable circuit breaker analyzer
PHYSICAL SPECIFICATIONS 16” W by 11” H by 14” D (40.6 cm x 29.9 cm x 35.6 cm); Weight, less than 25 lbs (11.3 kg)
INPUT POWER 90-130 Vac or 200-240 Vac (selectable), 50/60Hz
DRY-CONTACT INPUTS 3, 6 or 12 dry-input channels. Each channel detects Main and Insertion-Resistor Contacts
TIMING WINDOWS Selectable: 1-second, 10-seconds, 20-seconds
TIMING RESOLUTION ±50 microseconds at 1-second duration, ±500 microseconds at 10-second duration,
±1.0 milliseconds at 20-second duration
TIMING ACCURACY 0.05% of reading, ±0.05 ms at 1-second duration
DRY CONTACT CHANNEL PROTECTION Fuses protect all isolated power supplies. All contact inputs are grounded until test. TVS and Zener-
diode protected.
DRY CONTACT DETECTION RANGE Closed: <20 ohm, Open:> 5,000 ohm
RESISTOR DETECTION RANGE 50 to 5,000 Ohm
TRIGGER INPUT VOLTAGE Open/Close: 30-300V dc or peak ac
VOLTAGE SENSING INPUT RANGE V1: analog input; 0-255V dc or peak ac, Sensitivity ±1V; V2: voltage detector (present/absent) input;
30-300V cd or peak ac
BREAKER OPERATION Initiate Open, Close, Open-Close, Close-Open, Open-Close-Open
BREAKER INITIATE CAPACITY 30A/250V ac/dc max
INITIATE CURRENT READING RANGE One, Non-contact, Hall-Effect sensor, 0-20A, dc to 5Khz
DIGITAL TRAVEL TRANSDUCER INPUT 3 digital travel transducer channel; Linear range, 0.0-60.0 in (±0.01 in); Rotary range 0-360° (±0.36°)
RESISTOR TYPE TRANSDUCER INPUT 200 Ohms to 10K Ohms (optional)
CONTACT TRAVEL POINT DIFFERENCE Measures “Slow-Close” contact-point distances (hard copy)
DISPLAY 4 lines by 20 character back-lit LCD, sunlight viewable
PRINTOUT Both graphic contact and travel waveforms & tabulated results are printed on 4.5-inch thermal printer
TEST RECORD STORAGE Store up to 100 timing records and 99 test plans
COMPUTE INTERFACE USB and RS-232C port
PC SOFTWARE Furnished Circuit breaker analysis software running under Windows XP; features graphic display,
numerical reports, and data base utility for use at shop or office.
SAFETY Designed to meet UL 6101A-1 Certification and CAN/CSA C22.2 No 1010.1-92
ENVIRONMENT Operating: -10°C to 50°C (+15°F to +122°F); Storage: -30°C to70°C (-22°F to +158°F)
OPTIONS Hard case for shipping; available for both Travel Transducers and CT-7000
WARRANTY One-year warranty on parts and labor
Note: The above specifications are valid at nominal voltage and ambient temperature of +25°C (+77°F). Specifications are subject to change without notice.