You are on page 1of 10

Ecolibrium

THE OFFICIAL JOURNAL OF AIRAH MAY 2016 · VOLUME 15.4

Doing WELL
Making buildings better
for people. PRINT POST APPROVAL NUMBER PP352532/00001
FORUM
P E E R- R E V I E W E D T E C H N I C A L PA P E R S

A practical look at climatic data


for AC load calculation and
energy estimation
Murray Mason, L.AIRAH Director and principal engineer – ACADS-BSG


ABSTRACT
The objective of this technical paper is to identify some misconceptions in the industry in regard to the use and application
of climatic data for the design of air conditioning systems, and to highlight some of the practical issues confronting designers
when deciding on the particular climatic data to use. With both estimating loads and estimating energy consumption it is
often as much an art as it is a science, and there is all too often no “absolutely right” answer. For example, there are a number
of methods of deriving the empirical design temperatures for load calculations. A second example is the “representative”
or “average” hourly climatic data used in energy simulations is different to that when comparing actual measured energy
consumption with predictions where a number of individual years of real-time hourly data are required.
When supporting software used by the industry, the author has on numerous occasions had to explain to users many
of the issues covered in this paper.

INTRODUCTION not only the accuracy and relevance of the climatic data
that is available but also the method of calculation used,
Climatic data is required when estimating the thermal the estimated thermal properties of the materials used in the
loads in buildings. This climatic data includes dry and wet bulb building and the estimated internal loads. (Refer Ecolibrium
temperatures, solar data and wind speeds. In the air conditioning feature article “Where Legals Dare”, October 2004).
industry there are three main types of calculations that use
this data: Even with more reliable and extensive recording of climatic
data that is now carried out by the Australian Bureau of
• Air conditioning load estimation for sizing
air conditioning plant Meteorology (BOM) it is wise to give serious consideration to
applying an appropriate safety factor to any of these calculations.
• Energy Simulations to predict the likely energy consumption In the words of Aristotle, “It is the mark of an instructed mind
of a building, and to rest satisfied with the degree of precision which the nature
• Energy simulations to check compliance with the energy of a subject admits, and not to seek exactness when only
provisions of the NCC or building rating systems such an approximation of the truth is possible”.
as Green Star and NABERS.
These three types of calculations require distinctly different THE DIFFERENCE BETWEEN LOAD
climatic data. Air conditioning load estimation calculations CALCULATION AND ENERGY ESTIMATION
require empirical derived monthly design temperatures and
clear sky solar data. Energy estimation calculations require It is very important to understand the difference between
hourly temperature, solar and wind speed data. For predicting air conditioning load calculations and calculations associated
the likely energy consumption, individual years of recorded with estimating energy consumption of a building.
data are required whilst for checking compliance with the NCC Load calculations are estimates of the peak or near peak
or building rating schemes, averaged hourly data is required. air conditioning loads on individual items of plant such as
This article discusses the climatic data required for each air handling units, chillers, boilers, etc. For air-handling units,
of these types of calculations from a practical point of view the cooling and heating loads and air quantities are based on
including the limitations and availability. estimated hourly fabric loads, internal loads and outside air loads
on a single “design day” in each month of the year.

ACCURACY OF LOAD CALCULATIONS The internal loads include people occupancy, lighting and
equipment. More often than not the pattern of these throughout
AND ENERGY SIMULATIONS the day is not known. For example in a conference room
It is essential that designers recognise that all three calculations meetings might take one hour, a number of hours or a full day
are estimates only and lie within a tolerance (+-%) depending and there will be times when the conference room will have

80 E CO L I B R I U M   •  M AY 2 0 1 6
FORUM

no or minimal internal loads. The same people that occupy For the estimation of the energy consumption of a building
the conference room may also occupy other parts of the the question of which year of data should be used arises, and
building. Hence load calculations are usually based on peak in practice this may mean trying to find a hot year and a cold
occupancy, lighting and equipment loads. year to establish a range for the likely energy consumption.
When estimating the capacity of primary plant such as For the NCC and the various energy rating schemes, typical
chillers, boilers, cooling towers, etc. providing the cooling reference years of data known as reference meteorological
and heating media to the air handling units it is very important years (RMY), test reference years (TRY), etc. are required
to apply diversity to the cooling and heating loads being handled to be used and for rating purposes it does not matter which
by the air handling units so that there is no “doubling up” reference year is used because the analysis of the proposed
of internal loads. Diversity is usually very difficult to estimate and deemed to satisfy (or reference) building must use the
as it is a function of the way people move around and in and same climatic year. Furthermore, for the same reason, it does
out of the building, which in turn is a function of the building not matter which years of climatic data the reference years are
type and usage. And the exact usage of the building is not always based on. Hence with the NCC a JV3 simulation can use a TRY
known at the design stage and may well change during the life year of data that is not based on recent climatic recorded data.
of the building.
Other examples of where diversity is difficult to estimate DESIGN CONDITIONS
include shopping centres where there may be a maximum
people load in some of the shops but then at this time the people
FOR LOAD ESTIMATION
load in the Mall or food courts will be lower and visa-versa. The design conditions for load estimation are empirical
Similarly in theatres allowance for maximum people occupancy temperatures established by interrogating available climatic data.
must be considered when sizing the air handling unit serving Depending on the method of calculating design conditions, the
the lobby and the unit serving the theatre. If these two units available data can be hourly data or where hourly data is not
have CW and HW coils then the load on the chiller will not available, 9am and 3pm data. At hundreds of locations BOM
be the sum of the two air handling unit cooling coil capacities; only has 9am and 3pm readings or three-hourly readings, thus
it will be diversified. Similarly, the load on the boiler will not enabling the derivation of design conditions for a total of 850
be the sum of the two air handling unit heating coil capacities. locations in Australia
Energy simulations on the other hand involve the summation Design Conditions in
of the energy consumption of all the air handling units,
AIRAH’s Application Manual DA9
the primary plant and the internal loads over the whole year.
These loads not only vary across the day but from day to day Design conditions in the initial versions of DA9 (published
and month to month. Load profiles for people, lights, in 1973) were developed from hourly data that was available
equipment, primary plant and their ancillaries and all other at the time for18 Australian locations and one location in
energy consuming plant in the building have to be estimated PNG, by the Federal Government Department of Housing
and sometimes this can be extremely difficult. Buildings and Construction (DOHC). The number of locations was
where it can be very difficult to estimate load variations subsequently and progressively increased as BOM established
include theatres, shopping centres and office buildings more weather recording stations. A large majority of these
accommodating sales personal or people who work mainly weather recording stations did not take hourly readings but
on site who are not permanently in the building. the DOHC established a method (documented in DA9) based
on 8am and 3pm readings. In the third edition (published
The BCA and Green Star have default profiles for people in 1994).there is data for approximately 600 locations
occupancy, lights and equipment. These are average profiles and this data has been used by the Industry since then.
and should NOT BE USED in load calculations. For example
the maximum occupancy in the NCC default occupancy profile One of the criticisms of this data is that it is now out of
for people in shops and shopping centres is 25% and this is date being developed in the 1970-80s. ACADS-BSG has very
only at hour 12 and 13 (Fig 1). If designers use these figures recently re-calculated the design conditions using hourly data
when calculating design loads the air conditioning plant will supplied by Exemplary Energy for 200 locations in Australia
be undersized even more so if the peak load occurs at 3pm and 9am and 3pm data supplied by BOM. These calculations
when the occupancy is only 15%. With 3.5m2. per person say were based on data between 1990 and 2013. BOM have ceased
and the default NCC metabolic rate of 75W sensible and 55W recording climatic data at some of the original locations so
latent even with 35% occupancy value for a busy shopping day, including these locations (and their old data) there are now
this is an under sizing of 35%-15% x 130 W /3.5 = 7.43 W/m2. around 850 locations where design conditions are available.

Daily Load Profile


Nº 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Description
1 No Load 24 hrs
2 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 Full Load 24 hrs
3 10 20 20 15 25 25 15 15 15 15 5 5 2C Occup 7 days

Fig 1:  NCC occupancy daily load profile for shops and shopping centres.

M AY 2 0 1 6  •  E CO L I B R I U M 81
FORUM

Design conditions based on climatic data before 1990


JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC
3pm
38.4 38.8 33.7 29.1 24.7 18.3 19.3 22.3 23.5 30.8 34.3 37.0
CDB
3pm
21.9 21.2 21.6 19.1 15.6 13.2 12.8 13.3 15.9 18.1 19.6 20.8
CWB
Years on which design conditions are based 1975–1984

Table 1A:  Melbourne critical design conditions (DA9) (based on 1975 to 1984 data).

Design conditions based on climatic data after 1990


JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC
3pm
40.1 38.6 35.3 29.4 23.4 19.1 18.3 21.9 25.5 31.1 34.1 38.1
CDB
3pm
22.5 22.2 20.4 18.4 15.8 13.8 12.5 13.6 15.5 17.8 19.8 20.3
CWB
Years on which design conditions are based 1990–2012

Table 1B:  Melbourne critical design conditions (based on 1990 to 2012 data).

Design conditions based on climatic data before 1990


JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC
3pm
35.1 34.4 35.3 29.5 25.3 21.4 21.9 24.7 29.2 32.4 35.4 36.1
CDB
3pm
24.0 24.3 22.9 21.0 19.2 16.6 15.0 16.2 17.9 19.5 21.7 23.3
CWB
Years on which design conditions are based 1979–1988

Table 1C:  Sydney critical design conditions (DA9) (based on 1979 to 1988 data).

Design conditions based on climatic data after 1990


JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC
3pm
32.6 32.1 29.9 28.6 26.3 22.4 22.6 25.5 29.3 32.9 32.6 32.9
CDB
3pm
23.7 24.0 22.8 20.8 18.9 16.5 15.4 16.3 18.3 20.0 21.4 22.7
CWB
Years on which design conditions are based 1990–2012

Table 1D;Sydney critical design conditions (based on 1990 to 2012 data).

The monthly design conditions for cooling listed in DA9 They will also be able to be visualised and compared in the
and more recently calculated/recalculated are the independent soon-to-be published design conditions before and after 1990,
dry and wet-bulb temperatures for “comfort” and for “critical” on the AIRAH website. In some locations there was an increase
air conditioning. but in others there was a decrease. For many locations, in some
months the temperatures increased while in others it decreased.
When ACADS-BSG recalculated the design conditions
For Melbourne (Tables 1A and 1B) there is a noticeable increase.
using the more recent climatic data (1990 to 2013) it was found
In Sydney (Tables 1C and 1D) the majority of months show
that there was no consistent increase or decrease in the design
a decrease.
conditions and there were very few locations with a change
significant enough to increase or decrease the load because To illustrate the possible significance of the changes in design
the ambient temperature only affects the conduction and outside conditions, ACADS-BSG did runs to calculate the loads for an
air load. This can be seen in CAMEL where the design conditions office building in Sydney using the design conditions before 1990
based on data prior to 1990 and after 1990 are now displayed (Table 1C) and the design conditions after 1990 (Table 1D).
and can be selected by users for each of the 850 locations. The results are shown in Figure 2.

82 E CO L I B R I U M   •  M AY 2 0 1 6
FORUM

Supply Air Outside GTH GTSH GTLH Coil entering Coil leaving Time of
Title
l/s l/s kW kW kW CDB CWB CDB CWB Peak Load

Before 1990
Grnd Shop1 641 75 9.91 8.66 1.25 24.8 17.6 13.6 12.9 3PM APR
Coffee Shop 540 150 11.7 8.41 3.29 26.1 18.8 13.2 12.3 3PM MAR
Grnd Shop3 534 75 8.2 6.95 1.25 24.8 17.6 14 13 3PM MAR
Grnd Shop4 582 75 8.76 7.5 1.26 24.7 17.6 14 13 3PM APR
Typical Floor 4off 3388 347 51.1 43.5 7.6 24.7 17.7 14.1 13.1 3PM MAR
Top Floor Nth 1589 50 19.3 18.5 0.8 24.1 17.2 14.5 13.5 1PM MAY
Top Floor East 776 41 10.1 9.17 0.93 24.1 17.3 14.3 13.3 9AM DEC
Top Floor West 1049 41 13.3 12.4 0.9 24.2 17.3 14.4 13.4 5PM MAR
Top Floor Cntr 961 216 18.8 14 4.8 25.6 18.4 13.5 12.5 3PM DEC
Chiller GTH 199 kW (Typical Floor Units)     Boiler 71.7 kW
After 1990
Grnd Shop1 628 75 9.69 8.41 1.28 24.7 17.6 13.6 12.9 3PM APR
Coffee Shop 517 150 11.5 7.98 3.52 25.9 18.9 13.1 12.2 3PM MAR
Grnd Shop3 517 75 7.99 6.71 1.28 24.7 17.6 13.9 12.9 3PM MAR
Grnd Shop4 566 75 8.53 7.26 1.27 24.6 17.6 14 13 3PM APR
Typical Floor 4off 3275 347 50 41.8 8.2 24.6 17.7 14 13.1 3PM MAR
Top Floor Nth 1609 50 19.1 18.5 0.6 24 17.1 14.4 13.4 11AM MAY
Top Floor East 758 41 9.91 8.97 0.94 24.1 17.3 14.3 13.3 9AM DEC
Top Floor West 1098 41 13.1 12.8 0.3 24.2 17.1 14.5 13.4 4PM SEP
Top Floor Cntr 971 216 18.7 13.6 5.1 25.1 18.3 13.4 12.5 4PM DEC
Chiller GTH 195 kW (Typical Floor Units)     Boiler 77.3 kW

Fig. 2:  Comparison of cooling loads with design conditions based on data before and after 1990.

The extent of the difference will depend significantly on load calculations are the monthly design conditions. This
the amount of outside air and to a lesser extent the building data for Melbourne is listed in Table 2 and comprises monthly
geometry, the extent of shading from adjacent buildings, Dry and Mean Coincident Wet-bulb temperatures and monthly
the orientation of the building and to some limited extent, wet and mean coincident dry-bulb temperatures that are not
the type of air conditioning systems in the building. exceeded for 0.4, 2, 5 and 10% of the time.
There is also another problem in comparing design conditions ASHRAE (2013 Fundamentals page 14.6) states that
before 1990 and after 1990 at a given location. In many “the dry bulb and mean coincident WB values represent hot
cases BOM have changed the location of its measurement sunny days and are often used in sizing chillers and AC units
site, particularly with the introduction of automatic weather and that the WB and CDB are useful for designing cooling
stations (AWS). For example the January comfort design towers, evaporative coolers and O.A ventilation systems”.
DB for Armidale in NSW based on data prior to 1990 is 31.8°C. Earlier versions of ASHRAE have similar statements.
Based on data after 1990 the January comfort design DB is 30.8°C,
a decrease of 1°C. However, the data for Armidale prior to 1990 Using the DB and CWB temperatures may lead to
is for the BOM site in Armidale itself. The data after 1990 is at underestimation of the peak latent load particularly in places
Armidale Airport which although only 8km away is at an elevation like Darwin and Brisbane. Using both the DB and CWB
approximately 100m higher than the Armidale township. conditions and the WB and CDB conditions, however leads
to two different psychometric results (sensible and latent heat
ASHRAE design conditions and leaving coil conditions), and when a selection is made
for Australian locations. a unit must be selected with a capacity to handle both.
ASHRAE has calculated design conditions for approximately The question arises as to which of the ASHRAE percentage
362 locations in Australia using temperature data recorded exceedance levels should a designer use and which are equivalent
from 1990 to 2012 by BOM primarily at their automatic weather to the DA9 comfort and critical conditions. Table 3 lists for all
stations. The ASHRAE data for each location comprises a range the Australian capital cities, the 0.4% and 2.0% design dry bulb
of climatic data but of interest to designers undertaking temperatures for the month with the highest design dry bulb

M AY 2 0 1 6  •  E CO L I B R I U M 83
FORUM

Monthy Climatic Design Conditions


Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
DB 39.3 37.6 35.1 28.7 22.8 18.7 17.4 21.1 25.0 30.0 33.5 36.9
0.4%
Monthly   MCWB 20.2 19.7 18.0 16.4 14.4 12.8 10.8 13.1 14.0 15.7 17.8 17.9
design   DB 34.7 33.9 30.8 25.9 20.6 17.1 15.8 18.6 22.1 26.4 29.7 32.7
Dry Bulb 2%
MCWB 18.8 19.2 18.1 15.5 13.7 12.3 10.6 11.9 14.0 15.2 17.3 17.5
and Mean
coincident DB 31.4 31.2 27.9 23.7 19.0 15.9 14.9 17.0 19.9 23.8 26.8 29.3
5%
Wet Bulb MCWB 18.7 18.8 17.6 15.2 13.2 11.5 10.2 10.8 12.8 14.2 16.5 17.3
temperatures DB 27.9 28.2 25.2 21.7 17.6 14.9 14.0 15.6 18.1 21.3 24.1 25.8
10%
MCWB 18.6 18.6 17.0 14.7 12.7 10.9 9.8 10.2 11.7 13.5 15.7 16.8
WB 22.6 22.7 20.4 18.2 15.7 14.3 12.3 14.1 16.3 17.9 20.1 20.5
0.4%
Monthly   MCDB 29.1 30.7 28.2 24.9 19.1 17.1 15.3 18.6 21.7 24.8 26.6 28.1
design   WB 21.4 21.2 19.4 17.0 14.9 13.0 11.6 12.5 14.8 16.4 18.7 19.4
Wet Bulb 2%
MCDB 29.1 28.3 26.3 22.5 18.5 15.8 14.5 17.4 20.3 22.9 25.6 26.7
and Mean
coincident WB 20.1 20.3 18.5 16.0 14.1 12.1 10.9 11.5 13.5 15.2 17.6 18.5
5%
Dry Bulb MCDB 28.1 27.1 25.1 21.7 17.8 15.0 13.8 15.8 18.8 21.6 24.7 25.6
temperatures WB 19.0 19.4 17.7 15.1 13.4 11.4 10.3 10.7 12.2 14.1 16.5 17.6
10%
MCDB 26.0 26.1 23.9 20.4 16.9 14.3 13.2 14.6 16.9 19.8 22.8 24.7
MDBR 9.5 9.3 8.6 8.3 6.6 5.5 5.7 6.8 7.6 8.6 9.0 9.3
5%
Mean daily MCDBR 16.8 15.5 14.3 12.3 8.8 6.7 6.8 9.2 10.7 14.0 14.8 16.5
DB
temperature MCWBR 5.0 4.6 4.5 5.0 4.4 3.6 3.7 4.5 5.1 5.5 5.4 5.0
range MCDBR 12.7 11.7 11.1 9.9 7.0 5.4 5.8 8.2 9.2 10.9 11.7 12.3
5%
WB MCWBR 5.3 4.5 4.5 4.7 4.0 3.3 4.5 4.8 4.8 5.1 5.2 5.1

Table 2:  ASHRAE design conditions for Melbourne.

temperature and compares this with the revised (post 1990) INDEPENDENT OR COINCIDENT
comfort and critical design conditions. This limited evaluation
suggests that the Critical DA9 figures are approximately DESIGN CONDITIONS?
equivalent to the ASHRAE 0.4% values whilst the Comfort When DOHC metricated the “Carrier Air Conditioning”
DA9 figures are approximately equivalent to the 2.0% values. Air Conditioning Load Estimation and Psychrometrics Manual,
The correlation however is not precise as the method of (the forerunner of AIRAH’s DA9) and included design conditions
calculation is different and in the case of Darwin the ASHRAE for a number of Australian locations, they were added in the third
2.0% value is 2.0 degrees lower than the DA9 comfort figure. edition of DA9 included the independent DB and WB conditions.

ASHRAE ASHRAE ASHRAE


ASHRAE 0.4% 0.4% ASHRAE 2.0%
DA9 Comfort DA9 Critical
0.4% compared to compared to 2.0% compared to 
DA9 Comfort DA9 Critical DA9 Comfort

MELBOURNE 39.3 34.6 40.1 5.3 above 0.8 below 34.7 0.1 ABOVE
SYDNEY 34.0 30.1 32.6 3.9 above 1.4 above 29.8 0.3 Below
BRISBANE
32.9 30.3 30.9 2.6 above 2.0 above 30.6 0.3 above
AIRPORT
ADELAIDE 39.8 35.3 40.3 4.5 above 0.2 below 35.8 0.5 above
PERTH 39.3 36.7 40.0 2.6 above 0.7 below 35.8 0.9 below
CANBERRA
36.9 34.3 37.6 2.6 above 0.7 below 34.1 0.2 below
AERO
HOBART
32.7 27.1 31.2 5.6 above 1.5 above 27.8 0.7 above
AERO
DARWIN
35.0 34.6 35.2 0.4 above 0.2 below 32.6 2.0 below
AIRPORT

Table 3:  Comparison of ASHRAE 0.4% and 2.0% and DA9 critical and comfort design dry temperatures for Australian capital cities.

84 E CO L I B R I U M   •  M AY 2 0 1 6
FORUM

The corresponding mean coincident WB (MCWB) and mean


coincident DB (MCDB) conditions. ASHRAE, as described above,
lists the DB and MCWB and WB and MCDB temperatures.
The DB and MCWB temperatures will generally give the peak
sensible load. The WB and MCDB will generally give the peak
latent load which is also required information, particularly in
tropical locations such as Darwin, for sizing and selecting an air
conditioning unit. However, if these two calculations with the
different ambient conditions are carried out there will be two
different unit capacities and associated psychrometrics (entering
and leaving coil conditions). If a supplier is presented with this
information they are just as likely to ask, “Which figures do you
want to make the selection on?”
Figure 3:  ASHRAE DB and CWB and WB and CDB design conditions
With the DB and CWB condition, the latent load can sometimes for Sydney with different psychrometrics and independent conditions.
be negative (refer Fig 3) which means humidification is required
if the room RH is to be maintained. Whichever way the calculations are made (two runs using the
To overcome this and to avoid having to do two load calculations coincident temperatures or the one run using the independent
for every project, the DOHC design staff used the independent temperatures) there can be difficulties in achieving the room
conditions – refer Fig 3. Now the independent DB and WB relative humidity. This is because at the time of the peak sensible
temperature may never occur together and designers have load the latent capacity will be too high and this could result
commented on this but they don’t have to occur together, they in a drop in room RH. At the time of the peak latent load, with
are conditions that will enable an estimate of the sensible and dry-bulb control only, once the sensible load is satisfied the coil
latent capacities in the one run and produce the psychometrics will cease cooling and the room RH will rise, i.e. there will not
to match these capacities. be enough de-humidification.

1990–2012
JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC
3pm
32.6 32.1 29.9 28.6 26.3 22.4 22.6 25.5 29.3 32.9 32.6 32.9
CDB
3pm
23.7 24.0 22.8 20.8 18.9 16.6 15.4 16.3 18.3 20.0 21.4 22.7
CWB

1990–1999
JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC
3pm
32.3 31.8 29.8 28.3 26.6 22.5 22.4 26.0 26.7 32.3 32.5 32.0
CDB
3pm
23.3 23..9 22.4 21.0 18.8 16.4 15.2 16.4 17.9 20.0 21.0 22.6
CWB

2001–2012
JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC
3pm
33.0 32.7 30.0 29.0 26.0 22.5 22.8 25.3 30.7 33.3 32.8 33.0
CDB
3pm
23.9 24.2 22.8 20.7 18.6 16.7 15.7 16.3 18.5 20.0 21.6 22.7
CWB

2006–2012
JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC
3pm
31.9 32.8 29.8 28.3 26.5 20.6 22.8 25.8 31.4 33.5 35.2 30.8
CDB
3pm
23.8 24.0 22.9 20.5 18.7 16.0 15.8 16.3 18.0 19.9 21.6 22.5
CWB

Table 4:  Sydney comfort design conditions based on different years of climatic data,

M AY 2 0 1 6  •  E CO L I B R I U M 85
FORUM

To avoid this problem in situations where the low and high (because of the difference between local and solar time) and
humidity conditions are significant enough to cause discomfort, validated including interpolation of missing data, etc. In some
as can often occur in tropical locations or systems with high instances solar data from an adjacent location had to be merged
latent loads such as cinemas, possible solutions include: with ground recordings. From the resultant years of complete
• Install a humidity controller to override the temperature data, using three different correlation procedures, 12 average
control and use reheat, or months of data from different years were then merged into a
single year of data. The correlation procedures are dependent on
• Install a humidity controlled pre-conditioner on the outside
air, or the type of building and factors such as solar penetration (type A
for residential buildings and type B and C
• Lower the room temperature so that the sensible cooling for commercial buildings)
load increases and causes the coil to dehumidify for longer.
The federal government undertook this work and released the
There have been numerous suggestions in the past that comfort RMY files (69 locations) through NATHERS (National Housing
room conditions in tropical locations should be raised to say Energy Rating Scheme). Energy Partners also undertook similar
26°C in lieu of the traditional 24°C. This may save energy and development of ERMY files for the 69 RMY locations plus
reduce the thermal “shock” when entering a conditioned area
an additional 131 locations in Australia.
from outdoors but will aggravate the high humidity problem
described above. The TRY, RMY or ERMY files can be used for JV3 simulations
for checking NCC compliance and Green Star Ratings. Because
of the methodology of the NCC, JV3 compliance comparing
HOW MANY YEARS OF DATA the proposed building with a reference building, it does not
SHOULD BE USED TO CALCULATE matter that using these files will not result in a realistic estimate
DESIGN CONDITIONS? of the energy consumption of a building. In fact, it is more likely
to produce a lower than average estimate of the building energy
The recalculated conditions and the ASHRAE conditions
consumption because it is highly unlikely that a year with
were all based on climatic data for all years within the range
12 months of average weather will ever occur. The same applies
from 1990 to 2013 where BOM had recorded data available.
with a simulation for Green Star and simulators should fully
An investigation was carried out by ACADS-BSG using
understand this.
Sydney data as an example to illustrate the significance of
using a different number of successive years of data to calculate Actual individual years of data also need to be reliable
design conditions. The results are listed in Table 4 and it can and validated and the only such post-1990 data available in
be seen that it does make a noticeable difference. Not as much Australia are those that can be purchased from Energy Partners.
as the difference between the “before” data and the “after” This is despite the fact that the first step in the process of
data, but significant enough to make the point that the design developing the RMY files by the federal government was to
conditions are not precise numbers – another reason to always obtain a number of years of data (1990 to 2012) from BOM
add a safety factor to the estimate of cooling and heating loads. and carry out the complex task of validating the data and
merging the ground measured and solar data as described above.
HOURLY DATA FOR ESTIMATING When inquiries were made to the Department of Industry
on the availability of this data, the ridiculous response was
ENERGY CONSUMPTION that the individual years of data used by the Department
A variety of hourly climatic data files are available are owned by BOM and that users need to obtain the data
for energy simulations. They are of three types: from BOM (which of course is the federal government).
• A selected year of data where the monthly means and
standard deviations for that year match (or come closest to) Energy consumption – Sydney Office Building
those for a longer period of time. In Australia until more
recent data became available, a method developed in the 800,000
Cooling, heating and fan energy MJ

US was used to select these years from the limited hourly 700,000
data available in the 1970–80s. These files were known
as TRY files. 600,000

• Representative years of data comprising a concatenation 500,000


Fan MJ
of average months from different years. Two sets of these 400,000 Heating MJ

have been developed in Australia and are referred to as RMY Cooling MJ

files. Similar TMY and WEYC2 (Weather Year for Energy 300,000

Calculations) files developed by ASHRAE are also used 200,000


in some simulation programs used in Australia.
100,000
• Individual years of actual data.
0
1981 TRY
ERMY
1990
1991
1992
1993
1994
1995
1996
1997
1998
1990
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
AVE

The development of the RMY files is quite a complex


process. Appropriate and reliable hourly ground recordings Year
(temperatures, wind speed and direction, etc.) and solar
recordings were obtained from BOM and aligned in time Fig 4:  Estimated energy consumption of a six-storey building in Sydney.

86 E CO L I B R I U M   •  M AY 2 0 1 6
FORUM

These actual years of data are required for: It can be seen from this analysis that a more meaningful insight
• Estimating the likely energy consumption of a new building into the likely energy consumption of a building can be gained
for an owner, by running a number of simulations using individual years
of climatic data over a period of time. Even more so if realistic
• Estimating the energy consumption of a building for profiles for internal loads can be established rather than using
comparison with energy bills as required by NABERS. the default profiles of the NCC, GreenStar and NABERS.
This requires data for the period of the energy bill, The average energy consumption of the runs will invariably
which may be less than 12 months. be higher than the consumption using an RMY climate file
• Estimates of an off-axis energy consumption of a building and the average and a likely range of energy consumptions
as part of a Green Star submission. can also be presented to the client. Changing the weather file
is a simple matter when running an energy simulation program
Figure 4 is a plot of the estimated cooling, heating and fan and a batch file to run a number of years of data on the one
energy consumption of a six storey building in Sydney (using building should not be difficult.
the ACADS-BSG program BEAVER) for the individual years
from 1990 to 2012. At the left hand end of the plot is the energy
consumption using the TRY (1981) file and the ERMY files. SUMMARY
At the right-hand end is the average energy consumption In this presentation the author has attempted to explain
of the individual years. the difference between the empirical monthly design conditions
used for load estimation and hourly data used for energy
Cooling Heating Fan simulations. It also discusses the use and application of the
Total hourly data that is available, for simulations when investigating
Energy Energy Energy
JV3 compliance under the NCC and when calculating energy
1981 TRY 399774 140863 141888 682525 ratings for Green Star where representative data is used and
when individual years of data are used for advising Clients
of likely energy consumption, post occupancy simulations
ERMY 364252 144469 137386 646107
for NABERS ratings and off-axis simulations for Green Star.

Average 374840 145585 139234 659659 Some of the conclusions that can be drawn from the calculations
and comparisons undertaken in preparing this paper include:
Table 5:  Comparative energy consumptions (MJ)
for the TRY and ERMY and the average. Design conditions
Table 5 is a comparison of the cooling, heating, fan and the total • The monthly design conditions determined using
of these three energy consumptions when using the 1981 TRY more recent climatic data, are not necessarily higher
and the ERMY and the average energy consumptions for all years than the current design conditions listed in AIRAH’s DA9,
from 1990 to 2012. which were based on climatic data before 1990. In fact
sometimes they increase, sometimes they decrease and
in many occasions there is a shift in when the peak
Cooling Heating Fan temperatures occur.
Total
Energy Energy Energy
• Users need to be aware when comparing design conditions
based on the more recent climatic data that many of the
1981
Maximum 1981 (TRY) 2012 2004 BOM measuring stations have moved or been replaced by
(TRY)
stations at other nearby locations such as from the post office
in town to the airport.
Minimum 1995 2005 1992 1995
• There are benefits of using design conditions based on
Table 6:  Year when the estimated maximum and minimum
independently determined DB and WB conditions when
energy consumptions (MJ) occur compared to trying to achieve a single solution when using
the DB and coincident WB and the WB and CDB conditions
These values reveal some interesting results: published by ASHRAE.
• The ERMY consumptions are lower than the average • There is an element of uncertainty in assuming the
consumptions as can be expected because the ERMY file 0.4% exceedance levels equate to the “Critical” conditions
is 12 average months in one year, not an average year. in DA9 and 2.0% exceedance levels equate to “comfort”
• The 1981 TRY year cooling consumption is higher than the conditions.
ERMY consumption whilst the heating consumption is lower • In Australia there are many locations in close proximity that
suggesting that the weather on which the TRY year was based have noticeably different monthly design conditions. Hence
(10 years in the 1970–80s) were much warmer than those the more locations where design conditions are available, even
from 1990 to 2012. This correlates with the general reduction if based on 9am and 3pm data only, the more likely the site is
of design conditions for Sydney listed in Tables 1C and 1D. closer to a weather location and hence the more accurate the
• Although only one location was investigated, there is design calculations will be.
no indication of global warming or heat island affect. • Because load calculations even using more recent climatic
There is variation in energy consumption between years data are still only estimates, designers should still consider
due to variations in climate but no apparent upwards trend. adding a safety margin to their calculations.

88 E CO L I B R I U M   •  M AY 2 0 1 6
FORUM

Energy simulations • For energy simulations, it is not practical to obtain individual


• With the recalculation of design conditions using years of hourly data from BOM that is reliable and validated,
more recent data (post 1990) carried out by ACADS-BSG with the time of ground recorded data (local time) aligned
and typified in Table 1A to 1D, there is no evidence of with solar data (Satellite GMT), etc. as claimed by the
global warming of any significance to load estimation. Department of Industry. Fortunately Exemplary Energy
Nor is there any indication with energy calculations as has individual years of data from 1990 to 2013 and if required
typified in Figure 4. All that is apparent is the variation in (e.g., for NABERS) up to the present month.
climate from year to year. This is not to say we should not be • RMY climatic data and the default operating schedules for
looking seriously at reducing energy for other good and valid people, lights and equipment should only be used when rating
reasons (Ed’s note: nor, of course, that global warming isn’t a building for Green Star or checking compliance with NCC.  ❚
taking place).
• There is a definite need for individual years of data for
NABERS simulations, for off-axis simulations for Green Star
and when providing estimates to Clients of the likely range of
energy consumption that can be expected for a new building ABOUT THE AUTHOR
over a period of years. AIRAH should request the federal Murray Mason is a fellow and life member of AIRAH,
government release this valuable data to the public. a fellow of the Institute of Engineers and the Institute
• While it is appropriate to use RMY data for checking NCC of Energy and is a director and the principal engineer
compliance and energy ratings, using climatic data for a of ACADS-BSG. He has over 20 years’ experience as a
number of individual years can provide a better appreciation design engineer with DOHC and 35 years’ experience
of the likely energy consumption of a building by determining developing and supporting building services software.
a range of likely consumptions.

M AY 2 0 1 6   •   E CO L I B R I U M 89

You might also like