Professional Documents
Culture Documents
By
Chandana Dalugoda
This paper gives an actual calculation methods as well Usually, heat load is computed for peak load and par
as rule of thumbs and first cut analysis which may be tial load and then it is compared to achieve any load
particularly important to all mechanical and civil en reductions.
gineers who are not in the air conditioning field.
3.0 Building survey
1.0 Introduction
First step for a proper heat load calculation is to ob
Scope of this article is firstly to give a brief under tain an accurate physical data of the building, weather
standing of the standard practice and secondly giving it is a multi-storied complex or a small room.
a simple steps to do a heat load as in'the case for first
cut analysis or use of rule of thumb check figures. 1. Building plan - civil layout or sketch of the space
However these methods shall have limited applica to be air-conditioned with all the exterior walls
tions such as in-house small air conditioning jobs. adjacent rooms shown. Ceiling height, beam
heights etc.
Air conditioning can be classified in to two groups, as 2. Orientation of the building - compass points-
Human Comfort A / C and industrial A / C . In this arti North /south direction.
cle; our study is limited to Human comfort A / C with
cooling and de-humidification only. We shall ignore 3. Effect of other building structures - shading ef
the heating part of the A / C system for convenience of fects by other buildings, reflective surfaces by
study. parking lots, windows etc.
4. Weather data - Climatic conditions of the area of
Air conditioning provides controlling of following the building.
factors in a given environment:
79
Figure 1: Air conditioning ess without prc-heat/rchcat
5. TYPE OF SPACE USED FOR - WEATHER THE SPACE USED 5.0 Load calculation methods
FOR OFFICE, BANK, RESTAURANT, CONFERENCE HALL, FAC
TORY, BEDROOM ETC. THERE ARE THREE TYPES OF LOAD CALCULATION PROCEDURES
ESTABLISHED BY ASRHAE SUCH AS;
6. BUILDING CONSTRUCTION MATERIALS - TYPE OF MATERI
ALS AND THICKNESS, COLOUR OF THE ROOF, WALLS, 1. TRANSFER FUNCTION METHOD (TFM)
GLASSES, FLOOR FINISHES ETC. 2. COOLING LOAD TEMPERATURE DIFFERENCE METHOD
7. TYPE OF EQUIPMENT - WATER ANALYSES REPORT OR (CLTD/SCL/CLF)
SAMPLE TO DETERMINE WEATHER WATER COULD BE USED 3. TOTAL EQUIVALENT TEMPERATURE DIFFERENCE METHOD
AS CONDENSER MEDIA OR AIR COOLED SYSTEM IS PRE (TETD)
FERRED INSTEAD.
THE TRANSFER FUNCTION METHOD IS DIRECTLY USED IN COM
8. SUITABLE LOCATION OF EQUIPMENT
PUTER PROGRAMMES. TETD METHOD, DESCRIBES AN ALTER
9. ELECTRICAL POWER AVAILABILITY NATE COOLING LOAD CALCULATION METHOD PREFERRED FOR EX
10. MODE OF OPERATION - TIME OF DAY EQUIPMENT OP PERIENCED DESIGNER, REQUIRE GREATER FLEXIBILITY IN USING
JUDGEMENT IN COMPUTING COOLING LOADS. CLTD METHOD
ERATION.
IS THE MANUAL PROCEDURE OF CALCULATING LOADS, WHICH
DESCRIBES IN THIS ARTICLE.
4.0 Components of the heat load
CARRIER E-20 IS ANOTHER FAMOUS LOAD CALCULATION PROCE
THERE ARE TWO BASIC COMPONENTS OF THE AIR CONDITION
DURE, WHICH IS THE SAME METHOD, USED IN CI .TL )/S( "I /
ING HEAT LOAD;
CLF.
1. OUTDOOR LOADS
6.0 Load Calculation Procedure
2. INTERNAL LOADS
(CLTD/SCL/CLF) Method
OUTDOOR LOAD IS DUE TO OUTSIDE WEATHER CONDITIONS
OUTDOOR (EXTERNAL LOADS) AND INTERNAL LOADS ARE
AND THE SUN EFFECT THROUGH THE BUILDING ENVELOPE.
THESE ARE SOLAR HEAT GAIN FROM THE SUN AND THE TRANS CALCULATED USING;
MISSION HEAT GAIN (CONDUCTION) DUE TO TEMPERATURE
Q = U.A. (CLTD) WHERE, U-FACTOR AND TL, T2 HAVE TO
DIFFERENCE THROUGH THE BUILDING STRUCTURE.
BE CALCULATED. IN SOME CASES, U - FACTORS ARE GIVEN FOR
VARIOUS MATERIALS AND DIFFERENT COMBINATIONS. IT IS
INTERNAL LOADS DUE TO HEAT GENERATION FROM THE PEOPLE,
PREFERRED THAT ALL THE U-FACTORS ARE CALCULATED FOR THE
LIGHTS, APPLIANCES, ELECTRIC MOTORS, OUT-DOOR AIR FOR
PARTICULAR COMPOSITE WALLS AND OTHER MATERIALS. IN
VENTILATION AND BY PASS AIR THROUGH THE COOLING APPA
APPENDIX A, USEFUL U-FACTORS AND SUNGAIN TEMPERA
RATUS.
TURE DIFFERENCE ARE INCLUDED FOR TYPICAL CASES THAT CAN
BE USED IN QUICK HEAT LOAD CALCULATIONS.
80
External Loads 9. Lights
1 latent
q = UA(t -t )
> f
7. Glass
CFM = volume flow rate of infiltrating air, ft3/min
q = A(SC) (SCL) t o = outdoor temp.
A = Area calculated from building plans, ft 2
t r = room design temp.
SC = shading coefficient, dimensionless 13. Infiltration of air (Latent)
2
SCL = solar cooling load factor, Btu/fh.ft )
q = 4840 (CFM) (w^w^
Internal Loads
CFM = volume flow rate of infiltrating air, ft3/min
8. People w o = moisture content for outdoor air, lb/lb
^1 sensible = N F q, (CLF)
d hg
w r = moisture content for room air, lb/lb
^ latenl = N F In*
d Ventilation Load
81
15. Ventilation air (Latent) Design Dry Bui = 90 °F
Design Wet Bui = 81°F
q 1= 4840 (CFM) (v^-w^
M e a n Daily rang = 15 °F
CFM = volume flow rate of ventilation air, ftVmin Wind speed = 6 knots
w o = moisture content for outdoor air, lb/lb These data required to determine the peak solar time
w r = moisture content for room air, lb/lb and the month of the year and to compute the solar
gain through glasses. These data are very useful to
16. Heat gain in air distribution system determine the solar gain through glass during morn
ing hours of the East exposure and the evening of the
q = U A (t,-t) d
West exposure of a building.
U = design heat transfer coefficient (U-factor)
Btu/(h.ft2.°F) 9.0 Indoor Design Conditions
2
A = out side surface area of duct, ft Indoor design conditions are given in A S H R A E for
t n = temp, of duct surface, °F deferent space utilisation.
t r = room design temp., °F For commercial and public buildings, inside design
conditions would be
N O T E : The heat gains of duct system must be consid
ered when the ducts are not in the conditioned space. SPACE USED FOR "F RH%
Total heat gain from ducts would be 1 to 3 % of the DB
room sensible heat gain, when the ducts are not in the
Office Buildings 74/78 40/50
conditioned space and insulate.
Restaurants 74/78 55 / 60
Grand Total Heat Libraries & M u s e u m s 68/72 40/55
Airport Terminals 74/78 50/60
Grand total heat (GTH) in Btu/h is the addition of the
above individual loads from 1 to 16. However tropical climates with high relative humid
G T H could be given in Tons of Refrigeration (TR); ity such as Sri Lanka is find it difficult to maintain in
T R = G T H / 12'000. door conditions of 5 0 % R H by a normal air condition
In SI units, K W = T R x 3.517. ing. Therefore it is much appropriate to maintain in
R
times of the day. els. . Air quantity is proportional to the total occu
pancy for given application. Outdoor air quantities
For simplicity of the calculation, chart given in
per person are derived to achieve m a x i m u m concen
Apendix-1 describes the (CLTD/SCL/CLF) method.
tration of 1000 p p m of C O or below.
z
82
11.0 Psychrometric Analysis CFM OT = volume flow rate of out door air, ftVmin
CFM ra = volume flow rate of return air, ff/min
The heat load computed as above is then be used to
determined various parameters for selection of equip CFM M = volume flow rate of supply air, frVmin
ment and design of the air distribution system.
Coil Leaving Temperature
1. Room sensible heat factor (RSHF)
t, = t . + BF (t -1 . )
2. Supply air flow rate, CFM
3. Bypass Factor t >d = temp, apparatus dew-point, °F db
4. Coil entering conditions, °F db, Pre-heating
°Fwb
5. Coil leaving conditions, °F db, In winter season, although refrigeration is not re
°Fwb quired for controlling the dry bulb temperature, it is
required to control the relative Humidity. Hence, air
6. Pre-heating (sensible heating)
conditioning machine has to run despite low ambient
7. Re-heating (sensible heating) conditions. In these conditions, mixed air temperature
entering the coil becomes too low, and heating is re
Typically an air conditioning system undergoes 'cool
quired, which is usually a waste full of energy. Con
ing and de-humidification' process with' heating and
sequently air undergoes a sensible heating process.
humidification' process.
Return air duct heat gain also part of this sensible
If we consider the return air duct heat gain and fan
heating process.
motor and supply air duct heat gain, there will be an
additional process, namely, sensible heating. Re-heating
Room sensible heat factor (RSHF) Re-heating is sensible heating, usually occur after air
v leaves the coil before it enters the room. This is mainly
RSHF = Room sensible heat
due to Fan motor heat and supply duct heat gain.
Room sensible + Room latent
However, re-heating is used effectively and economi
NOTE: Refer to Figure-1 cally for reducing the RH% of a given space.
RSH = add 1 tol2 (only sensible portion) Also it requires in spaces where high latent load are
RLH = add 8+11+13 (only latent portion) prevails with low RSHF values.
83
SELECTED DESIGN CRITERIA FOR FIRST CUT Following areas require specific calculations to deter
ANALYSIS (ASHRAE) mine the load, hence do not apply check figures.
2
400 ft /TR, However w e m a y not require all of the above for a
small A / C job, hence following points could be the
However, above data differs greatly with the country desirable requirements.
and the weather conditions that you're working with.
If w e consider the Sri Lanka conditions, following Sensible Load
check figures would be much appropriate for first cut
Total sensible load should be equal or higher than the
analysis.
equipment sensible heat Capacity (SHC). If the equip
Offices - Ground floor levels ment S H C of the equipment is smaller than the load,
room designed dry bulb temperature could not
2
220 ft /TR, based on; achieve and discomfort results. Therefore all ways
2
1.5 W / ft for lights match the S H C and the sensible load and to do this
Ground floor level you require equipment performance curves / tables.
less windows Because of the standard capacity data in catalogues
400-350 cfm /TR are based on standard outdoor/indoor conditions
2
200 ft /person for occupancy they should be corrected for the particular design con
ditions that the designer has selected before selecting
Offices - Upper floor levels equipment
2
190 ft /TR Latent Load
Banks As shown in the above Total latent capacity of the
2 room also match with equipment latent heat capacity
190 ft /TR banking area
(LHC), unless, relative Humidity control would be
2
220 ft /TR, other areas impossible.
Restaurants Usually most of the general A / C applications have
2
8 0 % S H L and 2 0 % L H L of a building. All n e w Pack
190 ft /TR
aged equipment / factory charged room air condi
Computer rooms- normal tioners are also having a similar ratio of the S H C and
L H C . Hence it is not a problem in selecting packaged
2
200 ft /TR equipment for a normal comfort application. H o w
ever, spaces like Auditoriums, Theatres, and restau
rants, Conference halls have much higher Latent heat
loads and the above rule m a y not be true.
84
14.0 Conclusion References
Heat load is depend upon various factors due to 1. ASHRAE -1997 Fundamentals Volume
weather conditions, building materials, occupancy, 2. ASHRAE - Cooling & Heating Load Manual
equipment etc., hence it cannot be guess or use rule of
3. Air conditioning System Design Manual
thumb. However it is, a close assumption could be
made with check figures if we use common sense.
Appendix 1
ITEM 1
AERA (FT ) CLTD U-FACTOR BTU/HR
GLASS (N)
GLASS (S)
GLASS (W)
GLASS (E)
WALL (N)
WALL (S)
WALL (W)
WALL(E)
ROOF
ALL GLASS
PARTITION
CEILING
FLOOR
INFILTRATION
INTERNAL HEAT
PEOPLE
POWER
LIGHTS
APPUANCES
OUTDOOR AIR
LATENT HEAT
PEOPLE
STEAM
APPUENCES
OUTDOOR AIR
SENSIBLE
LATENT
G R A N D TOTAL
85