Professional Documents
Culture Documents
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
The Phoenix Integrated Surface Panel (ISP) is the equipment used to interface between the
Downhole Multisensor Tool and the operator. It supplies the power to the Multisensor, and
decodes the data returned. It also outputs the data in a format that can be used by the operator.
This section of the Manual gives a detailed description on the functions, operation, set-up and
installation of the ISP. It also gives some basic fault finding hints to help resolve some field
problems.
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
SAFETY
WARNING
WARNING
WARNING
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
COMPLIANCE NOTICE
EN 61000-4-4 (1995) at 1kV (signal lines) and 2kV (AC power lines)
for Fast Transients Immunity
(1990)
THE PHOENIX MULTISENSOR SYSTEM IS PROVEN ACROSS THE RANGE OF
MOTORS AND PUMPS FROM THE FOLLOWING MANUFACTURERS;
Reda Pump Company, Inc
Centrilift, Inc
Oil Dynamics, Inc
ESP, Inc
ALNAS
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
This manual is the copyright of Phoenix Petroleum Services Ltd and must not be copied in part or full
without the prior written permission of Phoenix Petroleum Services.
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
COMPLIANCE NOTICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2. SPECIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
8. POWER UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
8.1 Power Up Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
8.2 Running Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
ALARM TRIP
4 x 20 CHARACTER LCD
BACK-LIGHT Pi 1 2 0 0 PS I (9mm HIGH CHARACTERS)
& HIGH CONTRAST
Pd 2 2 0 0 PS I
F l ow 1 0 0 0 0 b f p d
DO WN U P ACK MOR E
4 SOFT KEYS
TERMINAL
ACCESS PANEL PHOENIX PETROLEUM SERVICES LIMITED
INVERURIE
ABERDEENSHIRE
ASSEMBLY No. A446229 AB51 0ZJ
IP66 ENCLOSURE
U.S. PATENT 5,539,375 SCOTLAND
U.K. PATENT PENDING UNITED KINGDOM
NORWAY PATENTS PENDING TEL. (44) 1467 620102
OTHER PATENTS PENDING FAX. (44) 1467 620824
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
1. S y s te m D e s c r i p t i o n - I n t e g r a t e d S u r f a c e Pa n e l ( I S P )
Monitoring, local and remotely, with logging of events together with protection of the well and electric
submersible pump is the function of the Phoenix Integrated Surface Panel for the Phoenix range of
MultiSensor instrumentation.
Within the range of Phoenix MultiSensor systems are measurements detailed below
Interfacing to other well information is provided to allow integrated well systems management. Surface
flow meters, pressure measurements and valve positions are typical of the external data which may be
gathered, displayed locally or remotely, logged and protected upon.
Outputs are made available to provide both protection (alarm or trip if the well is in a fault condition)
and feedback control to move the system to a more optimum operating point (using analogue outputs).
These all provide for an Integrated Monitoring and Protection Solution from Phoenix.
To provide remote monitoring and control a Modbus RTU protocol port is standard with both RS232 and
RS485 options on board. All measured data may be accessed via this port.
For local monitoring a Data Logging Port (RS232) is standard and is used for logging to a PC while local
to the ISP or by the Phoenix Portable Data Collector to upload the Data Logger memory (2 Mbyte of data
logger is a standard feature to ensure that all information leading to an event - alarm or trip - is
captured).
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
2. Specification
Dimensions Height 30 0 m m
Wi d t h 230 m m
Depth 96mm
We i g h t 7. 5 k g
M a te r i a l Aluminium
Finish L e a d Fr e e Po w d e r C o a t Pa i n t
Colour O r a n g e ( Pa n t o n e 150 5 )
Po w e r S u p p l y Vo l t a g e U n i v e r s a l 8 5 - 26 4 V AC , ( 110 - 370 V D C )
Fr e q u e n c y 47 - 4 4 0 H z ( o r D C )
N o m i n a l Po w e r 35 W
Fu s e R a t i n g 3 . 15 A ( T )
Ke y p a d 4 b u t t o n t a c t i l e k e y p a d t o I P 6 6 ( k e y m e a n i n g s g i v e n o n LC D
during operation)
Set Up Memory 16 K n o n - v o l a t i l e I S P s e t u p a n d s h o r t d u r a t i o n l o g m e m o r y
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
Standard Outputs
1 off Tr i p R e l a y 24 0 Va c / d c , 5 A , N C - Po l e - N O ( C Fo r m )
1 off M o d b u s RT U Po r t m e n u s e l e c t a b l e R S 232 ( 3 w i r e ) o r R S 4 8 5 ( 4 w i r e ) b a u d r a t e
s e l e c t e d t o 19 20 0 , 9 6 0 0 , 4 8 0 0 , 24 0 0 , 120 0 , p a r i t y n o n e ,
1 s t o p b i t , 8 d a t a b i t s , a d d r e s s 1- 255 , n o h a r d w a r e h a n d s h a k i n g
2 off A u x . Po w e r S u p p l y 12 Vd c + / - 10 % , 10 m A f o r u s e w i t h r e m o t e r e l a y s / p u s h - b u t t o n s a n d
ISP analogue inputs
Standard Inputs
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
T Y P I C A L I N T EG R AT E D S U R FAC E PA N E L ( I S P ) I N STA L L AT I O N
MOTOR TERMINALS A
MOTOR TERMINALS
INTEGRATED SURFACE PANEL (ISP)
B STAR
POINT
ALARM TRIP
C
Pi 1 2 0 0 PS I
Pd 2 2 0 0 PS I
F l ow 1 0 0 0 0 b f p d
DO WN U P ACK MOR E
STAR
POINT
CHOKE
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
SW3
SW6
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
SW2
SW5
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
SW1
SW7
A B C D E F G H A B C D E F G H
1+ 2+ 3+ 4+ 5+ 6+ 7+ 8+ +12V GND 1+ 2+ 3+ 4+ 5+ 6+ 7+ 8+
1- 2- 3- 4- 5- 6- 7- 8- +12V GND GND GND GND GND GND GND GND GND
ANALOGUE OUTPUTS ANALOGUE OUTPUTS
FUSE
N.C.
COM
N.O.
N.C.
COM
N.O.
LINE
CHASSIS
X Y
00
RX
TX
CALIBRATION KEY
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
3. I n s t a l l a t i o n a n d Wi r i n g
Enclosure is rated to IP66 (dust and water resistant) and will perform in the severest of environments.
This enclosure is wall or door mounted and the host wall or door requires four fixing holes to accept M5
bolts, refer installation sketch.
There is no restriction to equipment placement with the exception that bottom cable access will be
required and it is recommended that 150 mm be left clear below the ISP for routing cables.
3.2 R o u t i n g C a b l e s i n t o t h e I n te g r a te d S u r f a c e Pa n e l ( I S P )
ISP incorporates a lower gland plate through which all cables are run. Prior to installing the cables,
remove the Terminal Access Plate on the front of the ISP to permit access to the cables when installed.
You will see the terminations under this Terminal Access Plate and a clear area for cable marshalling.
E n s u r e t h e I S P p o w e r i s i s o l a te d b e f o r e r e m o v i n g t h e g l a n d
p l a te o r te r m i n a l a c c e s s p l a te .
Th e c o n n e c t i o n t o t h e C h o k e C o n s o l e m a y b e l i v e e v e n w h e n t h e
I S P i s n o t p o w e r e d d u e t o v o l t a g e s c o m i n g b a c k f r o m t h e ES P
s y s te m .
Refer to the terminal block diagram on Page 10 (Typical Integrated Surface Panel).
4. B a s i c Wi r i n g C o n n e c t i o n s
The following basic connections must be made to allow the ISP to communicate with the downhole
MultiSensor and display accurate information. All connections are accessible via the terminal access
plate on the front of the ISP.
Access to the terminal blocks is via the terminal access plate on the front of the enclosure. When all of
the connections are made ensure the gland plate and Terminal Access Plate are securely fastened.
E n s u r e t h e I S P p o w e r i s i s o l a te d b e f o r e r e m o v i n g t h e g l a n d
p l a te o r te r m i n a l a c c e s s p l a te .
Th e c o n n e c t i o n t o t h e C h o k e C o n s o l e m a y b e l i v e e v e n w h e n t h e
I S P i s n o t p o w e r e d d u e t o v o l t a g e s c o m i n g b a c k f r o m t h e ES P
s y s te m .
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
4.1 Po w e r S u p p l y Vo l t a g e / Fr e q u e n c y
This is universal and requires no user set up. Voltages 85 - 264Vac (110 - 370 Vdc) are permitted with
frequencies 50 and 60 Hz ( + / - 10%). Supply should be fused at 3.15A.
T H I S U N I T M U ST B E E A R T H E D ( G R O U N D E D )
4.2 C o n n e c t i o n t o D o w n h o l e To o l
Two connections require to be made to the Phoenix Choke Console. Wiring diagrams are attached for
both three phase and single phase choke console types.
4.3 C a l i b r a t i o n Ke y
Insert the key into the socket located on the main circuit board in the middle of the terminal block.
Compatibility is maintained with previous Calibration Keys used on the Phoenix MSP/TSP/MWP systems.
The calibration key should be read to the ISP memory. This is done by selecting the set-up menu on the ISP. Select set-
up Panel, Then select calibration module in this window, press new. This will read the fitted calibration module to the
memory in the panel.
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
5. O p t i o n a l Wi r i n g C o n n e c t i o n s
The following sections describe the optional outputs and inputs that may be used with the ISP. Refer to
the relative annotated drawing of the circuit board.
Access to the terminal blocks is via the terminal access plate on the front of the enclosure. When all of
the connections are made ensure the gland plate and Terminal Access Plate are securely fastened.
E n s u r e t h e I S P p o w e r i s i s o l a te d b e f o r e r e m o v i n g t h e g l a n d p l a te o r
te r m i n a l a c c e s s p l a te .
Th e c o n n e c t i o n t o t h e C h o k e C o n s o l e m a y b e l i v e e v e n w h e n t h e I S P
i s n o t p o w e r e d d u e t o v o l t a g e s c o m i n g b a c k f r o m t h e ES P s y s te m .
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
5.1 A l a r m a n d Tr i p R e l a y O u t p u t s
Each relay has Normally Open and Normally Closed contacts and the contact format is selected by
terminating to the appropriate terminal block position.
Example
the diagram below shows a Normally Open (NO) ALARM which lights
a 12 V d c l a m p a n d t h e T R I P c o n n e c te d a s N o r m a l l y C l o s e d ( N C ) t o
d e a c t i v a te a R u n r e l a y ( 24 0 Va c ) t o s h u t d o w n a s w i t c h b o a r d i n t h e
e v e n t o f a Tr i p c o n d i t i o n .
FUSE
RESET
MODBUS 232 TRIP ALARM TOOL MAINS
RTS
N.C.
COM
N.O.
N.C.
COM
N.O.
LINE
CHASSIS
L N
0V
RX
TX
110V/240V 0V +12V 0V
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
5.2 M o d b u s R S 232 / R S 4 8 5 S e l e c t i o n
TB1 has terminations for RS232 (3 wire) and RS485. Only one may be used at any one time and cables
must not be connected to both or communications problems will occur.
5 . 3 . 1 Pa r a m e te r t o Po r t A l l o c a t i o n
CO N N EC T I O N M E AS U R E M E N T
analogue output 1 T B 2 - 21 ( + ) / 22 ( G N D ) intake pressure
analogue output 2 T B 2 - 23 ( + ) / 24 ( G N D ) discharge pressure
analogue output 3 T B 2 - 25 ( + ) / 26 ( G N D ) intake temperature
analogue output 4 T B 2 - 27 ( + ) / 28 ( G N D ) motor temperature
analogue output 5 T B 2 - 29 ( + ) / 30 ( G N D ) flowrate
analogue output 6 T B 2 - 31 ( + ) / 32 ( G N D ) vibration
analogue output 7 T B 2 - 33 ( + ) / 34 ( G N D ) spare
analogue output 8 T B 2 - 35 ( + ) / 36 ( G N D ) current leakage
The allocation of analogue outputs and the represented signal ranges can be changed through the Liquid
Crystal Display (LCD) panel and keypad or via the Portable Data Collector (PDC).
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
5 . 3 . 2 O u t p u t Ty p e S e l e c t i o n
Analogue outputs are on the upper circuit board and selected as either 4-20 mA, 0-1V, 0-10V using the
switches provided (SW5 - SW7). Option and switch positions are ;
ANALOGUE 1
ANALOGUE 2
ANALOGUE 3
ANALOGUE 4
ANALOGUE 5
ANALOGUE 6
ANALOGUE 7
ANALOGUE 8
1 2 3 4 5 6 7 8 ON
SWITCH POSITIONS
SW6
OFF OFF OFF OFF OFF OUTPUT RANGE SW5 SW6 SW7
1 2 3 4 5 6 7 8 ON
0V - 1V OFF OFF OFF
SW5
A B C D E F G H OFF
1+ 2+ 3+ 4+ 5+ 6+ 7+ 8+
GND GND GND GND GND GND GND GND
ANALOGUE OUTPUTS
Ensure that connections are made to the correct polarity; loop +ve is always upper, GND lower in this
double height terminal block.
Example :
t h e d i a g r a m b e l o w s h o w s i n t a k e p r e s s u r e ( a n a l o g u e 1 ) c o n n e c te d a s
a 4 - 20 m A l o o p , t h e m o t o r te m p e r a t u r e ( a n a l o g u e 4 ) a s 0 - 1 Vd c a n d
t h e v i b r a t i o n a s 0 - 10 Vd c ( o n a n a l o g u e 6 ) .
1 2 3 4 5 6 7 8 ON
SW6
1 2 3 4 5 6 7 8 ON
SW5
1 2 3 4 5 6 7 8 ON
SW7
A B C D E F G H OFF
1+ 2+ 3+ 4+ 5+ 6+ 7+ 8+
GND GND GND GND GND GND GND GND
ANALOGUE OUTPUTS
}
}
}
4mA - 20mA RANGE
Pi OUTPUT
0V - 1V RANGE
Tm OUTPUT
0V - 10V RANGE
VIBRATION OUTPUT
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
5.3.3Output Scaling
Scaling on the analogue output can be changed, but defaults to the case where the zero point (0 Vdc or 4
mA depending on whether hardware is set-up for current or voltage) is always 0 measurement on the
parameter (intake pressure 0 psi, temperature 0°C etc.). Full scale can also be changed, and defaults to
the values shown in the table below.
-refer to installation for setting output style
20 mA or
10 Vdc or
1 Vdc
(current or voltage)
analogue output
4 mA or
0 Vdc or
0 Vdc
Example
i f a n a l o g u e 1 i s s e t f o r 4 - 20 m A a n d i s g i v i n g o u t 12 m A t h i s i s h a l f
way through the range. Analogue 1 is pre-defined as intake pressure
a n d t h e r e f o r e 12 m A e q u a te s t o h a l f o f t h e 120 0 0 p s i r a n g e r e s u l t i n g
i n t h e 12 m A r e p r e s e n t i n g 6 0 0 0 p s i o r 412 . 6 5 b a r.
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
Selected as either 4-20 mA, 0-1V, 0-10V, using the switches provided on the upper circuit (SW1 - SW4).
Options and switch positions are ;
ANALOGUE 1
ANALOGUE 2
ANALOGUE 3
ANALOGUE 4
ANALOGUE 5
ANALOGUE 6
ANALOGUE 7
ANALOGUE 8
1 2 3 4 5 6 7 8 ON
SWITCH POSITIONS
SW4
OFF OFF OFF OFF OFF OUTPUT RANGE SW1 SW2 SW3 SW4
1 2 3 4 5 6 7 8 ON 0V - 1V OFF - OFF OFF
SW3
A B C D E F G H OFF
1+ 2+ 3+ 4+ 5+ 6+ 7+ 8+ +12V GND
1- 2- 3- 4- 5- 6- 7- 8- +12V GND
ANALOGUE INPUTS
Where the input is a switch or relay contact 12V is provided which should be fed as input to the switch
and the return taken to an analogue input +ve terminal. Negative (-ve) terminal does not require
connection.
Example
h o o k u p w h i c h h a s a 4 - 20 m A a n a l o g u e i n p u t o n a n a l o g u e i n p u t 1
a n d a r e l a y / s w i t c h t y p e i n p u t o n a n a l o g u e 2 i s s h o w n b e l o w.
1 2 3 4 5 6 7 8 ON
SW4
1 2 3 4 5 6 7 8 ON
SW3
A B C D E F G H OFF
1 2 3 4 5 6 7 8 ON
SW2
1 2 3 4 5 6 7 8 ON
SW1
A B C D E F G H OFF
1+ 2+ 3+ 4+ 5+ 6+ 7+ 8+ +12V GND
1- 2- 3- 4- 5- 6- 7- 8- +12V GND
ANALOGUE INPUTS AUX SUPPLY
}-VE INPUT RANGE 4mA - 20mA
REMOTE RELAY/SWITCH
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
A PC may be connected to the ISP engineers port to log to file all the measurements made. Software that
may be used is ;
For report generation and printing the PDC must be downloaded to the PumpView™ software.
ISP PC Signal
Connector Connector
Pin 2 Pin 2 Tx
Pin 3 Pin 3 Rx
Pin 5 Pin 5 Gnd
ISP
Connect to Special
ISP Comms
Terminal
DATA Pd 2 2 0 0 PS I
Off Del
.
F l ow 1 0 0 0 0 b f p d
OFFICE
7 8 9 *
LOGGING DO WN U P ACK MOR E 4
1
5
2
6
3
_
+
0 . / Enter
A B C D E F
G H I J K L
M N O P Q R
S T U V W X
Shift Y Z
Ctrl Space
F ICE
OF
PHOENIX PETROLEUM SERVICES LIMITED
INVERURIE
ABERDEENSHIRE
ASSEMBLY No. A446229 AB51 0ZJ
O
U.S. PATENT 5,539,375 SCOTLAND
ET
U.K. PATENT PENDING UNITED KINGDOM
NORWAY PATENTS PENDING TEL. (44) 1467 620102
OTHER PATENTS PENDING FAX. (44) 1467 620824
K
TA
PHOENIX
DOWN
THRUS
4000 T 200
VIBRATION IN G * 10,
TEMPERATURE IN F,
ESP IN UPTHRUST TOO LONG
HIGH MOTOR TEMPERATURE
ESP SHUTDOWN
55 Hz
3000 150
UPT
HRU
2000 100
Connect to Special
ST
Terminal
0 0
PHOENIX PETROLEUM SERVICES 19/12/95 19/12/95 19/12/95 19/12/95 19/12/95 19/12/95 19/12/95 19/12/95 19/12/95
PORTABLE DATA COLLECTOR 10:30:00 11:00:00 11:30:00 12:00:00 12:30:00 13:00:00 13:30:00 14:00:00 14:30:00
DATE AND TIME OF PHOENIX ESP PROTECTION LOG
Off Del
.
7 8 9 *
4 5 6 _
1 2 3 +
0 . / Enter
A B C D E F
G H I J K L
M N O P Q R
S T U V W X
Shift Y Z
Ctrl Space
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
7. Menu Structure
Dependent upon which ISP menu you are in the four softkeys (directly underneath the display) have
different functions. The function is displayed above the softkey (on the last line of the display below the
black line on the LCD).
SO F T K EY D ETA I L
FUNCTION
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
P OW E R O N A N D S E L F T EST S EQ U E N C E
///
PHOENIX
PETROLEUM SERVICES
ESP PROTECTION
TOOL DIAGNOSTICS
MULTISENSOR
COMMUNICATIONS
INSULATION
Pi OK Tm OK Pi OK Tm OK Pi OK Tm OK
Pd OK flow OK Pd OK flow OK Pd OK flow OK
Ti OK Vib OK Ti OK Vib OK Ti OK Vib OK
COMMUNICATIONS LOST ANALOGUE INPUT FAIL SURFACE PANEL FAULT
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
C H A N G I N G A L A R M A N D T R I P L E V E LS - PA R T 1
Pi 899 PSI
Pd 2992 PSI
Flow 0 bfpd
DOWN UP MENU
Pi 899 PSI
Pd 2992 PSI
Flow 0 BPFD
SETUP LOG RAPID MORE
PA S S W O R D :
PA S S W O R D : I S P
CANCEL OK
S I T E : D E F A U LT S I T E
W E L L : D E F A U LT W E L L
I N TA K E P R E S S U R E
DOWN UP CHANGE DONE
3 TIMES
W E L L : D E F A U LT W E L L
I N TA K E P R E S S U R E
DISCHARGE PRESSURE
DOWN UP SELECT DONE
Pd
DISCHARGE PRESSURE
HIGH TRIP OFF
DOWN UP CHANGE DONE
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
C H A N G I N G A L A R M A N D T R I P L E V E LS - PA R T 2
Pd
DISCHARGE PRESSURE
HIGH TRIP OFF
DOWN UP CHANGE DONE
3 TIMES
DISCHARGE PRESSURE
HIGH TRIP OFF
HIGH ALARM OFF
DOWN UP CHANGE DONE
DISCHARGE PRESSURE
HIGH TRIP OFF
HIGH ALARM OFF
UP DOWN LEFT DONE
DISCHARGE PRESSURE
HIGH TRIP OFF
HIGH ALARM 0
UP DOWN LEFT DONE
3 TIMES
DISCHARGE PRESSURE
HIGH TRIP OFF
HIGH ALARM 0
UP DOWN LEFT DONE
DISCHARGE PRESSURE
HIGH TRIP OFF
HIGH ALARM 1000
UP DOWN LEFT DONE
DISCHARGE PRESSURE
HIGH TRIP OFF
HIGH ALARM 1000
CANCEL OK
DISCHARGE PRESSURE
HIGH TRIP OFF
HIGH ALARM 1000
DOWN UP CHANGE DONE
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
V I E W I N G DATA
Pi OK Tm OK
Pd OK flow OK
Ti OK Vib OK
DOWN MENU
Pi 899 PSI
Pd 2911 PSI
Flow 0 bfpd
DOWN UP MENU
Ti 24.3 C
Tm 122.2 C
Vib 0.346 g
UP MENU
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
R E V I E W I N G E V E N TS
Pi OK Tm OK
Pd OK flow OK
Ti OK Vib OK
DOWN MENU
Pi 899 PSI
Pd 2992 PSI
Flow 0 bfpd
SETUP LOG RAPID MORE
1 0 : 1 1 R E L AY S R E S E T
10:06 Tm HI ALARM
09:47 Ti HI ALARM
DOWN UP 23-FEB
1 0 : 1 1 R E L AY S R E S E T
10:06 Tm HI ALARM
09:47 Ti HI ALARM
DOWN UP ? 23-FEB
1 0 : 1 1 R E L AY S R E S E T M OTO R T E M P E R AT U R E
10:06 Tm HI ALARM 23-FEB-1998 10:06:12
09:47 Ti HI ALARM HI ALARM 122.2 C
DOWN UP ? 23-FEB DOWN UP 23-FEB
10:06 Tm HI ALARM
09:47 Ti HI ALARM
22:12 Flow LO ALARM
DOWN UP ? 22-FEB
EXIT LOG
GOTO OLDEST RECORD
GOTO NEWEST RECORD
DOWN UP SELECT DONE
Pi 899 PSI
Pd 2992 PSI
Flow 0 bfpd
DOWN UP MENU
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
R ES ET T I N G A L A R M A N D T R I P R E L AYS
Pi 899 PSI
Pd 2992 PSI
Flow 0 bfpd
DOWN UP ACK
RESET TRIP
AND ALARM RELAYS
CANCEL OK
Pi 899 PSI
Pd 2992 PSI
Flow 0 bfpd
DOWN UP MENU
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
R ESTA R T PA N E L A N D I N H I B I T T R I P S
Pi 899 PSI
Pd 2992 PSI
Flow 0 bfpd
DOWN UP MENU
Pi 899 PSI
Pd 2992 PSI
Flow 0 bfpd
SETUP LOG RAPID MORE
Pi 899 PSI
Pd 2992 PSI
Flow 0 bfpd
R E S TA R T INHIBIT DONE
R E S TA R T S U R FAC E I N H I B I T T R I P R E L AY ? E N A B L E T R I P R E L AY ?
PA N E L ?
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
R A P I D SA M P L E R AT E
Pi 899 PSI
Pd 2992 PSI
Flow 0 bfpd
DOWN UP MENU
Pi 899 PSI
Pd 2992 PSI
Flow 0 bfpd
SETUP LOG RAPID MORE
Pi 899 PSI
Pd 2992 PSI
Flow 0 bfpd
DOWN UP MENU
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
8. Po w e r U p
Before powering the panel ensure the output to the choke console
( 120 Vd c ) i s i s o l a te d o r c o n n e c te d t o t h e d o w n h o l e S e n s o r v i a t h e
t r a n s f o r m e r a n d ES P c a b l e .
E n s u r e t h e te r m i n a l a c c e s s p l a te i s r e p l a c e d b e f o r e p o w e r i n g t o
avoid electric shock.
8.1 Po w e r U p D i a g n o s t i c s
Apply power to the ISP and the Phoenix banner will display and hold for approximately 5 seconds during
initialisation.
///
PHOENIX
PETROLEUM SERVICES
ESP PROTECTION
After this banner the system reports on ISP self tests (of memory and the port for communications to the
downhole tool). Note: this takes around 1 minute. If a fault is detected a fault code will display with a
short message. Refer Fault Finding.
When the ISP is confirmed healthy then communications to the downhole tool are tested. Note: this
takes around 40 seconds. Tested are communications between the downhole tool and the Integrated
Surface Panel (has link been set up and is it a good quality link) and the ESP insulation :
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
TOOL DIAGNOSTICS
MULTISENSOR
COMMUNICATIONS
INSULATION
TOOL DIAGNOSTICS
MULTISENSOR FOUND
COMMUNICATIONS GOOD
INSULATION GOOD
COMMUNICATIONS LOST
TOOL NOT FOUND-OPEN
CIRCUIT, CHECK FUSES
CODE 307 OK
Note the “FC307” fault code number. Always send the fault code number to Phoenix if you require help.
The ISP does not halt if a fault is found. Note that if a severe tool communications problem is recorded
during operation (i.e. not only at start up but tested every 20 seconds) then an alarm is set and logged,
data before and after the problem will be logged and any alarms or trips based on downhole data locked
out. The ISP continues to attempt communications with downhole and will restore alarm and trip features
should downhole parameters be restored. A log event will be made of this restoration of features.
N o te s t s a r e m a d e o f M o d b u s c o m m s , A l a r m a n d Tr i p r e l a y s a n d
Analogue Inputs and Outputs at power up. Refer the manual section
o n f a u l t f i n d i n g o n h o w t o te s t t h e s e .
After these diagnostics both the ISP and downhole tool are confirmed to be operating.
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
ISP will now display the status of the six downhole parameters.
Pi OK Tm OK
Pd OK flow OK
Ti OK Vib OK
DOWN MENU
Note that the ‘ACK’ (ACKnowledge) menu option is only available when alarms or trips are present and
the relays need to be reset.
Pi 899 PSI
Pd 2911 PSI
Flow 0 bfpd
DOWN UP MENU
Note that the number of screens available and their contents can be tailored to the application and may
not display exactly as here.
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
9. A l a r m a n d Tr i p P r o te c t i o n
which will cause either the TRIP relay to activate (HH, LL levels) or the ALARM relay to activate
(H, L level).
To p r e v e n t s p u r i o u s Tr i p a n d A l a r m s i g n a l s , t h e a l a r m o r t r i p
threshold must be breached for the period of the Holddown.
Holddown is the number of readings taken between the alarm
o r t r i p l e v e l b e i n g b r e a c h e d a n d t h e a l a r m b e i n g a c t i v a te d
(factory default is 3).
Th e r e l a y i s n o t d e a c t i v a te d u n t i l t h e r e a d i n g h a s b e e n b e l o w t h e
threshold for the period of the holddown.
S h o u l d t h e I S P d e te c t a f a u l t i n t h e c o m m u n i c a t i o n s t o t h e S e n s o r
t h e n a n A L A R M i s a c t i v a te d a n d t h e T R I P r e l a y i s h e l d i n t h e
d e a c t i v a te d s t a te t o p r e v e n t a T R I P d u e t o b a d S e n s o r d a t a .
9.3 R e v i e w i n g A c t i v e A l a r m s a n d Tr i p s
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
9.4 S e t t i n g t h e Th r e s h o l d s
Alarms are set by Low and High thresholds whilst Trip is set by Low Low and High High thresholds. TRIP
thresholds are outside the ALARM thresholds (i.e. TRIP LOW LOW is below ALARM LOW, TRIP HIGH
HIGH is above ALARM HIGH)
TIME
Thresholds are set in the SETUP menu for each parameter. See page 22 for SETUP sequence.
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
SO F T K EY FUNCTION
To s w i t c h O F F a n a l a r m o r t r i p s e t t h e a l a r m o r t r i p t h r e s h o l d t o
OFF (decrease to minimum until OFF is displayed)
It is not possible to set a low trip above a low alarm value and
correspondingly not possible to set the high trip below the high
alarm for a measurement
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
Within the system is a non-volatile data logger which contains records of all events and measurements
(intake pressure, discharge pressure, etc.) leading up to and away from the event. Events are the
activation or reset of an alarm or trip signal (including a Sensor or ISP failure), power up of the ISP, and
deviation of a measurement by more than a value from the last record in the data log.
EVENT TYPE 1
a measured value goes above or below (i.e. transitions through) the ALARM
or TRIP level
EVENT TYPE 2
with respect to the last record made to the log file, a measured value has
c h a n g e d m o r e t h a n t h e s t a te d p e r m i t te d d e v i a t i o n v a l u e
EVENT TYPE 3
Th e f u l l p e r i o d i c l o g g i n g t i m e h a s e l a p s e d w i t h o u t a r e c o r d b e i n g t a k e n ( t h i s
time period is setup so that the logger will still store readings at regular
i n te r v a l s , e v e n w h e n e v e n t t y p e s 1 a n d 2 a r e n o t a c t i v a te d )
if no event
log every few hours
ALARM relay ACTIVE
TIME
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
Pi 899 PSI
Pd 2992 PSI
Flow 0 bfpd
SETUP LOG RAPID MORE
1 0 : 1 1 R E L AY S R E S E T
10:06 Tm HI ALARM
09:47 Ti HI ALARM
DOWN UP 23-FEB
1 0 : 1 1 R E L AY S R E S E T
10:06 Tm HI ALARM
09:47 Ti HI ALARM
DOWN UP ? 23-FEB
1 0 : 1 1 R E L AY S R E S E T
10:06 Tm HI ALARM
09:47 Ti HI ALARM
DOWN UP ? 23-FEB
10:06 Tm HI ALARM
09:47 Ti HI ALARM
22:12 Flow LO ALARM
DOWN UP ? 22-FEB
EXIT LOG
GOTO OLDEST RECORD
GOTO NEWEST RECORD
DOWN UP SELECT DONE
Pi 899 PSI
Pd 2992 PSI
Flow 0 bfpd
DOWN UP MENU
and the table of events can be viewed through the LOG menu option. The LOG accesses the listing of
event names in chronological order (most recent at top) and displays the following information on screen;
• time and date of log
• a fault code
• LL, L, H, HH identifier for alarms and trips
• dev identifier for deviation events
• fault measurement short code (e.g. Pi, Pd, Ti, etc.)
• identifier for 6 hour logs and system boot ups (Bu)
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
To u p l o a d t h e l o g f i l e t h e Po r t a b l e D a t a C o l l e c t o r ( P D C ) o r a P C r u n n i n g
P u m p Vi e w ™ ( b o t h f r o m P h o e n i x ) i s c o n n e c te d t o t h e P D C / E n g i n e e r s p o r t o n
t h e g l a n d p l a te . L o g f i l e s m a y t h e n b e d o w n l o a d e d f o l l o w i n g t h o s e p r o d u c t
P u m p Vi e w instructions (as shown below).
Pi 1 2 0 0 PS I
Pd 2 2 0 0 PS I
F l ow 1 0 0 0 0 b f p d
DO WN U P ACK MOR E
Connect to Special
ISP Comms
PumpView Exit
Terminal
Off Del
.
7 8 9 *
4 5 6 _
1 2 3 +
0 . / Enter
A B C D E F
G H I J K L
M N O P Q R
S T U V W X
Shift Y Z
Ctrl Space
ISP to Pumpview
Fo r r e a l t i m e g ra p h i c a l d i s p l ay o f M u l t i s e n s o r d a t a , t h e p a n e l c a n b e c o n n e c t e d
directly to Pumpview on a PC.
Connect the PC to the engineer port
O n t h e P C s e l e c t P u m p v i e w by s e l e c t i n g S t a r t ¶ P r o g ra m s ¶ P u m p v i e w ¶ P u m p v i e w.
Pumpview will then start
I n P u m p v i e w s e l e c t S e t - u p ¶ Po r t s e t - u p , s e l e c t t h e c o m m p o r t yo u h ave c o n n e c t e d t o
o n t h e P C , t h e n s e l e c t “ s ave s e t t i n g s ” t h e n s e l e c t “ D o n e ”
A t t h e m a i n s c r e e n s e l e c t “ Fi l e ” a n d e i t h e r s e l e c t o p e n w e l l d a t a b a s e o r c r e a t e n e w
w e l l d a t a b a s e a n d s e l e c t t h e d a t a b a s e t h a t yo u wa n t t o s ave t h e d a t a t o .
A t t h e m a i n s c r e e n , o n P u m p v i e w, c l i ck o n t h e I S P i c o n .
Th e d a t a f r o m t h e I S P i s t h e n d i s p l aye d o n P u m p v i e w
PDC
Integrated Surface Panel : User Manual Page 37
1 ISP.qxd 5/17/99 3:00 PM Page 38
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
11 . A d d i t i o n a l Fe a t u r e s
11 . 1 R a p i d S a m p l e R a te
Phoenix Multisensor systems can be instructed to send only Intake Pressure and to update this at 1
second intervals using the Rapid Sample Rate ON/OFF option in the menu. (this will disable readings
from the other tool parameters, alarms and trips will also be disabled
Pd 2992 PSI
Flow 0 bfpd
DOWN UP MENU
Pi 899 PSI
Pd 2992 PSI
Flow 0 bfpd
SETUP LOG RAPID MORE
Wh e n e n te r i n g o r e x i t i n g f r o m R S R t h e s y s te m m a y t a k e u p t o 1
m i n u te .
R a p i d S a m p l e R a te c a n a l s o b e s t a r te d b y a n a n a l o g u e i n p u t o r b y
using the PDC.
11 . 2 R e s t a r t i n g t h e I S P
RESTART TYPE
Hot Restart s e l e c t R E STA RT PA N E L i n t h e m e n u
Wa r m R e s t a r t p r e s s R E S ET p u s h b u t t o n i n s i d e p a n e l ( S 1 )
Cold Restart d i s c o n n e c t p o w e r a n d r e a p p l y.
FUSE
RESET
MODBUS 232 TRIP ALARM TOOL MAINS
RTS
N.C.
COM
N.O.
N.C.
COM
N.O.
LINE
CHASSIS
L N
0V
RX
TX
C A L I B R AT I O N K EY
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
12 . ISP Set Up
12 . 1 Pa s s w o r d a n d S e t U p M e n u
The Set Up menu option allows access to all of the configuration options for the Integrated Surface Panel,
including alarm and trip level, parameter names, display set up and much more. Anybody can view the
current settings , however, if you want to change anything, you will have to provide the correct password
when you first select ‘Setup’ from a running screen menu. See page 22.
If you have supplied the correct password, the system remembers the password and will not ask you for a
password again until five minutes has elapsed (from the moment that you leave the set up menus). In
effect you can jump in and out of the set up menus without having to supply passwords time after time.
The password can be changed by using the ‘Change Password’ option under ‘Setup Panel’.
12 . 2 S e t U p M e n u
The set up menu allows you to change the main parameter settings, such as alarm and trip levels, and
provides access to other menus to set up ISP options.
SITE: Default Site Use this option to change the site name.
W E L L : D e f a u l t We l l Use this option to change the well name (used by Phoenix data management software
Intake Pressure Access to alarm and trip levels, change of name etc. for each of the downhole
Discharge Pressure m e a s u r e m e n t s . Th e a c t u a l n a m e s d i s p l a y e d h e r e c a n b e c h a n g e d — I n t a k e P r e s s u r e i s
I n t a k e Te m p e r a t u r e t h e d e f a u l t f o r t h e f i r s t m e a s u r e m e n t . S e e t h e ‘ Pa r a m e t e r M e n u ’ s e c t i o n f o r f u r t h e r
M o t o r Te m p e r a t u r e details.
Flowrate
Vi b r a t i o n
Analogue Inputs Use this option to define the analogue inputs used, set the input ranges and
e n g i n e e r i n g u n i t s , a n d t h e a l a r m a n d t r i p l e v e l s . S e e t h e ‘A n a l o g u e I n p u t s ’ s e c t i o n f o r
further details.
Analogue Outputs Use this option to define the analogue output required and their ranges. See the
‘A n a l o g u e O u t p u t s ’ s e c t i o n f o r m o r e d e t a i l s .
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
12 . 3 Pa r a m e te r M e n u
The parameter menu is in the same format for each of the downhole measurements (Intake Pressure
through to Vibration), and allows you to change the alarm and trip levels for each parameter.
Pi Allows you to change the short name used to identify the parameter on some screens.
Intake Pressure A l l o w s y o u t o c h a n g e t h e d e s c r i p t i o n o f t h e p a r a m e t e r, u s e d o n s o m e s c r e e n s w h e r e
H i g h Tr i p OFF S e t s a ‘ H i g h Tr i p ’ t h r e s h o l d . Th e t r i p l i g h t a n d r e l a y w i l l b e a c t i v a t e d w h e n t h e
m e a s u r e d v a l u e i s c o n s i s t e n t l y a b o v e t h i s t h r e s h o l d . Yo u c a n n o t s e t t h e h i g h t r i p
t h r e s h o l d l o w e r t h a n t h e h i g h a l a r m t h r e s h o l d . Th e t h r e s h o l d i s s e t i n t h e
a p p r o p r i a t e s y s t e m u n i t s f o r e a c h p a r a m e t e r, i . e . b a r o r P S I , C o r F e t c . Wh e n t h e
t h r e s h o l d i s O F F, n o h i g h t r i p s w i l l b e g e n e r a t e d .
L o w Tr i p 800 S i m i l a r t o t h e ‘ L o w A l a r m ’ t h r e s h o l d . Th e t r i p l i g h t a n d r e l a y w i l l b e a c t i v a t e d w h e n
Deviation 5 Th i s i s u s e d t o c o n t r o l t h e a m o u n t o f d a t a g a t h e r e d b y t h e I S P ’ s d a t a l o g g e r. I f t h e
measured value is different from the last logged value by at least this amount, a new
s e t o f r e c o r d s i s s t o r e d i n t h e l o g . Th e v a l u e i s s e t i n t h e a p p r o p r i a t e u n i t s f o r t h e
p a r a m e t e r, i . e . b a r o r P S I , C o r F e t c . N o a l a r m s o r t r i p s a r e g e n e r a t e d .
Holddown 3 Th i s v a l u e s e t s t h e n u m b e r o f c o n s e c u t i v e r e a d i n g s r e q u i r e d t o t r i g g e r a n a l a r m o r
t r i p . Th i s v a l u e i s ‘ c o n s i s t e n t l y ’ m e n t i o n e d i n t h e a l a r m a n d t r i p t h r e s h o l d s .
Deadband 10 Wh e n a v a l u e i s i n a n a l a r m o r t r i p c o n d i t i o n a n d m o v e s i n t o a l e s s s e v e r e s t a t e t h i s
d e a d b a n d i s a p p l i e d t o t h e a l a r m o r t r i p t h r e s h o l d . Th e e f f e c t i s t o p r e v e n t r e p e a t e d
t h r e s h o l d . Fo r e x a m p l e , i f I n t a k e P r e s s u r e g o e s b e l o w 9 0 0 P S I a n d t r i g g e r s a L o w
A l a r m , t h e i n t a k e p r e s s u r e m u s t r i s e t o 910 P S I b e f o r e t h e a l a r m i s d e a c t i v a t e d .
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
12 . 4 A n a l o g u e I n p u t s
The eight analogue inputs available on the ISP are set up through this menu option. The first menu
selects which analogue input to configure, which then takes you on to the analogue input configuration
menu. Most of the menu options are identical to those for the downhole measurements, however there
are extra options to set up the range and engineering units for the input.
A1 Allows you to change the short name used to identify the parameter on some screens.
Analogue Input 1 A l l o w s y o u t o c h a n g e t h e d e s c r i p t i o n o f t h e p a r a m e t e r, u s e d o n s o m e s c r e e n s w h e r e
Units Hz S e t s a l a b e l f o r t h e e n g i n e e r i n g u n i t s f o r t h i s i n p u t . Th i s l a b e l h a s n o m e a n i n g t o t h e
Decimal Places 1 Sets the number of decimal places when values for this parameter are shown.
Fu l l S c a l e 10 0 Th e e n g i n e e r i n g u n i t s v a l u e c o r r e s p o n d i n g t o a f u l l s c a l e i n p u t , i . e . t h e r e a l - w o r l d
v a l u e c o r r e s p o n d i n g t o 20 m A , 1 V o r 10 V d e p e n d i n g o n t h e r a n g e .
Zero Scale 0 Th e e n g i n e e r i n g u n i t s v a l u e c o r r e s p o n d i n g t o a z e r o s c a l e i n p u t , i . e . c o r r e s p o n d i n g t o
4 m A , o r 0 V.
H i g h Tr i p OFF S e t s a ‘ H i g h Tr i p ’ t h r e s h o l d . Th e t r i p l i g h t a n d r e l a y w i l l b e a c t i v a t e d w h e n t h e
m e a s u r e d v a l u e i s c o n s i s t e n t l y a b o v e t h i s t h r e s h o l d . Yo u c a n n o t s e t t h e h i g h t r i p
t h r e s h o l d l o w e r t h a n t h e h i g h a l a r m t h r e s h o l d . Th e t h r e s h o l d i s s e t i n t h e
e n g i n e e r i n g u n i t s s p e c i f i e d . . Wh e n t h e t h r e s h o l d i s O F F, n o h i g h t r i p s w i l l b e
generated.
L o w Tr i p 800 S i m i l a r t o t h e ‘ L o w A l a r m ’ t h r e s h o l d . Th e t r i p l i g h t a n d r e l a y w i l l b e a c t i v a t e d w h e n
Deviation 5 Th i s i s u s e d t o c o n t r o l t h e a m o u n t o f d a t a g a t h e r e d b y t h e I S P ’ s d a t a l o g g e r. I f t h e
measured value is different from the last logged value by at least this amount, a new
s e t o f r e c o r d s i s s t o r e d i n t h e l o g . Th e v a l u e i s s e t i n t h e e n g i n e e r i n g u n i t s s p e c i f i e d .
Holddown 3 Th i s v a l u e s e t s t h e n u m b e r o f c o n s e c u t i v e r e a d i n g s r e q u i r e d t o t r i g g e r a n a l a r m o r
t r i p . Th i s v a l u e i s t h e ‘ c o n s i s t e n t l y ’ m e n t i o n e d i n t h e a l a r m a n d t r i p t h r e s h o l d s .
Deadband 10 Wh e n a v a l u e i s i n a n a l a r m o r t r i p c o n d i t i o n a n d m o v e s i n t o a l e s s s e v e r e s t a t e t h i s
d e a d b a n d i s a p p l i e d t o t h e a l a r m o r t r i p t h r e s h o l d . Th e e f f e c t i s t o p r e v e n t r e p e a t e d
threshold.
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
12 . 5 A n a l o g u e O u t p u t s
This menu sets up the eight analogue outputs available from the ISP. You can decide which analogue
output follows which measured parameter and set up the zero and full scale ranges. The first menu
selects which of the eight analogue outputs you want to configure, and then takes you to the detailed
menu shown below.
Pa r a m e t e r : Pi Allows you to change the measured parameter used to drive this output.
Fu l l S c a l e 10 0 Th e e n g i n e e r i n g u n i t s v a l u e c o r r e s p o n d i n g t o a f u l l s c a l e o u t p u t , i . e . t h e r e a l - w o r l d
v a l u e c o r r e s p o n d i n g t o 20 m A , 1 V o r 10 V d e p e n d i n g o n t h e r a n g e .
Zero Scale 0 Th e e n g i n e e r i n g u n i t s v a l u e c o r r e s p o n d i n g t o a z e r o s c a l e o u t p u t , i . e . c o r r e s p o n d i n g
t o 4 m A , o r 0 V.
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
12 . 6 S e t u p Pa n e l
This menu system allows you to setup options for the ISP as a whole.
S e t u p Ti m e a n d D a t e S e t ’ s t h e c u r r e n t t i m e a n d d a t e i n t h e I S P.
a n d t h e Tr i p O n Ti m e h a s e l a p s e d . Th e ‘ L a t c h ’ m o d e
o r t h r o u g h M O D B U S . Th e ‘ I N H I B I T ’ m o d e w i l l p r e v e n t
r e l a y w i l l b e a c t i v a t e d i n ‘A u t o ’ m o d e . Th i s i s t o a l l o w a
a l a r m r e l a y.
A l a r m O n Ti m e 0 I d e n t i c a l t o t h e Tr i p O n Ti m e .
Fa u l t R e l a y Alarm Wh e n s e t t o ‘A l a r m ’ a n y s y s t e m f a u l t s o r c o m m u n i c a t i o n
f a i l u r e s w i l l a c t i v a t e t h e ‘A l a r m ’ r e l a y. S e t t h i s t o
‘ I n h i b i t ’ t o p r e v e n t t h i s b e h a v i o u r.
Setup Display No. Screens 3 Sets the number of ‘Running Screens’ available. By
measured parameters
Contrast U s e t h i s o p t i o n t o c h a n g e t h e LC D c o n t r a s t .
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
Local Comms O u t p u t Po l l A SC I I Sets the mode for output on the local (Engineer’s) serial
p o r t . Va l i d m o d e s a r e A SC I I ( h u m a n r e a d a b l e ) , B I N A R Y
Baud Rate 9600 Sets the baud rate for the engineer’s serial port.
o p t i o n s a r e 16 - b i t i n t e g e r v a l u e s , 24 - b i t ( o l d s t y l e
Baud Rate 9600 Sets the baud rate for the MODBUS port. (Other
Slave Address 1 Sets the MODBUS slave address for this unit. Each ISP
Comms G i v e s t h e o p t i o n t o c h a n g e b e t w e e n R S 232 a n d R S 4 8 5 .
C a l i b r a t i o n Ke y A l l o w s a n e w c a l i b r a t i o n k e y t o b e u s e d w i t h o u t r e b o o t i n g t h e I S P.
S e t u p Pa s s i v e C L S e t s u p t h e Pa s s i v e C u r r e n t L e a k a g e m e a s u r e m e n t . Th i s m u s t b e d o n e w h i l e t h e E S P
m o t o r i s o f f, a n d i s u s u a l l y p e r f o r m e d a t c o m m i s s i o n i n g .
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
13 . M o d b u s Po r t
This Modbus Remote Terminal Unit port may be either RS232 (3 wire) or RS485 (4 wire). Refer to the
installation section for this set up.
A menu is available under SETUP-PANEL (last menu in the SETUP DATA tree) to alter the port speed and
slave address.
13 . 1 O v e r v i e w
The Modbus interface enables the Phoenix surface equipment to connect to an industry standard Modbus
RTU Master.
13 . 2 E x te r n a l E q u i p m e n t C o n n e c t i o n
External connection can be made using the RS232 or the RS485 interface standard. Refer the manual
section on wiring and installation.
13 . 3 O p e r a t i o n a n d S t a t u s
13 . 3 . 1 S t a t u s I n d i c a t i o n
There are 5 LED’s mounted on-board, located above the Calibration key socket. LED are marked as
follows ;
TxLED and RxLED light up every time the communication channel is receiving or transmitting data.
A flashing Status LED indicates a running Modbus interface.
13 . 3 . 2 M O D B U S S e t - u p
The board contains non-volatile memory for storage of the set up. Set up is for ;
• Modbus address of the panel,
• Baud Rate of the Modbus Channel.
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
This configuration has a factory default of 9600 baud and address 1 although it may be changed through
the menu structure. Baud rates permitted are : 19200, 9600, 4800, 2400, 1200, baud. Address may be in
the standard Modbus range of 1 - 255 (excluding address 8).
13 . 3 . 3 C o n t r o l o f D o w n h o l e M u l t i S e n s o r S a m p l e R a te
The following procedure applies across Modbus to set the system into rapid sample mode for collection of
Intake Pressure at 1 second intervals.
To set a panel in fast or slow sampling mode, a command may be generated through the Modbus channel.
This is achieved by setting register 1008 to the appropriate value. Two values are valid, 6 and 13. They
have the following meaning.
Va l u e Meaning
06 S e t Fa s t M o d e
13 Set Slow Mode
When the command has been propagated through the system, address 1008 is cleared.
13 . 4 M O D B U S P r o t o c o l I m p l e m e n t a t i o n
13 . 4 . 1 M a s te r a n d S l a v e D e f i n i t i o n
Modbus communicates using a master-slave technique in which only one device, the master, can initiate
queries to the slave. The slave returns a message called a ‘response’, to the master.
Phoenix equipment acts as a Modbus RTU (Slave) device.
13 . 4 . 2 F U N C T I O N CO D ES U S E D
The board is compatible with a subset of the Modicon Modbus protocol and uses the RTU mode of
transmission. The table below shows the function codes supported by the board.
Code Name
03 Read Holding Registers
06 Pre-set Single Register
13 . 4 . 3 M e s s a g e Tr a n s a c t i o n
In the RTU (Slave) mode, the ‘Query’ and ‘Response’ take the following form ;
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
Query Phoenix
from Master Integrated Surface Panel
Query Format
-slave address
-function code
-data bytes
-error check (CRC)
Query Phoenix
from Master Integrated Surface Panel
Answer Format
-slave address
-function code
-data bytes (answer data)
-error check (CRC)
13 . 4 . 4 R e g i s te r A d d r e s s i n g
There are two ranges of Holding Register Addresses, one which contains the information received from
the panel and one which is used for the Board Set-up data. The ranges are:
Range R e g i s te r C o n te n t s
0 - 99 Sensor Measurement Data
1001-1008 Set Up Registers
Other registers are reserved and used by the Integrated Surface Panel and complete monitoring solutions
including remote data logger access, alarm and trip remote set up, and other features. Consult Phoenix
for System Solutions for ESP Monitoring and Protection.
The data format is 16 bit per Holding Register Address, high byte first.
A TxA
B TxB
Y RxA
Z RxB
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
13 . 4 . 5 We l l D a t a 4 8 b i t Fo r m a t
Each parameter of the well information conforms to a specific format in relation to the returned register contents. The
value it’s self is either 24-bit 16-bit or IEEE floating point with fixed scaling employed. Either format can be selected
via the menu structure. Format of the registers for the three options holding the data is ;
24-bit Format
H o l d i n g R e g i s te r A d d r e s s n ( e v e n ) H o l d i n g R e g i s te r A d d r e s s n + 1 ( o d d )
Byte 3 Byte 2 Byte 1 Byte 0
MSB LSB MSB LSB
Measured value not used
16-bit format
Holding Register Address n
Byte 1
Byte 2
MSB
LSB
Measured Value
IEE Floating Point Format
Holding Register Address n +1 (odd)
Holding Register Address n (even)
Byte 0
Byte 1
Byte 2
Byte 3
Bit 31
Bit 30 to Bit 23
Bit 22 to Bit 0
Sign
Exponent “e”
Mantissa “m”
The relation ship for calculating a value from the floating point format is as follows
Measured Value = Sign * 2(e-127) *1+f Where f=m/223
Measured Parameters
Parameter
Register
The 24-bit value is signed, that is if bit 7 of byte 3 (above) is set, the value is negative. 2’s complement
arithmetic is used. Fixed scaling factors are employed in the 24 bit and 16 bit measurement ;
Pa r a m e te r, Scaling Employed
Intake Pressure actual in psi times 1
a c t u a l i n b a r t i m e s 10
Discharge Pressure actual in psi times 1
a c t u a l i n b a r t i m e s 10
I n t a k e Te m p e r a t u r e a c t u a l i n C t i m e s 10
a c t u a l i n F t i m e s 10
M o t o r Te m p e r a t u r e a c t u a l i n C t i m e s 10
a c t u a l i n F t i m e s 10
F l o w R a te actual in bpd times 1
a c t u a l i n m 3 / d t i m e s 10
Vi b r a t i o n a c t u a l i n g t i m e s 10 0 0
Reserved —
Current Leakage a c t u a l i n m A t i m e s 10 0 0
D i a g n o s t i c Va l u e no scaling
Integrated Surface Panel : User Manual Page 48
1 ISP.qxd 5/17/99 3:00 PM Page 49
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
13 . 4 . 6 D a t a A d d r e s s e s
Register 16-Bit Mode 24-Bit and IEEE Floating Point Modes Register 16-Bit Mode 24-Bit and IEEE Floating Point Modes
The next block of addresses represents control, status and configuration information. The format described
bellow is independent of the MODBUS styles described above.
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
14 . B a s i c Fa u l t F i n d i n g
The Integrated Surface Panel is substantially self testing and self diagnosing of faults both at power on and
during normal running.
14 . 1 Fu s e P r o te c t i o n
Should the panel not start up then the fuses within the panel may have failed. It is recommended that the
unit be returned for fault identification and repair. Replacement circuit and faceplate assemblies are
available from Phoenix.
14 . 2 Po w e r O n
Should any problems be found at power up the system will log the fault and display a message. A fault
code is shown on the display and this should be notified to Phoenix in all correspondence.
This fault code is made available in Modbus register 103 where decimal 0 indicates no fault
found/system healthy.
14 . 3 D u r i n g O p e r a t i o n
At the end of each set of data received from the downhole Sensor the following are checked ;
• check communications to Sensor, and
• check ESP and cable insulation.
Again if any problem is identified a warning is displayed and the fault code register in Modbus
(register 103) is changed.
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
15 . A d v a n c e d Fa u l t F i n d i n g
Some aspects are not self testing and most notable are:
• Modbus function
• Analogue input and output function
• Relay function
as these are external connections. Various methods of checking operation of these interfaces are
described overleaf.
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
15 . 1 M o d b u s
TX and RX LED are used for fault finding on Modbus. TX flashes when data is sent by the Modbus port to
the RS232/485 drivers. RX flashes when data is received from the RS232/485 drivers.
15 . 1 . 1 Fa u l t F i n d i n g
OBSERVED D I AG N O S I S
Data RX LED flashes with ISP is receiving but not replying. May be wrong address,
no resultant TX LED flash baud rate, bits, parity or invalid Modbus request.
C h e c k M a s t e r a d d r e s s a n d s l a v e a d d r e s s ( i n DATA m e n u )
a n d b a u d r a t e . C o n f i r m M a s t e r i s 8 d a t a b i t s , n o p a r i t y, n o
stop bits.
P r o b l e m p e r s i s t s : p o s s i b l e R S 232 / R S 4 8 5 r e c e i v e r f a i l u r e .
Return circuit to Phoenix. Replace with spare circuit.
P r o b l e m p e r s i s t s : p o s s i b l e R S 232 / R S 4 8 5 r e c e i v e r f a i l u r e .
Return to Phoenix.
P r o b l e m p e r s i s t s : p o s s i b l e R S 232 / R S 4 8 5 r e c e i v e r f a i l u r e .
Return to Phoenix.
Fa u l t C o d e ( R e g 10 3 ) s h o w s v a l u e o t h e r t h a n 0 C h e c k t h a t a l a r m o r t r i p r e l a y i s n o t s e t i n I S P. I f s e t t h e n
t h e r e g i s t e r i s c o r r e c t . I f n o t R e s t a r t Pa n e l a n d s e n d
n o t i f i c a t i o n t o P h o e n i x w i t h f a u l t c o d e n u m b e r.
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
OBSERVED D I AG N O S I S
Data received is wrong (Bus system) Check all slaves have different addresses to this one.
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
15 . 2 A n a l o g u e O u t p u t s
Analogues are set to one of three ranges (4-20 mA, 0-1 Vdc, 0-10 Vdc) and are polarity sensitive. They
are not isolated from the main board power supplies except that to the downhole Sensor.
When selected the output no longer follows the measurement but is driven to these values. Relationship
of full scale analogue output to pressures, temperatures, etc. is as tabulated.
Hardware Setup Ze r o to Fu l l S c a l e
current loop 4Ma 20 m A
voltage output 0 Vd c 1 Vd c
voltage output 0 Vd c 10 Vd c
Allocation of analogues to port are fixed presently and are allocated as below ;
CO N N EC T I O N M E AS U R E M E N T
analogue output 1 T B 2 - 21 ( + ) / 22 ( G N D ) intake pressure
analogue output 2 T B 2 - 23 ( + ) / 24 ( G N D ) discharge pressure
analogue output 3 T B 2 - 25 ( + ) / 26 ( G N D ) intake temperature
analogue output 4 T B 2 - 27 ( + ) / 28 ( G N D ) motor temperature
analogue output 5 T B 2 - 29 ( + ) / 30 ( G N D ) flowrate
analogue output 6 T B 2 - 31 ( + ) / 32 ( G N D ) vibration
analogue output 7 T B 2 - 33 ( + ) / 34 ( G N D ) not used
analogue output 8 T B 2 - 35 ( + ) / 36 ( G N D ) current leakage
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
15 . 2 . 1 Fa u l t F i n d i n g
OBSERVED D I AG N O S I S
A n a l o g u e o u t p u t v o l t a g e i s c . 20 Vd c I S P a n a l o g u e i s s e t u p a s 4 - 20 m A a n d e i t h e r n o r e c e i v e r i s
connected or receiver is for voltage not current. Set receiver
for current loop operation.
A n a l o g u e o u t p u t p u t s o u t c . 0 Vd c I S P a n a l o g u e i s s e t u p a s v o l t a g e ( 0 - 10 V, 0 - 1 V ) a n d e i t h e r
measurement is in fact 0 or a mA loop receiver is
connected. Set receiver for voltage measurement operation,
or ISP for current loop operations.
Fa u l t p e r s i s t s . Po s s i b l e l o s s o f p o w e r i n a n a l o g u e s e c t i o n .
Return to Phoenix.
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
15 . 3 R e l a y s
Activation of the relays is indicated through illumination of either the Alarm or Trip LED on the face
plate. To test the alarm or trip relay set a High or High High, respectively, threshold value below the
present running value for a parameter. Three readings in alarm/trip condition are required to activate.
Alarm or Trip LED should illuminate and the relay contacts should OPEN and CLOSE for NC and NO to
pole respectively.
Confirm from the LOG file that the event has been noted in the system.
15 . 3 . 1 Fa u l t F i n d i n g
OBSERVED D I AG N O S I S
N o L E D l i g h t s w h e n A l a r m o r Tr i p i s a c t i v e Confirm that the alarm and trip relays are not inhibited in
the set up menu.
Check that the link cable from the circuit to the face plate/
LC D a s s e m b l y i s m a t e d ( t h i s i s c o n n e c t e d t o J 15 o n t h e
board)
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
15 . 4 C o m m u n i c a t i o n t o S e n s o r
In remaining compatible with previous Sensor surface equipment the diagnostics referred to as Cz and Cf
are measured by the ISP every time a set of measurements is received from the Sensor. These are not
normally displayed as the ISP determines possible faults by interrogation of them both at power up and
every time they are received.
To display these use the SETUP DISPLAY feature to add Cz and Cf to the running screens.
If you are familiar with using Cz, Cf, and CL for fault finding (although the ISP performs this function for
you) then the fault finding guide below may be used.
Cz Cf CL Diagnosis Remedial
D i s p l a y e d Va l u e s Action
10 . 5 - 12 19 - 22 > 0.5 Normal Operation with low check all surface cabling and
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
Cz Cf CL Diagnosis Remedial
D i s p l a y e d Va l u e s Action
H V S y s te m Fa u l t
disconnect the cables from choke
t o t r a n s f o r m e r H V. R e p l a c e F 1 , F 2 ,
F3 and if readings change then
fault is on the ESP HV system.
Surface Problem
pull fuse F4 and if diagnostics
change then replace choke console.
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
Cz Cf CL Diagnosis Remedial
D i s p l a y e d Va l u e s Action
7 - 21 Same value whatever wrong values displayed Advise Phoenix (send problem fax
as Cz with all information)
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
16 . Fa u l t R e p o r t i n g
I n t h e e v e n t o f p r o b l e m s w i t h t h e M u l t i s e n s o r s y s te m t h e f o l l o w i n g f o r m
should be filled in and sent to Phoenix to assist in resolving of the problem
Th e r e l e v a n t e n g i n e e r r e p o r t i n g t h e f a u l t m u s t f i l l o u t t h e f o l l o w i n g
p a r a m e te r s
Nature of problem -
Effects on system -
SYSTEM
Date Engineer
Client Well site
Pump on/ off Bottom hole temp
Well free flowing/ back spinning Megga value of cable
Single/ 3- phase surface choke Surface fuses checked (state)
Check frame test on tool (state) Tool installed/ pulled
MULTISENSOR
Serial No Zero Cal (Cz) mA
Calibration Module No Full Cal (Cf) mA
Tool Speed Hz Current Leakage (Cl) mA
PANEL
Serial No Fuses checked 4 off (state)
ISP/ MSP/ Multi or TSP Check output voltage + - V
Version of Firmware Digital board serial No
WELL PARAMETERS (please state units)
PI Pd Ti Tm Flow Vib
ISP Only – (Report Diagnostics for)
Open Current mA Voltage mA Stability mA
Power up Panel check fault log (state) Analogue board fitted
MSP Only
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
Leakage current on the ESP high voltage electrical system measured by the ISP is a diagnostic on the
insulation integrity of this electrical system. This is measured in two ways in the Integrated Surface Panel;
• active measurement (may be referred to as CL-1)
• passive measurement (may be referred to as CL-2)
where active measurement is more accurate when the motor is off and passive measurement when the
motor is on.
17. 1 S e t U p : A c t i v e M e a s u r e m e n t ( C L- 1 )
17. 2 S e t U p : Pa s s i v e M e a s u r e m e n t ( C L- 2 )
Based on an increased current drawn by the downhole Sensor system rather than active measured leakage
from the cable to ground this measurement requires set up when the Sensor is installed.
During installation the current leakage will increase from a surface value, settling out circa 12 hours after
landing the completion. Typical initial values (for diagnostic current leakage) would be 0.000 - 0.050
mA.
When the completion has been landed for at least 12 hours and the ESP is off, set the Passive (CL-2) value
by using the option to SETUP PASSIVE CL in the SETUP/Setup Panel menu.
MODBUS
CALIBRATION KEY
SETUP PASSIVE CL
DO WN U P S E L E C T D O N E
This requires the motor to be off and you are prompted to confirm it is off.
For systems which monitor and utilise current leakage as a protective alarm, the alarm threshold is set to
typically twice this initial value. Should an alarm occur or the on-line current leakage is observed to be
excessively high then this value requires to be confirmed. The most accurate leakage is Active Leakage
(Cl-1) when the motor is powered down (off). Should this value be high then there is most likely a fault
on the downhole or surface ESP electrical system.
P r o te c t i o n a n d M o n i t o r i n g PHOENIX
D o w n l o a d i n g D a t a f r o m I S P t o H y p e r Te r m i n a l i n Wi n d o w s 9 5
To enable the viewing and manipulation of data from the data log of the ISP in Microsoft Excel, the data
has to be downloaded using HyperTerminal.
The following steps have to be carried out to enable the Download:
To set-up HyperTerminal:
2. Enter the name that you want to save your HyperTerminal set up to and press OK.
3. In Phone number menu, select Connect direct to comm 1 (where comm 1 is the port you are going to
connect the ISP to) then press OK
4. In Port setting window: select Bits per second: 19200, Data bits: 8, Parity: none, stop bits: 1, Flow
control: none, then select OK.
1. To save data, Select Transfer Menu, Capture Text, enter file name that you want to save the data to,
ensuring data is saved as a .csv file. Then press start.
2. All data that now appears on screen will be saved to that file.
2. Press enter, on the PC, a Menu will be displayed on the PC showing the options and commands
available.