11.21 A balanced Y-connected load, with impedances 65∠ -20° Ω, is connected to a three-
phase, three-wire, CBA system, where V AB= 678.8∠-120 V. Obtain the three line currents.
Solution:
208 √ 2∠−90 °
( )
V √3 I B=2.613∠−135 °+ 120 I C =2.613 ∠−15 ° +120
I A= AN =
ZY 65 ∠ 45°
Solution:
A
IA
Z ∆=9 ∠−25 ° ΩZY =10 ∠−30 ° Ω
V AN =169.8∠ 90°
L1 L2
I1 I2
N
11.34 Obtain the readings of two wattmeters in a three-phase, three-wire system having
effective line voltage 240 V and balanced, Δ-connected load impedances 20∠ 80°Ω.
Solution:
Z ∆=20 ∠ 80 ° Ω
240 √ 2
∠90 °
V AN √ 3
I A= = =29.39 ∠10° A
Z∆ 20
∠ 80°
3
29.39
[
W A =ℜ ( V AB eff ¿ I A eff ) =ℜ (240 ∠120 ° )(
√2
∠−10 ° )
]
W A =−1705.876 Watts
29.39
[
W b =ℜ ( V BC eff ¿ I C eff )=ℜ (240 ∠ 0 ° )(
√2
∠230° )
]
W B=3206 Watts
11.29 A Y-connected load, with Z A = 10∠0 Ω , Z B =10 ∠60 Ω, and ZC = 10∠ 60° Ω, is
connected to a three phase, three-wire, ABC system having effective line voltage 141.4 V.
Find the load voltages V AO , V BO , V COand the displacement neutral voltageV ON . Construct a
phasor diagram similar to Fig. 11-18.
Solution:
V eff = 141.4 V
V OB−V AB V OB V OB+ V BC
+ + =0
ZA ZB ZC
141.4 √2 ∠ 120 141.4 √ 2 ∠0
V OB ( 10 ∠10 ° Ω + 10∠601 ° Ω + 10 ∠−60°
1
Ω ) =
10 ∠0 ° Ω
−
10 ∠ 0 ° Ω
V OB V AB V OB V OB V BC
− + + + =0 V OB=−100V ∧V BO =100∠ 0° V
ZA Z A Z B Z C ZC
1 1 1 V V −V OB −100
V OB
( + +
)
Z A Z B ZC
= AB − BC
ZA ZC
I B=
ZC
=− (
10∠ 0 )
=10 ∠0 ° A
V OA +V AB =V OB V OC =V OB −V BC
V AO=173.18 ∠ 90 ° V
141.4 √ 2 ∠ 120
V ON =V OA +V AN =(173.18 ∠−90 ° V )( )
√3
V ON =57.73∠−90 ° V
11.26. A three-phase, ABC system, with V BC = 294.2∠ 0° V, has the Δ-connected load
Solution:
V BC =294.2∠0 ° V ; Z AB=5.0 ∠0 ° Ω
V AB 294.2 ∠ 120°
I AB= = =58.84 ∠ 120 ° A
Z AB 5.0 ∠ 0 °
V BC 294.2∠ 0 °
I BC = = =73.55 ∠−30 ° A
Z BC 4.0 ∠ 30°
V CA 294.2∠−120 °
I CA = = =49.03 ∠−105° A
Z CA 6.0∠−15 °
I C =I CA −I BC