Professional Documents
Culture Documents
ADICOMP - Компрессор - Инструкция 4-7.5 - ENG - стр 55 - 1232028+++
ADICOMP - Компрессор - Инструкция 4-7.5 - ENG - стр 55 - 1232028+++
VG3-LD-INV(OF-EV-CF) Ex
Technical Specifications
VG10328
GE P/N 1232028
VG10432
GE P/N 1232029
9200.4146-04 07/2016
Editions Record
Code Revision Edition Changes
9200.4146 00 02/2016
9200.4146 01 05/2016 GA rev01, P&ID rev03, Taglist (CF1 and PCV1)
TABLES
Table A-1 Technical Specifications - VG3-LD-INV(OF-EV-CF) Ex ......................................... 7
Table A-2 Maintenance Program for Screw Compressors - VG3-LD-INV(OF-EV-CF) Ex .... 16
Table A-3 Tag List for P&ID Schematic - VG3-LD-INV(OF-EV-CF) Ex ................................. 19
Table A-4 Safety and Control Devices ................................................................................. 21
Table A-5 PED Equipment ................................................................................................... 21
Table A-6 ATEX Equipment ................................................................................................. 21
Table A-7 Simple Apparatus - Intrinsic Safety Connection ................................................... 21
Table A-8 Troubleshooting Guidelines ................................................................................. 27
Table A-9 Light alarms List .................................................................................................. 30
Table A-10 Light alarms Troubleshooting............................................................................. 31
TECHNICAL SPECIFICATIONS
Table A-1 Technical Specifications - VG3-LD-INV(OF-EV-CF) Ex
INSTALLATION
Positioning
The compressor can be positioned in an ATEX Zone 2.
The electrical cabinet must be positioned in an unclassified (not hazardous) zone.
For additional notes regarding the mechanical and electrical installation please refer to the “VG
Operation & Maintenance” manual.
Before introducing the gas into the compressor for the first time and after any maintenance
operation, the purge procedure shall be performed for the compressor in order to discharge the
residual air in the system. The inlet and outlet gas isolation valves (provided by the Customer)
shall be closed and the inertization of the whole system shall be performed using the appropriate
inlet and outlet purge connections. The purge has to be performed by an inert gas, for example
Nitrogen, following carefully the CE rules in force.
To purge the system use the following procedure:
BV9
4. Unscrew the pipe plug of both the purge inlet valve BV2 and the purge discharge valve
BV10.
5. Open both the BV2 and BV10 valves.
BV2 BV10
The purging time depends on the internal volume being purged (Vint), on
the flow rate (Fpurg) of the inert gas supply system, on initial oxygen
content, on oxygen content of inert gas, and on the final desired purity
(oxygen content after purging). As a rule of thumb, to reduce the
percentage of oxygen to an acceptable value, the volume of purging gas
Vpurg should be 2 to 3 times Vint. In case of VG3 compressors, the total
gas capacity of the system (internal volume of gas end, receivers, filters,
tubes) is around 30 litres. The purging time (Tpurg) is given by:
Tpurg=Vpurg/Fpurg=2*Vint/Fpurg=60lt/Fpurg
9. When purging is complete, close the purge discharge valve BV10 and immediately turn
off inert gas flow.
10. Close the purge inlet valve BV2.
11. Disconnect both the inert gas hose from BV2 and the discharge tube from BV10.
12. Screw the pipe plug both for BV2 and for BV10.
13. Close the bypass valve BV9.
14. Open both the gas inlet and discharge isolation valves.
Bypass circuit
The motor speed is regulated by inverter from 100% down to 60% when the load pressure P L is
reached. From 60% down to 0% capacity a by-pass system intervenes.
The Bypass circuit (set to 7.3 bar with a delta pressure of -0.2 bar) is composed of the MPV2.
This circuit allows to bypass the compressed gas into the suction and maintain a steady
pressure at discharge. When the discharge pressure reaches 7.3 bar, the minimum pressure valve
MPV2 lets part of the gas to be bypassed into the suction. If the compressed gas demand
increases, the pressure decreases, the MPV2 is closed: all compressed gas flows to discharge.
In any case, when the compressor is stopped, the internal pressure is leveled through the
pressure damper receiver PD1.
Preliminary actions
1. Stop the compressor and close the inlet and outlet isolating valves.
2. Isolate the unit from the mains electrical supply by turning off the disconnector on the
electrical panel.
3. Wait for the internal pressure to decrease to about 2.2 bar (see PI2 manometer).
PI2
4. Unplug the valve BV10 and open carefully BV10 to depressurize completely the compressor
to 0 bar. Do not proceed until the internal pressure manometer PI2 shows zero.
Oil Filling
plug
BV3
Earth cable
Terminal box
7. Unscrew the four bolts B4 that connect the gas end to the PD1 pulsation dumper.
B4
8. Close with an adequate cover the gas end inlet to avoid the dust to enter the rotors
9. Unscrew the fitting P1 of the oil injection pipe and move away the pipe. Plug properly the
pipe to protect against dust.
10. Remove the fitting P2 of the gas end discharge and insert below the related pipe a support to
avoid the bending of the pipe.
11. Unscrew the gas end fixing bolt B5 at the base.
Earth cable
B1
13. Remove the whole package (gas end-bell house-motor) and put it on a test bench.
Bell house
B2
15. Detach the motor from the package leaving the hub A and the elastic element M of the
flexible coupling attached to the motor shaft.
Set screw S
Hub B (on gas end shaft)
Elastic element M
Flexible
coupling
B3
Individuate the position of the hub B on the gas end shaft in order to
mount it on the same position on the new gas end. This is to maintain the
same space between the hubs A and B (the one on the motor shaft an
the other on the gas end). Upon complete installation of the flexible
coupling the space between hub A and hub B shall be 2.5 mm.
18. Insert the hub B on the shaft of the new gas end and lock it in position with the set screws S
(refer to the flexible coupling picture shown earlier).
19. Ensure the elastic element M of the flexible coupling is in place.
Final actions
22. Follow the procedure to fillup the unit with fresh oil.
SPECIAL TOOLS
Tools kit for SCA7L2 oil seal mounting 8866.0502 1
Gas End
SCA7L2
Set Set
Tag Description Function
alarm shutdown
Emerge
electrical panel
SB2 Emergency pushbutton on board Emergency stop from compressor. --- ---
Connected to S1-20.
High temperature protection on gas/oil circuit by
Temperature
105 °C 110 °C
controller board S1-20
TTS1 Temp. Probe PT100
Connected to safety temperature switch.
High temperature protection on gas/oil circuit 110 °C
(overcomes S1-20 failure).
TT2 Temp. Probe PTC Main motor high temperature protection. --- 130 °C
PT1 Pressure Transducer Discharge gas pressure control 7.8 bar 8.0 bar
Pressure
adicomp S.r.l.
Via del Progresso, 35
36050 – Sovizzo (VI)
ITALY
PRESSURE EQUIPMENT IDENTIFICATION
Assembly:”SCREW COMPRESSOR”
Model: VG3-LD-INV Ex
Design code: VG10328
S/N: 152420CV
Module A1
Fluid group 1 DN 32
Component source: The tag/description of the physical component that generates the error. In
case of a list of components these are preceded by small letters a, b, c, ….
Panel source: The electric input type/location on the control panel that generates the
error.
Menu: parameter: The error related parameter that is set in the control panel Menu.
Description: A brief description of the error. In case of a list of component sources the
description is preceded by the same letter of the component.
Action: What to do to solve the fault condition. In case of a list of component
sources the action is preceded by the same letter of the component.
Table A-8 shows a number of faults that may occur, describes their probable cause and suggests
the proper remedies.
Should any fault remain unsolved, please contact the Technical Support dept.
Er:0010 E
Component source a. SB1 Emergency pushbutton on electric panel
b. SB2 Emergency pushbutton on compressor
c. TTS1 safety temperature switch
Panel source digital input 2
Menu: parameter ---
Description a. Emergency pushbutton on electric panel is pushed.
b. Emergency pushbutton on compressor is pushed
c. Compressed gas at gas end outlet reached the higher temperature limit (110 °C). The
safety temperature converter G1-TTS1 generates this error.
Action a, b Remove the emergency stop cause. To release the emergency turn the push
button counter clockwise.
c. Remove the high temperature cause (see Trouble “High temperature” in the
Troubleshooting table) and reset manually the temperature switch if available for
the switch model.
Er:0020 E
Component source PS1 low pressure switch
Panel source digital input 3
Menu: parameter ---
Description a. Inlet pressure too low
b. Gas leaks at inlet.
Action a. Increase the inlet gas pressure.
b. Check any gas leakages at inlet by a soaped water spray and correct as
necessary.
Er:0080 E
Component source a. Inverter
b. Fan motor
c. Main motor
Panel source digital input 9
Menu: parameter ---
Description a. Alarm coming from the inverter of the main motor.
b. Fan motor overload (1Q2).
c. Main motor overload (TT2 PTC).
Action a. Check inverter manual for a list of alarms.
b. Check fan motor protection switch. Remove the overload cause.
c. Remove the overload cause (see “Motor overload” in troubleshooting table ).
Er:0115 E
Component source S1-20 Controller
Panel source analog input 1
Menu: parameter ---
Description Sensor fault: PT1 delivery pressure transducer is not working (sensor fault or loss of
signal).
Action Check the sensor and sensor cabling.
Er:0119 E
Component source PT1 delivery pressure transducer
Panel source analog input 1
Menu: parameter P03:Pd
Description Delivery pressure reached the shutdown threshold.
Action Check the suction valve works properly.
Er:0135 E
Component source S1-20 Controller
Panel source analog input 3
Menu: parameter
Description PT100 Sensor fault: TTS1 gas temperature transducer at gas end outlet is not
working (sensor fault or loss of signal).
Action Check the sensor and sensor cabling
Er:0139 E
Component source TTS1 gas temperature transducer at gas end outlet
Panel source analog input 3
Menu: parameter P03:Td
Description Gas temperature at gas end outlet reached the shutdown threshold.
Action Remove the high temperature cause (see Trouble “High temperature” in the
Troubleshooting table)
Er:0821 E
Component source S1-20 Controller
Panel source Any analog/digital input
Menu: parameter
Description Low resistance, short circuit or short circuit to earth condition exists on an analog or digital
input (incorrect connection, cable fault or sensor fault)
Action Check the presence of short circuits on the instruments and terminal connections
Er:0846 E
Component source S1-20 Controller
Panel source ---
Menu: parameter P10:Dr
Description Delivery pressure sensor range is set too low for default pressure settings to be
applied.
Action Check the setting for delivery pressure range in the control panel menu.
Alarms
Alarm errors are intended as warnings only and do not make the compressor stop.
Er:2118 A
Component source PT1 delivery pressure transducer
Panel source analog input 1
Menu: parameter P04:Pd
Description Delivery pressure reached the high pressure alarm threshold.
Action Check the suction valve works properly.
Er:2138 A
Component source TTS1 gas temperature transducer at gas end outlet.
Panel source analog input 3
Menu: parameter P04:Td
Description Gas temperature at gas end outlet reached the high temperature alarm threshold.
Action Remove the high temperature cause (see Trouble “High temperature” in the
Troubleshooting table)
Er:2816 A
Component source S1-20 Controller
Panel source S1-20 power supply.
Menu: parameter ---
Description Power failure occurred while compressor was in the Started state
Action Check power supply fuses.
Check the power supply is stable.
Er:3133 R
Component source S1-20 Controller
Panel source Analog input 3
Menu: parameter P05:Td
Description Delivery temperature below the set low temperature run inhibit level. Controller will
allow the motor to start when temperature increases above the set low level.
Action Check the antifreeze system (heater, heating cables) is working properly.
Ensure the ambient temperature is within the operating temperature range.
Service Alarm
Er:4804 A
Component source S1-20 Controller
Panel source ---
Menu: parameter P04:SD
Description Service hours period expired: maintenance is required.
Action Perform the maintenance tasks according to the maintenance program table. Set
again the service hours period (5000 h).
Max numbers of starts per hour Max number of starts per hour parameter on control panel (P07:Sh)
Main motor Running at low speed The inverter slows down the motor speed due to an overload.
3. No delivery pressure
Low pressure at Increase the gas suction pressure according to the compressor
External
suction specifications.
Not running due to Remove grommet from bell housing and visually check coupling.
Gas end
drive coupling failure Replace coupling
PT1 Pressure
Cabling transducer cable not Use shielded cables for pressure transducer.
shielded.
Load (PL) and unload
(PU) values set on
Controller board Choose and set a higher pressure difference between PL and PU.
control panel are too
cloase (< 0.5 bar)
5. High temperature
Check oil level through sight glass while the machine is stopped
Oil low level
and depressurized. Fill up the oil and restore to the right level.
Visually check for the presence of external oil. Repair leaks, fill up
Oil leaks
the oil and restore to the correct level.
Oil circuit
Deoiler, oil filter, oil scavenge visors, blocked or flooded with oil.
Examine oil passageways. Check for hydrocarbon deposit. Clean
Oil flow restricted and rebuild.
If using highly aggressive gas, check the presence of any rusty
element and replace it.
Visually examine cooler matrix for excessive dirt. Clean the cooler
Dirty oil cooler
by using compressed air and degreaser.
Oil cooler Restricted oil cooler Clean up the cooler internally. Drain the oil and fill up with fresh oil.
Blocked cooler fan Check for fan integrity and rotation, fan motor working (Er0080)
Remove sample and compare with recommended oil type. Drain oil,
Incorrect oil type
clean filter, fill up with fresh oil.
Oil Oil deterioration due to
Stop the compressor for about 5/6 hours. Open the oil drain valve
large amount of
and check water is draining initially.
condensate.
High ambient Ensure the ambient temperature is in the operating temperature
temperature range of the compressor
A low pressure differential between suction and discharge leads to
High pressure at low oil flow.
suction Decrease the gas suction pressure according to the compressor
specifications.
External
High cooling water
temperature (if the
Remedy to decrease the cooling water temperature
system is water
cooled)
Low cooling water flow Remedy to increase the cooling water flow.
rate Adjust the gate valve GV to achieve the correct flow rate.
Faulty temperature Check the correct operation of the temperature probe and replace if
probe necessary.
Gas end Oil seal Check for excessive oil leakage from gas end oil seal.
List alarms
The table below lists alarms selectable as “light alarm”.
Table A-9 Light alarms List
Heat sink overheat Heat sink temperature increased to the trip level.
Inverter internal overheat The temperature inside the inverter abnormally has increased.
Option communications error Communications error between the inverter and an option.
PID feedback wire break The PID feedback signal wire(s) is brocken.
Temperature around the inverter Measure the temperature around the inverter.
exceeded the inverter’s Lower the temperature around the inverter (e.g., ventilate the
specification range. panel where the inverter is mounted).
Check if there is sufficient clearance around the inverter.
Change the mounting place to ensure the clearance.
Ventilation path is blocked.
Check if the heat sink is not clogged.
Clean the heat sink.
Check the cumulative run time of the cooling fan.
Heat sink overheat
Cooling air’s airflow volume Replace the cooling fan.
decreased due to the service life
expired or failure. Visually check whether the cooling fan rotates normally.
Replace the cooling fan.
Measure the output current.
Reduce the load (e.g. Use the heat sink overheat early warning
(E01 through E09) or the overload early warning (E34) and
Overload. reduce the load before the overload protection is activated).
Decrease the motor sound (carrier frequency) (F26)
Enable the overload prevention control (H70)
Activation level for the electronic Check the continuous allowable current of the motor.
thermal protection was inadequate. Reconsider and change the data of function code F11.
Recalculate the acceleration/deceleration torque and time needed
The specified for the load, based on the moment of inertia for the load and the
acceleration/deceleration time was acceleration/deceleration time.
too short. Increase the acceleration/deceleration time (F07, F08, E10
Overload of motor through E15, and H56).
1 through 4
Measure the output current.
Overload. Reduce the load (e.g. Use the overload early warning (E34) and
reduce the load before the overload protection is activated). In
winter, the load tends to increase.
Check whether decreasing the torque boost (F09) does not stall the
Excessive torque boost specified motor.
(F09)
If no stall occurs, decrease the F09 data.
There was a problem with the Check whether the connector on the option card is properly
connection between the option card engaged with that of the inverter.
Option and the inverter. Reload the option card into the inverter.
communications
error Check whether appropriate noise control measures have been
implemented (e.g. correct grounding and routing of signal wires,
Strong electrical noise. communications cables, and main circuit wires).
Implemented noise control measures.
Communications conditions of the Compare the setting of the y codes (y01 to y10, y11 to y20) with
inverter do not match that of the those of the host equipment.
host equipment Correct any settings that differ.
Even though no-response error
detection time (y08, y18) has been Check the host equipment.
set, communications is not Change the settings of host equipment software or disable the
performed within the specified no-response error detection (y08, y18 = 0).
cycle.
The host equipment did not operate Check the host equipment (e.g., PLCs and personal computers).
due to defective software, settings
or defective hardware. Remove the cause of the equipment error..
The RS-485 converter did not Check the RS-485 converter (e.g., check for poor contact).
RS-485
communications operate due to incorrect Change the various RS-485 converter settings, reconnect the
error (COM port1) connections and settings, or wires, or replace hardware with recommended devices as
defective hardware. appropriate.
RS-485
communications Check the continuity of the cables, contacts and connections.
Broken communications cable or
error (COM port2)
poor contact. Replace the cable.
Check if appropriate noise control measures have been
implemented (e.g., correct grounding and routing of
communications cables and main circuit wires)
Inverter affected by strong electrical
noise. Implement noise control measures.
Implement noise reduction measures on the host side.
Replace the RS-485 converter with a recommended insulated
one.
PID feedback wire Check if appropriate noise control measures have been
break implemented (e.g., correct grounding and routing of signal wires,
PID feedback related circuit communication cables and main circuit wires).
affected by strong electrical noise.
Implement noise control measures.
Separate the signal wires the main power as far as possible.
P&ID SCHEMATICS
ADI2590.00-Rev05
ADI2649.00-Rev04
ELECTRICAL SCHEMATICS
ADI2738.00
A
DN25 PN16 DN25 PN16
1032
B
817
817
100
120
50
20
C 42,5 100 890 100 42,5 480
1175
600
1207
E
A
DN25 PN16 DN25 PN16
1009
B
817
817
100
120
50
20
C 42,5 100 890 100 42,5 480
1175
580
1207
E
A
VG10328 VG3-LD-F-INV Ex_RID1
A
VG10432 VG3-LD-F-INV Ex_RID2
Adicomp s.r.l.
B B
ADI2738.00 REVISION
ELECTRICAL PANEL
N. DATE DESCRIPTION 900x600x300
Wall mounting kit
01 13/11/15 First issue
C C
13/11/2015 1:1
D D
LAST REVISON P&ID JOB DESIGNER
E E
ADICOMP
N s.r.l.
S Data 20/12/2011
ADI2738.00
Disegnato Christian VG10328-VG10432 VG3-LD-F-INV Ex
Controllato Christian Foglio 0
Rev. Modifica Data Nome Approvato Christian Orig. Sostituiti Sostituito da Fg.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A S A
T
R
+ E.P.
1.6
+ E.P. + E.P. 1F3
5
1Q2
5
1F1 4A
/4.7E
10A + E.P.
6
KML
1.12
1.16
/3.8F
/2.4E
/4.7D
1.1
1.2
1.3
Overload fan motor
6
protection
1.10
Set. 0.77A
1.4
1.5
Range 0.55-0.8A
P+
P1
L1
L2
L3
B B
1.10
PLC 0 230 400 + E.P.
N
L
+ E.P. 1T1
FRN4.0 FWD PE + E.P. + E.P. 350VA
1F2
Frenic mega 1G1 1A 230-400V
+ E.P. 30B
10
/3.8E
Weidmuller 24V
3A
1
1Q1
1.7
1.8
1.9
0 24
0V
24V
20
30C /3.8E
1.14
1.12
2
Main
switch C1+ 30
PE
/2.7C
400V
1.17
25A
11- 40
/2.7C + E.P.
TM1
W
U
C Θ C
+ E.P.
5
KMF Set. 25°C
+ E.P.
/2.3E 1F4
6
6A
1.15
1M3
2
1.13
Cooling fan
1.13 1.13
1.11
4G2.5mm²
U V W screened U1 V1 W1
32
32
32
32
D 1M4 D
+ E.P. + E.P. + E.P. + E.P.
G1 G2 G3 G4
1
2
-X01 -X01 -X01 Cooling fan
9116 9106 9202 9202
/2.1F
/2.1D
U1 V1 W1
31
31
31
31
E PE E
/3.1E
ATTENTION:
PE1
PE
W1
U1
V1
1M2
W
400/3/50 M
1M1 3AC AND INTERVENTION CURVE TYPE D
M Fan motor
3AC 400V
Main motor 0.7A
400V 0.25kW
ATTENZIONE:
7.6A IL CLIENTE E' TENUTO A INSTALLARE UN INTERRUTTORE
4kW
DIFFERENZIALE MAGNETO/TERMICO CON SENSIBILITA'
F 0,3A E CURVA INTERVENTO TIPO D F
Data 02/04/2012
VG10328 VG3-LD-F-INV Ex ADI2738.00
Disegnato Christian
Controllato Christian Main power circuit Foglio 1
Rev. Modifica Data Nome Approvato Christian Orig. Sostituiti Sostituito da Fg.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A
Electronic controller
A
General fault
Line contactor
Star contactor
4-20mA
Common
SV
Run
R5
R6
-X02
RS485/1 RS485/2
-X03
POWER SUPPLY
24Vac
-X01
X06 -X07 -X08
B B
1 2 1 2 3 4 5 6 1 2 3 4 A0 GND L1 L2 L1 L2
2.1
2.2
2.3 2.3 40 40
/1.3C
PE
2
2
2.3
30 30
/1.3C
+ E.P.
/4.8D /4.8E
C 2F1 C
2F1
2.4
2.5
2.6
2.8
1.6A
2
2 2
/1.8D /3.7B
2.7
2.8
6
D 2.6 -X01
0
4
-X01 2.8
+ Comp
10
8
SV2 -X01 -X01
Solenoid valve
2
inlet gas
A1
-X01 0 2.9 2.11
+ E.P.
KR5
E E
A2
General fault
7
0 -X01 + E.P. + E.P.
+ E.P. KML KR5
A1
A1
A1
A2
A2
Fan Main
CLOSED= RUN CLOSED=FAULT
contactor Set:3sec. contactor
Delay error
0
PS1 on start
0 0
/1.8D /3.7D
2.10 2.12
1 2 15 16
/4.2B .8E .8E
11
3 4
9
/1.4C /1.3A
5 6 -X01 -X01
F F
Data
VG10328 VG3-LD-F-INV Ex ADI2738.00
Disegnato
Controllato electronic controller output Foglio 2
Rev. Modifica Data Nome Approvato Orig. Sostituiti Sostituito da Fg.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Pressure transmitter
A
Analog input 3
Analog input 2
Analog input 1
Remote start/stop
Common
Not used
Not used
E0010
E0030
E0040
E0080
E0020
RS1
Analog input Digital inputs
-X05 -X04
6 5 4 3 2 1 1 2 3 4 5 6 7 8 9
B B
PE
3.7
3.8
3.9
3.10
3.11
3.12
3.15
2 2
/2.6D /4.1A
3.1
3.2
3.3
3.5
3.13
14
G2-PT1
-X01
+ E.P.
12 11
3.13
C 43 44 + Comp C
3.1
3.2
TT2
3.13
3.12 PTC
Overtemperature
/4.7A
/4.7A
main motor
12
-X01 3.14
3.4 3.6
3.8
15
-X01
1
3.12
/4.8E
-X02 -X02
+ E.P. + E.P. + E.P. 3.14
11
13
+ E.P. RPS1 RPS2 ROPT + E.P.
15
A1
3.4 3.6
S1
T1
T2
KT1 RS1
Low High Alarm
pressure pressure optional
1
-X03 -X03
/4.4E
switch alarm switch alarm
18
D /4.1E /4.3E /4.3E
Remote D
+ E.P.
/4.8D
start/stop
A2
3.4 3.6
12
14
15
16
RPTC
3.7
3.7
13
- + -X01 0 0
/2.6F /4.1E
+ Comp
PT1
10
3.7
P
/1.3B
Delivery gas pressure
Inverter
alarm
E E
/1.3C
20
PE PE
/4.5B
/1.8E
+ E.P.
1Q2
3.7
3.7
3.7
3.7
3.7
Overload
fan motor
alarm
/1.4A
F F
Data
VG10328 VG3-LD-F-INV Ex ADI2738.00
Disegnato
Controllato Electronic controller input Foglio 3
Rev. Modifica Data Nome Approvato Orig. Sostituiti Sostituito da Fg.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
2
/3.7B
A A
9 9
2
4.10 -X03 4.10 -X02 4.10 13
41
1+
10 10 3.2
/3.2C
11
4.11 -X03 4.11 -X02 4.11
G1-TTS1
42
1-
TTS1-PT100
3 3 5 5 7 7 11 11
11 -X03 -X02 13 11 4.12 -X03 4.12 -X02 4.12
4.1 -X03 -X02 4.4 4.7 -X03 -X02 3.1
51
41
41
43
/3.1C
2+
12
+ Comp
4.1 4.1 + Comp 4.4 4.4 + Comp 4.7 4.7 12 12
G3-CH1
G3-CH2
G4-CH1
+ Comp Optional 4.13 -X03 4.13 -X02 4.13
PS2
44
PS1
2-
High 14
Low
pressure pressure NC
switch 4.2 4.2 switch 4.5 4.5 4.8 4.8 PE
53
43
43
4.5 /3.3E
4.2 -X03 -X02 12 -X03 -X02 14 4.8 -X03 -X02 12
B 4 4 6 6 8 8 B
4.16
+ E.P.
15
KT2 + E.P.
SB1
/2.3E
16
Emergency
stop button
4.3
4.6
4.9
4.17
C C
13 13
4.14 -X03 -X02 13
51
+ Comp 4.14 4.14
G4-CH2
SB2
/2.2C
/3.4D
/1.3B
Emergency
stop button
1.5
3.7
4.15 4.15
53
4.15 -X03 -X02 14
14 14
4.18
4.20
D D
A1 S33 S34 S39 13 23 33
K1
+ E.P.
LOGIC
RSIC K2
XPSAF5130
+ E.P.
A1
B1
A1
A1
A1
A2
A2
A2
0
0
/3.7D
15 18
/3.5D /3.5D /3.6D /3.4D
1.6
2.3
3.8
/1.3A
/2.2C
/3.4C
F F
Data
VG10328 VG3-LD-F-INV Ex ADI2738.00
Disegnato
Controllato Auxiliary circuit Foglio 4
Rev. Modifica Data Nome Approvato Orig. Sostituiti Sostituito da Fg.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
P10: configuration
600 P01:Operation valore P07:Configuration valore valore
300
2nd level
Rt:reset factory
A PU:Unload pressure 7,5 Y/D:Star/delta time 1 x
150 defaults A
100
250
Sensor range
do:drain operation SS:start/stop Ir:internal pressure
180
x 2 x
time remote req. range.
dt:drain interval Td:Temperature
x R5:relay 5 function 2 250
160 time sensor type.
Rt:standby run on
160
15 R6:relay 6 function 10 Ar:temp. Range 3
time
B At: autorestart B
St:stop run on time 15 30 TI1: AI1 setting 0
delay time
Bt:Blowdown time 60 Sh:starts per hour 10 TI2:AI2 setting 1
900
F F
Data
VG10328 VG3-LD-F-INV Ex ADI2738.00
Disegnato
Controllato Layout electrical panel + S1-20 data Foglio 5
Rev. Modifica Data Nome Approvato Orig. Sostituiti Sostituito da Fg.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
INTERCONNECTION DIAGRAM
A A
OPT
SV2
PS1
PS2
SB2
PT1
TT1
3AC 3AC
M M
TT2
U1
W1
W
U
V1
1 2
Junction box
+ Comp
-X03
10
11
12
13
14
1
9
4G2.5mm² sch
2x0.75mm²
4G1.5mm²
2x1mm²
C C
2x0.75mm² sch
4x0.75mm² sch
2x0.75mm²
2x0.75mm²
2x0.75mm²
2x0.75mm²
start/stop
Remote
Spare
Fault
Run
D D
+ E.P.
U V W -X01
10
11
12
13
14
15
1
+ E.P.
Potential free contact -X02
10
11
12
13
14
INVERTER
9
Electrical panel Electrical panel
E E
interconnecting cables between control panel, junction box, motors and solenoid valves are supplied by others F
F
Data
VG10328 VG3-LD-F-INV Ex ADI2738.00
Disegnato
Controllato 297 x 420mm, per Schema Elettrico connection
Foglio
Rev. Modifica Data Nome Approvato Orig. Sostituiti Sostituito da Fg.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
External Cable
Internal Cable
A
Terminal Segment
A
Terminal number
1.5mm²
1.5mm²
Representation
1mm²
1mm²
Comment
Ponte
Type
Wire
External Destination Internal Destination
Device comment Function Location Device Pin Function Location Device Pin Device comment
Terminal blocks:-X01
Number of terminal:15
D D
E E
F Pagina 1 di 1
F
Data -X01
Disegnato VG10328 VG3-LD-F-INV Ex + E.P.-X01
Controllato Foglio Morsettiera Foglio -X01
Rev. Modifica Data Nome Approvato Orig. Sostituiti Sostituito da Fg.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
0.75mm² screened
0.75mm² screened
External Cable
Internal Cable
A
Terminal Segment
Terminal segment
A
0.75mm²
0.75mm²
Representation
1mm²
1mm²
Comment
Ponte
Type
Wire
External Destination Internal Destination
Device comment Function Location Device Pin Function Location Device Pin Device comment
Terminal blocks:-X02
Number of terminal:14
D D
E E
F Pagina 1 di 1
F
Data -X02
Disegnato VG10328 VG3-LD-F-INV Ex + E.P.-X02
Controllato Foglio Morsettiera Foglio -X02
Rev. Modifica Data Nome Approvato Orig. Sostituiti Sostituito da Fg.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
0.75mm² screened
0.75mm² screened
External Cable
Cavo Interno
A
Terminal Segment
A
Terminal number
0.75mm²
0.75mm²
Representation
1mm²
1mm²
Comment
Ponte
Type
Wire
External Destination Internal Destination
Device comment Function Location Device Pin Function Location Device Pin Device comment
Terminal blocks:-X03
Number of terminal:14
D D
E E
F Pagina 1 di 1
F
Data -X03
Disegnato VG10328 VG3-LD-F-INV Ex + Comp-X03
Controllato Foglio Morsettiera Foglio -X03
Rev. Modifica Data Nome Approvato Orig. Sostituiti Sostituito da Fg.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Riga Designation ▲ Comment Destination 1 Destination 2 Electrical drawing ref. Wire section
4 PE ADI2738.00 2.6C
8 ADI2738.00 4.6B
B B
9 ADI2738.00 4.5B
23 U Main motor + Comp connectionM1 U + E.P. FRN4.0 U ADI2738.00 1.2D 2.5mm² screened
24 V Main motor + Comp connectionM1 V + E.P. FRN4.0 V ADI2738.00 1.2D 2.5mm² screened
25 W Main motor + Comp connectionM1 W + E.P. FRN4.0 W ADI2738.00 1.2D 2.5mm² screened
F F
Data
Disegnato VG10328 VG3-LD-F-INV Ex
Riga Designation ▲ Comment Destination 1 Destination 2 Electrical drawing ref. Wire section
44 3.4 PT1 + E.P. -X02 1 + E.P. G3 G2-PT1 43 ADI2738.00 3.3C 0.75mm² screened
45 3.4 PT1 + Comp -X03 1 + E.P. -X02 1 ADI2738.00 3.3D 0.75mm² screened
46 3.4 PT1 + Comp -X03 1 + Comp PT1 - ADI2738.00 3.3D 0.75mm² screened
47 3.6 PT1 + E.P. -X02 2 + E.P. G3 G2-PT1 44 ADI2738.00 3.3C 0.75mm² screened
48 3.6 PT1 + Comp -X03 2 + Comp PT1 + ADI2738.00 3.3D 0.75mm² screened
C 49 3.6 PT1 + Comp -X03 2 + E.P. -X02 2 ADI2738.00 3.3D 0.75mm² screened
C
50 3.7 RS1 + E.P. -X01 13 + E.P. KT1 18 ADI2738.00 3.6E 1mm²
53 3.12 RS1 + E.P. -X01 12 + E.P. S1-20 input 6 ADI2738.00 3.6C 1mm²
67 2.8 SV2 + E.P. -X01 6 + E.P. S1-20 output 4 ADI2738.00 2.6D 1mm²
F F
Data
Disegnato VG10328 VG3-LD-F-INV Ex
Riga Designation ▲ Comment Destination 1 Destination 2 Electrical drawing ref. Wire section
D D
E E
F F
Data
Disegnato VG10328 VG3-LD-F-INV Ex
Riga Location Designation ▲ Comment Description Code number Brand Electrical drawing ref.
A 1
A
2 ADI2738.00 2.6C
11 + E.P. 1Q2 1Q2 Fan motor protection 6001.2025 Siemens ADI2738.00 1.4A
12 + E.P. 1T1 1T1 Transformer 6001.5017 Bimec ADI2738.00 1.8B
13 + E.P. 2F1 2F1 Fuse 6001.3028 Italweber ADI2738.00 2.1C
14 + E.P. -X01 -X01 Terminal strip \ Wago
19 + E.P. FRN4.0 FRN4.0 FRENIC MEGA 4kW 2011.0027 FUJI ADI2738.00 1.2B
20 + Comp 1M2 Fan motor Fan motor 2010.0400 Motive ADI2738.00 1.4E ,ADI2738.00 …
21 + E.P. G1 G1 Galvanic isolator 5710.0040 PR electronics ADI2738.00 1.5D
22 + E.P. G2 G2 Galvanic isolator 5710.0075 PR elctronics ADI2738.00 1.6D
D D
23 + E.P. G3 G3 Galvanic isolator 5710.0038 PR electronics ADI2738.00 1.6D
24 + E.P. G4 G4 Galvanic isolator 5710.0038 PR electronics ADI2738.00 1.7D
25 + E.P. KMF KMF Contactor 6001.1013 Siemens ADI2738.00 2.3E
26 + E.P. KML KML Relay 6001.2040 Omron ADI2738.00 2.4E
F Pagina 1 di 2
F
Data
Disegnato VG10328 VG3-LD-F-INV Ex
Riga Location Designation ▲ Comment Description Code number Brand Electrical drawing ref.
42 + E.P. S1-20 output S1-20 output Electronic controller 5810.0035 CMC ADI2738.00 2.1A
C C
D D
E E
F Pagina 2 di 2
F
Data
Disegnato VG10328 VG3-LD-F-INV Ex
www.adicomp.com