VLF-60KV 0.1Hz Ultra-Low Frequency High Voltage Generator (HV TANK)
VLF-60KV 0.1Hz Ultra-Low Frequency High Voltage Generator (HV TANK)
Contents
V. Instrument Structure……………………………………………… 7
X.Notes………………………………………………………………… 16
Notes
Warning: If the frequency does not meet the requirements when the boost,
will certainly damage the instrument, such damage is not covered by the
warranty。
1.Before the use of this instrument in cable and generator pressure test, should
be tested with megohmmeter, megger test no problem, can use the instrument.
2.Fully discharge the tested object with discharge rod before starting up, (the
discharge rod using method is: first discharge with the current-limiting discharge
end, then ground terminal). Ultra low frequency connection method with two
booster:When using the booster I alone (test voltage is 30 KV or less), instrument
control output I must be connected to booster I, don't connect control output II.
When the booster I and booster II are used in series (test voltage is 80 KV or
less), instrument control output I must be connected to booster I, and instrument
control output II must be connected to booster II, absolutely not inversely
connection! Otherwise the instrument or tested object will be damaged.
3.Please use the STOP button and discharge by rod then shut down the power if
you need to discontinue the machines which in the high pressure
conditions.Otherwise it will damage the instrument!
4.Please operation it according to the screen instructions.
5.It is a normal phenomenon to see small amount of oil spill after boosting the
pressure because the insulating oil in the booster is full, besides, it will not affect
your use.
6.When carrying out 10KV cable test, one-phase test is strongly suggested. The
voltage shall be 18KV and the frequency shall be 0.1Hz、0.05Hz、0.02Hz. The
manual said load capacity is the theoretical value, the scene 10KV cable length
can reach 3-8 km.
7.When carrying out 35KV cable test, one-phase test is strongly suggested.
Voltage is set to 60KV (General Requirements)-78KV (according to the rules
needed) and the frequency is set to 0.1Hz, 0.05Hz, and 0.02Hz. The manual said
load capacity is the theoretical value, the scene 35KV cable length can reach 3-5
km.
8.In case the cable is too short(less than 500 meters), the capacitance of the test
object is smaller than 0.1μF and the pressure cannot be normally boosted, please
connect 0.1μF high-voltage capacitance in parallel way.
9.Keep high-voltage terminals nylon spin by the above numbers to the
corresponding nylon seat, high-voltage lines to ensure good contact , no contact
1
VLF-60KV
is good , it will cause a discharge , burned the high side . When nylon terminals
tightened, pay attention to the intensity, excessive tightening may damage the
nylon terminals.
10.If it is equipped with two booster ultra low frequency:When the test voltage is
30 KV or less, at this point it needs booster I to boost only, not connecting
booster II. Booster number can also be set to I+II, at this point booster I and II
boost in series; When test voltage is more than 30 KV, booster I and II must be
used in series, see operating instructions in instruction book for connecting
methods.
11.Laboratory examination timing, because DC voltage divider sampling speed is
very slow, need to see more than ten cycle, in order to see the peak positive and
negative voltage, the peak is the actual output voltage value.
12.Control output line connected to the booster side air plugs need to be rotated
downward pressure to pull out!
13.Recommend the use of AC power supply of 220V: if you have to use a
generator to supply power, because the 0.1Hz ultra low frequency is based on
the power input frequency modulation, have higher requirements, to the
generator requirements are: frequency 50Hz±1%, voltage 220V±5%, power is
greater than 10KW, the special requirements of the generator output frequency
stability, frequency changes with the load (the best use of digital frequency
conversion generator), in order to stabilize the generator speed, if the frequency
is not stable, certainly not normal booster. otherwise will seriously damage the
instrument!!!
14.When turning on the power supply lamp does not light or no screen display,
the insurance tube may be burned, for a safety tube is good, we are equipped
with 10 insurance tube standby.
15.The lower part of the screen main menu has the voltage input frequency
display, the voltage input frequency request is 50HZ + / - 0.5Hz, over this
range,indicating the input voltage is not stable, can not boost,This time boost
will damage the device!
16.If long-term work is required (continuous working time is more than 20
minutes), please take out the booster before use, open the oil injection hole, and
tighten the oil injection hole after test.
2
VLF-60KV
Warning: in the cable voltage withstand test, must be the core wire and the
insulating layer of the physical separation, not with the other items covered in the
above, otherwise it will cause the high voltage discharge, damage the
instrument!!!
3
VLF-60KV
4
VLF-60KV
3、Products test current estimation method
Formula :I=2πfCU
Ultra-Low Frequency Dielectric Strength Test is the alternative way for power
frequency voltage withstand test. as we know , it is needed huge capacity
testing transformer or a resonant transformer for power frequency voltage
withstand test to large generator ,cables etc due to larger electrical capacity
of insulating layer . The huge equipment not only bulky but also expensive
and not suitable for use. The electricity sector makes some test to solve the
problems. according to theory and test result from domestic and overseas ,
0.1Hz ultra-low frequency voltage withstand test can solve this problems and
the advantage is not only got same test results but also the instrument
dimensions is small and considerably reduced the weight of it . The capacity
of it is 1/500 of tradition way. Greatly simplify testing procedures, That is why
commonly used in the developed countries, china ‘s ministry of electric power
entrust Wuhan high voltage research institute to drafting “ 35Kv and below
XLPE insulated power cable ultra-low frequency (0.1Hz) voltage withstand
test methods ‘for promoting this approach. The instrument is developed
according to China's made of this need. It can be widely used in cable, large-
scale high-pressure rotary motor, power capacitors into AC voltage withstand
test.
III.Products Introduction
5
VLF-60KV
and light weight , large-screen LCD ( clear and intuitive ) , printer output
test report , easy to use . designed to fully meet the power industry
standards .mechanical approach are widely use for modulation and
demodulation ultra-low-frequency signals but no standard sine wave ,
some error of measuring and spark discharge in high-pressure part etc,
the products can overcome the shortcoming of above and the following
features need to indicate in particular:
★ Data of current and voltage are obtained directly through the sampling
of high-pressure side and it is true and accurate.
★ Over-voltage protection: the instrument will shut down to protection
within 20 ms when the output voltage is exceeding limiting values of
setting.
★ Over-current protection: design for dual protection of high and low
voltage, downtime protection can be accurately set in high-pressure
side. Shut down to protection times is within 20 ms when the current of
low-voltage sides exceeds reacted current.
★ High-voltage output protection resistor design in the body boost and it is
no need to additional outside resistor.
★ Closed-loop negative feedback control circuit of high and low voltage.
IV.Technical Parameter
1、output rated voltage , Table 1 for reference
2、output frequency :0.1Hz、0.05Hz、0.02Hz。
3、loading capability : Table 1 for reference
0.1 Hz maximum 0.5µF
0.05 Hz maximum 1.0µF
0.02 Hz maximum 2.5µF
4、accuracy :± (3% of full scale +0.5 KV)
5、voltage waveform distortion :≤5%
6
VLF-60KV
6、condition of use : indoor, outdoor; temperature : -10℃∽+40℃;
humidity :≤85%RH
7、power supply :AC50 Hz,220V ±5%
8、power fuse : Table 1 for reference
V.Instrument Structure
1、control panel diagram
Table 1
(1)“GROUND ”:ground terminal ,used link with the earth .
(2)“I / II ”:output multi-core sockets , used with input multi-core socket of
body boost.
(3)“CONTRAST”:contrast adjustment for LCD
(4)“FUNCTION KEY ”:display prompt bar corresponds to location cue
(5)“AC”:power input , fuse insider
(6)“POWER ”:indicator insider.
(7)“PRINTER ”:for test report
(8)“LCD SCREEN”:display test data .
7
VLF-60KV
Table 2
VI.How To Operation
1、connection method
(1)Connection method of using booster I alone for boosting (test voltage
of 30 KV or less)
8
VLF-60KV
9
VLF-60KV
Please move the cursor to “ start test voltage “and confirmed it then
enter into below Table 6 boost interface .
Table 6(boost )
Automotive boost
the instrument enter into boost status when finished self checking success .
it will take some times to make the voltage reach the setting values . The
instrument will shut down voltage output and enter into start interface if you
press the stop button when boost procedure.
Table 7 will appear in the interface when the boost values is close to setting
values
11
VLF-60KV
Table 7
Please press on the “on and off ”button for 1 second and adjust the
voltage then press the confirm button , Figure 8 appears, instrument start
time,the instrument will start timing and the test report will print out when it
is finished . Back to the start screen, after discharge shutdown before the
start of the next measurement.
Table 8
15
VLF-60KV
X.Notes
1、The booster used in the instrument is not allowed for another use
2、Please contact the factory for repairs if the instrument malfunction and
do not open it by yourself .
3、before stitches , please fully discharge the test products by discharge rod
after power off the instrument .
4、please fully discharge the test products by discharge rod before power
on the instruments .
5、please fully discharge the test products by discharge rod before press on
boost button each times .
XI.Packing List
1、0.1Hz/60KV control box (1pcs)
2、0.1Hz/60KV booster (2pcs)
3、0.05μF/60KV shunt capacitor (1pcs)
4、30KV high-voltage output lines (1pcs)
16
VLF-60KV
5、60KV high-voltage output lines (1pcs)
6、Booster I and II high voltage cables(1pcs)
7、Shunt capacitance high-voltage cables (1pcs)
8、Special control cables (2pcs)
9、Power lines (1pcs)
10、Ground wire (1pcs)
11、Discharge Rod (1pcs)
12、Power fuse (10pcs)
13、Printing paper (2pcs)
14、Instruction manual (1pcs)
15、Factory certification (1pcs)
16、Factory inspection report (1pcs)
XII.Appendix I
Rated voltage Over test voltage Preventive test voltage
Uo/UN(KV) Voltage Voltage values Voltage Voltage
multiplier (KV) multiplier (KV)
1.8/3 3 Uo 5 2.1 Uo 4
3.6/6 3 Uo 11 2.1 Uo 8
6/6 3 Uo 18 2.1 Uo 13
6/10 3 Uo 18 2.1 Uo 13
8.7/10 3 Uo 26 2.1 Uo 18
12/10 3 Uo 36 2.1 Uo 25
21/35 3 Uo 63 2.1 Uo 44
26/35 3 Uo 78 2.1 Uo 55
Uo is the nominal phase voltage , UN for the cable rated line voltage .
test times :1-5 minutes
17
VLF-60KV
XIII.Appendix II
The cross-sectional Capacitance(uF/Km)
area of the cable YJV、YJLV YJV、YJLV YJV、 YJV、 YJV、
conductor(Square 6/6KV、 8.7/10KV、 YJLV YJLV YJLV
millimetre) 6/10KV 8.7/15KV 12/20KV 21/35KV 26/35KV
1*35 0.212 0.173 0.152
1*50 0.237 0.192 0.166 0.118 0.114
1*70 0.270 0.217 0.187 0.131 0.125
1*95 0.301 0.240 0.206 0.143 0.135
1*120 0.327 0.261 0.223 0.153 0.143
1*150 0.358 0.284 0.241 0.164 0.153
1*185 0.388 0.307 0.267 0.180 0.163
1*240 0.430 0.339 0.291 0.194 0.176
1*300 0.472 0.370 0.319 0.211 0.190
1*400 0.531 0.418 0.352 0.231 0.209
1*500 0.603 0.438 0.388 0.254 0.232
1*630 0.667 0.470 0.416 0.287 0.256