Generator set data sheet

Model: C2000 D6
Frequency: 60 Hz
Fuel type: Diesel

Spec sheet: SS17-CPGK


Noise data sheet: ND60-OSHHP
Airflow data sheet: AF60-HHP
Derate data sheet: DD60-OSHHP
Transient data sheet: RTF

Standby Prime
Fuel consumption kVA (kW) kVA (kW)
Ratings 2500 (2000) 2281 (1825)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
US gph 43 71.6 102.5 137.5 38.1 65.3 94.0 123.1
L/hr 163 272 388 521 144 247 356 466

Standby rating Prime rating


Engine
Engine manufacturer Cummins
Engine model QSK60-G6
Configuration Cast iron, 60 º V16 cylinder
Aspiration Turbocharged and low temperature aftercooled
Gross engine power output, kWm 2180 1975
BMEP at set rated load, kPa 2420 2185
Bore, mm 159
Stroke, mm 190
Rated speed, rpm 1800
Piston speed, m/s 11.4
Compression ratio 14.5:1
Lube oil capacity, L 378
Overspeed limit, rpm 2070 ±50
Regenerative power, kW 207
Governor type Electronic
Starting voltage 24V Volts DC

Fuel flow
Maximum fuel flow, L/hr 1685
Maximum fuel inlet restriction, mm Hg 203
Maximum fuel inlet temperature, °C 70

power.cummins.com
©2017 Cummins Power Generation Inc. | DS86 -CPGK (10/17)
Standby rating Prime rating
Air
Combustion air, m3/min 174 161
Maximum air cleaner restriction, kPa 6.2

Exhaust
Exhaust gas flow at set rated load, m3/min 439 399
Exhaust gas temperature, °C 475 460
Maximum exhaust back pressure, kPa 6.7

Standard set-mounted radiator cooling


Ambient design, °C 40
Fan load, kWm 45
Coolant capacity (with radiator), L 456
Cooling system air flow, m3/sec @ 12.7 mmH2O 34.3
Total heat rejection, Btu/min 70530 62010
Maximum cooling air flow static restriction mm H2O 12.7

Open Enclosed
Weights*
Unit dry weight kgs 14880
Unit wet weight kgs 15945

* Weights represent a set with standard features. See outline drawing for weights of other configurations.

Length Width Height


Dimensions
Standard open set dimensions 6175 2286 2537
Standard enclosed set dimensions

Genset outline
Open set

Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.

power.cummins.com
©2017 Cummins Power Generation Inc. | DS86 -CPGK (10/17)
Alternator data
Connection Temp rise ºC Duty Alternator Voltage
Wye, 3-phase 150/125 S/P PI734F 380 V
Wye, 3-phase 125/105 S/P PI734F 480 V
Wye, 3-phase 125/105 S/P MVSI804R 4160 V
Wye, 3-phase 125/105 S/P HVSI804R 13200-13800 V

Ratings definitions

Base load
Emergency standby Limited-time running
Prime power (PRP): (continuous) power
power (ESP): power (LTP):
(COP):

Applicable for supplying Applicable for supplying Applicable for supplying Applicable for supplying
power to varying electrical power to a constant power to varying electrical power continuously to a
load for the duration of electrical load for limited load for unlimited hours. constant electrical load
power interruption of a hours. Limited Time Prime Power (PRP) is in for unlimited hours.
reliable utility source. Running Power (LTP) is in accordance with ISO Continuous Power (COP)
Emergency Standby Power accordance with ISO 8528. 8528. Ten percent is in accordance with ISO
(ESP) is in accordance with overload capability is 8528, ISO 3046, AS
ISO 8528. Fuel Stop power available in accordance 2789, DIN 6271 and BS
in accordance with ISO with ISO 3046, AS 5514.
3046, AS 2789, DIN 6271 2789, DIN 6271 and BS
and BS 5514. 5514.

Formulas for calculating full load currents:

Three phase output Single phase output


kW x 1000 kW x SinglePhas eFactor x 1000
Voltage x 1.73 x 0.8 Voltage

For more information contact your local Cummins


distributor or visit power.cummins.com

©2017 Cummins Power Generation Inc. All rights reserved.


Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand, AmpSentry, InPower
and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names
may be trademarks or service marks of others. Specifications are subject to change without notice. power.cummins.com
DS86-CPGK (10/17)