You are on page 1of 4

S541.

RF 4G Datasheet
This document contains information that is the
proprietary and confidential property of INNCOM
International Inc. By acceptance hereof, each
recipient agrees to use the information
contained herein only for the purpose
anticipated by INNCOM, and not to disclose to
others, copy or reproduce, any part hereof
without the written consent of INNCOM. The
recipient agrees to return this document to
INNCOM immediately upon request.

Contents
S541.RF 4G Datasheet ....................................................................................................................................... 1
Overview .............................................................................................................................................................. 2
Application ........................................................................................................................................................... 2
S541 .............................................................................................................................................................. 2
RT3................................................................................................................................................................ 2
RT4................................................................................................................................................................ 2
Features ............................................................................................................................................................... 2
Specification ........................................................................................................................................................ 2
Network Topology ................................................................................................................................................ 2
Installation ............................................................................................................................................................ 3
Installing Door Switches ................................................................................................................................ 3
Commissioning .................................................................................................................................................... 3
Safety/Regulatory ................................................................................................................................................ 3
Mechanical Drawings........................................................................................................................................... 4
Dimensions .......................................................................................................................................................... 4
Ordering Information ............................................................................................................................................. 4
Magnetic Door Switch ................................................................................................................................... 4
References .......................................................................................................................................................... 4
Document Revision History ................................................................................................................................. 4

1
Copyright 2014 INNCOM by Honeywell
guestroom temperature and Parameter S541.RF 4G
Overview humidity where the thermostat
The S541 family of remote must be located close to the Outdoor/RF line- 540ft
monitors is a member of heat/ cool source. The RT4 has
of-sight range
INNCOM’s Integrated Room a temperature accuracy of 0.5°C Transmit Power 1mW (+0dBm)
Automation System (IRAS). from 0°C to +65 °C and can Receive -94.6dBm
These devices provide remote measure relative humidity to +/-
Sensitivity
reporting of door switch status, 5%RH over a compensated Frequency Band 2.4Ghz
temperature and humidity. The range of 5°C–50°C. Encryption AES-128
models consist of the S541
Protocol 802.15.4
Battery Operated Door Switch The S541 family operates in three
modes: sleep, to conserve battery Frequency 11-26
Monitor, the RT3 Battery Channels
Operated RF remote life when there are no events to
Temperature 0.5°C from 0°C–65
temperature sensor, and the report; operation, to transmit Sensing Accuracy °C
RT4 Battery Operated RF switch status, temperature, or
Humidity Sensing +/- 5%RH over a
remote temperature and humidity; and bind, when Accuracy compensated range
commissioning the product into of 5°C - 50°C
humidity sensor.
the INNCOM RF IRAS. Input Voltage 3VDC (Battery
Each of these family members is Powered—2AAA)
equipped with a 2.4Ghz radio for The S541 family uses 2.4Ghz Battery Life 5 years
wireless RF communications wireless radio frequency to
Operating 0°C–40 °C
and is battery operated, with up communicate to the INNCOM Ambient
to a 5 year battery life. IRAS, therefore direct line of Temperature
sight is not required for LED / Switch Flashes on power up.
Application communication between the Flashes slow in bind
mode. Flashes fast on
S541 S541family of remote monitors receiving the bind
and the e4 digital thermostat. command. Switch
The S541 monitors guestroom presses are used for
teach mode and to
door status and reports the status Features initiate bind mode.
into the IRAS. This, in conjunction • Small, wall mountable design
with motion sensing performed by
• 2.4Ghz IEEE 802.15.4 INNCOM RF IRAS
S541.RF
another INNCOM IRAS device e4 Digital Thermostat
compliant 0dB RF
such as the K595 or the INNCOM
transceiver
e4 thermostats on-board motion
sensor, is used for energy • Deep mesh networking
management. It is ideal for retrofit • On-board door switch
situations and for transmitting monitor, temperature sensor,
door status from balcony doors or and humidity sensing
other room openings. To switch contacts
• Industrial temperature ratings
Figure 1 S541.RF Topology
RT3 0–65°C
The RT3 remotely monitors • FCC Part 15b listed Network Topology
guestroom temperature where The S541.RF wirelessly
Specification transmits the switch status to the
the thermostat must be located
Parameter S541.RF 4G e4 digital thermostat in an
close to the heat/cool source.
The RT3’s temperature accuracy INNCOM RF IRAS application.
RF Data Rate 250kbps
is 0.5°C from 0°C to +65 °C.
Antenna Type SMT
RT4 Indoor Range 70ft
The RT4 remotely monitors

2
Copyright 2014 INNCOM by Honeywell
The RT3/RT4 topology is • Push the S541 wires through Address.
virtually the same, wirelessly the frame hole.
For the first minute during
transmitting temperature / • Attach the S541 in position power up, the S541 is in test
humidity data to the e4. on the wall. mode (the RT3 and RT4 have
Installation • Strip the ends of the S541 no test mode). In that period,
The S541, RT3, and RT4 should wires about 1/6 in. long and the LED will illuminate when the
be mounted unobtrusively within attach to the S241 terminal. device is actuated.
operational range (70 ft. indoors) Push excess wire inside
Safety/Regulatory
of the e4 thermostat and any frame.
Parameter Condition Status
other devices it may • Insert the S241 door switch
communicate with. Care should FCC Part 15 FCC listings
into the door. are pending.
be taken to avoid possible
sources of interference such as Commissioning This device contains FCC ID:
metallic boxes, WiFi access To function as part of the deep GTC202913TXR.
points, water pipes, and the like. mesh network, the S541, RT3,
This device complies with part
It should also not be mounted in or RT4 must accept
15 of the FCC Rules. Operation
areas of high humidity. identification and instruction
is subject to the following two
from an e4 thermostat.
The RT3 and RT4, used to conditions: (1) This device may
remotely measure temperature 1. Enter the Service Mode on not cause harmful interference,
and humidity, must be mounted the e4 thermostat (press and and (2) this device must accept
vertically with the ventilation slits hold the °F/°C button; press any interference received,
at the bottom edge of the unit. and release the OFF/AUTO including interference that may
This allows convection to create button; press and release the cause undesired operation.
airflow through the unit. DISPLAY button; release the
°F/°C button) IC:1609A-202913TXR
Additional placement
considerations include This Class B Digital Apparatus
2. On the thermostat LCD, scroll
complies with Canadian ICES-
• avoiding areas in direct to Adr and press OFF/AUTO.
0003. Operation is subject to the
sunlight 3. Set the address to teach the following two conditions: (1) this
• avoiding areas of direct air S541 (typically 209). device may not cause interference,
discharge (preferably closer and (2) this device must accept
4. Press OFF/AUTO. The LCD
to an air intake point) any interference, including
will display bnd.
• avoiding areas around interference that may cause
windows and exterior doors 5. Remove the S541/RT3/RT4 undesired operation of the device.
cover and press the switch
Installing Door Switches Cet appareil numérique de la
once to send a bind request
classe B est conforme à la
The S541 receives open / close towards the thermostat.
norme NMB-0003 du Canada.
status from doors or windows 6. The thermostat sends a bind L’exploitation est autorisée aux
equipped with INNCOM S241 offer to the S541. If accepted, deux conditions suivantes: (1)
magnetic switches (PN 04-1095 the thermostat will buzz l’appareil ne doit pas produire de
or surface-mounted 04-1097). loudly. The S541 will reset. brouillage, et (2) l’utilisateur de
To install the switches in a door
7. Test the S541 functionality. l’appareil doit accepter tout
and frame
brouillage radioélectrique subi,
• Make a 0.75". diameter, 1.5" If multiple S541s, RT3s, and même si le brouillage est
deep hole in the door and RT4s are installed, each must susceptible d’en compromettre
frame (align holes). have a unique Address. Use the le fonctionnement.
procedure above to set the

3
Copyright 2014 INNCOM by Honeywell
Part OPN Description
Number
Document Revision
Mechanical History
201-913- S541.RF Battery powered
Drawings LA.P 4G RF door switch, Revision Date Reason
Light Almond Issued
0.1 03-Oct-2013 First draft
201-913- RT3 Battery powered
RFTWH.P RF temperature 0.2 09-Oct-2013 First R&D
sensor, White review
0.3 13-Nov- Correct
201-913- RT3 Battery powered 2013 binding
RFTBK.P RF temperature instructions,
sensor, Black FCC
statement
201-913- RT3 Battery powered
RFTEA.P RF temperature 1.0 20-Nov- Add mag door
7 sensor, Eagle 2013 switch info;
Almond prepare for
release.
201-913- RT3 Battery powered
RFTLA.P RF temperature 1.1 06-May- Fixed OPN
sensor, Light 2014
6 Almond
Figure 3: S541.RF Mechanical Drawings
201-913- RT4 Battery powered
Item Description RFHWH.P RF humidity
1 Top Housing sensor, White

2 PCB Assembly 201-913- RT4 Battery powered


RFHBK.P RF humidity
3 Bottom Housing sensor, Black

4 Double Sided Tape 201-913- RT4 Battery powered


RFHEA.P RF humidity
5 Battery 1.5 AAA sensor, Eagle
6 Security Screw Almond

7 Mounting Screw Holes 201-913- RT4 Battery powered


RFHLA.P RF humidity
sensor, Light
Almond
Dimensions
L=102mm×W=32mm×H=14mm Magnetic Door Switch
The door-mounted magnetic
Ordering Information door status switch is PN# 04-
Part OPN Description 1095. The surface mounted
Number switch is PN# 04-1097.
201-913- S541.RF Battery powered
WH.P 4G RF door switch, References
White
Title Location
RT3 T:\Library\INNCOM
201-913- S541.RF Battery powered Engineering Products\Devices\S541_
BK.P 4G RF door switch, Manual RFT\RT3 Engineering
Black- Manual.pdf
201-913- S541.RF Battery powered
EA.P 4G RF door switch,
Eagle Almond